Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Similar documents
Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

CFD Model of a Specific Fire Scenario

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

Sprinklers Modeling for Tunnel Road Fire Fighting

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

CFD Simulation of the Water Mist Effect on Fire

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Smoke Layer Height and Heat Flow through a Door

Tunnel Fire Dynamics and Evacuation Simulations

Fire protection for buildings

Computational simulation of road tunnel fire protection by sprinklers

and Sprinkler System in Resalat Tunnel of Tehran

Tunnel Fire Dynamics

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

Engineering Simulation in Built Environment and Civil Engineering Projects

FDS MODELLING OF HOT SMOKE TESTING, CINEMA AND AIRPORT CONCOURSE

OPTIMIZATION OF FIRE SUPPRESSION USING FIRE DYNAMICS SIMULATOR

Computational Study of Effects of Drop Size Distribution in Fire Suppression Systems

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

Fire Suppression Performance of Manually Applied CAF and Other Water Based System

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

THE COMBINATION OF FIRE EXTINGUISH SYSTEM AND LOCAL EXHAUST SYSTEM IN FUME HOOD

Validation of a Smoke Detection Performance Prediction Methodology. Volume 3. Evaluation of Smoke Detector Performance

Validation of a Smoke Detection Performance Prediction Methodology. Volume 4. Evaluation of FDS Smoke Detection Prediction Methodology

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

Test One: The Uncontrolled Compartment Fire

Recent BRANZFIRE enhancements and validation

Refining and Petrochemical Heater trouble shooting

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Modeling a real backdraft incident fire

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

WATER MIST CONVENTION AND EXHIBITION

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

Smoke Layer Height and Heat Flow through a Door

RESEARCH TECHNICAL REPORT. Numerical Simulations of Sprinkler Activations and Spray Transport under Obstructed, Sloped Ceilings

Advantages and Disadvantages of Fire Modelling

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

Firefighter Safety in Battery Energy Storage System Fires

An experimental study of the impact of tunnel suppression on tunnel ventilation

Validation of a Smoke Detection Performance Prediction Methodology. Volume 2. Large-scale room fire tests

Simulation of Engine Room Fire and Water Mist. Einar Kolstad and Bjarne P. Husted Stord/Haugesund University college

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

Considerations in the Design of Smoke Management Systems for Atriums

Research on fire protection methods and a case study "Futurum"

Figure 1. Structure Used For the Simulations.

CFD Analysis of Fire Characteristics on Subway Junction Station

Heat Transfer in Evacuated Tubular Solar Collectors

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

HI-FOG for Ro-Ro and Special Category spaces

CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

A study for a fire spread mechanism of residential buildings with numerical modeling

Water-mist systems in mass-production industries: A successful application to a tissue-converting plant

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit

WHAT IS IMPORTANT IN THE SIMULATION OF SPRAY DRYER PERFORMANCE AND HOW DO CURRENT CFD MODELS PERFORM?

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

ABSTRACT. Stephen Kerber, Master of Science, Dr. James Milke, Fire Protection Engineering

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

Sub-scale Analysis of New Large Aircraft (NLA) Pool Fire-Suppression

Adrian Milford Sereca - a Jensen Hughes Company, Project Engineer Vancouver, BC, Canada

The Science Behind Water Mist Protection of Typical Building Hazards

High flying fire protection HI-FOG for aircraft hangars

Developing a fire model for offshore QRA

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

What is HI-FOG? The natural enemy of fire

CFD Analysis of Co-current Spray Dryer with Swirler at Air Inlet

Fike set out to develop a better understanding of the power density trends in data centers around the world.

Case study: EconAqua water mist sprinkler system

HI-FOG for buildings. Technical introduction. Protecting people, property and business continuity. Jussi Tiainen

The Experimental Study and Simplified Model of. Water Mist Absorbing Heat Radiation

Fire Research and Education at the University of Maryland

Water-mist systems for fire-protection of saunas

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

A STUDY ON THERMAL ENERGY AT FIRE RESISTANCE TEST FOR REESS

FIRESEAT

Chapter 2 Background. 2.1 VID Technology

Ensuring safe passage HI-FOG for underground stations

European Ethylene Producers Conference (EEPC) October 24-26, 2012 Flame Interaction and Rollover Solutions in Ethylene Cracking Furnaces

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

Fire Dynamics Simulation and Evacuation for a Large Shopping Center (Mall): Part I, Fire Simulation Scenarios

A Priori Modelling of Fire Test One

High challenge warehouse case study Summary

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

A Comparison of Aspirated Smoke Detectors

FLACS-Fire. Djurre Siccama Gexcon R&D and Software VP Products. FLUG 3 rd - 4 th. November 2015, Shanghai China

article continues below

A Novel Approach for the Thermal Management. of PC Power Supply

Water Mist and Heritage Buildings Case - St. Mark s Dome, Venice

Transcription:

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Hai Jiang, Vaidya Sankaran, Med Colket, May Corn United Technologies Research Center Kati Laakkonen Marioff Corporation 14th International Water Mist Conference, Istanbul, Turkey October 22-23, 2014

BACKGROUND Motivation: Develop modeling methodology that provides physical understanding into water mist fire suppression enable efficient test planning and execution Previous large scale simulations: Ro-Ro Deck Fire with Cooling Mist Simulation approach Water mist injection Fire growth prescribed heat release rate pyrolysis Fire suppression VTT, Finland Wood pallets, 35 GJ fire size Water mist sprinklers discharged: 12 Ceiling gas temperatures model test Modeling platform utilized with pyrolysis models: FDS 5 (svn 10095) Reference: SupDet 2013, Modeling water-mist based suppression of 34 GJ car-deck fires using FDS Can we apply the same methodology to simulate other fire test scenarios? 2

OBJECTIVE Demonstrate a modeling approach that simulates a water mist-based fire suppression of the European Ordinary Hazard I office space scenario. Fire load includes: Wood Paper Plastics Foam Water mist injection: Marioff HI-FOG 2000 sprinkler 3

OVERALL MODELING APPROACH Water mist injection Water mist-based fire suppression Droplet injection Air entrainment Droplet transport Fire growth Modeling platform utilized in office space simulation: FDS 6 (svn 17743) 4

WATER MIST SPRAY INJECTION Approach Offset plane droplet data 1) Measure experimental data from single spray jet near the exit 2) Scale measured droplet number densities and velocities to conserve mass and momentum 3) Inject spray distribution with prescribed drop size and velocities at the offset plane 4) Use gas velocities from spray data to represent entrained gas motion Reference: SupDet 2011 presentation, A novel approach for simulating droplet transport for watermist applications 5

WATER MIST SPRAY INJECTION Cold spray simulation of the HI-FOG 2000 sprinkler verified with spray data Droplet dispersion from Marioff HI-FOG 2000 sprinkler Mesh number Mesh resolution (cm) # cores Simulated test period (sec) Wall clock time (hrs.) 720,000 5 9 10 1.4 Water flux distribution Volume flux profile through jet#1 Patternation measurement (top view) Accumulated Mass Per Unit Area (AMPUA) from simulation (top view) 6

OVERALL MODELING APPROACH Water mist injection Water mist-based fire suppression Fire growth Fire ignition Fire growth 7

OFFICE SPACE: FIRE GROWTH Realistic fuel package set up in a large domain with a non-uniform grid Geometry visualization in Smokeview Computational domain (L x W x H): 5.12 m x 5.04 m x 4.96 m Non-uniform grid: 4 cm hexahedral mesh surrounding fuel package 8 cm mesh away from the table Mesh partition top view Parallel simulation on 48 computing processors 8

OFFICE SPACE: FIRE GROWTH Approach: prescribe a heat release curve and ignition temperature for each material Example of input HRRPUA for wood* Tune HRRPUA magnitude and ignition temperature for each material until fire growth is matched qualitatively. *Based on scaled U.MD wood crib test data Reference: Suppression Effectiveness of Water Sprays on Accelerated Wood Crib Fires, Bryson Jacobs, University of Maryland, 2011 Case Mesh number # Cores Simulated test period (Sec) Wall clock time (Hrs.) Fire growth simulation 734,000 48 800 32 9

OFFICE SPACE: FIRE GROWTH Simulation verified with fire size image, ceiling gas temperatures from free burn case Fire growth free burn Verification: fire size at 435s after ignition Evolution of ceiling gas temperature 10

OVERALL MODELING APPROACH Water mist injection Water mist-based fire suppression Fire growth Primary suppression mechanisms Gas phase extinction Reduction of burning rate via wetting 11

OFFICE SPACE: FIRE SUPPRESSION Set-Up: Under 1 sprinkler simulation For each material, prescribe Heat release rate per unit area (HRRPUA) Ignition temperature Under 1 sprinkler configuration with temperature measurement locations sprinkler position TC 1 Computational domain (L x W x H): 8 m x 8 m x 3.52 m Non-uniform grid: 4 cm hexahedron mesh surrounding fuel package 8 cm mesh away from the table TC 2 TC 3 Mesh partition top view Parallel simulation on 36 computing processors sprinkler activation: set at 159s after ignition Case Mesh number # Cores Simulated test period (sec) Wall clock time (hrs.) Fire suppression simulation 978,000 36 800 160 12

OFFICE SPACE: FIRE SUPPRESSION Under 1 sprinkler suppression case demonstrated; suppressed fire size trend captured Modeled fire growth and spray suppression Flame shape at 280s after ignition Test image FDS result 13

OFFICE SPACE: FIRE SUPPRESSION Ceiling gas temperature trends captured by simulations Test data Simulation sprinkler position TC 1 TC 2 TC 3 14

Summary A simulation of the European Ordinary Hazard Group 1 Office Space was successfully demonstrated and verified with limited fire test data Modeling methodology used FDS 6 as a platform and included the following: Defining the spray with experimentally-derived measurements of drop size, velocity, and entrained gas Defining the fire growth of different fuel load types (wood, paper, plastics, foam) with unique heat release rates and ignition temperatures Applying the extinction model and wetting 15

Thank you! Questions?

Modeling & Numerical Considerations Fire Dynamics Simulator (NIST) Eulerian-Lagrangian approach for multi-phase physics Dynamic (or constant) Smagorinsky large eddy solver Finite rate reaction, a mixing controlled reaction, or a mixedmode reaction Low Mach number assumption Low oxygen-limit flame extinction model Radiation solver gray gas, wide band model, Mie theory for scattering/absorption 17

Water Mist modeling Traditional approaches: Apply downstream droplet distribution at nozzle exit Nozzle exit Downstream location Set droplet velocity based on flow-rate Iterate to match downstream profile Disadvantages: Require non-trivial tuning for different nozzles & conditions Near nozzle simulation expensive and poses substantial numerical challenges Can violate conservation laws UTC PROPRIETARY 18