WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

Similar documents
Removal of Non-condensable Gases and Air Is Critical In A Steam System

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Series 151 and AV5. A wide range of process thermostatic steam traps is available to match almost any application need.

How to Trap: Installation and Testing

How to Trap: Trap Selection and Safety Factors

THE PRESSURIZED CONDENSATE RECOVERY SYSTEM:

WATER HAMMER something that never should occur in a steam system

How to Trap: Steam Tracer Lines

YARWAY PROCESS THERMOSTATIC STEAM TRAPS SERIES 151 AND AV5

How to Trap: Process Air Heaters

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

Economical and simplified solutions that offer quality and optimum steam trap service.

Steam Trap Selection

Steam Systems 101. Understanding Your Energy Systems Better. May 5, 2016

How to Trap: Troubleshooting

How to Trap: Rotating Dryers Requiring Syphon Drainage

HEAT EXCHANGER FORMULAS & EXAMPLE

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units

The right trap for the right application.

Bringing Energy Down to Earth

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

STEAM CONSERVATION GUIDELINES

GESTRA Information A 1.7

Steam System Best Practices Document No. 11

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

THE THERMOSTATIC STEAM TRAP

How to Trap: Conversion Factors

A M E M B E R O F T H E K E N D A L L G R O U P

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

Water Fuel + Air for combustion Blowdown

.005 ATMOSPHERIC DEAERATOR

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

.03 ATMOSPHERIC DEAERATOR

DEAERATORS .005 ATMOSPHERIC DEAERATOR

Steam Traps and Steam Specialties

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT

Steam Conservation Guidelines for Condensate Drainage Steam Trap Sizing and Selection.

Steam Conservation Guidelines for. Drainage. Mead O'Brien (800) LP Steam. Condensate. HP Steam RECEIVER TANK HEATER

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS

Silhouette. Feedwater Heater. Boiler Feedwater

THERMOSTATIC STEAM TRAPS

STEAM AND TRAP FUNDAMENTALS

ABSORPTION REFRIGERATION SYSTEMS

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

Yarway Repairable Drip and Tracer Steam Traps Series 751/761, 711/721, 731/741, 500/546, 460/515/D3

By: Prof K. M. Joshi,

COBREX. Semi-Instantaneous. Steam-Fired Domestic Hot Water Generator. Up to 7000 MBH 150/ 175/ 215 Gallon Tank 25-year Warranty. PVI.

Section H11 BLOWDOWN SEPARATORS CONTENTS FEATURES AND BENEFITS...H11-3 PRODUCT OFFERING...H11-3 SAMPLE SPECIFICATIONS...H11-11 ILLUSTRATIONS

FT600 & FT601* Steam Traps Float & Thermostatic Steam Trap. Float & Thermostatic STEAM TRAPS

The. Steam ONE-PIPE STEAM SYSTEMS

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

PIP PNE00004 Steam Trap Guidelines

Liquid Drainers LIQUID DRAINERS

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

Bringing Energy Down to Earth

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

Chapter 2.3: Steam System

Series 1140 and 1141 Temperature Regulators

Efficient Steam System Design

Series 300 VTB. Installation Instructions

Installation and Operating Service Manual

SERVICE MANUAL. For Service & Parts please call APK THERMAL at or SAFETY INSTRUCTION

TYPE.005 DA-2C. Deaerating Boiler Feed Pumps. SHIPCO Deaerators can save you money!!! BULLETIN 149 Revised 8/09

Reliable Vacuum Condenser Performance

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

Instruction Manual STR MODEL RESISTO-FLO ELECTRIC BOILER

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018

Installation and Operating Instructions ISH ELECTRIC STEAM SUPERHEATER

"SXDDR" Series Steam Heat Exchanger Humidifiers

Our Know-How. Your Peace of Mind. Steam Solutions

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

FUEL-FIRED VERTICAL TUBELESS BOILERS

Instruction Manual HWR MODEL RESISTO-FLO ELECTRIC BOILER

RSES Technical Institute Training Manual 2 72 hours, 72 NATE CEHs, 7.2 CEUs

Use this Construction/HVAC Glossary to answer the questions below.

Annual Steam Startup at Cornell University

LIQUIDATOR 450 SERIES

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

What is a Secondary Pressure Drainer?

Installation, Operation, and Maintenance Information

Installation and Maintenance "L" and "LS" Series

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133.

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass

Hoffman Specialty General Catalog

BASICS OF STEAM TRAPS BASICS OF STEAM TRAPS

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Operation & Maintenance Manual

High Capacity Instantaneous Steam Fired Water Heater

Niles Steel Tank Hot Water Generator Installation and Operation Manual

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No.

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

Diocese of Cleveland Facilities Services Corporation

OIL MIGRATION IN R-12 & R-22 SYSTEMS By: Norman Sharpe Professor, Air Conditioning & Refrigeration Dept., California State Polytechni College

Transcription:

BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production problems for a plant s operation. Air in a steam system dramatically reduces the system s performance. For example, the thermal conductivity of air is 0.000049, compared with 0.002 for water, 0.20 for iron, and 0.96 for copper. Not removing air and noncondensable gases from the steam system can reduce heat transfer efficiencies by 21 percent or more depending on the air concentration in the steam system. Since air is one of the greatest insulators, a major steam operation objective is eliminating air in a steam system. Adding to this problem is that steam systems are typically not designed to eliminate the air at startup or during operation. During shutdown of the steam system or steam components, the system is depressurized: the steam condenses and reduces in volume by as much as 1,600 times. This reduction in volume produces a vacuum in the steam system or steam components. Air is drawn into the steam system through steam components, such as air vents, valve packing, flanges, and so forth, and the air drawn in fills the vacuum. When energizing a steam system or steam heat transfer components, one of the first goals should be to vent the air out of the steam system or components. I. WHERE DO THE NONCONDENSABLE GASES AND AIR COME FROM? Feedwater contains a certain small percentage of noncondensable gases in solution. When the boiler water changes state (liquid to vapor), the noncondensable gas is released and is carried with the steam into the plant. Steam will release the latent energy to the process and condense down to condensate in the heat transfer area, but the noncondensable gases do not condense. These gases stay in the heat transfer component unless some method or action removes them. During the steam system operation, the percentage of steam in the system will be close to 100 percent steam vapor with a small percentage of noncondensable gases. When steam is shut down to the heat transfer unit or steam supply line for maintenance or process changes, the steam will condense and decrease in volume, which will open the vacuum breakers on the steam heat transfer unit that allow air to flow into the system. On heat transfer units, it is extremely important to have functional vacuum breakers on the heat transfer units to enable the condensate to drain out of the unit by gravity. If vacuum breakers are not on the heat transfer unit, then the vacuum will hold the condensate in the unit and cause another set of issues. On a steam line that does not have vacuum breakers, the vacuum that will occur will draw air in from components on the system (such as valve packing, flanges, etc.) and fill the void in the line with air. II. HOW DOES AIR AFFECT THE SYSTEM? A. Air Reduces the Heat Transfer Efficiency The release of latent energy (change of state) to condensate in the steam components takes place on the heat transfer surface, which is where heat is being transferred due to the temperature difference (steam to the process). The steam component transfer is consuming the latent energy, and the steam is condensing to a liquid (condensate); the condensate is drained away by gravity, but the noncondensable gas and air remain. The noncondensable gases form a stagnant film on the walls of the heat transfer surface, which creates resistance. Heat energy transmitting through the heat transfer surface has to pass by conduction through these films of resistance. A film of air or

noncondensable gas that is only one thousandth of an inch thick has the resistance of a three-inch wall of iron. See Figure 1. The latent heat energy of steam must pass from the steam heat transfer area to the area where the process material is being heated. To do so, it must pass through several obstacles: Figure 1: Steam Processes 1. A stagnant film of air/steam on the steam side 2. Condensate film 3. Buildup of rust or corrosion material 4. Heat transfer metal wall 5. Product side burned product or scale 6. Stagnant film of material on the process side of the wall B. Air Reduces the Temperature of Steam 1. Dalton s Law of Partial Pressures Dalton s law of partial pressures states that in a mixture of gases and/or vapors, the total pressure of the mixture is made up of the partial pressures exerted by each gas or vapor. The partial pressure exerted by each is the fraction of the total pressure equal to the fraction of the total volume of each. Figure 2: Resistance of Air Compared to Copper and Iron The pressure reading is in absolute units. For example, the total pressure of a mixture of air and steam is 114.7 lbs. per sq. in. absolute (337.87 F). The mixture is made up of 75 percent steam and 25 percent air or noncondensable gases. The partial pressure of steam is 114.7 x 0.75 or 86.02 lbs. per sq. in. absolute (psia) (317 F). The partial pressure of the air is 114.7 x 0.25 = 28.56 lbs. per sq. in. absolute (psia). The temperature of saturated steam at 114.7 lbs. per sq. in. absolute is 317 F vs. 337.87 F, if the steam line or steam component is filled with a mixture consisting of 75 percent steam and 25 percent air and noncondensable gases. Figure 3: Obstacles to Energy Transfer There are other steam system issues with the

concentration of air and noncondensable gases. The buildup or volume of air and noncondensable gases in the heat transfer area is not constant. The thickness of a stagnant film of air can vary due to velocities, baffles, flow direction, metal finish, and other heat transfer internal designs. This factor provides even more problems with uneven heating of the products. Plants increase steam pressures to overcome the issues with air and noncondensable gases. In turn, the higher cost of producing higher steam pressures increases the plant s energy cost. III. ELIMINATING THE NONCONDENSABLE GASES OR AIR FROM THE SYSTEM A. Devices or Methods to Vent the Noncondensable Gas or Air There are several methods to vent air from the system or heat transfer unit. 1. Manual Valve Negative: a. Requires an employee to operate the device Positives: a. Plant employee can ensure all air has been vented from the system b. Plant employee can also drain condensate from the system during startup c. Typically used on steam and pressurized condensate lines 2. Automatic Valve Negatives: a. Requires an automatic valve with electric or compressed air connections b. More complex c. No method of ensuring all the air has been removed Positive: a. Plant employee does not have to be at the location of each valve 3. Air Venting Device One factor differentiates an air/ steam mixture from 100 percent steam: temperature. Therefore, an automatic air vent can be provided with the use of a thermostatic device. The air venting device is typically a thermostatic balance pressure bellows unit with a very low sub-cool. The device will be able to sense air or noncondensable gases due to the resulting temperature suppression. The air venting device is used on the heat transfer units that have shutdowns and startups during the operational week. Negative: a. Reliability can be a issue if the proper air venting device is not purchased Positives: a. No plant personnel have to be at the location during startup b. Greatly improves the operation of the heat transfer system 4. Steam Trap Steam traps are never considered to be the primary air venting mechanism due to the methods steam traps incorporate into their design to accomplish this task. Therefore, the steam trap is always considered a secondary air vent mechanism. There are two methods to vent air in any steam trap: a leak path and a thermostatic mechanism. a. Create a leak path The steam trap design has a leak path incorporated into the operational design. The steam trap leak path is a very small path to ensure no significant steam loss occurs during operation. Due to the small leak path, the steam trap is not able to provide sufficient air venting capabilities. b. Thermostatic mechanism

The other method is to use a thermostatic element inside of the steam trap that can offer a high capacity of venting air at startup due to the orifice size. In process applications, the preferred steam trap is a float and thermostatic steam trap, which incorporates a thermostatic air venting mechanism. Note: the strainer blowdown valve is also open at startup to allow the strainer to be blown down The plant may decide to use one or more of the above items to remove the air from the steam system during startup or operation. IV. INSTALLATION OF AIR VENTING AND DEVICES A. Steam Lines When the steam lines are activated or started up, one of the main tasks will be to remove the noncondensable gases. During the startup period, the drain valve off the steam line drip pocket is open for venting air from the steam line. Its other major function is to remove the condensate. In some cases, to ensure all air is removed from the system, a second manual air venting valve is installed on top of the steam line. See Figure 4. Figure 5: Steam Lines B. Examples of a Process Equipment Placement of Air Vents and Vacuum Breakers A key factor in the location of air vents on process equipment is to understand the design of the unit. For example, a shell and tube heat exchanger has a port typically on the top of the shell for the placement of a vacuum breaker and air vent. The process steam side needs to have the air purged to ensure proper startup and temperature control. See Figure 5. Figure 4: Air Venting Device Figure 6: Shell and Tube Heat Exchanger

Steam coils will have a vacuum breaker located at the entrance of the steam into the coils. The preferred method is to have a port on the top header for the devices. Steam coil manufacturers will incorporate the port on the top header for the devices. See Figure 6. For process application steam traps, the preferred steam trap design is the float and thermostatic, which incorporates a thermostatic air vent mechanism. The steam trap thermostatic air vent mechanism becomes the secondary air venting device. ROAD MAP: 1. Survey all process equipment and ensure units have air vents and vacuum breakers. 2. Survey all steam lines drip legs and ensure proper blowdown valves are installed. 3. Have Standard Operating Procedures (SOP) for the use of manual air vents on steam lines and process applications. Figure 7: Steam Coils