Technical Selection. elevent ceiling diffusers. Swirl, Jet, Louvred and Curved ceiling diffusers

Similar documents
ASSEMBLY HALL AIR DISTRIBUTION

Air distribution systems. Opticlean OC-Q...

Ceiling swirl diffusers

Ceiling swirl diffusers

Air distribution systems. Rectangular displacement outlet VA-RN... with adjustment device VA-RV...

Air distribution systems. Opticlean OC-Q... DS 4136 E /1

Space Air Diffusion II

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

Ceiling diffusers. Type DLQL

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

Installation Instructions

PRODUCT RANGE: ROOFTOP PACKAGE

Installation Instructions

Units for suspended ceilings

INSTALLATION, BALANCING & MAINTENANCE

INSTALLATION & OPERATIONS MANUAL

Displacement Ventilation

Ceiling air diffuser INDULTHERM INDULTHERM-e

AIR HANDLING UNITS ASSET REFERENCE: DESIGN AHU 1 AHU 2

WAILEA OWNER S MANUAL

C o o l i n g a n d h e a t i n g s y s t e m s

When you have a Bonaire ducted gas heater installed, you won t know it is winter until you look out the window Ducted Gas Heating Range

KADO LUX LED EXHAUST FAN 200

Rectangular displacement outlet VA-RN... with adjustment device VA-RV...

Technical Data ISU Series. Underceiling/Console Split System Air Conditioners kw 15 kw

Water Cooled Units HWP 370, 445. Cooling Capacity 36.6kW kW. Heating Capacity 34.9kW kW

Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design

NTD-125-*, NTD-204-* & NTD-220-* Nuaire Round & Rectangular Thermal Ducting Installation Guide

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and

INSTALLATION GUIDE ISODRIVE MOTOR. ST - 900m 3 /hr.

Installation and Care Instructions. Wood Blinds and Alternative Wood Blinds. LiteRise Touch System. Getting Started

Polaris-I-60. active chilled beam. the future of space conditioning

QUANTUM. Reliable solar hot water, whenever you want it

SPACE CONDITIONING IN RESIDENTIAL BUILDINGS

Units for suspended cei lings

Ceiling displacement outlet non-adjustable Q-DN... adjustable Q-DV...

Whole of Home ADD ON. Add some cool comfort to your life. That s better. That s Actron.

INSTALLATION. Glass Panel Doors (select models) CAUTION

RAYCON ENGINEERS PTY LTD. Attic Mounted Whole House Fans. Owner s Manual

VCD,VRD,VSD 4/5 GREEN TEMPERATURE OFFSET FOR WINTER HEATING AND COOLING CHANGEOVER MECHANICAL THERMAL MECHANISM

Type VDW WITH LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH INDIVIDUALLY MANUALLY ADJUSTABLE AIR CONTROL BLADES

contents INTRODUCTION Welcome 1.1 About Us 1.3 Our Service Promise 1.5 DRAWERS, HINGES & ASSEMBLY DEVICES

Technical Data Ducted Three Phase Split System Air Conditioner

CASSETTE TYPE AIR CONDITIONER

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections

Installation and Care Instructions

Gladiator. A specialised high impact resistant luminaire for harsh environments

CEILING FAN OWNER'S MANUAL

FerronTM. Instruction Manual A Kichler Decor ceiling fan

Indirect Evaporative Air Conditioning

iq Star LYRA II chilled beam cassette

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

Air circulation. Xpelair air circulation products are able to provide for your fixed or spot cooling needs throughout the year.

1. SAFETY RULES. 1. To reduce the risk of electric shock, insure electricity has been turned off at the circuit breaker or fuse box before beginning.

Split System AIR CONDITIONING RANGE. Australians love a Kelvinator

Fan Coil Unit CULTRA

MB Therma-Fuser Standalone Motorized Disc VAV Diffuser

ValkyrieTM. Instruction Manual. Includes our new CoolTouch TM 6 Speed DC Control System Looks permanent, but goes wherever you go! U.S.

MBS Therma-Fuser Standalone Motorized Swirl VAV Diffuser

EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units

THE ULTIMATE HEATING + COOLING GUIDE PCRAU0318

STANDARD OPERATING PROCEDURES

Ceiling Fan Installation Instructions

SECTION AIR OUTLETS AND INLETS

The Future In Air Distribution

PERTH SYDNEY MELBOURNE BRISBANE ADELAIDE NEWCASTLE DARWIN MACKAY KALGOORLIE

AXICO ANTI-STALL CONTROLLABLE PITCH-IN-MOTION AND ADJUSTABLE PITCH-AT-REST VANEAXIAL FANS

LaceyTM. Instruction Manual. Includes our new CoolTouch TM 6 Speed DC Control System Looks permanent, but goes wherever you go! U.S.

Cooktop Chimney Ventilation Hoods

DESCRIPTION OF TECHNOLOGY

Technical Data OPA RKTBG-P. Ducted Three Phase Packaged Air Conditioners. 47 kw 96 kw

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION

Technical Data OPA 294, 340, 370. Ducted Three Phase Packaged Air Conditioners kw 34.0 kw 39.1 kw. Twin System Enables Staging

Indirect Evaporative Air Conditioning

Inffusers. idl20 (2 WAY) ids60 (4 WAY)

- Murdoch University, Western Australia.

TLW Therma-Fuser Linear Sidewall Thermally Powered VAV Diffuser

CEILING FAN OWNER'S MANUAL

GIVE A FAN A CHANCE Installation Dos & Don ts

Recessed. Air Curtain. Fig 1. Recessed air curtain

KLIMA Active Chilled Beams

READ AND SAVE THESE INSTRUCTIONS

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

The Corona air inlet TECHNICAL SPECIFICATIONS

Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award

RAPID RESPONSE. Quiet Operation. Powerful Performance. Header Box Exhaust Fan

42AM. Air heaters PRODUCT SELECTION DATA

CEILING FAN OWNER'S MANUAL

RC3-LCD remote control

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

DUOPEX WATER MANUAL mm WM WMKA021044

1. SAFETY RULES WARNING WARNING. 8. Avoid placing objects in the path of the blades.

High Performance Diesel Fueled Cabin Heater. Abstract

CEILING FAN OWNER'S MANUAL

breeze easytm model # F100-1W

Owner s Guide and Installation Manual

42 Kevlar. Instruction Manual. Kichler Lighting 7711 East Pleasant Valley Road P.O. Box Cleveland, Ohio

INSTALLATION DO S AND DON TS

NOVALED. The Revolutionary downlight is re-powered

Transcription:

elevent ceiling diffusers Technical Selection Swirl, Jet, Louvred and Curved ceiling diffusers Paltech elevent Ceiling Diffusers are protected by: Australian Patent 0179430 + other patents pending Australian Registered Designs: 0910888 0910889 0910890 0910891 0910892 0910893 0910894 0910895 0910896 0910897 0910898 0910899 0910900 0910901 0910902 0910903 0911156 0911157 0911158 0911159 0911160 0911161 0911241 0911242 Paltech, elevent and Loc-it-in are registered trademarks Telephone (03) 9212 7777 Fax (03) 9212 7766 Email sales@paltech.com.au Website Copies of this manual available from /datasheets/elevent.pdf 11/02/10

Overview Contents Selector Chart 3 Swirl Technical data 4 Swirl Flow and Pressure Data 6 Swirl Acoustic Data 7 Jet Technical Data 8 Jet Flow and Pressure Data 9 Jet Acoustic Data 10 Jet Throw Data 11 Louvred and Curved Technical Data 12 Louvred Flow and Pressure Data 13 Curved Flow and Pressure Data 14 Curved and Louvred Acoustic Data 15 Curved and Louvred Throw Data 16 Construction and Dimensional Data 17 Mounting and Cleaning Instructions 18 Mounting Clip Instructions 19 BCA insulation requirement tables - 09 BCA insulation requirement tables - 10 21 Ordering information 22 Shipping information 23 Smoke tests 24 Overview Ceiling diffusers for Refrigerated cooling, and reverse cycle heating and cooling Gas ducted heating Air-shifters, ventilation and exhaust Four diffusers styles, three colours, five sizes, some with adjustable direction Swirl, Jet, Louvred, Curved White, Satin Chrome plated, Satin Gold plated Sizes from mm to 300mm Louvred and Curved adjustable direction Two part design Universal adaptor and separate diffuser Adaptor available with optional butterfly dampers Adaptor can be installed and fit-off completed before painting - diffuser can be easily inserted afterwards Diffuser can be easily removed by householder for cleaning or when ceiling is being painted Low profile design Harmonises with modern downlights and recessed light fittings in modern interiors Smaller ceiling footprint for a given duct size and less bulky appearance than traditional diffusers Opportunity to provide additional smaller outlets for improved air distribution Swirl Diffuser Improved supply air mixing performance provides uniform temperature and improved air changes throughout living space for refrigerated and reverse cycle cooling and heating Jet Diffuser High throw, fixed direction, for gas ducted heating, ventilation and exhaust, and for reverse cycle with high ceilings Louvred and Curved High throw with adjustable direction for gas ducted heating, ventilation and exhaust, and for reverse cycle with high ceilings Designed and manufactured in Australia Page 2

Selector Chart Swirl Jet Louvred (adjustable) Curved (adjustable) Gas ducted heating Gas ducted heating with add-on cooling Reverse cycle heating and cooling Reverse cycle heating - high or cathedral ceiling Refrigerated cooling Exhaust grille Warm air shifter inlet Warm air shifter outlet Application selector chart - suggested Elevent type Preferred Possible Page 3

Swirl Technical Data The high induction Swirl diffuser creates high entrainment of room air above the occupancy zone, thereby strongly diluting the supply air with room air. Unlike traditional cone-type ceiling diffusers that produce a steady stream of air that flows radially hugging the ceiling, the elevent Swirl produces a number of rotational jets at a downward angle away from the ceiling. With traditional ceiling diffusers, the slow moving air can suddenly break away from the ceiling, leading to cold air dumping and localised stagnation of air. The effective mixing of the elevent Swirl leads to lower air velocity in the occupancy zone with minimal draughts, uniform temperature through the living space, and high effective air changes. 0 mm Swirl The Swirl vane design has been configured to provide a lower static pressure than typical swirl designs used in commercial installations, in order to improve compatibility and design familiarity with traditional cone type diffusers and multi-directional outlets that are commonly used in the residential market. Swirl diffusers operate at a slightly higher static pressure to cone type diffusers because of the need to force the airflow through the vanes. The different pressure characteristics of the swirl diffusers means that an installation should avoid mixing diffuser types. The stable discharge characteristics of the diffuser over a range of supply air temperatures and velocities means that the diffuser is suitable for refrigerated cooling and heating at ceiling heights of 2.4 to 4 metres. The Swirl diffuser has been optimized for refrigerated cooling and reverse cycle heating in which the supply air is +/- degrees of room temperature and the supply air fan runs continuously. 2 mm Swirl The elevent Swirl has been designed to maximise the most important aspect of the diffuser the airflow and reduce the space requirements of the installation and mounting mechanisms, which can contribute to an obtrusive appearance in other outlets. The result is a small, low profile design with an elegant appearance that harmonises with downlights, recessed light fittings and other ceiling fittings. The elevent Swirl is available in three sizes: 0, 2 and 300mm, and three colours: Ceiling White, Satin Chrome plated and Satin Gold plated. The adaptor has optional butterfly dampers for system balancing. The outlet face can be easily removed from the fixed adaptor by hand for cleaning, or to enable the ceiling to be painted, ensuring a neat painted finish around the outlet. 300 mm Swirl Page 4

elevent Ceiling Diffusers 1311-1900 Swirl Technical Data Mixing zone Room air becomes entrained with supply air Turbulent flow increasing mixing of supply and room air Occupancy zone Supply air transfers momentum to room air, increasing mixing, and decreasing temperature gradient The elevent Swirl jets air from a multitude of jets in a vortex motion at an angle of 40 o from horizontal, and radially away from the centre of the diffuser. The jets entrain the room air, dragging it along in a turbulent motion. The entrained room air continues moving, further entraining more room air until all momentum is lost The result is thorough mixing of the supply and room air, which occurs primarily in the mixing zone above the occupancy zone. Further low intensity mixing is accomplished by the continual airflow created by the system fan drawing air back to the return air grille. Page 5

elevent Ceiling Diffusers 1310 1311-1900 Swirl Flow and Pressure Data Volumetric flow rate V max @ Pa Discharge height l/s m 3 /h m 0 1 540 2.2-6.0 2 240 864 2.2-6.0 300 380 1368 2.2-6.0 0 Static pressure (Pa) 40 30 0 mm Swirl 2 mm Swirl 300 mm Swirl 15 10 5 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 6

elevent Ceiling Diffusers 1310 1311-1900 Swirl Acoustic Data Sound power level db(a) ref. 10-12 W 40 30 0 mm Swirl 2 mm Swirl 300 mm Swirl 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 7

Jet Technical Data The elevent Jet diffuser jets air vertically downward with low static pressure, creating high entrainment of room air within the occupancy zone. The diffuser is suitable for gas ducted heating, reverse cycle heating for very high ceilings, air shifters and ventilation systems as a supply or return diffuser. The jet has a longer throw than DownJets, and like DownJets, consideration needs to be given to diffuser placement within the living space to avoid draughts. mm Jet In gas ducted heating applications, the supply air is typically 30 to degrees above room temperature, with fan cycling. Ceiling diffusers need to penetrate the occupancy zone with supply air, and encourage convective currents to mix the warm supply air with the cooler room air throughout the living space. For gas ducted heating applications, installers have the opportunity of using multiple smaller outlets, including a mm model, instead of a single outlet to provide improved distribution of warm air. The use of multiple small outlets provides the opportunity to strategically place the outlets in room positions that will maximise heating effectiveness, such as near the two corners of a bedroom opposite the door. A maximum length of 3 metres of duct from the branch is recommended when using mm diffusers to avoid high static pressure within the duct. 1 mm Jet The elevent Jet has been designed to maximise the most important aspect of the diffuser the airflow and reduce the space requirements of the installation and mounting mechanisms, which can contribute to an obtrusive appearance in other outlets. The result is a small, low profile design with an elegant appearance that harmonises with downlights, recessed light fittings and other ceiling fittings. The elevent Jet is available in three sizes:, 1 and 0mm, and three colours: Ceiling White, Satin Chrome plated and Satin Gold plated. The adaptor has optional butterfly dampers for system balancing on the 1 and 0mm sizes, and a blanking cap is available on the mm model to replace the diffuser when shut-off is required. The outlet face can be easily removed from the fixed adaptor by hand for cleaning, or to enable the ceiling to be painted, ensuring a neat painted finish around the outlet. 0 mm Jet Ideally, equal lengths of ductwork should be used from the branch to each outlet when using the mm model if equal airflow is desired. The elevent Jet has low static pressure and consideration needs to be given to system design if mixing the Jet with Louvred and/or Curved elevent diffusers. Equalisation can be achieved by the use of shorter duct lengths and fewer bends on the branches with Louvred and/or Curved. Page 8

elevent Ceiling Diffusers 1310 1311-1900 Jet Flow and Pressure Data V max with 3 metres of duct and 90 o bend @ Pa Discharge height l/s m 3 /h m 55 198 2.2-6.0 1 140 4 2.2-6.0 0 300 1080 2.2-6.0 Static pressure (Pa) 0 40 30 15 mm Jet with 3 metres duct including 90 degree bend 0 mm from outlet 1 mm Jet with 3 metres duct including 90 degree bend 0 mm from outlet mm Jet 0 mm Jet with 3 metres duct including 90 degree bend 0 mm from outlet 1 mm Jet 0 mm Jet 10 5 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 9

elevent Ceiling Diffusers 1310 1311-1900 Jet Acoustic Data Sound power level db(a) ref. 10-12 W 40 30 Note: the Jet diffusers have a low static pressure profile which contributes to a low sound power level. If consideration is being given to sound power level, the contribution from the associated ductwork is likely to be greater. mm Jet 1 mm Jet 0 mm Jet 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 10

elevent Ceiling Diffusers 1310 1311-1900 Jet Throw Data v = 5.0 m/s 0.0 m 14 o v = 2.2 m/s 1.4 m 0.25 m/s v = 1.6 m/s 0.25 m/s 1.8 m 600 mm v = 1.0 m/s 2.2 m Typical isothermal throw profile of Jet ( mm @ 40 l/s) Isothermal throw (metres) @ 0.3 m/s terminal velocity Airflow (l/s) mm Jet 1 mm Jet 0 mm Jet 25 2.8 1.4 1.1 5.0 2.8 2.1 75 3.9 2.9 5.0 3.6 1 6.8 4.7 0 5.2 Page 11

Louvred and Curved Technical Data The Louvred and Curved are adjustable direction ceiling diffusers that produce a stream of air at around 30 degrees from the vertical, with long throw. They are suitable for gas ducted heating, reverse cycle heating with very high ceilings, air shifting and ventilation. The airflow direction can be adjusted by the householder to provide draught free airflow within the living space. With the damper set to open, the diffusers have low static pressure. The Louvred and Curved has a longer throw than DownJets, and like DownJets, consideration needs to be given to diffuser placement within the living space to avoid draughts. mm Curved In gas ducted heating applications, the supply air is typically 30 to degrees above room temperature, with fan cycling. Ceiling diffusers need to penetrate the occupancy zone with supply air, and encourage convective currents to mix the warm supply air with the cooler room air throughout the living space. In one placement configuration, the diffusers can be directed towards a wall to encourage convection currents within the room. Installers have the opportunity of using multiple smaller outlets, including a mm model, instead of a single outlet to provide improved distribution of air. The use of multiple small outlets provides the opportunity to place the outlets in room positions that will maximise heating effectiveness, such as near the two corners of a bedroom opposite the door. A maximum length of 3 metres of duct from the branch is recommended when using mm diffusers to avoid high static pressure within the duct. 1 mm Louvred The elevent Louvred and Curved has been designed to maximise the most important aspect of the diffuser the airflow and reduce the space requirements of the installation and mounting mechanisms, which can contribute to an obtrusive appearance in other outlets. The result is a small, low profile design with an elegant appearance that harmonises with downlights, recessed light fittings and other ceiling fittings. The elevent Louvred and Curved is available in three sizes:, 1 and 0mm, and three colours: Ceiling White, Satin Chrome plated and Satin Gold plated. The adaptor has optional butterfly dampers for system balancing on the 1 and 0mm sizes, and a blanking cap is available on the mm model to replace the diffuser when shut-off is required. The outlet face can be easily removed from the fixed adaptor by hand for cleaning, or to enable the ceiling to be painted, ensuring a neat painted finish around the outlet. 0 mm Curved Ideally, equal lengths of ductwork should be used from the branch to each outlet when using the mm model if equal airflow is desired. The Louvred and Curved have higher static pressure than the Jet and consideration needs to be given to system design if mixing the Louvred/Curved with the Jet. Equalisation can be achieved by the use of shorter duct lengths and less bends on the branches with Louvred and/or Curved. Page 12

elevent Ceiling Diffusers 1310 1311-1900 Louvred Flow and Pressure Data V max with 3 metres of duct and 90 o bend @ Pa Discharge height l/s m 3 /h m 45 162 2.2-6.0 1 85 306 2.2-6.0 0 230 828 2.2-6.0 Static pressure (Pa) 0 40 30 15 mm Louvred with 3 metres duct including 90 degree bend 0 mm from outlet mm Louvred 1 mm Louvred with 3 metres duct including 90 degree bend 0 mm from outlet 1 mm Louvred 0 mm Louvred with 3 metres duct including 90 degree bend 0 mm from outlet 0 mm Louvred 10 5 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 13

elevent Ceiling Diffusers 1310 1311-1900 Curved Flow and Pressure Data V max with 3 metres of duct and 90 o bend @ Pa Discharge height l/s m 3 /h m 42 151 2.2-6.0 1 80 288 2.2-6.0 0 2 792 2.2-6.0 Static pressure (Pa) 0 40 30 15 mm Curved with 3 metres duct including 90 degree bend 0 mm from outlet mm Curved 1 mm Louvred with 3 metres duct including 90 degree bend 0 mm from outlet 1 mm Curved 0 mm Curved with 3 metres duct including 90 degree bend 0 mm from outlet 0 mm Curved 10 5 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 14

elevent Ceiling Diffusers 1310 1311-1900 Louvred and Curved Acoustic Data Sound power level db(a) ref. 10-12 W 40 30 mm Louvred and Curved 1 mm Louvred and Curved 0 mm Louvred and Curved 30 40 0 400 l/s 0 300 400 600 800 0 m 3 /h Page 15

elevent Ceiling Diffusers 1310 1311-1900 Louvred and Curved Throw Data 60 o v = 5.0 m/s 0.0 m 0.25 m/s 12 o 0.25 m/s v = 1.0 m/s Typical isothermal throw profile of Louvred ( mm @ 40 l/s) 2.2 m Isothermal throw (metres) @ 0.3 m/s terminal velocity Airflow (l/s) mm Jet 1 mm Jet 0 mm Jet 25 3.0 1.6 1.3 5.2 3.0 2.3 75 4.1 3.1 5.2 3.8 1 7.1 4.9 0 5.5 Page 16

Construction and Dimensional Data A Construction C D E B The diffuser faces are constructed of ABS polymers, and are suitable for heated air up to 80 o C and cooled air down to 0 o C. All sizes except for mm can be supplied with butterfly dampers installed in the adaptor for balancing. The mm has an optional shut-off face, which can be inserted by the householder/occupier in place of any of the standard faces to shut-off a room or area. The Swirl is available in three sizes: 0, 2 and 300mm. The Jet, Louvred and Curved types are available in three sizes:, 1 and 0mm. F mm (4 inch) 1 mm (6 inch) 0 mm (8 inch) 2 mm (10 inch) 300 mm (12 inch) Diffuser (all types) overall diameter Diffuser (all types) height Diffuser (all types) collar outer diameter Adaptor overall diameter Adaptor height Adaptor mid-taper collar diameter A 140 190 240 329 379 B 37 42 49 49 49 C 104 154 4 283 333 D 135 183 235 324 374 E 130 132 155 167 192 F 102 152 3 254 305 Hole size 122 172 222 300 3 Page 17

Mounting and Cleaning Instructions Maximum span between hanging: 1.5 m, from AS/NZS 4254:02 part 2.8.5 (a) Minimum mm straight section AS/NZS 4254:02 part 2.8.5 (c) R Both the BCA(09), J5.2, part 2 (a) and AS/NZS 4254:02, 2.8.4 require joint to be taped, and secured with a draw band Duct velocity V < 5 m/s (most common) R/D ratio R D mm 1 mm Duct diameter (D) 0 mm 2 mm 300 mm =0.6 R=60 R=90 R=1 R=1 R=180 R 5 < V < 8 m/s =1.0 R= R=1 R=0 R=2 R=300 D R V > 8 m/s =1.5 R=1 R=225 R=300 R=375 R=4 D Minimum required bend radius Table from AS/NZS 4254:02 Part 2.8.5 (h) Installation 1. Mark and cut hole - holesaws are available for some sizes. 2. Pull duct through hole from above. 3. Attach duct to adaptor to AS/NZS 4254 part 2.8.4, using adhesive tape and draw band 4. Pull mounting clips inwards towards centre of adaptor. 5. Push adaptor and duct up through hole in plaster board. 6. With one hand on the adaptor and pushing adaptor against plaster board: a) Move mounting clip upward. b) Push mounting clip about half-way in. c) Bring mounting clip down towards top of plaster board. d) When the clip reaches the plaster board, push the clip inwards firmly. e) Repeat for all clips. 7. Put diffuser against adaptor and rotate until mounting slots correspond to grooves in adaptor. 8. Push diffuser into adaptor firmly until it clicks. The elevent adaptor is designed for use with plaster or panel board from 5 to mm thickness. For panels up to 30 mm, the top of the mounting clips can be cut off to increase the available panel thickness. Removal of adaptor 1. Remove diffuser from adaptor by placing two fingers into the diffuser and pulling firmly. 2. Using a narrow flat blade screwdriver, gently lever mounting clip inwards. 3. Repeat for all clips. Painting and fit-off The ceiling can be painted with the adaptor installed, and the diffuser pushed in afterwards. Each size of the elevent shares the same adaptor, so the diffuser style or colour can be changed after installation. Cleaning The diffuser can be removed by placing two fingers into the diffuser and pulling down. The diffuser can be cleaned with warm water and non-abrasive cleaning cloths and solutions. Extra care should be given to Satin Chrome and Satin Gold colours to avoid scratching the surface. Page 18

Mounting Clip Instructions After placing adaptor in hole, move mounting clip upward and pull inwards. With adaptor in position, push mounting clip about half-way in. While holding adaptor firmly against plaster, bring clip downwards until it stops against the plaster. While continuing to push adaptor against plaster, push clip in 90% of the way. Repeat for all the clips. If the adaptor is holding firmly against the plaster, push all clips in the rest of the way. However if any edges are sagging, repeat the process to ensure all clips are tight. To remove, place small flat blade screwdriver under clip. Gently level clip inwards. Page 19

Australian Building Code (BCA 09) Insulation Tables For systems up to 65 kw (most domestic systems) Evaporative cooling system Heating-only system or refrigerated cooling-only system Combined heating and refrigerated cooling system All climate zones s 1,3,4,6 and 7 2 and 5 8 1,3,4,6 and 7 2 and 5 8 Melbourne Sydney East Melbourne Sydney East Sydney West Canberra Brisbane SE coast Qld Alpine regions of Victoria and NSW Sydney West Canberra Brisbane SE coast Qld Far north Qld Adelaide Far north Qld Adelaide Country Vic. except alpine Perth Country Vic. except alpine Perth Alpine regions of Victoria and NSW Tasmania Tasmania Ductwork R t 0.6 1.0 1.0 1.5 1.5 1.0 1.5 Fittings R t 0.4 Data current for 09 BCA - current table available at - go to datasheets, duct, BCA Complete climate zone data available from: http://www.abcb.gov.au/go/whatweredoing/workprogram/projectsae/energy/eemaps For systems over 65 kw Evaporative cooling system Heating system or refrigerated cooling system All climate zones s 1, 3 and 4 2 and 5 6 and 7 8 Ductwork and fittings R t - within a conditioned space Ductwork and fittings R t - all other locations Darwin Sydney East Melbourne Inland and arid Australia Far north Qld Brisbane SE coast QLD Adelaide Perth Sydney West Canberra Country Vic. except alpine Tasmania Alpine regions of Victoria and NSW Nil 1.0 1.0 1.3 1.5 0.9 1.8 1.5 1.8 2.0 Data current for 09 BCA - current table available at - go to datasheets, duct, BCA Complete climate zone data available from: http://www.abcb.gov.au/go/whatweredoing/workprogram/projectsae/energy/eemaps Page

Australian Building Code (draft BCA 10) Insulation Tables For class 1 buildings (houses etc.) Heating-only system or cooling-only system, including evaporative Combined heating and refrigerated cooling system s 1,3,4,6 and 7 2 and 5 8 1,3,4,6 and 7 2 and 5 8 Melbourne Sydney East Melbourne Sydney East Sydney West Canberra Brisbane SE coast Qld Alpine regions of Victoria and NSW Sydney West Canberra Brisbane SE coast Qld Far north Qld Adelaide Far north Qld Adelaide Country Vic. except alpine Perth Country Vic. except alpine Perth Alpine regions of Victoria and NSW Tasmania Tasmania Ductwork - insulation R 1.0 1.0 1.5 1.5 1.0 1.5 Fittings R t 0.4 Data current for 09 BCA - current table available at - go to datasheets, duct, BCA Complete climate zone data available from: http://www.abcb.gov.au/go/whatweredoing/workprogram/projectsae/energy/eemaps For class 2 to 9 buildings (commercial etc.) with > 10 kw Heating system or refrigerated cooling system 1, 2, 3 and 5 4, 6 and 7 8 Ductwork and fittings - insulation R - within a conditioned space Ductwork and fittings - insulation R - exposed to direct sunlight Ductwork and fittings - insulation R - all other locations Sydney East Brisbane SE coast QLD Adelaide Perth Melbourne Sydney West Canberra Country Vic. except alpine Tasmania Alpine regions of Victoria and NSW 1.2 1.0 1.6 3.0 3.0 3.4 2.0 2.0 2.4 Data current for 09 BCA - current table available at - go to datasheets, duct, BCA Complete climate zone data available from: http://www.abcb.gov.au/go/whatweredoing/workprogram/projectsae/energy/eemaps Page 21

Ordering Information Qty. per box mm (4 inch) 1mm (6 inch) 0mm (8 inch) 2mm (10 inch) 300mm (12 inch) Adaptor 1311 1321 1331 1341 1351 Adaptor with Damper set 1322 1332 1342 1352 Damper set 1323 1333 1343 1353 Blank Cap 1312 Swirl White (standard) Swirl Satin Chrome Swirl Satin Gold Jet White (standard) Jet Satin Chrome Jet Satin Gold Louvred White (standard) Louvred Satin Chrome Louvred Satin Gold Curved White (standard) Curved Satin Chrome Curved Satin Gold Holesaw and arbour 1731 1741 1751 1732 1742 1752 1733 1743 1753 1411 1421 1431 1412 1422 1432 1413 1423 1433 1511 1521 1531 1512 1522 1532 1513 1523 1533 1611 1621 1631 1612 1622 1632 1613 1623 1633 1 1314 1324 Page 22

Shipping Information Mass (kg) Volume (m 3 ) Size (mm) Units per box Unit Box Dimensions Box Adaptor without dampers - 1311 Adaptor without dampers - 1321 Adaptor with dampers - 1322 Adaptor without dampers - 1331 Adaptor with dampers - 1332 Adaptor without dampers - 1341 Adaptor with dampers - 1342 Adaptor without dampers - 1351 Adaptor with dampers - 1352 0.14 2.8 1 x 467 x 572 0.040 1 0.21 4.2 375 x 375 x 560 0.079 1 0.25 4.9 375 x 375 x 560 0.079 0 0.31 6.1 490 x 490 x 670 0.161 0 0.39 7.7 490 x 490 x 670 0.161 2 0.43 8.6 345 x 632 x 740 0.162 2 0.55 11.0 345 x 632 x 740 0.162 300 0.57 11.4 425 x 735 x 7 0.235 300 0.74 14.8 425 x 735 x 7 0.235 Elevent 0.11 2.1 1 x 390 x 272 0.016 Elevent 1 0.18 3.5 5 x 370 x 430 0.033 Elevent 0 0.22 4.4 260 x 470 x 5 0.062 Elevent 2 0.38 7.6 340 x 495 x 645 0.109 Elevent 300 0. 10.0 392 x 0 x 745 0.146 Page 23

Comparative Smoke Tests Elevent Jet mm Elevent Louvred mm Elevent Curved mm Downjet 1mm Multi Directional Outlet 230 x 230 Cone Ceiling Diffuser 0mm Elevent Swirl 0mm Page 24