qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

Similar documents
TECHNICAL DATA OBSOLETE

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

Microfast quick response Fusible element hsw sprinkler

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

standard response fusible link sidewall sprinkler VK112 (K5.6)

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

standard response Fusible Link Upright sprinkler VK204 (K8.0)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

micromatic Standard response Horizontal Sidewall sprinkler

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

microfast quick response Pendent sprinkler VK302 (K5.6)

quick response horizontal sidewall sprinkler vk360 (K8.0)

TECHNICAL DATA. Page 1 of 6

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

micromatic Standard response Horizontal Sidewall sprinkler

STANDARD/quick. Sprinkler 42o. August 8, 2011

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

standard/quick response extended coverage light and ordinary hazard elo sprinklers

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

microfast quick response extended coverage hsw sprinkler vk606

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

quick response Sprinkler 105a October 25, 2010

standard response elo upright and pendent sprinklers (storage-density/area)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

micromatic standard response Upright sprinkler VK100 (K5.6)

microfast and microfasthp quick conventional sprinklers

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

standard response large orifice dry

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

standard response/ quick response extended coverage

standard response elo upright sprinkler

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

micromatic standard response stainless steel sprinklers

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

TECHNICAL DATA vk470 (K3.0)

TECHNICAL DATA. Page 1 of 5

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

freedom residential pendent sprinkler vk466 (K5.2)

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT LEAD FREE SPRINKLER VK4700 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

Standard Spray concealed horizontal sidewall sprinkler VK481

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK460 (K5.8) TECHNICAL DATA

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

Transcription:

March 14, 2013 Sprinkler 42h 1. DESCRIPTION Viking Quick Response Fusible Element Upright and Pendent Sprinklers are small thermosensitive solder link spray sprinklers available with various finishes and temperature ratings to meet design requirements. The special Polyester and Polytetrafluoroethylene (PTFE) coatings can be used in decorative applications where colors are desired. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Classes 2002 and 2020 Refer to Approval Chart 1 and Design Criteria on page 42k for culus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 42l for FM Approval requirements that must be followed. 3. technical data Specifications: Available since 2007. Minimum Operating Pressure: 7 psi (0.5 bar) Rated to 175 psi (12 bar) water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Overall Length: 2-1/4 (58 mm) Viking Technical Data may be found on The Viking Corporation s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 13956 and 13959. QM Brass for Sprinklers 17535 and 17536. Deflector: Brass UNS-C26000 for Sprinklers 13956 and 13959. Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 17535 and 17536. Bushing (for Sprinklers 13956 and 13959): Brass UNS-C36000 Fusible Element Assembly: Nickel Alloy Trigger and Support: Stainless Steel UNS-S31600 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Screw: Brass UNS-C36000 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Fusible Element Upright and Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome-Enloy = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N Temperature Suffix: 165 F (74 C) = C, 205 F (96 C) = E, and 280 F (138 C) For example, sprinkler VK326 with a Brass finish and a 165 F (74 C) temperature rating = Part No. 13956AC Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Sprinkler Accessories section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for recessed pendent sprinklers: Part No. 13577W/B* (available since 2006) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.) * A ½ ratchet is required (not available from Viking). **Allows use from the floor by attaching a length of 1 diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) Form No. F_021407 Replaces page 42h-m, dated June 21, 2012 (Added UL approval for VK301 and VK303.)

Sprinkler 42i March 14, 2013 B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. Installation Refer to appropriate NFPA Installation Standards. 5. Operation During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and spring assemblies to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availability Viking Quick Response Fusible Element Upright and Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. Guarantee For details of warranty, refer to Viking s current list price schedule or contact Viking directly. Figure 2: Upright Sprinkler Dimensions Figure 1: Standard Sprinkler Wrench 10896W/B

March 14, 2013 Sprinkler 42j Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Frame Paint Color Ordinary 165 F (74 C) 100 F (38 C) None Intermediate 205 F (96 C) 150 F (65 C) White High 280 F (138 C) 225 F (107 C) Blue Sprinkler Finishes: Brass, Chrome-Enloy, White Polyester 3, Black Polyester 3, and Black PTFE 3 Footnotes 1 Decorative sprinklers may not be color coded. The temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and PTFE coatings. For PTFE coated open sprinklers only, the waterway is coated. Figure 3: Wrench 16036W/B for Recessed Pendent Sprinklers

Sprinkler 42k March 14, 2013 Base Part Number 1 SIN Sprinkler Style Approval Chart 1 (UL) Quick Response Fusible Element Upright and Pendent Sprinklers Maximum 175 PSI (12 Bar) WWP Thread Size Nominal K-Factor Overall Length Listings and Approvals 3 (Refer also to Design Criteria below.) NPT BSP U.S. metric 2 Inches mm culus 4 NYC VdS LPCB Standard Orifice 17535 VK301 Upright 1/2 15 mm 5.6 80.6 2-1/4 58 A1 See Footnote 5. -- -- -- -- 17536 VK303 Pendent 1/2 15 mm 5.6 80.6 2-1/4 58 B1Y, A1Z See Footnote 5. -- -- -- -- Small Orifice 7 13956 6 VK326 Upright 1/2 15 mm 2.8 40.3 2-1/4 58 A1 See Footnote 5. -- -- -- -- 13959 6 VK330 Pendent 1/2 15 mm 2.8 40.3 2-1/4 58 A1Z, B1Y See Footnote 5. -- -- -- -- Approved Temperature Ratings A - 165 F (74 C), 205 F (96 C), 280 F (138 C) B - 165 F (74 C) and 205 F (96 C) Approved Finishes 1 - Brass, Chrome-Enloy, White Polyester 8, Black Polyester 8, and Black PTFE Footnotes 1 Base part number shown. For complete part number, refer to Viking s current price schedule. Approved Escutcheons Y - Standard surface-mounted escutcheons or the Viking Microfast Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic Model E-1 or E-2 Recessed Escutcheon Z - Standard surface-mounted escutcheons or the Viking Microfast Model F-1 Adjustable Escutcheon 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 Meets New York City requirements, effective July 1, 2008. 6 The sprinkler orifice is bushed. 7 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. 8 Other colors are available on request with the same Listings and Approvals as the standard colors. culus Listing Requirements: DESIGN CRITERIA - UL (Also refer to Approval Chart 1 above.) Quick Response Fusible Element Upright and Pendent Sprinklers are culus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. - Designed for use in Light and Ordinary Hazard occupancies. (NOTE: small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only.) - Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m). - Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13. - Minimum distance from walls is 4 in. (102 mm). - Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. - The sprinkler installation rules contained in NFPA 13 for standard spray upright and pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

March 14, 2013 Sprinkler 42l Base Part Number 1 SIN Sprinkler Style Approval Chart 2 (FM) Quick Response Fusible Element Upright and Pendent Sprinklers Maximum 175 PSI (12 Bar) WWP Thread Size Nominal K-Factor Overall Length FM Approvals 3 NPT BSP U.S. metric 2 Inches mm Standard Orifice (Refer also to Design Criteria below.) 17535 VK301 Upright 1/2 15 mm 5.6 80.6 2-1/4 58 A1 17536 VK303 Pendent 1/2 15 mm 5.6 80.6 2-1/4 58 A1Y Small Orifice 4 13956 5 VK326 Upright 1/2 15 mm 2.8 40.3 2-1/4 58 A1 13959 5 VK330 Pendent 1/2 15 mm 2.8 40.3 2-1/4 58 A1Z Approved Temperature Ratings A - 165 F (74 C), 205 F (96 C), and 280 F (138 C) Approved Finishes 1 - Brass and Chrome-Enloy Footnotes 1 Base part number shown. For complete part number, refer to Viking s current price schedule. Approved Escutcheons Y - Standard surface-mounted escutcheons or recessed with the Viking Micromatic Model E-1 or E-2 Recessed Escutcheon Z - Standard surface-mounted escutcheons or the Viking Microfast Model F-1 Adjustable Escutcheon 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4 FM Approved as quick response Non-Storage upright and pendent sprinklers. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). 5 The sprinkler orifice is bushed. FM Approval Requirements: DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) Sprinklers in Approval Chart 2 are FM Approved as quick response Non-Storage upright and pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from culus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Sprinkler 42m March 14, 2013 Figure 4: Pendent Sprinkler VK330 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon Figure 5: Pendent Sprinkler VK330 Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_021407 Replaces page 42h-m, dated June 21, 2012 (Added UL approval for VK301 and VK303.)