Sigler Southern California 205 S. Puente St. Brea, CA 92821 PH: 714-578-5100 Salesman: Tim Dres SUBMITTAL DATA PROJECT: LAUSD South Region High School 15 MECHANICAL CONTRACTOR: Mechanical Technology Systems Attn: Russ We are pleased to submit the following equipment for your approval on the above project: Mark For Qty Model Number Description PAC-A1 1 48A2M020-AC611HJ 20 Ton Gas Heat Packaged Unit w/ R-410a 460-3-60 Stainless Steel Drain Pan Dry-Bulb Economizer Modulating Power Exhaust CV Vertical ComfortLink w/puron Low Gas Heat S.S. Heat Exch High Efficiency 5 HP Motor Cu/Cu Cond, Cu/Cu Evap PAC- 3 48TCSD14A2F6-0A0A0 12.5 Ton Gas Heat Packaged Unit w/ R-410a 460-3-60 A2,B1,B3 Stainless Steel, Low Heat HX Medium Static Option Cu/Cu - Cu/Cu Hinged Access Panels PAC- 3 CRFLUEDS001A00 Flue Discharge Deflector A2,B1,B3 PAC- 3 4682-0203-MA930 Mod. Power Exhaust/Economizer A2,B1,B3 PAC-B2,D3, 5 48HCSA07A2F6-0A3A0 6 Ton High Eff. Gas Heat Packaged Unit w/ R-410a 460-3-60 D6,E7,F7 Stainless Steel, Low Heat HX Medium Static Option - Belt Drive Cu/Cu - Cu/Cu Hinged Access Panels PAC-B2,D3, 5 CRFLUEDS001A00 Flue Discharge Deflector D6,E7,F7 PAC-D3 1 4682-0203-1/2-MA930 Mod. Power Exhaust/Economizer PAC-B2,D6, 4 0688HJ712DBEC DOWN DISCHARGE FIXED DRY BULB ECONOMIZER E7,F7 PAC-C1,C2 2 48A2M035-DC611HJ 35 Ton Gas Heat Packaged Unit w/ R-410a 460-3-60 Stainless Steel Drain Pan Dry-Bulb Economizer Modulating Power Exhaust CV Vertical ComfortLink w/puron Low Gas Heat S.S. Heat Exch High Efficiency 15 HP Motor Cu/Cu Cond, Cu/Cu Evap PAC-C3,C4, 5 48HCSD08A2F6-0A3A0 7.5 Ton High Eff. Gas Heat Packaged Unit w/ R-410a 460-3-60 D2,E8,F8 Stainless Steel, Low Heat HX Medium Static Option - Belt Drive Cu/Cu - Cu/Cu Electro-mechanical controls Hinged Access Panels
PAC-C3,C4, 5 CRFLUEDS001A00 Flue Discharge Deflector D2,E8,F8 PAC-C3,C4, 5 4682-0203-MA930 Mod. Power Exhaust/Economizer D2,E8,F8 PAC-D1 1 48A4M020-AC611EF 20 Ton Gas Heat Packaged Unit w/ R-410a 460-3-60 Stainless Steel Drain Pan Dry-Bulb Economizer CV Horizontal ComfortLink w/puron Low Gas Heat S.S. Heat Exch High Efficiency 5 HP Motor Cu/Cu Cond, Cu/Cu Evap PAC-D1 1 1090-1102-MA910 Modulating Power Exhaust PAC-D4,D5, 12 48HCLA05A2F6-0A3A0 4 Ton High Eff. Gas Heat Packaged Unit w/ R-410a 460-3-60 E1-5,F1-5 Low NOx, Low Heat Medium Static Option - Belt Drive Cu/Cu - Cu/Cu Hinged Access Panels PAC-D4,D5, 12 CRFLUEDS001A00 Flue Discharge Deflector E1-5,F1-5 PAC-D4,D5, 12 0688HJ36DBEC DOWN DISCHARGE FIXED DRY BULB ECONOMIZER E1-5,F1-5 PAC-E6,F6 2 48HCLA06A2F6-0A3A0 5 Ton High Eff. Gas Heat Packaged Unit w/ R-410a 460-3-60 Low NOx, Low Heat Medium Static Option - Belt Drive Cu/Cu - Cu/Cu Hinged Access Panels PAC-E6,F6 2 CRFLUEDS001A00 Flue Discharge Deflector PAC-E6,F6 2 0688HJ36DBEC DOWN DISCHARGE FIXED DRY BULB ECONOMIZER FCU-2 Ton 14 24HBX0-120-W/R410ATXV 2 Ton First Co Modular AHU 115V - Coated Coil CU-2 Ton 14 24ABB324C003 2 Ton Air Conditioner w/ R-410a and Coastal Option 208-1-60 FCU-3 Ton 6 36HBX0-120-W/R410ATXV 3 Ton First Co Modular AHU 115V - Coated Coil CU-3 Ton 6 24ABB336C003 3 Ton Air Conditioner w/ R-410a and Coastal Option 208-1-60 CU-B1-3,4 2 38AUQA12A0C6-0A0A0 10 Ton Heat Pump w/ R-410a 460-3-60 Factory E-Coated Al/Cu Coil CU-C1-5,6 2 24ABB360C003 5 Ton Air Conditioner w/ R-410a and Coastal Option 208-1-60 FCU-2 Ton 14 24VHBX0-120-W/R410ATXV 2 Ton First Co Modular AHU 115V - Coated Coil HP-2 Ton 14 25HBB324C003 2 Ton Heat Pump w/ R-410a and Coastal Option 208-1-60 FCU-3 Ton 2 36VHBX0-120-W/R410ATXV 3 Ton First Co Modular AHU 115V - Coated Coil HP-3 Ton 2 25HBB336C003 3 Ton Heat Pump w/ R-410a and Coastal Option 208-1-60 FCU-4 Ton 8 60VHBX0-120-W/R410ATXV 4,5 Ton First Co Modular AHU 115V - Coated Coil HP-4 Ton 8 25HBB348C003 4 Ton Heat Pump w/ R-410a and Coastal Option 208-1-60 HP-E1-5 2 38AUQA08A0C6-0A0A0 7.5 Ton Heat Pump w/ R-410a 460-3-60 and F1-5 Factory E-Coated Al/Cu Coil HP-E1-5 2 40RUQA08A1A6-0A0A0 7.5 Ton Heat Pump Air Handler 208/230/460-3-60 - Coated Coil and F1-5 ALL FCUs 46 BLYGOLDEVAPCOAT Blygold Evap Coatings - All Fan Coil NOTE: A COPY OF THIS SUBMITTAL MUST BE RETURNED MARKED APPROVED OR APPROVED AS NOTED PRIOR TO OUR ENTERING FACTORY ORDER. Carrier of Southern California, Inc. August 5, 2010
Performance Summary For PAC-A1 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number: 48A2M020-AC611HJ Unit Refrigerant: R410A EER (ARI 360): 10.1 IEER: 11.4 Shipping Dimensions Unit Length: 13' 9'' Unit Width: 7' 10'' Unit Height: 6' 1'' Unit Shipping Weight: 4711.0 lb Unit Supply/Return: Vertical/Vertical Application Type: CV 2-stage Voltage: 460-3-60 Cooling Airflow: 6000 CFM Altitude: 0 ft Cond. Ent. Air Temp: 94.0 F Ent. Air Dry Bulb: 82.6 F Ent. Air Wet Bulb: 66.5 F Ent. Air Enthalpy: 31.02 BTU/lb Lvg. Air Dry Bulb: 55.1 F Lvg. Air Wet Bulb: 53.2 F Lvg. Air Enthalpy: 22.10 BTU/lb Gross Cooling Capacity: 240.89 MBH Gross Sensible Clg. Cap: 178.19 MBH Compressor Power: 18.0 kw Coil Bypass Factor: 0.17 Part Load(%) Operation Standard Capacity Steps: 30,100 Gas Heating Data: Heating Airflow: 6000 CFM Heating Ent. Air Temp: 52.6 F Gas Input (Min): 265.6 MBH Gas Input (Max): 350 MBH Gas Output: 287 MBH Heating Lvg. Air Temp: 96.9 F Steady State Eff: 82 Temp.Rise: 44.3 F Supply Fan Information: Ext.Static Pressure: 2.50 in wg Selection External Static Pressure: 2.50 in wg Supply Fan RPM: 909 Supply Fan BHP: 4.62 BHP Supply Fan Motor HP: 05 HP Power Exhaust Fan Information: P.E./R.F. Airflow: 4200 CFM P.E./R.F. Ext. Static: 0.50 in wg P.E./R.F. Tot. Static: 1.14 in wg Electrical Data Minimum Voltage: 414 Maximum Voltage: 508 Compressor #A1 RLA: 10.6 Compressor #A1 LRA: 75 Compressor #A2 RLA: 10.6 Compressor #A2 LRA: 75 Compressor #B1 RLA: 14.7 Compressor #B1 LRA: 95 Indoor Fan Motor HP: 5 Indoor Fan Motor FLA: 7.6 Condenser Fan Motor Qty: 2 Applied Rooftop Builder 2.09 Page 27 of 34
Performance Summary For PAC-C1,C2 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number: 48A2M035-DC611HJ Unit Refrigerant: R410A EER (ARI 360): 10.0 IEER: 11.8 Shipping Dimensions Unit Length: 13' 9'' Unit Width: 7' 10'' Unit Height: 6' 1'' Unit Shipping Weight: 5399.0 lb Unit Supply/Return: Vertical/Vertical Application Type: CV 2-stage Voltage: 460-3-60 Cooling Airflow: 12000 CFM Altitude: 0 ft Cond. Ent. Air Temp: 94.0 F Ent. Air Dry Bulb: 76.8 F Ent. Air Wet Bulb: 68.8 F Ent. Air Enthalpy: 32.93 BTU/lb Lvg. Air Dry Bulb: 58.0 F Lvg. Air Wet Bulb: 58.0 F Lvg. Air Enthalpy: 25.26 BTU/lb Gross Cooling Capacity: 414.23 MBH Gross Sensible Clg. Cap: 244.28 MBH Compressor Power: 30.9 kw Coil Bypass Factor: 0.019 Part Load(%) Operation Standard Capacity Steps: 50,100 Gas Heating Data: Heating Airflow: 12000 CFM Heating Ent. Air Temp: 67.6 F Gas Input (Min): 262.5 MBH Gas Input (Max): 350 MBH Gas Output: 283.5 MBH Heating Lvg. Air Temp: 89.5 F Steady State Eff: 81 Temp.Rise: 21.9 F Supply Fan Information: Ext.Static Pressure: 1.25 in wg Selection External Static Pressure: 1.25 in wg Supply Fan RPM: 980 Supply Fan BHP: 10.44 BHP Supply Fan Motor HP: 15 HP Power Exhaust Fan Information: P.E./R.F. Airflow: 10800 CFM P.E./R.F. Ext. Static: 0.50 in wg P.E./R.F. Tot. Static: 0.13 in wg Electrical Data Compressor #A1 RLA: 10.6 Compressor #A1 LRA: 75 Compressor #A2 RLA: 10.6 Compressor #A2 LRA: 75 Compressor #B1 RLA: 16.7 Compressor #B1 LRA: 114 Compressor #B2 RLA: 16.7 Compressor #B2 LRA: 114 Indoor Fan Motor HP: 15 Indoor Fan Motor FLA: 21 Condenser Fan Motor Qty: 2 Applied Rooftop Builder 2.09 Page 29 of 34
Base unit dimensions 48A2,A3020-035 NOTES: 1. Weights include economizer. 2. center of gravity. 3. Unit clearances: Top of units: no overhang Condenser coil: 4-0 [1219] Economizer side: 6-0 [1829] Heat side: 4-0 [1219] Filter access side: 10-0 [3048] (for removal of evaporator coil) 4. For smaller service and operational clearances, contact Carrier application engineering department. 5. Bottom ducts are designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended that the ducts be supported by cross braces as done on accessory roof curb. 6. Dimensions in [ ] are in millimeters. All other dimensions are in inches. *Operating weight includes largest indoor fan motor, microchannel heat exchanger, modulating power exhaust (variable air volume units), and variable frequency drive (variable air volume units). a48-8342 19
Performance Summary For PAC-D1 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number: 48A4M020-AC611EF Unit Refrigerant: R410A EER (ARI 360): 10.1 IEER: 11.4 Shipping Dimensions Unit Length: 13' 9'' Unit Width: 7' 10'' Unit Height: 6' 1'' Unit Shipping Weight: 4251.0 lb Unit Supply/Return: Horizontal/Horizontal Application Type: CV 2-stage Voltage: 460-3-60 Cooling Airflow: 6600 CFM Altitude: 0 ft Cond. Ent. Air Temp: 94.0 F Ent. Air Dry Bulb: 84.3 F Ent. Air Wet Bulb: 67.8 F Ent. Air Enthalpy: 32.05 BTU/lb Lvg. Air Dry Bulb: 57.9 F Lvg. Air Wet Bulb: 55.7 F Lvg. Air Enthalpy: 23.61 BTU/lb Gross Cooling Capacity: 250.70 MBH Gross Sensible Clg. Cap: 188.12 MBH Compressor Power: 18.1 kw Coil Bypass Factor: 0.183 Part Load(%) Operation Standard Capacity Steps: 30,100 Gas Heating Data: Heating Airflow: 6600 CFM Heating Ent. Air Temp: 41.0 F Gas Input (Min): 265.6 MBH Gas Input (Max): 350 MBH Gas Output: 287 MBH Heating Lvg. Air Temp: 81.3 F Steady State Eff: 82 Temp.Rise: 40.3 F Supply Fan Information: Ext.Static Pressure: 1.50 in wg Selection External Static Pressure: 1.50 in wg Supply Fan RPM: 763 Supply Fan BHP: 4.12 BHP Supply Fan Motor HP: 05 HP Electrical Data Minimum Voltage: 414 Maximum Voltage: 508 Compressor #A1 RLA: 10.6 Compressor #A1 LRA: 75 Compressor #A2 RLA: 10.6 Compressor #A2 LRA: 75 Compressor #B1 RLA: 14.7 Compressor #B1 LRA: 95 Indoor Fan Motor HP: 5 Indoor Fan Motor FLA: 7.6 Condenser Fan Motor Qty: 2 Condenser Fan Motor FLA (ea): 3.3 Power Supply MCA: 53.8 Power Supply MOCP (Fuse or HACR): 60 Electrical Convenience Outlet: None Acoustic Information Applied Rooftop Builder 2.09 Page 31 of 34
Base unit dimensions 48A4,A5020-035 NOTES: 1. Weights include economizer. 2. center of gravity. 3. Unit clearances: Top of units: no overhang Condenser coil: 4-0 [1219] Economizer side: 6-0 [1829] Heat side: 4-0 [1219] Filter access side: 10-0 [3048] (for removal of evaporator coil) 4. For smaller service and operational clearances, contact Carrier application engineering department. 5. Dimensions in [ ] are in millimeters. All other dimensions are in inches. *Operating weight includes largest indoor fan motor, microchannel heat exchanger, modulating power exhaust (variable air volume units), and variable frequency drive (variable air volume units). a48-8345 22
Performance Summary For PAC-A2 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48TCSD14A2F6-0A0A0 ARI EER: 10.80 IEER: 11.0 Base Unit Weight: 1118 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 4250 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 80.3 F Evaporator Entering Air WB: 64.1 F Entering Air Enthalpy: 29.20 BTU/lb Evaporator Leaving Air DB: 55.8 F Evaporator Leaving Air WB: 52.9 F Evaporator Leaving Air Enthalpy: 21.88 BTU/lb Gross Cooling Capacity: 139.87 MBH Gross Sensible Capacity: 112.44 MBH Compressor Power Input: 10.10 kw Coil Bypass Factor: 0.208 Heating Performance Heating Airflow: 4250 CFM Entering Air Temp: 61.1 F Leaving Air Temp: 93.3 F Gas Input Capacity: 120.0 / 180.0 MBH Gas Heating Capacity: 147.60 MBH Temperature Rise: 32.2 F NOTE: Second Stage Supply Fan External Static Pressure: 0.75 in wg Fan RPM: 963 Fan Power: 2.68 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Compressor #2 RLA: 10.6 Compressor #2 LRA: 75 Outdoor Fan Motor Qty: 1 Outdoor Fan FLA (ea): 3.1 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 4.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 30.5 Power Supply MOCP (Fuse or HACR): 40 Min. Unit Disconnect FLA: 32 Min. Unit Disconnect LRA: 190 Electrical Convenience Outlet: None Acoustics Packaged Rooftop Builder 1.20 Page 1 of 34
Performance Summary For PAC-B1 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48TCSD14A2F6-0A0A0 ARI EER: 10.80 IEER: 11.0 Base Unit Weight: 1118 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 4250 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 82.1 F Evaporator Entering Air WB: 65.2 F Entering Air Enthalpy: 30.02 BTU/lb Evaporator Leaving Air DB: 57.2 F Evaporator Leaving Air WB: 54.1 F Evaporator Leaving Air Enthalpy: 22.58 BTU/lb Gross Cooling Capacity: 142.21 MBH Gross Sensible Capacity: 114.34 MBH Compressor Power Input: 10.10 kw Coil Bypass Factor: 0.213 Heating Performance Heating Airflow: 4250 CFM Entering Air Temp: 57.4 F Leaving Air Temp: 89.6 F Gas Input Capacity: 120.0 / 180.0 MBH Gas Heating Capacity: 147.60 MBH Temperature Rise: 32.2 F NOTE: Second Stage Supply Fan External Static Pressure: 0.75 in wg Fan RPM: 963 Fan Power: 2.68 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Compressor #2 RLA: 10.6 Compressor #2 LRA: 75 Outdoor Fan Motor Qty: 1 Outdoor Fan FLA (ea): 3.1 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 4.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 30.5 Power Supply MOCP (Fuse or HACR): 40 Min. Unit Disconnect FLA: 32 Min. Unit Disconnect LRA: 190 Electrical Convenience Outlet: None Acoustics Packaged Rooftop Builder 1.20 Page 3 of 34
Performance Summary For PAC-B3 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48TCSD14A2F6-0A0A0 ARI EER: 10.80 IEER: 11.0 Base Unit Weight: 1118 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 3900 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 75.6 F Evaporator Entering Air WB: 63.6 F Entering Air Enthalpy: 28.86 BTU/lb Evaporator Leaving Air DB: 53.2 F Evaporator Leaving Air WB: 51.4 F Evaporator Leaving Air Enthalpy: 21.06 BTU/lb Gross Cooling Capacity: 136.83 MBH Gross Sensible Capacity: 94.20 MBH Compressor Power Input: 10.10 kw Coil Bypass Factor: 0.189 Heating Performance Heating Airflow: 3900 CFM Entering Air Temp: 57.9 F Leaving Air Temp: 92.9 F Gas Input Capacity: 120.0 / 180.0 MBH Gas Heating Capacity: 147.60 MBH Temperature Rise: 35.0 F NOTE: Second Stage Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 981 Fan Power: 2.53 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Compressor #2 RLA: 10.6 Compressor #2 LRA: 75 Outdoor Fan Motor Qty: 1 Outdoor Fan FLA (ea): 3.1 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 4.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 30.5 Power Supply MOCP (Fuse or HACR): 40 Min. Unit Disconnect FLA: 32 Min. Unit Disconnect LRA: 190 Electrical Convenience Outlet: None Acoustics Packaged Rooftop Builder 1.20 Page 7 of 34
CURBS & WEIGHTS DIMENSIONS - CHASSIS 3 48TC Fig. 11 - Dimensions 48TC -14 C08521 20
CURBS & WEIGHTS DIMENSIONS - CHASSIS 3 (cont.) 48TC GASKET (SUPPLIED WITH CURB) NAIL C08522 COUNTER FLASHING (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) CANT STRIP (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) Fig. 13 - Curb Installation Detail (Typical) C07457 C D B A Fig. 12 - Curb Dimensions C08309 Fig. 14 - Service Clearance LOC DIMENSION CONDITION 48 (1219 mm) Unit disconnect is mounted on panel 36 (914 mm) If dimension--- B is 12 (305 mm) A 18 (457 mm) No disconnect, convenience outlet option 18 (457 mm) Recommended service clearance (use electric screwdriver) 12 (305 mm) Minimum clearance (use manual ratchet screwdriver) 36 (914 mm) Unit has economizer B 12 (305 mm) If dimension--- A is 36 (914 mm) Special Check for sources of flue products within 10---ft of unit fresh air intake hood C 36 (914 mm) Side condensate drain is used 18 (457 mm) Minimum clearance 48 (1219 mm) No flue discharge accessory installed, surface is combustible material D 42 (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft of this unit s flue outlet C08337 21
Performance Summary For PAC-B2 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSA07A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 765 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 41.3 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 1920 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 81.9 F Evaporator Entering Air WB: 65.1 F Entering Air Enthalpy: 29.94 BTU/lb Evaporator Leaving Air DB: 53.9 F Evaporator Leaving Air WB: 52.8 F Evaporator Leaving Air Enthalpy: 21.82 BTU/lb Gross Cooling Capacity: 70.14 MBH Gross Sensible Capacity: 58.15 MBH Compressor Power Input: 4.80 kw Coil Bypass Factor: 0.081 Heating Performance Heating Airflow: 1920 CFM Entering Air Temp: 60.2 F Leaving Air Temp: 88.7 F Gas Input Capacity: 50.0 / 72.0 MBH Gas Heating Capacity: 59.00 MBH Temperature Rise: 28.5 F NOTE: Second Stage Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 753 Fan Power: 1.33 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 3.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.1 Power Supply MOCP (Fuse or HACR): 25 Min. Unit Disconnect FLA: 17 Min. Unit Disconnect LRA: 94 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Packaged Rooftop Builder 1.20 Page 5 of 34
Performance Summary For PAC-C3,C4 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSD08A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 925 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 2500 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 77.7 F Evaporator Entering Air WB: 68.0 F Entering Air Enthalpy: 32.26 BTU/lb Evaporator Leaving Air DB: 56.4 F Evaporator Leaving Air WB: 56.4 F Evaporator Leaving Air Enthalpy: 24.02 BTU/lb Gross Cooling Capacity: 92.80 MBH Gross Sensible Capacity: 57.42 MBH Compressor Power Input: 6.17 kw Coil Bypass Factor: 0.036 Heating Performance Heating Airflow: 2500 CFM Entering Air Temp: 77.8 F Leaving Air Temp: 115.9 F Gas Input Capacity: 90.0 / 125.0 MBH Gas Heating Capacity: 103.00 MBH Temperature Rise: 38.1 F NOTE: Second Stage Supply Fan External Static Pressure: 0.75 in wg Fan RPM: 754 Fan Power: 0.96 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 6.1 Compressor #1 LRA: 41 Compressor #2 RLA: 6.1 Compressor #2 LRA: 41 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 2.6 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.9 Power Supply MOCP (Fuse or HACR): 20 Min. Unit Disconnect FLA: 19 Min. Unit Disconnect LRA: 101 Electrical Convenience Outlet: None Acoustics Packaged Rooftop Builder 1.20 Page 9 of 34
Performance Summary For PAC-D2 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSD08A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 925 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 2600 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 85.2 F Evaporator Entering Air WB: 68.0 F Entering Air Enthalpy: 32.20 BTU/lb Evaporator Leaving Air DB: 57.2 F Evaporator Leaving Air WB: 56.7 F Evaporator Leaving Air Enthalpy: 24.21 BTU/lb Gross Cooling Capacity: 93.47 MBH Gross Sensible Capacity: 78.69 MBH Compressor Power Input: 6.17 kw Coil Bypass Factor: 0.038 Heating Performance Heating Airflow: 2600 CFM Entering Air Temp: 41.0 F Leaving Air Temp: 77.7 F Gas Input Capacity: 90.0 / 125.0 MBH Gas Heating Capacity: 103.00 MBH Temperature Rise: 36.7 F NOTE: Second Stage Supply Fan External Static Pressure: 1.50 in wg Fan RPM: 993 Fan Power: 1.77 BHP NOTE:Medium Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 6.1 Compressor #1 LRA: 41 Compressor #2 RLA: 6.1 Compressor #2 LRA: 41 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 2.6 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.9 Power Supply MOCP (Fuse or HACR): 20 Min. Unit Disconnect FLA: 19 Min. Unit Disconnect LRA: 101 Electrical Convenience Outlet: None Acoustics Packaged Rooftop Builder 1.20 Page 11 of 34
Performance Summary For PAC-D3 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSA07A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 765 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 41.3 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 2000 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 83.0 F Evaporator Entering Air WB: 66.3 F Entering Air Enthalpy: 30.86 BTU/lb Evaporator Leaving Air DB: 55.5 F Evaporator Leaving Air WB: 54.5 F Evaporator Leaving Air Enthalpy: 22.83 BTU/lb Gross Cooling Capacity: 72.30 MBH Gross Sensible Capacity: 59.41 MBH Compressor Power Input: 4.80 kw Coil Bypass Factor: 0.083 Heating Performance Heating Airflow: 2000 CFM Entering Air Temp: 50.3 F Leaving Air Temp: 77.6 F Gas Input Capacity: 50.0 / 72.0 MBH Gas Heating Capacity: 59.00 MBH Temperature Rise: 27.3 F NOTE: Second Stage Supply Fan External Static Pressure: 1.50 in wg Fan RPM: 890 Fan Power: 2.14 BHP NOTE: Medium Static Fan Option Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 3.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.1 Power Supply MOCP (Fuse or HACR): 25 Min. Unit Disconnect FLA: 17 Min. Unit Disconnect LRA: 94 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Packaged Rooftop Builder 1.20 Page 13 of 34
Performance Summary For PAC-D6 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSA07A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 765 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 41.3 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 2000 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 81.8 F Evaporator Entering Air WB: 67.2 F Entering Air Enthalpy: 31.58 BTU/lb Evaporator Leaving Air DB: 56.2 F Evaporator Leaving Air WB: 55.4 F Evaporator Leaving Air Enthalpy: 23.41 BTU/lb Gross Cooling Capacity: 73.52 MBH Gross Sensible Capacity: 55.38 MBH Compressor Power Input: 4.80 kw Coil Bypass Factor: 0.081 Heating Performance Heating Airflow: 2000 CFM Entering Air Temp: 53.2 F Leaving Air Temp: 80.5 F Gas Input Capacity: 50.0 / 72.0 MBH Gas Heating Capacity: 59.00 MBH Temperature Rise: 27.3 F NOTE: Second Stage Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 761 Fan Power: 1.38 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 3.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.1 Power Supply MOCP (Fuse or HACR): 25 Min. Unit Disconnect FLA: 17 Min. Unit Disconnect LRA: 94 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Packaged Rooftop Builder 1.20 Page 17 of 34
Performance Summary For PAC-E7,F7 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSA07A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 765 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 41.3 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 1800 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 90.0 F Evaporator Entering Air WB: 70.4 F Entering Air Enthalpy: 34.17 BTU/lb Evaporator Leaving Air DB: 58.1 F Evaporator Leaving Air WB: 57.5 F Evaporator Leaving Air Enthalpy: 24.70 BTU/lb Gross Cooling Capacity: 76.71 MBH Gross Sensible Capacity: 61.93 MBH Compressor Power Input: 4.81 kw Coil Bypass Factor: 0.067 Heating Performance Heating Airflow: 1800 CFM Entering Air Temp: 41.0 F Leaving Air Temp: 71.3 F Gas Input Capacity: 50.0 / 72.0 MBH Gas Heating Capacity: 59.00 MBH Temperature Rise: 30.3 F NOTE: Second Stage Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 742 Fan Power: 1.26 BHP NOTE: Standard Static Fan Option Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 9.7 Compressor #1 LRA: 62 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 3.4 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.1 Power Supply MOCP (Fuse or HACR): 25 Min. Unit Disconnect FLA: 17 Min. Unit Disconnect LRA: 94 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Packaged Rooftop Builder 1.20 Page 23 of 34
Performance Summary For PAC-E8,F8 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCSD08A2F6-0A3A0 ARI EER: 12.00 IEER: 13.0 Base Unit Weight: 925 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 2250 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 90.0 F Evaporator Entering Air WB: 70.2 F Entering Air Enthalpy: 34.00 BTU/lb Evaporator Leaving Air DB: 57.5 F Evaporator Leaving Air WB: 57.4 F Evaporator Leaving Air Enthalpy: 24.63 BTU/lb Gross Cooling Capacity: 94.90 MBH Gross Sensible Capacity: 78.96 MBH Compressor Power Input: 6.18 kw Coil Bypass Factor: 0.028 Heating Performance Heating Airflow: 2250 CFM Entering Air Temp: 41.0 F Leaving Air Temp: 83.4 F Gas Input Capacity: 90.0 / 125.0 MBH Gas Heating Capacity: 103.00 MBH Temperature Rise: 42.4 F NOTE: Second Stage Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 819 Fan Power: 1.03 BHP NOTE:Standard Static Fan Option. A field-supplied drive is required. Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 6.1 Compressor #1 LRA: 41 Compressor #2 RLA: 6.1 Compressor #2 LRA: 41 Outdoor Fan Motor Qty: 2 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 2.6 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 17.9 Power Supply MOCP (Fuse or HACR): 20 Min. Unit Disconnect FLA: 19 Min. Unit Disconnect LRA: 101 Electrical Convenience Outlet: None Acoustics Packaged Rooftop Builder 1.20 Page 25 of 34
CURBS & WEIGHTS DIMENSIONS - 48HC 07-09 48HC Fig. 5 - Dimensions 48HC 07-09 C10514 19
CURBS & WEIGHTS DIMENSIONS - 48HC 07-09 (cont.) 48HC Fig. 6 - Dimensions 48HC 07-09 C10154 C D B A Fig. 7 - Service Clearance C08337 LOC DIMENSION CONDITION 48 (1219 mm) Unit disconnect is mounted on panel A 18 (457 mm) No disconnect, convenience outlet option 18 (457 mm) Recommended service clearance 12 (305 mm) Minimum clearance 42 (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall) B 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for sources of flue products within 10---ft of unit fresh air intake hood C 36 (914 mm) Side condensate drain is used 18 (457 mm) Minimum clearance 48 (1219 mm) No flue discharge accessory installed, surface is combustible material D 42 (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft of this unit s flue outlet 20
SUBMITTAL SUBMITTAL MicroMetl Down Discharge Economizer with 100% FORM NO. 5087-1P SUBMITTED TO EQUIPMENT: JOB NAME: DRAWN BY: COMPANY: M. HARGIS NOTES: DATE: 09 / 07 FEATURES: Gear driven dampers eliminate slippage associated with standard linkage. Designed specifically for down discharge applications. Easy to install. Easy to service. Lower static pressure loss through economizer dampers. Greater barometric relief capabilities. Factory assembled rainhood with aluminum filters in both outside air and relief hoods. Uses filter access door shipped with HVAC unit. Rainhoods are sloped for water run-off. Hardware cloth over relief damper. Many control systems, with plug-in harness, are available. Economizer includes modulating control system with dry bulb sensor. Shipping weight: 135 lbs. 0.300 0.250 0.200 0.150 0.100 0.050 Relief Capability for Carrier 48/50TF, HJ, TM 008-014 50HJQ 008-012 Economizer motor and harness Gear driven dampers Sloped 3000 2500 2000 1500 1000 500 Access door shipped with HVAC unit Part Number: 0688HJ712DBEC 688-0200 Barometric Barometric Relief Relief 0 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 Static Pressure (in w.g.) Side View Filters Evaporation coil 29 3/8" Outside air Aluminum water entrainment filters Rainhood ships fully assembled Relief air THIS DOCUMENT IS THE PROPERTY OF MICRO METL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICRO METL'S WRITTEN CONSENT. MICROMETL CORPORATION 3035 N. SHADELAND AVENUE, SUITE 300 INDIANAPOLIS, IN. 46226 1-800-662-4822 MICROMETL WEST 202 SOUTH 18TH ST. SPARKS, NV 89431 1-800-884-4662 Relief Airflow (CFM) 0.400 0.350 0688-0200 Static Static Pressure Pressure Loss Loss Through Economizer 0.000 0 1000 2000 3000 4000 5000 6000 Airflow (cfm) Static Pressure Return Air Outside Air
Performance Summary For PAC-D4,D5,E5,F5 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCLA05A2F6-0A3A0 ARI SEER: 15.60 Base Unit Weight: 590 lb Base Unit Dimensions Unit Length: 74.4 in Unit Width: 46.8 in Unit Height: 41.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 1200 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 82.0 F Evaporator Entering Air WB: 66.0 F Entering Air Enthalpy: 30.63 BTU/lb Evaporator Leaving Air DB: 53.6 F Evaporator Leaving Air WB: 52.8 F Evaporator Leaving Air Enthalpy: 21.85 BTU/lb Gross Cooling Capacity: 47.41 MBH Gross Sensible Capacity: 36.78 MBH Compressor Power Input: 3.18 kw Coil Bypass Factor: 0.049 Heating Performance Heating Airflow: 1200 CFM Entering Air Temp: 57.7 F Leaving Air Temp: 96.3 F Gas Input Capacity: 60.0 MBH Gas Heating Capacity: 50.00 MBH Temperature Rise: 38.6 F Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 1153 Fan Power: 0.64 BHP NOTE: Medium Static Fan Option Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 6.2 Compressor #1 LRA: 41 Outdoor Fan Motor Qty: 1 Outdoor Fan FLA (ea): 0.9 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 2.1 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 10.8 Power Supply MOCP (Fuse or HACR): 15 Min. Unit Disconnect FLA: 11 Min. Unit Disconnect LRA: 49 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Discharge Inlet Outdoor Packaged Rooftop Builder 1.20 Page 15 of 34
Performance Summary For PAC-E1-4,F1-4 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCLA05A2F6-0A3A0 ARI SEER: 15.60 Base Unit Weight: 590 lb Base Unit Dimensions Unit Length: 74.4 in Unit Width: 46.8 in Unit Height: 41.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 1360 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 81.2 F Evaporator Entering Air WB: 64.7 F Entering Air Enthalpy: 29.64 BTU/lb Evaporator Leaving Air DB: 54.1 F Evaporator Leaving Air WB: 52.9 F Evaporator Leaving Air Enthalpy: 21.89 BTU/lb Gross Cooling Capacity: 47.42 MBH Gross Sensible Capacity: 39.80 MBH Compressor Power Input: 3.18 kw Coil Bypass Factor: 0.059 Heating Performance Heating Airflow: 1360 CFM Entering Air Temp: 60.2 F Leaving Air Temp: 94.2 F Gas Input Capacity: 60.0 MBH Gas Heating Capacity: 50.00 MBH Temperature Rise: 34.0 F Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 1197 Fan Power: 0.79 BHP NOTE: Medium Static Fan Option Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 6.2 Compressor #1 LRA: 41 Outdoor Fan Motor Qty: 1 Outdoor Fan FLA (ea): 0.9 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 2.1 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 10.8 Power Supply MOCP (Fuse or HACR): 15 Min. Unit Disconnect FLA: 11 Min. Unit Disconnect LRA: 49 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Discharge Inlet Outdoor Packaged Rooftop Builder 1.20 Page 19 of 34
Performance Summary For PAC-E6,F6 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM Part Number:48HCLA06A2F6-0A3A0 ARI SEER: 15.20 Base Unit Weight: 600 lb Base Unit Dimensions Unit Length: 74.4 in Unit Width: 46.8 in Unit Height: 41.4 in Unit Voltage-Phase-Hertz: 460-3-60 Air Discharge: Vertical Fan Drive Type: Belt Actual Airflow: 1550 CFM Site Altitude: 0 ft Cooling Performance Condenser Entering Air DB: 94.0 F Evaporator Entering Air DB: 77.3 F Evaporator Entering Air WB: 63.9 F Entering Air Enthalpy: 29.07 BTU/lb Evaporator Leaving Air DB: 51.9 F Evaporator Leaving Air WB: 51.6 F Evaporator Leaving Air Enthalpy: 21.13 BTU/lb Gross Cooling Capacity: 55.37 MBH Gross Sensible Capacity: 42.46 MBH Compressor Power Input: 3.87 kw Coil Bypass Factor: 0.020 Heating Performance Heating Airflow: 1550 CFM Entering Air Temp: 61.0 F Leaving Air Temp: 90.9 F Gas Input Capacity: 60.0 MBH Gas Heating Capacity: 50.00 MBH Temperature Rise: 29.9 F Supply Fan External Static Pressure: 1.00 in wg Fan RPM: 1255 Fan Power: 0.99 BHP NOTE: Medium Static Fan Option Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 7 Compressor #1 LRA: 52 Outdoor Fan Motor Qty: 1 Outdoor Fan FLA (ea): 0.9 Indoor Fan Motor Type: MED Indoor Fan Motor FLA: 2.6 Combustion Fan Motor FLA (ea): 0.25 Power Supply MCA: 12.3 Power Supply MOCP (Fuse or HACR): 15 Min. Unit Disconnect FLA: 12 Min. Unit Disconnect LRA: 69 Electrical Convenience Outlet: None Acoustics Sound Power Levels, db re 10E-12 Watts Discharge Inlet Outdoor Packaged Rooftop Builder 1.20 Page 21 of 34
CURBS & WEIGHTS DIMENSIONS - 48HC 04-06 NOTES: 1. DIMENSIONS ARE IN INCHES, DIMENSIONS IN [ ] ARE IN MILLIMETERS. 33-3/8 [ 848] 2. CENTER OF GRAVITY 32-1/4 [ 818] ECONOMIZER HOOD (OPTIONAL) 16 [ 406] 3. DIRECTION OF AIR FLOW C 44 1117] 25-5/8 [ 652] RETURN AIR 10-7/8 [ 277] RETURN AIR 18-1/8 [ 459] 16-1/8 [ 411] 14-1/4 [ 363] 12-1/4 [ 312] SEE THRU THE BASE CHART W X Y Z E ALT. CONDENSATE DRAIN OPENING IN BASEPAN 6-1/4 [ 157] 17-3/4 [ 451] SUPPLY AIR 26-1/2 [ 673] 29-3/8 [ 747] SUPPLY AIR 48HC 10-1/2 [ 265] 1-1/4 [ 32] 25 [ 636] 4 [ 100] FLUE HOOD TOP 12-1/8 [ 307] 18-1/2 [ 470] 3-3/8 [ 85] 11-3/8 [ 289] 6-1/8 [ 155] E STD. CONDENSATE DRAIN 16-3/4 [ 427] SUPPLY AIR 25-1/8 [ 638] RETURN AIR FILTER OUTSIDE AIR 21-1/4 [ 539] J OPTIONAL FACTORY INSTALLED DISCONNECT CONTROL BOX ACCESS PANEL F INDOOR BLOWER ACCESS HANDLE 6-5/8 [ 168] 7 [ 177] 6 [ 152] 26-3/4 [ 681] SUPPLY AIR 31-1/4 [ 793] RIGHT RETURN AIR BAROMETRIC RELIEF FLOW HANDLE 30-1/8 [ 764] 8-3/8 [ 213] 74-3/8 [ 1888] FRONT K 4-5/8 [ 118] CONDENSER COIL OPTIONAL FACTORY INSTALLED CONVENIENCE OUTLET A, B, G D ELECTRICAL DISCONNECT LOCATION 19-1/2 [ 494] FILTER ACCESS PANEL (TOOL-LESS) INDOOR COIL ACCESS PANEL COMP. ACCESS PANEL CONDENSER COIL 6-5/8 [ 168] 3-3/4 [ 95] 46-3/4 [ 1187] LEFT THRU-THE-BASE CHART THESE HOLES REQUIRED FOR USE CRBTMPWR001A01, 003A01 BACK 2-5/8 [ 67] TYP CURB WIDTH A B C D E F G CONNECTION SIZES 1 3/8" [35] DIA FIELD POWER SUPPLY HOLE 2" [50] DIA POWER SUPPLY KNOCKOUT 1 3/4" [51] DIA GAUGE ACCESS PLUG 7/8" [22] DIA FIELD CONTROL WIRING HOLE 3/4"-14 NPT CONDENSATE DRAIN 1/2"-14 NPT GAS CONNECTION 2 1/2 " [64] DIA POWER SUPPLY KNOCK-OUT THREADED CONDUIT SIZE WIRE USE REQ'D HOLE SIZES (MAX.) W 1/2" ACC. 7/8" [22.2] X 1/2" 24V 7/8" [22.2] Y * 3/4" (001,003) POWER 1 1/8" [28.4] Z** (003) 1/2" FPT GAS 1 3/16" [30.0] FOR "THRU-THE-BASEPAN" FACTORY OPTION, FITTINGS FOR ONLY X,Y, & Z ARE PROVIDED * SELECT EITHER 3/4" OR 1/2" FOR POWER, DEPENDING ON WIRE SIZE UNIT J K 48HC-A04 48HC-A05 48HC-A06 33 3/8 [847] 41 3/8 [1051] 41 3/8 [1051] 18 5/8 [472] 14 7/8 [377] 14 7/8 [377] ** (001) PROVIDES 3/4" FPT THRU CURB FLANGE & FITTING. Fig. 1 - Dimensions 48HC 04-06 C10151 16
CURBS & WEIGHTS DIMENSIONS - 48HC 04-06 (cont.) STD. UNIT WEIGHT CORNER WEIGHT (A) CORNER WEIGHT (B) CORNER WEIGHT (C) CORNER WEIGHT (D) UNIT C.G. HEIGHT LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z 48HC-A04 505 229 124 56 117 53 128 58 136 62 36 1/8 [918] 24 3/8 [619] 19 [483] 48HC-A05 590 268 151 69 144 65 144 65 151 69 36 1/4 [921] 23 3/8 [594] 20 1/8 [511] 48HC-A06 600 271 156 71 145 66 144 65 155 70 35 7/8 [911] 23 1/4 [591] 19 1/2 [495] *- STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. FOR OTHER OPTINS AND ACCESSORIES REFER TO THE PRODUCT DATA CATALOG. CORNER A CORNER B Y Z 48HC CORNER D X CORNER C TOP Fig. 2 - Dimensions 48HC 04-06 C10152 C D B A Fig. 3 - Service Clearance C08337 LOC DIMENSION CONDITION 48 (1219 mm) Unit disconnect is mounted on panel A 18 (457 mm) No disconnect, convenience outlet option 18 (457 mm) Recommended service clearance 12 (305 mm) Minimum clearance 42 (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall) B 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for sources of flue products within 10---ft of unit fresh air intake hood C 36 (914 mm) Side condensate drain is used 18 (457 mm) Minimum clearance 48 (1219 mm) No flue discharge accessory installed, surface is combustible material D 42 (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) 36 (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft of this unit s flue outlet 17
Side View THIS DOCUMENT IS THE PROPERTY OF MICRO METL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICRO METL'S WRITTEN CONSENT. MICROMETL CORPORATION 3035 N. SHADELAND AVENUE, SUITE 300 INDIANAPOLIS, IN. 46226 1-800-662-4822 MICROMETL WEST 202 SOUTH 18TH ST. SPARKS, NV 89431 1-800-884-4662 Filters Evaporation coil S U B M I T T A L MicroMetl Down Discharge Economizer with 100% Relief FORM NO. 2895-8P SUBMITTED TO COMPANY: DRAWN BY: JOB NAME: EQUIPMENT: NOTES: DATE: 1 / 07 Capability for Carrier 48/50TC A/B04-A/B07; 50TCQ A04-A07; 48/50HC A04-A06; 48/50TF,TM,HJ,TFQ 004-007; 48/50HE 003-006 Units 0688-0101 Static Pressure Loss Through Economizer Part Number: 0688-0101 0688-0101 Barometric Relief FEATURES: Gear driven dampers eliminate slippage associated with standard linkage. Designed specifically for down discharge applications. Easy to install. Easy to service. Lower static pressure loss through economizer dampers. Greater barometric relief capabilities. Factory assembled rainhood with aluminum filters in both outside air and relief hoods. Uses filter access door shipped with HVAC unit. Rainhoods are sloped for water run-off. Hardware cloth over relief damper. ECONOMIZER PART NO.S 0688-0101-00920 Economizer w/ no controls 0688-0101-9J920 0688-0101-54920 0688-0101-9A920 Economizer w/ fixed dry bulb controls Economizer w/ modulating enthalpy controls Economizer w/ modulating adjustable dry bulb controls Access door shipped with HVAC unit Drive gear attached to the motor Economizer motor and harness Gear driven dampers Sloped 19 1/4" Economizer includes Honeywell W7212 controller capable of CO2, demand control and power exhaust control. Outside air Aluminum water entrainment filters Rainhood ships fully assembled Relief air
Performance Summary For CU-B1-3,4 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 08:35AM Pipe Length Liquid Line Size Suction Line Size 0-25 1/2 1 1/8 26-50 1/2 1 1/8 51-75 1/2 1 1/8 76-100 1/2 1 3/8 38AUQ012/40RUQ012 System: 1 System Quantity: ft 0.0 Altitude: 11.0 EER @ ARI Conditions: 3.3 Hi_TempCOP: NA IPLV: System meets ASHRAE 90.1 min EER requirement. Liquid and Suction Line Sizing V-Ph-Hz F F in wg in wg in wg in wg in wg in wg 1 38AUQ 10 Tons 1 460-3-60 94.0 47.0 0.60 0.00 0.00 0.00 0.00 0.60 Outdoor Unit Parameters Unit Quantity: Unit Model: Unit Size: No. of DX Circuits: Voltage: Clg Ent Air DB: Htg Ent Air DB: Indoor Unit External Static: Economizer Loss: Grille Loss: Plenum Loss: Acc. Heating Loss: Total Ext Static: V-Ph-Hz CFM MBH MBH F F BTU/lb F F BTU/lb 1 40RUQ 10 Tons 4 1 460-3-60 4000.0 119.1 90.5 80.0 67.0 31.44 59.0 57.7 24.82 NA Indoor Unit Parameters Unit Quantity: Unit Model: Unit Size: Coil Rows: No. of Splits: Voltage: Actual Airflow: Total Clg Cap.(Gross): Sensible Clg Cap.(Gross): Ent Air DB: Ent Air WB: Ent Enthalpy: Lvg Air DB: Lvg Air WB: Lvg Enthalpy: Coil Bypass Factor: MBH MBH kw F F 104.00 104.00 7.38 70.0 94.1 3.3 Heat Pump System Htg HP Capacity: Htg HP Integrated Capacity: Heating HP Compressor Power: Htg Ent Air DB Temp: Htg Lvg Air DB: High Temp COP: in wg in wg in wg in wg in wg in wg RPM BHP BHP Amps Indoor Supply Fan 0.60 Indoor Unit External Static: 0.00 Economizer Loss: 0.00 Grille Loss: 0.00 Plenum Loss: 0.00 Acc. Heating Loss: 0.60 Total Ext Static: 862 Fan Speed: 2.00 Fan Power: 2.40 Fan Motor Max: 2.6 Fan Motor FLA: Standard Motor and Standard Drive Required. V-Ph-Hz 460-3-60 Outdoor Electrical Data Unit Voltage: Amps 22.5 Unit#1 MCA: Amps 30.0 Unit#1 MOCP: NA Total Compressor Power of Unit #1: V 414 Voltage Range Min: V 506 Voltage Range Max: 16.7 Compressor RLA: 114 Compressor LRA: 1 Compressor Quantity: 2 Fan Motors Qty: Notice: Outdoor unit elect. data is based on 460-3-60 V-Ph-Hz 460-3-60 Indoor Electrical Data Unit Voltage: Amps 3.3 Unit MCA: Amps 15.0 Unit MOCP: Notice: Indoor unit elect. data is based on 460-3-60 Motor is rated for tri voltage 208/230/460-3-60V. Factory wired for 460-3-60 application. Acoustics Sound Power Levels, db re 10E-12 Watts Commercial Split Systems Builder 1.19d Page 1 of 2
Performance Summary For HP-E1-5 and F1-5 Project: LAUSD South Region HS 15 08/05/2010 Prepared By: 07:39AM System: 38AUQ008/40RUQ008 System Quantity: 2 Altitude: 0.0 ft EER @ ARI Conditions: 11.0 Hi_TempCOP: 3.3 IPLV: NA System meets ASHRAE 90.1 min EER requirement. Liquid and Suction Line Sizing Pipe Length Liquid Line Size Suction Line Size 0-25 1/2 1 1/8 26-50 1/2 1 1/8 51-75 1/2 1 1/8 76-100 1/2 1 1/8 Outdoor Unit Parameters Unit Quantity: 1 Unit Model: 38AUQ Unit Size: 7.5 Tons No. of DX Circuits: 1 Voltage: 460-3-60 V-Ph-Hz Clg Ent Air DB: 94.0 F Htg Ent Air DB: 47.0 F Indoor Unit External Static: 0.50 in wg Economizer Loss: 0.00 in wg Grille Loss: 0.00 in wg Plenum Loss: 0.00 in wg Acc. Heating Loss: 0.00 in wg Total Ext Static: 0.50 in wg Heat Pump System Htg HP Capacity: 82.78 MBH Htg HP Integrated Capacity: 82.78 MBH Heating HP Compressor Power: 6.79 kw Htg Ent Air DB Temp: 70.0 F Htg Lvg Air DB: 102.6 F High Temp COP: 3.3 Outdoor Electrical Data Unit Voltage: 460-3-60 V-Ph-Hz Unit#1 MCA: 17.1 Amps Unit#1 MOCP: 25.0 Amps Total Compressor Power of Unit #1: NA Voltage Range Min: 414 V Voltage Range Max: 506 V Compressor RLA: 12.2 Compressor LRA: 100 Compressor Quantity: 1 Fan Motors Qty: 2 Notice: Outdoor unit elect. data is based on 460-3-60 Indoor Unit Parameters Unit Quantity: 1 Unit Model: 40RUQ Unit Size: 7.5 Tons Coil Rows: 4 No. of Splits: 1 Voltage: 208/230-3-60 V-Ph-Hz Actual Airflow: 2350.0 CFM Total Clg Cap.(Gross): 84.2 MBH Sensible Clg Cap.(Gross): 66.2 MBH Ent Air DB: 79.6 F Ent Air WB: 64.1 F Ent Enthalpy: 29.20 BTU/lb Lvg Air DB: 53.5 F Lvg Air WB: 51.7 F Lvg Enthalpy: 21.24 BTU/lb Coil Bypass Factor: NA Indoor Supply Fan Indoor Unit External Static: 0.50 in wg Economizer Loss: 0.00 in wg Grille Loss: 0.00 in wg Plenum Loss: 0.00 in wg Acc. Heating Loss: 0.00 in wg Total Ext Static: 0.50 in wg Fan Speed: 643 RPM Fan Power: 0.63 BHP Fan Motor Max: 2.40 BHP Fan Motor FLA: 5.2 Amps Standard Motor and Standard Drive Required. Indoor Electrical Data Unit Voltage: 208/230-3-60 V-Ph-Hz Unit MCA: 6.5 Amps Unit MOCP: 15.0 Amps Notice: Indoor unit elect. data is based on 230-3-60 Acoustics Sound Power Levels, db re 10E-12 Watts Commercial Split Systems Builder 1.19d Page 33 of 34
6 C09236
DIMENSIONS 40RUQ C09637 40RUQ*07, 08, 12 6
24ABB3 Baset13 Air Conditioner with Puronr Refrigerant Submittal Data the environmentally sound refrigerant Carrier s Air Conditioners with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 24ABB has been designed utilizing Carrier s Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth s ozone layer. As an Energy Starr Partner, Carrier Corporation has determined that this product meets the Energy Starr guidelines for energy efficiency. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines. NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up -to -date ratings information. INDUSTRY LEADING FEATURES / BENEFITS Efficiency S 13-14 SEER/10.55-12 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 75 dba S Sound level as low as 74 dba with accessory sound blanket Comfort S System supports Edger Thermidistatt or standard thermostat controls Reliability S S S S S S Durability Puronr refrigerant - environmentally sound, won t deplete the ozone layer and low lifetime servce cost. Scroll compressor Internal pressure relief valve Internal thermal overload Filter drier Balanced refrigeration system for maximum reliability WeatherArmort protection package: S Solid, durable sheet metal construction S Dense wire coil guard available Baked -on, complete outer coverage, powder paint S Applications S Long -line - up to 250 feet (76.20 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.) S Low ambient (down to -20_F/-28.9_C)) with accessory kit
PHYSICAL DATA UNIT SIZE---VOLTAGE, SERIES 18---31 24---31 30---31 36---31 42---30 48---31 60---31 Operating Weight lb (kg) Shipping Weight lb (kg) Compressor Type REFRIGERANT Control Charge lb (kg) 107 (48.5) 130 (59.0) 3.50 (1.59) 110 (49.9) 134 (60.8) 3.80 (1.72) 111 (50.3) 136 (61.7) 141 (64.0) 170 (77.1) Scroll Puron (R---410A) TXV (Puron Hard Shutoff) 4.10 (1.86) 5.34 (2.42) 190 (86.2) 218 (98.9) 5.84 (2.65) 186 (84.4) 224 (101.6) 7.00 (3.18) 190 (86.2) 226 (102.5) COND FAN Propeller Type, Direct Drive Air Discharge Vertical Air Qty (CFM) 1792 2218 2218 2954 3167 3365 3129 Motor HP 1/12 1/10 1/10 1/4 1/5 1/4 1/4 Motor RPM 1100 1100 1100 1100 1100 1100 800 COND COIL Face Area (Sq ft) 8.4 8.4 9.80 13.13 17.25 19.40 12.93 Fins per In. 20 25 25 25 25 25 20 Rows 1 1 1 1 1 1 2 Circuits 3 3 3 3 4 5 5 VALVECONNECT.(In.ID) Vapor 3/4 3/4 3/4 7/8 7/8 7/8 7/8 Liquid 3/8 REFRIGERANT TUBES (In. OD) Rated Vapor* 3/4 3/4 3/4 7/8 7/8 7/8 1 --- 1/8 Max Liquid Line{ 3/8 * Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation. { See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables. 8.19 (3.71) 24ABB3 3
ELECTRICAL DATA UNIT SIZE --- VOLTAGE, SERIES V/PH OPER VOLTS* COMPR FAN MCA MIN WIRE SIZE{ MIN WIRE SIZE{ MAX LENGTH ft. (m)} MAX LENGTH ft. (m)} MAX MIN LRA RLA FLA 60 C 75 C 60 C 75 C MAX FUSE** or CKT BRK AMPS 18---31 48.0 9.0 0.5 11.8 14 14 66 (20.1) 63 (21.0) 15 24---31 58.3 13.5 0.77 17.6 14 14 44 (13.4) 42 (12.8) 25 30---31 64.0 12.8 0.77 16.8 14 14 46 (14.0) 44 (13.4) 25 36---31 208/230/1 253 197 77.0 14.1 1.4 20.5 12 12 61 (18.6) 58 (17.7) 30 42---30 112.0 17.9 1.1 23.5 12 12 53 (16.2) 51 (15.5) 40 48---31 109.0 19.9 1.4 26.2 10 10 76 (23.2) 72 (22.2) 40 60---31 134.0 26.4 1.2 34.2 8 10 62 (18.9) 55 (16.8) 50 * Permissible limits of the voltage range at which the unit will operate satisfactorily { If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70). } Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time --- Delay fuse. FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA ---RatedLoadAmps NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection. Complies with 2007 requirements of ASHRAE Standards 90.1 24ABB3 A-WEIGHTED SOUND POWER LEVEL UNIT SIZE --- VOLTAGE, SERIES STANDARD RATING (dba) TYPICAL OCTAVE BAND SPECTRUM (dba, without tone adjustment) 125 250 500 1000 2000 4000 8000 18---31 72 53.5 59.5 63.5 67.0 63.5 59.0 52.5 24---31 76 55.0 61.5 67.0 71.5 69.0 61.0 55.0 30---31 74 55.0 63.5 68.5 68.5 65.5 61.0 54.0 36---31 75 59.5 63.0 68.5 70.0 65.5 61.5 53.5 42---30 78 57.5 65.0 71.0 73.0 70.5 67.5 62.5 48---31 80 58.5 67.5 73.5 75.0 70.5 67.5 64.5 60---31 78 59.0 67.5 71.5 73.5 69.0 66.0 63.5 NOTE: Tested in accordance with ARI Standard 270---2008 (not listed in AHRI). A-WEIGHTED SOUND POWER LEVEL WITH SOUND SHIELD UNIT SIZE --- VOLTAGE, SERIES STANDARD RATING (dba) TYPICAL OCTAVE BAND SPECTRUM (dba, without tone adjustment) 125 250 500 1000 2000 4000 8000 18---31 71 55.5 60.5 64.0 66.0 63.0 58.5 52.0 24---31 74 55.5 60.5 68.5 70.0 67.0 61.0 53.6 30---31 73 55.5 64.0 68.0 67.0 64.0 60.0 52.5 36---31 74 59.5 63.0 68.0 69.5 65.0 60.5 50.5 42---30 77 57.5 65.0 70.5 72.0 70.0 67.0 62.0 48---31 79 60.5 67.5 73.5 74.5 71.0 68.0 63.5 60---31 78 59.0 68.0 70.5 72.5 68.0 67.0 63.0 NOTE: Tested in accordance with ARI Standard 270---2008 (not listed in AHRI). CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE) UNIT SIZE--- VOLTAGE & SERIES REQUIRED SUBCOOLING _F (_C) 18---31 10 (5.6) 24---31 10 (5.6) 30---31 10 (5.6) 36---31 14 (7.8) 42---30 10 (5.6) 48---31 15 (8.3) 60---31 13 (7.2) 9
24ABB3 DIMENSIONS - ENGLISH UNIT SERIES CHARACTERISTICS ELECTRICAL A B C D E F G K L M N P WEIGHT OPERATING (lbs) SHIPPING WEIGHT (lbs) SHIPPING DIMENSIONS (L x W x H) 24ABB318 1 XOOO 23 1/2" 25 5/16" 3 3/4" 3/4" 4 7/16" 18 1/16" 7 13/16" 2 13/16" 1/2" 16 1/2" 15" 12" 107 130 24 1/4" X 27 3/8" X 33 1/2" 24ABB324 1 XOOO 23 1/2" 25 5/16" 3 3/4" 3/4" 4 7/16" 18 1/16" 7 13/16" 2 13/16" 1/2" 16 1/2" 15" 12" 110 134 24 1/4" X 27 3/8" X 33 1/2" 24ABB330 1 XOOO 23 1/2" 28 11/16" 3 3/4" 3/4" 4 7/16" 18 1/16" 7 13/16" 2 13/16" 1/2" 16 1/2" 15" 14" 111 136 24 1/4" X 27 3/8" X 33 1/2" 24ABB336 1 XOOO 25 3/4" 32 5/16" 3 7/8" 7/8" 4 7/16" 21 1/4" 9 1/8" 2 15/16" 5/8" 14 1/4" 10 1/2" 16" 141 170 26 7/8" X 30 1/16" X 35 15/16" 24ABB342 0 XOOO 31 3/16" 32 5/16" 3 7/8" 7/8" 6 9/16" 24 11/16" 9 1/8" 2 15/16" 5/8" 15 3/4" 16 1/4" 13 3/4" 190 218 32 3/8" X 35 1/2" X 35 15/16" 24ABB348 1 XOOO 31 3/16" 35 3/4" 3 7/8" 7/8" 6 9/16" 24 11/16" 9 1/8" 2 15/16" 5/8" 16 3/8" 15 3/8" 15 1/4" 186 224 32 3/8" X 35 1/2" X 39 3/8" 24ABB360 1, 2 XOOO 31 3/16" 25 1/2" 3 7/8" 7/8" 6 9/16" 24 11/16" 9 1/8" 2 15/16" 5/8" 14 1/8" 15 3/8" 11 3/8" 190 226 32 3/8" X 35 1/2" X 32 9/16" X = YES O=NO NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55 ı$f, MAX. 125 ı$f. 208-230-1-60 230-1-60 208/230-3-60 460-3-60 3. SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODEL NUMBER. 4. CENTER OF GRAVITY. 5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. A SQ. G M AIR IN AIR DISCHARGE AIR DISCHARGE B FIELD CONTROL SUPPLY CONN. 7/8" HOLE FIELD POWER SUPPLY CONN. 7/8" HOLE WITH 1 1/8" KNOCKOUT AIR IN N F AIR IN P 3" E C 31/2" VAPOR D LINE CONN. 17/8" L 5/16" K AIR IN MINIMUM UNIT SIZE MOUNTING PAD DIMENSIONS 18,24,30 23 1/2" X 23 1/2" 36 26" X 26" 42,48,60 31 1/2" X 31 1/2" - 35" X 35" 3/8" TIEDOWN KNOCKOUTS (2) PLACES 10
MEETS 2006 DOE REQUIREMENTS (1) HBX0-120 Series Vertical / Horizontal Air Handler 120V-Cooling or Heat pump 2-5 tons Description : The HBX0-120 series air handler is designed to offer the industry an air handler that includes every available feature as well as up to 13 SEER, depending on the selected outdoor unit. The HBX0-120 is completely factory assembled with a cooling coil, 120V motor, 24V transformer, horizontal drain pan, and throw away filter. All components are installed within a fully insulated, galvanized steel cabinet. (1) First Co's customer is ultimately responsible for confirming which fan coil models are compatible with selected outdoor unit(s) and which expansion valves (if any) are required. To determine approved indoor/outdoor matches, go to: www.firstco.com or contact the factory. New Feature: Field or factory installable TXV s for optimum cooling performance. NOW AVAILABLE WITH FIELD OR FACTORY INSTALLED R22 OR R410A EXPANSION VALVES FEATURES: 1. Factory installed horizontal drain pan (Left or Right side down) 2. Compatible with all major brands of split condensing units and heat pumps 3. Piston-type metering device on cooling coil or field or factory installed R22 or R410a TXV s 4. Factory installed filter 5. Copper tube cooling coils 6. Primary and secondary drain connections on cooling coil 7. Fully insulated and painted galvanized steel cabinet Table of Contents Page # Description... 1 Features... 1 Efficiency... 2 Components... 2 Cabinets... 2 Installation... 2 Accessories... 2,4 Physical Dimensions... 3 Blower Data... 3 Model Numbers... 4 FIRST CO. - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.firstco.com
HBX0-120 Series DX / Heat Pump Efficiency: The HBX0-120 series air handler is the latest state-of-the-art air handler for heat pump or straight cool (DX) operation. Depending on the condensing unit or heat pump used, cooling efficiency is up to 14 SEER (depending on the selected outdoor unit). Cooling coils have either piston type metering devices, or R22 or R410a TXV s and are circuited for cooling or heat pump operation. First Co's customer is ultimately responsible for confirming which fan coil models are compatible with selected outdoor unit(s) and which expansion valves (if any) are required. To determine approved indoor/outdoor matches, go to: www.firstco.com or contact the factory Components: Each air handler includes a high efficiency cooling coil, 120V fan motor, 24V transformer, horizontal drain pan, and throw away filter. Cabinets: Cabinets are fully insulated. Installation: No modification is required for vertical or horizontal (right-to-left) airflow. A horizontal drain pan is factory installed for right-to-left airflow and can be re-positioned within the cabinet to offer left-toright airflow. Accessories: Accessories include cooling / heat pump TXV kits. (See page 4) 3-WAY AIRFLOW -2-
HBX0-120 Series D PHYSICAL DIMENSIONS UNIT MODEL A B C D E F G H J LIQ. (SWEAT) SUCT. (SWEAT) FILTER 24HBX0-120 40 20 20 18-1/2 16 2 18 16 3 3/8 5/8 18 X 20 X 1 36HBX0-120 42 23 20 21-1/2 16 2 18 17 5 3/8 3/4 20 X 22 X 1 48/60HBX0-120 48 28 21-1/4 26-1/4 17 2 19-1/4 18-1/4 8-7/8 1/2 7/8 20 X 25 X 1 (See P.4 for Model Numbers) BLOWER DATA UNIT MODEL NOM. COOL TONS MOTOR HP-AMP (120V) MIN. CKT. AMPACITY MAX. CKT. PROTECTION 24HBX0-120 2 1/5-3.0 3.75 15 36HBX0-120 3 1/3-6.0 7.5 15 48HBX0-120 4 1/2-8.0 10.0 15 60HBX0-120 5 3/4-10.5 13.12 15 MOTOR SPEED HIGH MED-HI MED-LOW LOW HIGH MED-HI MED-LOW LOW HIGH MED LOW HIGH MED LOW CFM vs. EXTERNAL STATIC PRESSURE 0.05 0.10 0.20 0.30 0.40 0.50 920 750 555 350 1220 1085 935 750 1730 1580 1360 2030 1630 1280 890 730 530 310 1185 1060 915 730 1690 1550 1340 2000 1615 1270 825 680 480 240 1120 1010 875 695 1620 1490 1310 1950 1580 1240 750 610 420 170 1070 960 830 650 1540 1430 1270 1900 1540 1210 680 540 330 100 1015 910 775 605 1450 1360 1210 1840 1490 1180 580 450 --- --- 960 865 700 550 1350 1270 1100 1770 1440 1140-3-
Model Numbers: MODEL SIZE (BTU) MODEL (PISTON) MODEL (R22 TXV) FACTORY INSTALLED TXV S MODEL (R410a TXV) 24,000 24HBX0-120 24HBX0-120 w/r22 TXV 24HBX0-120 w/r410a TXV 36,000 36HBX0-120 36HBX0-120) w/r22 TXV 36HBX0-120 w/r410a TXV 42,000/48,000 48HBX0-120 48HBX0-120 w/r22 TXV 48HBX0-120 w/r410a TXV 60,000 60HBX0-120 60HBX0-120 w/r22 TXV 60HBX0-120 w/r410a TXV All TXV's are approved for cooling only or heat pump operation. NOTE: Expansion valve requirement depends on the selected outdoor unit. Go to www.firstco.com or contact the factory for assistance. ACCESSORIES - (all field installed) EXPANSION VALVE KITS (Field installed) (cooling only or heat pump) PART NUMBER R22 FITS 9EVR22-4 24HBX0-120 9EVR22-5 36HBX0-120 9EVR22-6 48/60HBX0-120 R410a 9EVR410-3 24HBX0-120 9EVR410-4 36HBX0-120 9EVR410-5 48/60HBX0-120 NOTES: 1. Above expansion valve kits are approved for both cooling only (non heat pump) and heat pump applications. 2. Valves are external equalizing, internal bleed. 3. Valves have screw-on connections. In keeping with its policy of continuous progress and product improvement, First Operations reserves the right to make changes without notice. Maintenance for all First Co. products is available under Product Maintenance at www. firstco.com. Catalog HBX0-120-308-4-
25HBB3 Base 13 Heat Pump with Puronr Refrigerant 1---1/2 to 5 Nominal Tons (Sizes 18 to 60) Submittal Data the environmentally sound refrigerant Carrier heat pumps with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 25HBB has been designed utilizing Carrier s Puron refrigerant. The environmentally sound refrigerant allows consumers to make a responsible decision in the protection of the earth s ozone layer. As an Energy Starr Partner, Carrier Corporation has determined that this product meets the Energy Starr guidelines for energy efficiency. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines. NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up -to -date ratings information. INDUSTRY LEADING FEATURES / BENEFITS Efficiency S 13 SEER/ 10.1-10.8 EER/ 7.7-8.3 HSPF (nominal) S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 72 dba S Sound levels as low as 70 dba with accessory sound blanket Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Puronr refrigerant - environmentally sound, won t deplete the ozone layer and low lifetime service cost. S Scroll compressor S Internal pressure relief valve S Internal thermal overload S High pressure switch S Loss of charge switch S Filter drier S Balanced refrigeration system for maximum reliability Durability WeatherArmort protection package: S Solid, durable sheet metal construction S Dense wire coil guard S Baked -on powder paint Applications S Long -line - up to 250 feet (76.20 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.) S Low ambient (down to -20_F/-28.9_C) with accessory kit Warranty S 5 year limited compressor warranty S 5 year limited parts warranty
PHYSICAL DATA UNIT SIZE SERIES 18---30 24---30 30---30 36---30 42---30 48---30 60---30 Operating Weight lb (kg) 148 162 186 172 246 240 250 (67.13) (73.48) (84.37) (78.02) (111.58) (108.86) (113.40) Shipping Weight lb (kg) 174 189 215 207 278 274 282 (78.93) (85.73) (97.52) (93.89) (126.10) (124.28) (127.91) Compressor Type Scroll REFRIGERANT Puron (R---410A) Control TXV (Puron Hard Shutoff) Charge lb (kg) 5.1 5.9 8.2 6.8 8.4 11.4 11.3 (2.31) (2.68) (3.72) (3.08) (3.81) (5.17) (5.13) Outdoor Heating Piston # 42 46 55 57 61 63 76 COND FAN Propeller Type, Direct Drive Air Discharge Vertical Air Qty (CFM) 2196 2614 2614 3472 3810 4046 4046 Motor HP 1/10 1/10 1/10 1/8 1/5 1/4 1/4 Motor RPM 1100 1100 1100 800 800 800 800 COND COIL Face Area (Sq ft) 14.77 15.09 21.56 17.60 25.15 17.60 17.60 Fins per In. 25 20 20 20 20 20 20 Rows 1 1 1 1 1 2 2 Circuits 4 5 5 6 6 8 8 VALVE CONNECT. (In.) ID Vapor 5/8 5/8 3/4 3/4 7/8 7/8 7/8 Liquid 3/8 REFRIGERANT TUBES* (In.) OD Rated Vapor* 5/8 5/8 3/4 3/4 7/8 7/8 1 --- 1/8 Liquid 3/8 *Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation. 25HBB3 VAPOR LINE SIZING AND COOLING CAPACITY LOSS LONG LINE APPLICATION: An application is considered Long line when the total equivalent tubing length exceeds 80 ft. (24.38 m) or when there is more than 20 ft. (6.09 m) vertical separation between indoor and outdoor units. These applications require additional accessories and system modifications for reliable system operation. The maximum allowable total equivalent length is 250 ft. (76.2 m). The maximum vertical separation is 200 ft. (60.96 m) Unit Nominal Size (Btuh) 18,000 1 --- Stage Puron HP 24,000 1 --- Stage Puron HP 30,000 1 --- Stage Puron HP 36,000 1 --- Stage Puron HP 42,000 1 --- Stage Puron HP 48,000 1 --- Stage Puron HP 60,000 1 --- Stage Maximum Liquid Line Diameters (In. OD) 3/8 Vapor Line Diameters (In.) OD 26---50 (7.9---15.2) Standard Application 51---80 (15.5---24.4) 81---100 (24.7---30.5) when outdoor unit is above indoor unit, and 60 ft. (18.3 m) when the outdoor unit is below the indoor unit. Refer to Accessory Usage Guideline below for required accessories. See Longline Application Guideline for required piping and system modifications. Also, refer to the table below for vapor tube diameters based on the total length to minimize the cooling capacity loss. Cooling Capacity Loss (%) Total Equivalent Line Length ft. (m) 101---125 (30.8---38.1) Long Line Application Requires Accessories 126---150 (38.4---45.7) 151---175 (46.0---50.3) 176---200 (53.6---60.0) 201---225 (61.3---68.6) 226---250 (68.9---76.2) 1/2 1 2 3 4 6 7 8 9 10 5/8 0 0 1 1 1 2 2 3 3 5/8 0 1 1 2 3 3 4 4 5 3/4 0 0 0 0 1 1 1 1 1 5/8 1 2 3 3 4 5 6 7 8 3/4 0 0 1 1 1 2 2 2 3 7/8 0 0 0 0 1 1 1 1 1 5/8 1 2 4 5 6 7 9 10 11 3/4 0 0 1 1 2 2 3 3 4 7/8 0 0 0 0 1 1 1 1 2 3/4 0 1 2 2 3 4 4 5 6 7/8 0 0 1 1 1 2 2 2 3 3/4 0 1 2 3 4 5 5 6 7 7/8 0 0 1 1 2 2 2 3 3 3/4 1 2 4 5 6 7 9 10 11 7/8 0 1 2 2 3 4 4 5 5 1 --- 1/8 0 0 0 1 1 1 1 1 1 Puron HP Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Application Guidelines 3
ELECTRICAL DATA UNIT SIZE V/PH OPER VOLTS* COMPR FAN MCA MIN WIRE SIZE MIN WIRE SIZE MAX LENGTH ft (m) MAX LENGTH ft (m) MAX MIN LRA RLA FLA 60 C 75 C 60 C 75 C 18---30 48.0 9.0 0.8 12.0 14 14 66 (20.1) 62 (18.9) 20 24---30 58.3 12.8 0.75 16.8 14 14 47 (14.3) 45 (13.7) 25 MAX FUSE* *or CKT BRK AMPS 30---30 77.0 16.0 0.8 21.4 12 12 58 (17.7) 56 (17.1) 30 36---30 208/230/1 253 197 79.0 16.7 0.9 21.7 12 12 58 (17.7) 55 (16.8) 35 42---30 109.0 19.9 1.2 26.0 10 10 77 (23.5) 73 (22.3) 40 48---30 117.0 21.8 1.2 28.4 8 8 109 (33.2) 104 (31.7) 50 60---30 134.0 26.3 1.2 34.1 8 8 91 (27.7) 87 (26.5) 50 * Permissible limits of the voltage range at which the unit will operate satisfactorily { If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70). } Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time --- Delay fuse. FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- RatedLoadAmps NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection. Complies with 2001 requirements of ASHRAE Standards 90.1 25HBB3 A -WEIGHTED SOUND POWER STANDARD TYPICAL OCTAVE BAND SPECTRUM (dba, without tone adjustment) UNIT SIZE RATING (dba) 125 250 500 1000 2000 4000 8000 18---30 74 52.0 63.5 68.0 70.5 66.5 62.0 57.5 24---30 75 54.5 64.0 69.0 69.5 67.5 64.0 58.0 30---30 74 52.0 62.5 66.5 68.5 65.0 63.5 59.0 36---30 72 55.0 62.0 63.5 66.0 64.0 61.5 54.0 42---30 77 55.5 60.0 63.5 71.5 65.0 62.5 59.0 48---30 77 58.0 65.5 68.5 72.0 66.5 60.5 53.0 60---30 77 55.0 63.0 67.5 71.5 68.0 64.0 60.5 NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI). A -WEIGHTED SOUND POWER WITH SOUND HOOD STANDARD UNIT SIZE RATING TYPICAL OCTAVE BAND SPECTRUM (dba, without tone adjustment) (dba) 125 250 500 1000 2000 4000 8000 18---30 73 52.5 63.0 67.5 69.0 66.0 62.0 55.5 24---30 74 54.0 63.5 69.0 69.0 67.5 63.5 57.5 30---30 74 51.5 62.0 66.5 67.5 64.5 62.0 57.5 36---30 70 54.5 62.0 63.5 64.5 63.0 60.0 51.5 42---30 75 55.0 60.5 63.5 69.0 64.5 61.5 56.0 48---30 74 58.0 64.5 69.0 68.5 66.0 60.0 53.0 60---30 74 55.0 63.5 67.0 69.0 66.5 62.0 57.0 NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI). CHARGING SUBCOOLING (TXV -TYPE EXPANSION DEVICE) UNIT SIZE---SERIES REQUIRED SUBCOOLING F ( C) 18---30 10 (5.6) 24---30 12 (6.7) 30---30 11 (6.1) 36---30 9 (5.0) 42---30 11 (6.1) 48---30 11 (6.1) 60---30 12 (6.7) 7
DIMENSIONS 25HBB3 8
"VARIABLE SPEED" V_HBX Series Variable Speed 1.5-5.0 Tons Cooling and Heat Pump 0-25kW Electric Heat Upflow / Horizontal The V_HBX series includes a programmable, high efficiency motor that redefines comfort and energy savings. The V_HBX motor automatically adjusts its torque and speed to maintain a pre-programmed level of constant airflow over a wide range of external static pressures. This variable speed technology offers better indoor air quality, more precise humidity control, quieter operation, consistent indoor air temperature, and lower utility bills High Efficiency - At full load conditions the V_HBX motor is 20% more efficient than an induction motor and at constant fan speed it consumes only 60-80 watts of power compared to 400 watts for a standard induction motor. In addition, the V_HBX includes a high efficiency "A" coil with factory installed TXV for precise refrigerant control in either cooling or heat pump mode. (1) First Co's customer is ultimately responsible for confirming which fan coil models are compatible with selected outdoor unit(s) and which expansion valves are required. To determine approved indoor/outdoor matches, go to www.firstco.com or contact the factory. VOHBX Model - Reversing valve energizes in cooling mode VBHBX Model - Reversing valve energizes in heating mode Variable Speed Motor Quiet Operation - The versatile V_HBX motor quietly "ramps up" when the unit is turned on and "ramps down" when the thermostat is satisfied, eliminating the annoying sounds of changing airflow. Self-Regulating Constant Airflow - The V_HBX motor is factory programmed to maintain a predetermined level of airflow over a wide range of external static pressures, ensuring optimum system performance and whole-house comfort. The benefits of constant fan operation are: Consistent air distribution (and temperature) throughout the home Better indoor air quality (further improved with the addition of a high efficiency filter) - This allows the air to be filtered without excessive drafts and without sacrificing efficiency. Better humidity control - The V_HBX is designed to extract much more moisture from the air than a conventional system by slowing the airflow over the cooling coil. The result is an improved summer comfort level at higher indoor temperatures. Additional Standard Features Factory installed R22 or R410a TXV (cooling or heat pump operation) Factory installed electric heat (0-25kW) 208/240V motor Upflow / horizontal drain pans Higher efficiency pleated filter Factory installed disconnect switch (over 10kW) Compatible with major brands of split condensing units or heat pumps Primary and secondary drain connections on cooling coil Insulated cabinet with baked-on powder coat finish Compatible with most properly sized and installed zone control systems. Contact the zone control manufacturer. FIRST CO. - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.firstco.com
V_HBX Series Cooling with Electric Heat (See P.4 for Model Numbers) PHYSICAL DIMENSIONS UNIT MODEL A B C D E F G H J FILTER SIZE 24V_HBX 40 20 20 18-1/2 16 2 18 16 3 18 X 20 X 1 36V_HBX 42 23 20 21-1/2 16 2 18 17 5 20 X 22 X 1 48/60V_HBX 48 28 21-1/4 26-1/4 17 2 19-1/4 18-1/4 8-7/8 20 X 25 X 1 AIR FLOW DATA (see "heating select taps" below each table for proper field set-up) THERMOSTAT TERMINALS CONTROL BOARD SELECT TAPS HEAT TAP MODEL OPERATING MODE "X" ENERGIZED TERMINALS COOL TAP (See notes below) Y1 G O W1 A B C D A B C D COOLING X X X 800 720 600 525 CONTINUOUS BLOWER X 400 360 300 265 24V_HBX HEAT PUMP HEATING X X 720 650 600 550 ELECTRIC HEAT X 790 730 660 600 Heating Select Taps A 2 ton outdoor unit with 0-10 kw electric heat B 2 ton outdoor unit with 0-5 kw max. electric heat C 1-1/2 ton outdoor unit with 0-10 kw electric heat D 1-1/2 ton outdoor unit with 0-5 kw max. electric heat COOLING X X X 1200 1050 950 850 CONTINUOUS BLOWER X 600 525 475 425 36V_HBX HEAT PUMP HEATING X X 1080 950 850 760 ELECTRIC HEAT X 1130 1000 875 790 Heating Select Taps A 3 or 2-1/2 ton outdoor unit with 0-15 kw electric heat B 3 or 2-1/2 ton outdoor unit with 0-10 kw max. electric heat C 2-1/2 ton outdoor unit with 0-10 kw electric heat D 2-1/2 ton outdoor unit with 0-5 kw max. electric heat UNIT SIZE COIL CONNECTIONS LIQUID SUCTION 24 3/8 5/8 36 3/8 3/4 46/60 1/2 7/8 ACCESSORIES: Programmable Thermostat Part Description Number Touchscreen, T832 7-day programmable, with humidity control For All Models NOTE: Contact factory for brochure COOLING X X X 1600 1400 1250 1100 CONTINUOUS BLOWER X 800 700 625 550 48V_HBX HEAT PUMP HEATING X X 1440 1260 1125 990 ELECTRIC HEAT X 1500 1360 1190 1060 Heating Select Taps A+10% 4 or 3-1/2 ton outdoor unit with 20-25 kw electric heat A 4 or 3-1/2 ton outdoor unit with 10-20 kw max. electric heat B 4 or 3-1/2 ton outdoor unit with 0-10 kw max. electric heat C 3-1/2 ton outdoor unit with 10-15 kw electric heat D 3-1/2 ton outdoor unit with 0-10 kw max. electric heat T832 COOLING X X X 2000 1800 1600 1400 CONTINUOUS BLOWER X 1000 900 800 700 60V_HBX HEAT PUMP HEATING X X 1800 1625 1450 1250 ELECTRIC HEAT X 1875 1700 1500 1300 Heating Select Taps A 5 or 4 ton outdoor unit with 15-25 kw electrric heat B 5 or 4 ton outdoor unit with 0-15 kw max. electric heat C 4 ton outdoor unit with 10-20 kw electric heat D 4 ton outdoor unit with 0-10 kw max. electric heat Airflow shown are at standard air conditions, dry coil at 240 volts. Max. ext. static pressure is 0.50" wtr Notes: The cooling and heating speed taps are factory set on "A". The delay profile is factory set on "A" (Arid setting). The adjust profile is factory set on Normal. If humidistat function is activated the cooling CFM will be reduced by 20%. Adjust profile (+) will increase airflow by 10%, while tap (-) will decrease airflow by 10%. For additional sales and technical information on variable speed motors, visit www.thedealertoolbox.com Digital thermostats for these units must have a "C" terminal. -2-