EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

Similar documents
EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

kw COOLING kw HEATING

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

GLIDER EVO GLIDER EVO. rcgroupairconditioning

glider evo cla glider evo cla A-CLASS rcgroupairconditioning

GLIDER EVO CLA GLIDER EVO CLA HIGHEFFICIENCY ACLASS. rcgroupairconditioning

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

EQPHU PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR OUTDOOR INSTALLATION

EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION

kw. technicalcatalogue

44,9 202,0 kw. technicalcatalogue

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

pyxis pyxisa NEW rcgroupairconditioning

FRIGO SCREW CLA PLUS Packaged water cooled liquid chillers in A+ class energy efficiency for indoor installation. Cooling Capacity: kw

pyxis u pyxis ua NEW rcgroupairconditioning

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning

unico pf unico pf rcgroupairconditioning

kw. technicalcatalogue

PYXIS U PYXIS U. rcgroupairconditioning

pyxis hp "u" pyxis hp "u" IDEA NEW rcgroupairconditioning

KELVIN Clim F497. Kelvin air conditioning

UNICO TURBO FL FREE UNICO TURBO FL FREE HIGHEFFICIENCY INVERTER ACLASS FREECOOLING LOWNOISE. rcgroupairconditioning

unico turbo FL unico turbo FL LOW NOISE A-CLASS INVERTER rcgroupairconditioning

21,8 222 kw COOLING 25,2 236 kw HEATING

Kelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

Kelvin air conditioning. KELVIN Clim W250. Cooling Capacity: 250 ~ 1240 kw

rcgroup.it Flooded evaporator Low noise Minimum starting current EER up to 5,25 ESEER up to 8,88

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

nemo a hp rcgroupairconditioning R410A

rcgroup.it Flooded evaporator Refrigerant charge HFO1234ze, GWP<1 Low noise Minimum starting current EER up to 5,41 ESEER up to 9,10

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

NEXT DL NEXT DL. rcgroupairconditioning

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

NEMO A Split-system liquid chillers for indoor installation. Cooling Capacity: 5 26 kw

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

frigo turbo FL Chillers

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

next p dw next p dw rcgroupairconditioning

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Aquaflair TRAC-TRAF-TRAH

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

LZT High efficiency air to water heat pumps with E.V.I. compressors

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

next evo cw next evo cw rcgroupairconditioning

LZA High efficiency air to water heat pumps with HP compressor

Water chillers water/water type SIGMA Technical information manual

Blue Box Epsilon Echos +

GLIDER_. air cooled liquid chilled chillers / heat pumps

Air cooled industrial chillers

1

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Commercial and Technical Data

Technical Catalogue. Multi-Scroll Air-Cooled Liquid Chillers. Nominal cooling capacity: kw 50 Hz

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

ARV.

Modular Air-cooled Chillers

i-next DX kw FULL INVERTER direct expansion air conditioners for IT Cooling. To be matched with remote air-cooled condenser. rcitcooling.

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

next DX.U.S* 052.Z2.H6.DC

TCHVZ TCEVZ

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

EHW KH PF HIGH EFFICIENTY AIR CONDITONING UNITS TECHNICAL CATALOGUE

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

H4T R410A. refrigerant

ROOF TOP TYPE UNITS CENTRIFUGAL FANS ENGINEERING DATA MANUAL MODELS Rev. 100

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

ECV SP GUE ALO CAT ICAL TECHN

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

Transcription:

TECHNICAL CATALOGUE EQSL Air Cooled Water Chillers Models: 300 V2 F06 1310 V2 F16 Cooling capacity: 299 to 1310 KW 02.16 ref. 207598 Rev.100

Thank you for trusting in Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning and cooling installations for over 30 years. Our approach is based on efficiency, adaptability, usability and practical solutions. This has been the hallmark of our product catalogue. The versatility of our factory allows us to contribute solutions, almost tailored to each project s specifications, in search of a solution to every problem that arises in design and implementation of air conditioning installations. From all of us at Hiplus Aire Acondicionado, once again, thank you very much 2

GENERAL CHARACTERISTICS... 4 EQSL SERIES... 4 EQSL MODELS... 4 OPERATING LIMITS... 5 TECHNICAL SPECIFICATIONS... 9 MP.COM MICROPROCESSOR CONTROL SYSTEM... 13 OPTIONALS... 15 PUMP KITS... 15 HYDRONIC PUMPS PERFORMACE CHARTS... 18 OTHER OPTIONALS... 19 KIT "BRINE"... 19 KIT LNO... 19 KIT XLS... 19 HIGH PRESSURE EC AXIAL FANS... 20 TECHNICAL SPECIFICATIONS... 21 PARTIAL HEAT RECOVERY SYSTEM... 25 PARTIAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM... 25 TOTAL HEAT RECOVERY SYSTEM... 26 TOTAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM... 26 DIMENSIONS... 27 MODELS 300 320 360... 27 MODELS 390 430 480 530 540 560... 28 MODELS 610 650... 29 MODELS 710 770 850... 30 MODEL 910... 31 MODEL 950... 32 MODELS 1060 1120 1180 1310... 33

GENERAL CHARACTERISTICS Packaged air cooled liquid chillers for chilled water production. The machines are made with weather resistant materials and suitable for outdoor installation. Framework with sections of thick steel for high resistance to the greatest stress during handling and transport. Machines supply fully assembled with refrigerant charge and control systems. The installation requires electrical and hydraulic connections only allowing high costs and time reduction. Final assembly on all machines before shipment including running test, reading and monitoring of operating parameters, alarms simulation and visual check. Design, assembly and test as per the Company Quality Assurance program in full compliance with ISO 9001:2008. Environmental Management System Certification according to ISO 14001:2004. The machines are in full compliance with European Directive 2006/42EC, 2006/95EC, 2004/108EC, 97/23EC and subsequent amendments. EQSL SERIES Machines equipped with condensing coils in "W" position, screw compressors, axial fans and shell and tube evaporator. Horizontal air suction and vertical air delivery. Cooling capacity : 299-1310 KW. EQSL MODELS EQSL 520 V2 F10 Cabinet size 2 Number of compressors 520 Cooling capacity in KW under standard conditions 4

OPERATING LIMITS Cooling Production of chilled water Operating limits diagram for chilled water production according to the ambient temperature and chilled water outlet temperature. OPERATING CONDITIONS A Operating conditions for which the unit s cooling capacity can be measured with the electronic selection program. OPERATING CONDITIONS B Operating conditions for which the unit s cooling capacity has to be measured by our commercial and sales department. These values are indicative. Operating temperatures are influenced by a series of variables, such as: Working conditions. Thermal load. Active power stages. Cleanliness of the heat exchanging coils. Microprocessor regulation. TOTAL HEAT RECOVERY The system is totally controlled by the microprocessor and the heating capacity which is supplied depends on the microprocessor set. 30 60 C hot water outlet temperature range 3 8 C Δt range between water inlet/outlet PARTIAL HEAT RECOVERY The system is not regulated and the heating capacity which is supplied depends on the machine s working conditions. 40-75 C Range of hot water outlet temperature. 5-15 C Δt range between water intake/outlet. ANTIFREEZE MIXTURES Antifreeze mixtures must be used when the conditions are expected to produce outlet chilled water below 5 C. PROPYLENE GLYCOL Chilled water outlet Temp. Percentage of mixture (in weight) ETHYLENE GLYCOL Chilled water outlet Temp. Percentage of mixture (in weight) Attention: ºC 4 2 1-2 -4-6 -9 % 5 10 15 20 25 30 35 ºC 4 2 0-4 -7-9 -10 % 5 10 15 20 25 30 35 These values refer to the machine s operating temperature. The use of antifreeze mixtures may result in a decrease in the unit s performance. Please, use the selection program to obtain the effective performance. STORAGE TEMPERATURE If the unit is not installed immediately after reception and is to be stored for an extended period of time, please, make sure that storage temperatures range between -30 and 50ºC and the unit is not subject to condensation or direct sunlight. 5

FRAMEWORK Base, self supporting frame and panelling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders. COMPRESSORS - Twin screw semi-hermetic compressors with highly efficient screw profile and high peripheral speed, optimized for R134a refrigerant. - Integrated discharge check valve. - Flanged-on oil separator. - Integrated safety relief valve (overpressure inner valve). - Replaceable cartridge oil filter. - Oil flow switch. - Valves for oil filling and discharge. - Oil sight glass. Electronic protection device that includes : - Electric motor thermal protection via internal winding temperature sensors. - Phase sequence electronic relay. - Sensor on refrigerant discharge for temperature monitoring. - 2-pole 3-phase electric motor with Part-Winding starting from model 300 V2 F06 to model 530 V2 F08 included. - 2-pole 3-phase electric motor with Star / Delta starting from model 540 V2 F08 to model 1310 V2 F16 included. - Stepless capacity control, 50 100% for each compressor. - Crankcase heater. - Terminal box with IP54 class enclosure. - Rubber supports. EVAPORATOR - Single pass type shell and tube evaporator, optimized for R134a refrigerant. - Tubes with a helical rifled internal surface. - Intermediate baffles positioned to ensure optimum speed of the fluid and low pressure drops. - Single circuit on water side and independent circuits, one for each compressor, on refrigerant side. - Shell, header, tube sheets, made of carbon steel, tubes in Cu. - Anticondensate insulation made of polyurethane. - Temperature sensors on water inlet and outlet. - Antifreeze heater. - Hydraulic connections with grooved end arranged for flexible joint (the flexible joint and the adapter pipe are optional accessories). CONDENSING COIL Heat exchanger coil with high efficiency aluminum fins, specifically developed to provide high heat transfer and lower pressure drops. The combination of two factors, special tubes and fins, allows to optimally combine the following aspects: - Maximum capacity relative to the size of the exchanger. - Minimum charge of refrigerant. - Reduction of the air flow required for the heat exchange. Frame in galvanized steel. FAN SECTIONS - Axial fans with sickle-shaped blades, fan guard and optimized for low noise levels. - External rotor AC type electric motor with stepless variable speed for condensing pressure control with phase-cut electronic controller. - IP54 class enclosure. COOLING CIRCUIT - Electronic expansion valve that allows high performance and system efficiency thanks to a timely and accurate response to changes in temperature and pressure. - Energy reserve module for the electronic expansion valve to allow the closure of the valve in the event of lack of power supply. - Sight glass. - Filter dryer on liquid line. - Service valves on liquid line. - Service valves on compressor gas discharge. - Double safety valve (only one in function) on high and low pressure side. - The system include two safety valves with manual changeover system. - Pressure transducers with indication, control and protection functions, on low and high refrigerant pressure and oil pressure. - High pressure safety switch with manual reset. - Pressure gauge on high and low pressure. - Refrigerant circuit with copper tubing with anticondensate insulation of the suction line. - Plastic capillary hoses for pressure sensors connection. R134a refrigerant charge. ELECTRICAL PANEL In accordance with EN60204-1 norms, suitable for outdoor installation, IP54 class enclosure, complete with: - Main switch with door lock safety. - Fuses for each compressor. - Magnetothermic switches for fans. - Fuses for water pumps (if scheduled). - Contactors for each load. - Compressor Part-Winding starting system from model 290 V2 F06 to model 570 V2 F10 included. - Compressor Star / Delta starting system from model 620 V2 F10 to model 1510 V2 F24 included. - Transformer for auxiliary circuit and microprocessor supply. - Panel with machine controls. - Power supply 400/3/50. CONTROL SYSTEM MP.COM microprocessor system with graphic symbol for control and monitor of operating and alarms status. The system includes: - Voltage free contact slot for remote general alarm. - Service hour meter for main components. - Non-volatile flash memory for data storage. - Menu with password security. - LAN connection. HYDRAULIC CONNECTIONS - Heat exchangers threaded hydraulic connections ISO 228/1 G M, available up to a diameter of 3" included. - Pipes threaded hydraulic connections ISO 7/1 R, available up to a diameter of 3" included. - The hydraulic connections with flange (FL) are not supplied with counter flange. - The hydraulic connections with grooved end are not supplied with flexible joint (optional accessory). 6

ACCESSORIES - Pump KIT. Includes chilled water flow safety switch. - Kit LNO for reduction of noise emissions. - Kit XLS for extreme reduction of noise emissions. - High pressure axial fans equipped with EC motors. - Partial heat recovery system. (not available for units with double cooling circuits) - Voltage free contact slot for partial heat recovery with pump activation. - Partial Heat Recovery System. - Total Heat Recovery System. - Kit "BRINE A" for chilled water production up to -6ºC. (this accessory is not compatible with the Total Heat Recovery System). - Kit "BRINE B" for chilled water production below -6ºC. (this accessory is not compatible with the Total Heat Recovery System). Warning: with the BRINE KIT, it is mandatory to use an antifreeze mixture. Please, refer to the Antifreeze Mixture chapter in this manual. The use of antifreeze mixtures may result in a decrease in the unit s performance. (PLEASE, CONTACT OUR COMMERCIAL DEPARTMENT) OTHER ACCESSORIES - Chilled water safety flow switch. - Analog flowmeter (0 1V / 4-20mA) for measurement and display of the evaporator water flow. The optional accessory stops the machine in case of water flow anomalies. The installation of the analog flowmeter excludes the installation of the water flow switch. The optional accessory involves the installation of the microprocessor expansion module "1" and its driver. - Hydraulic connections of the evaporator and total heat reclaim heat exchangers with flexible joint with adapter pipe (solder type). Flexible joint with adapter for flange connection (FL). The counterflange is not supplied. - Anti-freeze kit for hydraulic pipes of the pumping group. - Compressor thermal protection relay. - Power factor capacitor for motor compressor - cosφ 0.9. - Supply network control relay. Measurement and control of the minimum line voltage, over line voltage, phase loss, phase unbalance and phases sequence of the unit. The system stops the machine in case of operative conditions malfunction. - Compressor operation signalling through additional voltage free contact. - Demand limit. The optional accessory limits the electrical absorption of the unit according to a set point value with a reduction of the machine engaged load (activation of the compressor capacity control or, in extreme cases, stop of a compressor). The optional accessory involves the installation of the microprocessor expansion module "2" and its driver. - Analog set point compensation (0-1V). Available only for machines with single refrigerant circuit. The optional accessory involves the installation of the microprocessor expansion module "1" and its driver. Available compensation systems: - Compensation according to ambient temperature (the system foresees the installation of the ambient temperature sensor). - Compensation according to an external analog signal. - Stop valve on compressor suction. - Air/gas heat exchanger protection net. - Air/gas heat exchanger in special execution (please contact our Commercial Dept.). - Spring antivibrating supports for the machine- supplied not installed. - Rubber supports for the machine supplied not installed. - Electrical panel heating system (suggested in case of operation of the machine with negative ambient temperature). - Ambient temperature sensor. The ambient temperature sensor requires the installation of the microprocessor expansion module "1" and its driver. 7

OTHER ACCESSORIES MP.COM microprocessor accessories : - Remote terminal. - Line voltage indication. - Line current indication. - Clock card for alarms date and time displaying and storing. - Serial port RCcom, MBUS/JBUS. - Serial port LON. - Serial port BACnet for Ethernet SNMP TCP/IP. - Serial port BACnet for MS/TP. - Serial port for GSM modem. - Data logger for the memorization of the intervened alarms. Additional module "1" with the following inputs / outputs: INPUTS : - Analog flowmeter / Line voltage indication / Line current indication. - Compensation / Line voltage indication / Line current indication. - Ambient air temperature. - The additional module "1" is already included with Water Pumps and Total heat reclaim optional accessories. Additional module "2" with the following inputs / outputs: INPUTS : - Demand limit. The accessory requires an additional digital input for enabling. - External alarm 1. - External alarm 2. OUTPUTS : - Programmable alarm 1. - Programmable alarm 2. - Programmable alarm 3. - General alarm 2. - Driver for the additional module. Warning : We reserve the right to accept possible combinations of optional accessories installed on the unit. 8

TECHNICAL SPECIFICATIONS MODEL 300 V2 F06 320 V2 F06 360 V2 F08 390 V2 F08 430 V2 F08 CAPACITIES Cooling capacities (1) KW 299 315 335 391 430 EER KW / KW 2,78 2,77 2,62 2,78 2,77 ESSER 3,06 3,03 3,20 3,18 3,10 REFRIGERANT Type R-134a Load Kg 110 146 146 145 145 Gas circuits 2 2 2 2 2 PCA 1430 1430 1430 1430 1430 COMPRESSOR Type Twin Screw Number 2 2 2 2 2 Absorbed power KW 96 102 116 125 140 Operating current A 162 163 200 208 237 Starting current A 404 383 469 630 639 Maximum absorbed current A 202 205 236 270 288 Power steps 25.. 100% 25.. 100% 25.. 100% 25.. 100% 25.. 100% EVAPORATOR FAN Type AXIAL Nominal air flow m 3 /h 135498 135498 135498 180664 180664 Number 6 6 6 8 8 Absorbed power (1) KW 11,6 11,7 11,7 15,4 15,4 Maximum absorbed current A 23,4 23,4 23,4 31,2 31,2 EVAPORATOR EXCHANGER Water load lt 113 113 113 160 160 Water flow m 3 /h 51,3 54,1 57,5 67,1 73,9 Maximum water flow m 3 /h 63 63 63 90 90 Pressure drop KPa 47 52 48 59 54 Pollution factor m²*k/kw 0,043 0,043 0,043 0,043 0,043 ELECTRICAL CHARACTERISTICS Voltage V/ph/Hz 400 / III / 50 NOISE LEVELS Acoustic pressure 1m (4) db(a) 73,1 71,7 72,0 71,6 76,0 Acoustic power (5) db(a) 92,9 91,4 91,8 91,9 96,2 DIMENSIONS AND WEIGHT Length mm 3520 3520 3520 4490 4490 Width mm 2260 2260 2260 2260 2260 Height mm 2550 2550 2550 2550 2550 Net weight Kg 3992 4258 4411 4544 4753 1. Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 C; Intake/Outlet hot water temperature 40/45 C Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C and Intake/Outlet hot water temperature 40/45 C. 4. Avergae sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 2. 9

MODEL 480 V2 F08 530 V2 F08 540 V2 F08 560 V2 F08 610 V2 F08 CAPACITIES Cooling capacities (1) KW 476 523 543 563 611 EER KW / KW 2,76 2,76 2,78 2,79 2,78 ESSER 3,13 3,17 3,23 3,21 3,17 REFRIGERANT Type R-134a Load Kg 145 145 170 194 194 Gas circuits 2 2 2 2 2 PCA 1430 1430 1430 1430 1430 COMPRESSOR Type Twin Screw Number 2 2 2 2 2 Absorbed power KW 157 174 180 186 204 Operating current A 261 286 297 309 332 Starting current A 790 811 526 545 545 Maximum absorbed current A 309 330 347 367 390 Power steps 25.. 100% 25.. 100% 25.. 100% 25.. 100% 25.. 100% EVAPORATOR FAN Type AXIAL Nominal air flow m 3 /h 180664 180664 177924 175184 175184 Number 8 8 8 8 8 Absorbed power (1) KW 15,4 15,4 15,5 15,6 15,6 Maximum absorbed current A 31,2 31,2 31,2 31,2 31,2 EVAPORATOR EXCHANGER Water load lt 150 150 143 143 256 Water flow m 3 /h 81,8 89,8 93,3 96,7 105,0 Maximum water flow m 3 /h 95 95 100 100 127 Pressure drop KPa 38 38 41 45 51 Pollution factor m²*k/kw 0,043 0,043 0,043 0,043 0,043 ELECTRICAL CHARACTERISTICS Voltage V/ph/Hz 400 / III / 50 NOISE LEVELS Acoustic pressure 1m (4) db(a) 76,2 76,4 76,4 76,4 78,0 Acoustic power (5) db(a) 96,4 96,7 96,7 96,7 98,2 DIMENSIONS AND WEIGHT Length mm 4490 4490 4490 4490 4490 Width mm 2260 2260 2260 2260 2260 Height mm 2550 2550 2550 2550 2550 Net weight Kg 4890 5012 5117 5221 5321 1. Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 C; Intake/Outlet hot water temperature 40/45 C Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C and Intake/Outlet hot water temperature 40/45 C. 4. Avergae sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 2. 10

MODEL 650 V2 F08 710 V2 F10 770 V2 F10 850 V2 F10 910 V2 F12 CAPACITIES Cooling capacities (1) KW 645 707 768 853 905 EER KW / KW 2,77 2,78 2,77 2,76 2,77 ESSER 3,24 3,18 3,18 3,19 3,26 REFRIGERANT Type R-134a Load Kg 194 241 241 302 289 Gas circuits 2 2 2 2 2 PCA 1430 1430 1430 1430 1430 COMPRESSOR Type Twin Screw Number 2 2 2 2 2 Absorbed power KW 217 237 258 289 303 Operating current A 354 377 400 456 479 Starting current A 568 581 611 721 827 Maximum absorbed current A 414 444 474 534 567 Power steps 25.. 100% 25.. 100% 25.. 100% 25.. 100% 25.. 100% EVAPORATOR FAN Type AXIAL Nominal air flow m 3 /h 175184 197082 218980 212690 262776 Number 8 9 10 10 12 Absorbed power (1) KW 15,6 17,6 19,5 20,1 23,4 Maximum absorbed current A 31,2 35,1 39,0 39,0 46,8 EVAPORATOR EXCHANGER Water load lt 256 256 247 238 223 Water flow m 3 /h 111 121 132 147 156 Maximum water flow m 3 /h 127 127 143 154 172 Pressure drop KPa 56 63 73 55 63 Pollution factor m²*k/kw 0,043 0,043 0,043 0,043 0,043 ELECTRICAL CHARACTERISTICS Voltage V/ph/Hz 400 / III / 50 NOISE LEVELS Acoustic pressure 1m (4) db(a) 79,2 79,4 80,0 79,7 78,8 Acoustic power (5) db(a) 99,4 100,1 100,7 100,4 99,8 DIMENSIONS AND WEIGHT Length mm 4490 5460 5460 5460 6430 Width mm 2260 2260 2260 2260 2260 Height mm 2550 2550 2550 2550 2550 Net weight Kg 5241 6232 6517 7032 7354 1. Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 C; Intake/Outlet hot water temperature 40/45 C Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C and Intake/Outlet hot water temperature 40/45 C. 4. Average sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 2. 11

MODEL 950 V2 F12 1060 V2 F16 1120 V2 F16 1180 V2 F16 1310 V2 F16 CAPACITIES Cooling capacities (1) KW 949 1063 1121 1181 1310 EER KW / KW 2,76 2,75 2,76 2,77 2,76 ESSER 3,32 3,29 3,34 3,32 3,30 REFRIGERANT Type R-134a Load Kg 289 290 290 290 389 Gas circuits 2 2 2 2 2 PCA 1430 1430 1430 1430 1430 COMPRESSOR Type Twin Screw Number 2 2 2 2 2 Absorbed power KW 320 355 375 396 443 Operating current A 515 597 634 680 742 Starting current A 903 1058 1138 1182 1324 Maximum absorbed current A 615 710 754 798 896 Power steps 25.. 100% 25.. 100% 25.. 100% 25.. 100% 25.. 100% EVAPORATOR FAN Type AXIAL Nominal air flow m 3 /h 262776 361328 361328 361328 350368 Number 12 16 16 16 16 Absorbed power (1) KW 23,4 30,9 30,9 30,9 31,2 Maximum absorbed current A 46,8 62,4 62,4 62,4 62,4 EVAPORATOR EXCHANGER Water load lt 223 382 382 370 359 Water flow m 3 /h 163 183 193 203 225 Maximum water flow m 3 /h 172 208 208 220 241 Pressure drop KPa 71 41 45 49 59 Pollution factor m²*k/kw 0,043 0,043 0,043 0,043 0,043 ELECTRICAL CHARACTERISTICS Voltage V/ph/Hz 400 / III / 50 NOISE LEVELS Acoustic pressure 1m (4) db(a) 78,8 81,1 81,1 81,1 81,4 Acoustic power (5) db(a) 99,8 102,9 102,9 102,9 103,2 DIMENSIONS AND WEIGHT Length mm 6430 8720 8720 8720 8720 Width mm 2260 2260 2260 2260 2260 Height mm 2550 2550 2550 2550 2550 Net weight Kg 7414 9491 9975 9995 10075 1. Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 C; Intake/Outlet hot water temperature 40/45 C Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 C; Ambient air temperature 35 C and Intake/Outlet hot water temperature 40/45 C. 4. Avergae sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 2. 12

MP.COM MICROPROCESSOR CONTROL SYSTEM The MP.COM microprocessor control system is equipped with an 8-key terminal and backlit graphic display on which all information in different languages or easily identifiable symbols are displayed. The system counts with a "flash" memory that preserves the information even in absence of an external power supply. FUNCTIONS 13

REMOTE CONTROLS/ALARMS Remote Controls/Alarms. Voltage free Control/Alarm. 14

A CLASS A ENERGY EFFICIENCY OPTIONALS PUMP KITS Pump KIT. It is possible to install only one of the following options: Standard version Pump KIT. - One pump. - Two pumps operating simultaneously. STANDARD VERSION SINGLE PUMP KIT HYDRAULIC DIAGRAM STANDARD VERSION TWIN PUMP KIT HYDRAULIC DIAGRAM The pumping group includes: - Control and working electric equipment contained in the chiller electric board and directly managed by the microprocessor control. - Valve on suction line. - Valve on discharge line. - In-line type water pump. - Safety flow switch (excludes the installation of the water flow switch on the evaporator). 01.16 Ref. 207585 Rev.100 15

Reserve pump version Pump KIT. - One operating pump and one reserve pump. - Two operating pumps and one reserve pump. All pump kits are factory installed. This optional does not affect the dimensions of the unit. RESERVE PUMP VERSION SINGLE OPERATING PUMP HYDRAULIC DIAGRAM RESERVE PUMP VERSION TWIN OPERATING PUMPS HYDRAULIC DIAGRAM Pumping group with two centrifugal pumps: - Control and working electric equipment contained in the chiller electric board and directly managed by the microprocessor control. - Valves on suction line. - Check valves on discharge line. - In-line type water pump. - GP-LN... Centrifugal pump with 4 poles electric motor. - Safety flow switch (excludes the installation of the water flow switch on the evaporator). The reserve pump automatically intervenes in case of failure of one of the main pumps. An automatic changeover system is foreseen in order to equalize the water pump working hours. 16

TECHNICAL SPECIFICATIONS STANDARD VERSION PUMP KIT STANDARD VERSION SINGLE PUMP TWIN MED. PUMPS WATER FLOW RATE Minimum water flow rate m 3 /h 10 20 Maximum water flow rate m 3 /h 120 240 DISCHARGE HEAD At minimum water flow rate KPa 160 160 At maximum water flow rate KPa 130 130 WATER PUMPS (1) Absorbed power KW 5,5 11,0 Absorbed current A 11,4 22,8 POWER SUPPLY Voltage V/ph/Hz 400 / III / 50 EMPTY WEIGHT Single pump version (2) Kg 212 318 RESERVE PUMP VERSION PUMP KIT RESERVE PUMP VERSION WATER FLOW RATE OPERATING PUMP SINGLE PUMP RESERVE PUMP TWIN MED. PUMPS OPERATING PUMP RESERVE PUMP Minimum water flow rate m 3 /h 10 10 20 10 Maximum water flow rate m 3 /h 120 120 240 120 DISCHARGE HEAD At minimum water flow rate KPa 160 160 160 160 At maximum water flow rate KPa 130 130 130 130 WATER PUMPS (1) Absorbed power KW 5,5 5,5 11,0 5,5 Absorbed current A 11,4 11,4 22,8 11,4 POWER SUPPLY Voltage V/ph/Hz 400 / III / 50 EMPTY WEIGHT Operating pump (2) Kg 318 477 Reserve pump (2) Kg 318 477 (1) The values shown refer only to the working pump. (2) Add this value to the chiller s weight. Note: The noise generated by the pumps does not increase the chillers overall acoustic pressure levels. 17

HYDRONIC PUMPS PERFORMACE CHARTS STANDARD VERSION PUMP KIT SINGLE OPERATING PUMP RESERVE PUMP TWIN PUMP VERSION PUMP KIT TWIN MED. OPERATING PUMPS RESERVE PUMP 18

OTHER OPTIONALS KIT "BRINE" The accessory allows the production of glycol solution leaving the machine down to a temperature of -12 C. This KIT includes: - Set of the working parameters. Warning: with the "BRINE" KIT optional, it is mandatory to use antifreeze mixtures. The use of antifreeze mixtures may result in a decrease in the unit s performance. KIT LNO This optional is available as an accessory with the purpose of obtaining a reduction in noise emissions. This KIT includes: - Set of the working parameters. - A cap made with noise-absorbing material on each compressor. There are 3 different types of LNO KITS: KIT LNO 100% No air flow reduction. Noise reduction is obtained through a different working set of the microprocessor control and an acoustic insulation of the noise source. KIT LNO 85% Noise reduction is obtained through a different working set of the microprocessor control, an acoustic insulation of the noise source and a reduction of the condenser coil air flow at 85% of the nominal value. KIT LNO 70% Noise reduction is obtained through a different working set of the microprocessor control, an acoustic insulation of the noise source and a reduction of the condenser coil air flow at 70% of the nominal value. Consider that a condenser coil air flow reduction induces a minor cooling capacity of the machine and a major energy consumption of the compressor. Warning: To obtain the effective working conditions of cooling capacity and noise reduction for unit equipped with LNO KIT, please refer to the selection program. KIT XLS This optional accessory is available to obtain an extreme noise reduction on the machine. The versions equipped with XLS KIT have the following characteristics : - Set of the working parameters. - Machine frame and panels insulated with soundproofing material. - Soundproof cap on each compressor. - Compressor soundproof box. Consider that a condenser coil air flow reduction induces a minor cooling capacity of the machine and a major energy consumption of the compressor. Warning : To obtain the effective working conditions of cooling capacity and noise reduction for unit equipped with XLS KIT, please refer to the selection program. 19

Sound pressure (dba) Power input (%) EQSL HIGH PRESSURE EC AXIAL FANS The "EC" axial fans are equipped with a brushless type synchronous motor with integrated electronic commutated system. The motor rotation control is obtained with the EC system (Electronic Commutation) that manages the motor according to the 0-10V proportional signal coming from the microprocessor control. Characteristics of EC motors: - No electromagnetic noise. - Efficiency 83-86%. - Minimum power input. The following is a characteristics comparison between an "AC" asynchronous electric motor with phase-cut control (voltage controller) and "EC" brushless type synchronous motor. Electric motor revolutions (%RPM) Electric motor revolutions (RPM) Sound pressure level 1 meter far in free field conditions. Warning: The graphs are referred to working condition with null available static pressure (0 Pa). 20

TECHNICAL SPECIFICATIONS MODEL 300 V2 F06 320 V2 F06 360 V2 F06 390 V2 F08 430 V2 F08 PARTIAL HEAT RECOVERY Heating capacity KW 59,5 62,7 66,7 77,8 85,6 Heat recovery water flow m 3 /h 10,2 10,8 11,5 13,4 14,7 Heat recovery pressure drop KPa 6,6 7,3 8,2 8,9 4,4 TOTAL HEAT RECOVERY Cooling capacity KW 294 311 333 386 429 Compressor power input KW 100 105 118 129 140 Heating capacity KW 394 417 451 515 570 Heat recovery water flow m 3 /h 68,5 72,4 78,4 89,5 99,0 Heat recovery pressure drop KPa 62 50 61 63 92 LNO KIT 100% Fan absorbed power KW 11,6 11,7 11,7 15,4 15,4 Total air flow (1) m 3 /h 135498 135498 135498 180664 180664 Acoustic power level dba 90,9 89,4 89,8 89,9 94,2 Acoustic pressure level dba 71,1 69,7 70,0 69,6 74,0 LNO KIT 85% Fan absorbed power KW 9,8 9,9 9,9 13,1 13,1 Total air flow (1) m 3 /h 115173 115173 115173 153564 153564 Acoustic power level dba 89,9 88,4 88,8 88,9 93,2 Acoustic pressure level dba 70,1 68,7 69,0 68,6 73,0 LNO KIT 70% Absorbed power KW 8,1 8,2 8,2 10,8 10,8 Total air flow (1) m 3 /h 94848 94848 94848 126464 126464 Acoustic power level dba 86,9 85,4 85,8 85,9 90,2 Acoustic pressure level dba 67,1 65,7 66,0 65,6 70,0 XLS KIT Fan absorbed power KW 8,1 8,2 8,2 10,8 10,8 Total air flow (1) m 3 /h 94848 94848 94848 126464 126464 Acoustic power level dba 83,9 82,4 82,8 82,9 87,2 Acoustic pressure level dba 64,1 62,7 63,0 62,6 67,0 **PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT 21

MODEL 480 V2 F08 530 V2 F08 540 V2 F08 560 V2 F08 610 V2 F08 PARTIAL HEAT RECOVERY Heating capacity KW 94,7 104,0 108,0 112,0 121,0 Heat recovery water flow m 3 /h 16,3 17,9 18,6 19,2 20,9 Heat recovery pressure drop KPa 4,1 3,8 3,5 2,6 3,1 TOTAL HEAT RECOVERY Cooling capacity KW 476 527 551 568 620 Compressor power input KW 157 171 175 183 198 Heating capacity KW 633 699 726 750 818 Heat recovery water flow m 3 /h 108,0 118,0 126,0 130,0 132,0 Heat recovery pressure drop KPa 94 81 63 69 71 LNO KIT 100% Fan absorbed power KW 15,4 15,4 15,5 15,6 15,6 Total air flow m 3 /h 180664 180664 177924 175184 175184 Acoustic power level (1) dba 94,4 94,7 94,7 94,7 96,2 Acoustic pressure level (2) dba 74,2 74,4 74,4 74,4 76,0 LNO KIT 85% Fan absorbed power KW 13,1 13,1 13,2 13,3 13,3 Total air flow m 3 /h 153564 153564 151235 148906 148906 Acoustic power level (1) dba 93,4 93,7 93,7 93,7 95,2 Acoustic pressure level (2) dba 73,2 73,4 73,4 73,4 75,0 LNO KIT 70% Fan absorbed power KW 10,8 10,8 10,9 10,9 10,9 Total air flow m 3 /h 126464 126464 124546 122628 122628 Acoustic power level (1) dba 90,4 90,7 90,7 90,7 92,2 Acoustic pressure level (2) dba 70,2 70,4 70,4 70,4 72,0 XLS KIT Fan absorbed power KW 10,8 10,8 10,9 10,9 10,9 Total air flow m 3 /h 126464 126464 124546 122628 122628 Acoustic power level (1) dba 87,4 87,7 87,7 87,7 89,2 Acoustic pressure level (2) dba 67,2 67,4 67,4 67,4 69,0 **PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT 22

MODEL 650 V2 F08 710 V2 F10 770 V2 F10 850 V2 F10 910 V2 F12 PARTIAL HEAT RECOVERY Heating capacity KW 128 141 153 170 180 Heat recovery water flow m 3 /h 22,1 24,2 26,3 29,2 31,0 Heat recovery pressure drop KPa 2,8 2,7 3,2 2,6 2,5 TOTAL HEAT RECOVERY Cooling capacity KW 668 718 783 878 924 Compressor power input KW 203 230 248 273 290 Heating capacity KW 870 948 1031 1151 1214 Heat recovery water flow m 3 /h 151 156 179 200 211 Heat recovery pressure drop KPa 69 78 81 86 86 LNO KIT 100% Fan absorbed power KW 15,6 17,6 19,5 20,1 23,4 Total air flow m 3 /h 175184 197082 218980 212690 262776 Acoustic power level (1) dba 97,4 98,1 98,7 98,4 97,8 Acoustic pressure level (2) dba 77,2 77,4 78,0 77,7 76,8 LNO KIT 85% Fan absorbed power KW 13,3 14,9 16,6 17,1 19,9 Total air flow m 3 /h 148906 167519 186133 180786 223359 Acoustic power level (1) dba 96,4 97,1 97,7 97,4 96,8 Acoustic pressure level (2) dba 76,2 76,4 77,0 76,7 75,8 LNO KIT 70% Fan absorbed power KW 10,9 12,3 13,7 14,1 16,4 Total air flow m 3 /h 122628 137957 153286 148883 183943 Acoustic power level (1) dba 93,4 94,1 94,7 94,4 93,8 Acoustic pressure level (2) dba 73,2 73,4 74,0 73,7 72,8 XLS KIT Fan absorbed power KW 10,9 12,3 13,7 14,1 16,4 Total air flow m 3 /h 122628 137957 153286 148883 183943 Acoustic power level (1) dba 90,4 91,1 91,7 91,4 90,8 Acoustic pressure level (2) dba 70,2 70,4 71,0 70,7 69,8 **PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT 23

MODEL 950 V2 F12 1060 V2 F16 1120 V2 F16 1180 V2 F16 1310 V2 F16 PARTIAL HEAT RECOVERY Heating capacity KW 189 212 223 235 261 Heat recovery water flow m 3 /h 32,5 36,4 38,4 40,5 44,9 Heat recovery pressure drop KPa 3,3 4,1 4,6 5,1 6,2 TOTAL HEAT RECOVERY Cooling capacity KW 979 1081 1159 1227 1357 Compressor power input KW 298 344 353 368 414 Heating capacity KW 1277 1425 1511 1595 1770 Heat recovery water flow m 3 /h 222 248 263 277 208 Heat recovery pressure drop KPa 82 105 74 81 86 LNO KIT 100% Fan absorbed power KW 23,4 30,9 30,9 30,9 31,2 Total air flow (1) m 3 /h 262776 361328 361328 361328 350368 Acoustic power level dba 97,8 100,9 100,9 100,9 101,2 Acoustic pressure level dba 76,8 79,1 79,1 79,1 79,4 LNO KIT 85% Fan absorbed power KW 19,9 26,2 26,2 26,2 26,5 Total air flow (1) m 3 /h 223359 307128 307128 307128 297812 Acoustic power level dba 96,8 99,9 99,9 99,9 100,2 Acoustic pressure level dba 75,8 78,1 78,1 78,1 78,4 LNO KIT 70% Absorbed power KW 16,4 21,6 21,6 21,6 21,8 Total air flow (1) m 3 /h 183943 252929 252929 252929 245257 Acoustic power level dba 93,8 96,9 96,9 96,9 97,2 Acoustic pressure level dba 72,8 75,1 75,1 75,1 75,4 XLS KIT Fan absorbed power KW 16,4 21,6 21,6 21,6 21,8 Total air flow (1) m 3 /h 183943 252929 252929 252929 245257 Acoustic power level dba 90,8 93,9 93,9 93,9 94,2 Acoustic pressure level dba 69,8 72,1 72,1 72,1 72,4 **PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT 24

PARTIAL HEAT RECOVERY SYSTEM **This optional accessory is not compatible with double cooling circuit units. The partial heat recovery exchanger is installed before the main condenser. The system is not regulated and the control is ON-OFF type. The heat recovery system s operation is subject to the supply and demand of cooling capacity. The system includes: - Copper brazed plate type heat exchanger with cover plates, plates and connections in AISI 316 stainless steel. - Anticondensate insulation made of polyurethane. - Upon request voltage free contact slot for partial heat recovery water pump activation. The water pump is not supplied. The heating capacity which is supplied depends on the kind of refrigerant gas which is used and working temperatures. The heat exchangers can produce hot water up to the maximum temperature of 70-75 C and according to the working conditions of the unit. PARTIAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM 25

TOTAL HEAT RECOVERY SYSTEM The total heat recovery exchange is installed in parallel to the main condenser. The system is totally controlled by the microprocessor and the control is ON-OFF type. The heat recovery system s operation is subject to the supply demand of cooling capacity. For each refrigerant circuit the system includes: - Shell and tube condenser optimized for R134a refrigerant with shell, header, tube sheets made of carbon steel, tubes in Cu. - Anticondensate insulation made of polyurethane. - Antifreeze heater. - Water temperature probe on heat reclaim water inlet. - Diverter valve. - Non return valve. - Liquid receiver. - Safety valve. **Upon request: voltage free contact for total heat recovery water pump activation. The water pump is not supplied. The parallel connection of the hydraulic circuit is at Customer care and the water temperature probe is supplied not installed. TOTAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM 26

DIMENSIONS MODELS 300 320 360 27

MODELS 390 430 480 530 540 560 28

MODELS 610 650 29

MODELS 710 770 850 30

MODEL 910 31

MODEL 950 32

MODELS 1060 1120 1180 1310 33

34

HIPLUS AIRE ACONDICIONADO S.L. Masia Torrents, 2 Tel. +34 93 893 49 12 Fax. +34 93 893 96 15 08800 Vilanova i la Geltrú Barcelona, Spain www.hitecsa.com 35