Explosion Venting and Suppression of Bucket Elevator Legs, G90-990

Similar documents
Progressive Safety Services LLC 1

A Global Leader in Explosion Protection

Protecting Facilities Against Explosions. Since 1956

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps

Protecting Critical Facilities Against Explosions

DUST COLLECTION TRAINING. Revision 2013

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

Aluminum Dust Management in a Metallizing Facility

General Design Practices in Reducing Risk in Grain Handling Facilities

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

Fire, extreme heat, smoke, toxic fumes, noise, falling objects, uneven terrain, debris,

Progressive Safety Services LLC 2

Industrial Explosion Suppression Technology

Portable Fire Extinguishers

EXTINGUISHING SYSTEM DETECTION AND CONTROL

An Overview of Extinguishing Systems for Computer Equipment

& Fire Extinguisher Training

Fire Safety and Utility Controls. CERT Basic Training Unit 2

Three elements of fire. Heat Oxygen Fuel. Remove one of the three and the fire is extinguished.

Explosion Prevention & Suppression James Maness JEM Safety Consulting Rehoboth, DE.

Fire Safety. Version 1.0

Before proceeding with the selection process, let s briefly look at the various explosion protection options:

With CV Technology products and care, you ll be better protected from dust explosions.

Portable Fire Extinguishers

AUTOMATIC FIRE SUPPRESSION SYSTEMS

Fire Safety and Utility Controls. CERT Basic Training Unit 2

There are always options in the management of explosion risks!

HOT WORK SAFETY PROGRAM:

Application Bulletin. LNG / LPG Facilities FLAME AND GAS DETECTION FOR LNG FACILITIES

FIRE-FIGHTING POWDERS. John Dowling. Kidde PLC

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE

Fire is No Accident Fire is No Accident It can be prevented.

WSU-TFREC Fire Safety Training

EXPLOSION PROTECTION MAES SAFETY PRODUCTS & SERVICES

AQ Translated English of Chinese Standard: AQ WORK SAFETY INDUSTRY STANDARD

Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

Risk Management Department. Fire Extinguishers

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

Soot Mitigation Strategies

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

To understand FIRE and how to EXTINGUISH it, we first need to know: What is FIRE?

Combustible Dust Issues

Vacuum - The Universal Conveying Force Suction and transportation of powders, liquids and gases

TECHNICAL EDUCATION FACILITY SAFETY AUDIT

Essentials of Fire Fighting 6 th Edition Firefighter I

AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS

Dust Explosions. by Clive de Salis. Telephone: +44 (0)

T.ex Single Gas Detector VISA

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems

BROWARD COLLEGE FIRE SAFETY GUIDE

Lamorinda CERT - Unit 2 09/15/2016

Institute for Plasma Research Welcomes you all on

mixed flow dryer one of the most efficient dryers on the market. Now CSA approved for Canada in 16, and 24' models.

Mixed Flow Dryer. One of the most efficient dryers on the market.

Cadet Entry Level Award(ELA) Part Four. Fire Safety

Data/ Specification Sheet

FIRE SUPPRESSION SYSTEM

SPECIAL HAZARDS THE MOST ADVANCED TECHNOLOGY FOR PROTECTING

UNIT 7: FIRE SAFETY. Fire Chemistry: How fire occurs, classes of fire, and choosing the correct means to extinguish each type of fire.

PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)

Mitigating Risk of Battery Testing in Environmental Chambers. Mark Chrusciel & Wayne Diener Cincinnati Sub-Zero

Industrial Dust Explosions Causes & Case Studies. Presented by Geof Brazier at Expocorma, Concepcion, Chile 10th November 2017

Introduction. Program Description. Section C.20 University of South Carolina Safety Program Guide FLAMMABLE AND COMBUSTIBLE LIQUIDS

E4218 Fire Extinguisher Basic Training. Leader s Guide

CHAPTER 8 OCCUPATIONAL HEALTH AND SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Safety Considerations for Hydrogen Installations

Flammable Liquid Storage

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

(Material correct at 1/11/2011)

automatic FiReFighTing SYSTeMS in PainT booths

Element C3.4 Fire Fighting Equipment

Management of In-Bin Natural Air Grain Drying Systems to Minimize Energy Cost

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Identifying and Preventing Dust Fire and Explosion Hazards

Senscient s team has more than 150 years collective experience in gas. detection.

Kice Dust Control System Design and Maintenance Basics Design, Maintenance, & Operation

Residential Fire Sprinkler Systems

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

GASEOUS HYDROGEN SYSTEMS

Combustible Dust Hazards- Awareness

Hazardous Material Safety Program

PRELIMINARY REVIEW OF APPLICABLE CODES AND STANDARDS, PROCESS HAZARD ANALYSIS AND OPERATIONAL FIRE SAFETY PLAN

Oxeo extinguishing systems

Advances in Explosion Protection Technology. Dr. John E. Going Fike Corporation Blue Springs, MO

The correlating committee has revised the numbering in these sections to provide clarity for the next edition of the document.

Official Journal of the European Union

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 7 Extinguisher Types Revised

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

Dust Explosion Hazard Overview

PRESSGUARD PDF-VERSION (ADJUSTED FROM BROCHURE) PRESS & HOT OIL PUMPS PROTECTION

Managing Combustible Dust

Fire suppression systems for server rooms and data centres

7 Fire Protection Systems Synopsis

Carbon monoxide (CO) is a colorless, odorless gas that is the product of incomplete combustion of carbon-based fuels.

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants

Fire Extinguisher Training

InstrumentationTools.com

Transcription:

Page 1 of 6 G90-990 Explosion Venting and Suppression of Bucket Elevator Legs Explosion vents and explosion suppression devices limit the danger and damage associated with grain dust explosions. This NebGuide discusses these devices and design guidelines for application on bucket elevator legs. David Jones, Extension Agricultural Engineer [Previous Category] [Catalog] [Order Info] Grain Dust Explosions Explosion Venting Explosion Suppression Summary The bucket elevator leg has been identified as a major source of grain dust explosions. As a bucket elevator leg conveys grain, the elements necessary for a grain dust explosion are possible. Fuel (grain dust in suspension above the minimum explosive concentration), oxygen and confinement are inherent inside a functioning bucket elevator leg. Introduction of an ignition source will initiate a grain dust explosion.

Page 2 of 6 Any bucket elevator leg conveying grain is susceptible to grain dust explosions. The more grain conveyed with a particular leg, the greater the likelihood of a grain dust explosion. The possibility of a grain dust explosion exists in small on-farm legs, but it is much greater in larger commercial legs conveying millions of bushels of grain each year. Grain Dust Explosions A grain dust explosion is actually a series of explosions consisting of a primary explosion followed by multiple secondary explosions. The primary explosion is usually a small over-pressure propagating a pressure front of approximately 2 pounds per square inch (psi). The pressure front expands from the point of ignition at an approximate velocity of 1000 feet per second. The pressure front may expand throughout a facility and aerate layered dust in its path. The subsequent fire front may serve as an ignition source for the newly formed dust clouds. In this way multiple secondary explosions can occur throughout a grain handling facility. Secondary grain dust explosions are by far the most devastating. These explosions propagate a pressure front of approximately 80 psi moving at more 1000 feet per second. No conventional grain handling structure can withstand this magnitude of internal pressure. The state-of-the-art in bucket elevator design is to locate the bucket elevator leg outside the facility, thereby eliminating the headhouse and decreasing the potential for catastrophic damage. Additional technologies, such as explosion venting and explosion suppression devices, will further decrease the potential for catastrophic damage. Explosion Venting Explosion venting is the process of providing escape routes for high pressure gases within a bucket elevator leg. Explosion vents replace a portion of the leg casing and are designed to rupture or release at

Page 3 of 6 relatively low pressures. Atmospheric vents should not be confused with explosion vents. Most atmospheric vents are not big enough to sufficiently exhaust the high pressure gases. When an explosion occurs, explosion vents are ruptured, relieving the internal pressure and maintaining the structural integrity of the bucket elevator leg casing. Venting exterior legs is simple. Venting interior legs is more difficult and often impractical. Table I. Ratio of explosion vent area to vented volume Section head trunk boot Vent Area per 100 ft³ of Vented Volume 5 ft² 8 ft² 5 ft² Explosion vents are sized as a ratio of vent area to vented volume. In the trunk, or mid-section of the leg, the minimum vent ratio is 8 square feet of vent space per 100 cubic feet of vented volume. In the head section the minimum vent ratio is 5 square feet of vent area per 100 cubic feet of vented volume. Given the compact and cramped nature of the boot section of the leg, venting is generally not practical. However, if venting of the boot is required, the minimum vent ratio is 5 square feet of vent area per 100 cubic feet of vented volume. A summary of the required vent area to vented volume is shown in Table I. Vent panels should be on the side of the leg housing. When looking into the leg through the vent panel, the edge of the belt should be visible as shown in Figure 1. Another design parameter is that the total vent area should be approximately 60% of the leg cross-sectional area. Vents along the mid-section of the leg should be spaced 15 feet apart along the entire height of the trunk. Figure 1 illustrates the placement and configuration of the explosion vents. The boot section should be treated as an interior leg if it is below grade. Figure 1. Location of explosion vents. Inset shows how the edge of the belt should be visible through an open vent panel. Venting interior legs is not easy. Although the same design parameters are used, consideration must be given to the space where the pressure will be exhausted. Little is accomplished if the explosion is vented into a basement, gallery or work area. Ducting is needed to exhaust the pressure outside. The ducting should have at least the same cross-sectional area as the vent. The ducting should be no longer than 10 feet and have no bends or elbows. The material used for vent panels is also important. The vent material should have a rupture strength of no more than 1 psi, preferably less. The material may vary from aluminum to polyvinyl-chloride. Heavier material can be used if the bolts attaching the vent to the leg casing are designed to fail under

Page 4 of 6 less than 1 psi of pressure. Depending on the design of the vent panels, they may become dislodged from the leg casing during an explosion. The vent panels should be secured to the leg with a chain or cable so they will not fall to the ground. Explosion vents can be used in other applications. Galleries, bins, basements and loadout bins also can be vented. Consult an experienced engineer or a qualified manufacturer or distributor for further information on venting these locations. Explosion Suppression Explosion suppression is accomplished by detecting a grain dust explosion early and flooding the confinement with an extinguishing agent. Research has shown that this technology can effectively suppress grain dust explosions in bucket elevator legs. A grain dust explosion can be detected by optical, thermal, or pressure sensors, or a combination of sensors. Optical sensors react to ultraviolet radiation from a spark or flame. Dust concentrations inside the leg can impede optical sensors. Thermal sensors compare the air temperature at the leg outlet to the air temperature at the leg inlet. If this temperature difference exceeds a prescribed threshold, a signal is initiated. Pressure sensors are most commonly used for detecting grain dust explosions. Pressure sensors use a diaphragm-type device which responds to the initial pressure front of an explosion by quickly closing electrical contacts. As the explosion develops, both a pressure front and a flame front propagate from the point of ignition. The pressure front travels approximately 10 times faster than the flame front. The pressure sensor detects the pressure front and sends a signal through a control unit to a high-rate discharge extinguisher. This process is illustrated in Figure 2. Figure 2. Operation of explosion suppression device. The control unit electronically controls the detector and extinguisher and may provide inter-locking to the leg and other equipment. It may be battery powered to provide protection during a power failure.

Page 5 of 6 High-rate discharge extinguishers are pressurized, rechargeable spherical containers. The extinguishers are activated by a signal from the control unit. The extinguisher valve can be completely opened in 5 milliseconds to provide rapid flooding of the confinement with discharge velocities that can exceed 100 feet per second. The extinguishers are filled with a suppression agent, generally dry chemical powders or halon gases. Dry chemical powders commonly used are mono-ammonium phosphate or sodium bicarbonate. Sodium bicarbonate is generally preferred over mono-ammonium phosphate for grain handling systems because it is compatible with food and is water soluble. Sodium bicarbonate is stable under long-term storage conditions and is nontoxic and noncorrosive. When a dry powder is used, the extinguisher is pressurized with carbon dioxide or nitrogen. Halon gases have an advantage over dry chemical powders in that they completely dissipate after each discharge. This eliminates the messy cleanup after an accidental discharge of dry chemicals. However, high concentrations of halon gas are toxic to humans and should never be used where workers are present. This problem is minimized, however, when halon gas is discharged inside a bucket elevator leg and dissipated below potentially harmful concentrations. Explosion suppression systems are best for interior legs where explosion venting is impractical. Injecting the suppressing agent at several locations within the leg more effectively suppresses the flame front than a single or dual point application. Suppression systems generally consist of eight to 10 units mounted on the head, boot and trunk sections of the leg. Figure 3 illustrates a typical arrangement of explosion suppression devices. Figure 3 (left). Location of explosion suppression devices on bucket elevator legs. Figure 4 (right). Location of explosion vents and suppression devices when used together on bucket elevator legs. The explosion suppression devices on the trunk section of the elevator leg prevent the flame front from moving through the leg. Explosion suppression devices also are recommended for the inlet and outlet of the elevator leg. They create a chemical barrier to prevent the flame front from spreading to other parts of the facility such as tunnels or galleries. The exact number of devices and their arrangement will depend on the manufacturer's specifications and the configuration of the particular leg. Most explosion suppression devices can be installed directly on

Page 6 of 6 the elevator leg casing with minor structural changes. In certain situations, explosion suppression devices can be used with explosion venting. An exterior leg equipped with both explosion vents and explosion suppression devices (located at the inlet and outlet of elevator leg) can vent any explosions which might occur and prevent propagation of the flame front to adjacent equipment as shown in Figure 4. Summary Explosion venting and suppression of elevator legs can significantly decrease the probability of a devastating secondary grain dust explosion. These techniques will not eliminate primary explosions, but can help control them by preventing secondary explosions. Before installing explosion vents or suppression devices, discuss your alternatives with an engineer experienced with this technology. Also, visit other grain handling facilities that use these devices or talk with your insurance company for more information about these. File G990 under: HEALTH AND SAFETY A-12, Accident Prevention Issued July 1990; 7,500 printed. Electronic version issued February 1997 pubs@unl.edu Issued in furtherance of Cooperative Extension work, Acts of May 8 and June 30, 1914, in cooperation with the U.S. Department of Agriculture. Elbert C. Dickey, Director of Cooperative Extension, University of Nebraska, Institute of Agriculture and Natural Resources. University of Nebraska Cooperative Extension educational programs abide with the non-discrimination policies of the University of Nebraska-Lincoln and the United States Department of Agriculture.