STUDY OF CONDENSATE FORMATION AND FREEZING IN HEAT EXCHANGERS OF AIR-SOURCE HEAT PUMP SYSTEMS

Similar documents
Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Global Journal of Engineering Science and Research Management

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

A Method of Heat Exchange Structure Optimization of the Cricoid Plastic Parts

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Study of air circulation inside the oven by computational fluid dynamics.

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Numerical study of heat pipe application in heat recovery systems

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

TWO-PHASE MICRO-CHANNEL HEAT SINK FOR SPACE CRAFT THERMAL CONTROL

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Possibilities of Heat Exchanger Use in Pigsty Ventilation Systems

High-efficiency Turbo Chiller (NART Series)

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS

Efficiency evaluation for the heat pump system in sharp continental climate

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Heat Transfer in Evacuated Tubular Solar Collectors

CHAPTER 7 COMPARISON OF HEAT EXCHANGERS

TMCI Padovan Evaporators

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Compression of Fins pipe and simple Heat pipe Using CFD

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Heat transfer and heating rate of food stuffs in commercial shop ovens

ENSC 388: Engineering Thermodynamics and Heat Transfer

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

COOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Structure Improvement and Flow Field Analysis of Condenser in Freeze drying Equipment

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Natural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review

c o n d e n s e r Glossary of Terms

Modelling the Performance of a Diffusion Absorption Refrigeration System

Smart Defrost Control for Refrigeration System

Simscape Refrigerant Loop Product

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

Heat Recovery Units. Heat Recovery 1

Modification of Passivation Unit in Galvanizing Line

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Mallikarjun 1, Anandkumar S Malipatil 2

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Heat pump supplemental heating system for motor vehicles

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

Transcription:

STUDY OF CONDENSATE FORMATION AND FREEZING IN HEAT EXCHANGERS OF AIR-SOURCE HEAT PUMP SYSTEMS Vasilyev G. P. 1, Leskov 1,2 V. А., Mitrofanova N. V. 1, Gornov V. F. 1, Timofeyev N. А. 2, Kolesova М. V. 2, Yurchenko I. А. 2 and Filippov М. D. 2 1 JSC "NIIMosstroy", Moscow, Russia 2 JSC "INSOLAR-ENERGO", Moscow, Russia E-Mail: insolar-invest@mail.ru ABSTRACT This article is devoted to the study of condensate formation and freezing in the heat exchangers utilizing lowgrade heat of atmospheric air and prepared according to the results of theoretical and experimental research. The article presents the results of numerical experiments carried out by JSC "INSOLAR-ENERGO" during elaboration of technical solutions on protection of heat exchangers from freezing the moisture, which is condensed on heat exchange surfaces while recovering low-grade air heat in the heat pump systems. The purpose of the calculations is simulation of the condensation of moisture in the humid air flow during its cooling for heat recovery. The results presented in this article can be extended on heat pump systems that use low-grade air heat, for example for space heating or snow melting, and on exhaust air heat recovery in ventilation systems of buildings. Keywords: condensation, phase transition, heat exchanger, de-frostation, heat pump system, energy efficiency, thermal conditions. INTRODUCTION The problem of condensation and subsequent freezing of moisture on surfaces of heat exchangers for air heat recovery cooled to subzero temperatures is one of the major technical obstacles to the widespread use of air-source heat pump systems in countries with cold climate. Technical problems are associated with frost formation and icing of heat exchange surfaces, and as a consequence - with a sharp decline in the efficiency of heat exchangers. Similar problems are observed in the recuperative heat exchangers that use low-grade heat of exhaust air in ventilation systems. These problems are characteristic for air-source heat pump systems in their use almost on the entire territory of Russia. According to (G.I. Sultan, E. A. ElShafieea, M. G. Safana, M. A. Elraouf, 2012) the coefficient of performance decreasing with time for a range from (10-15%) due to the frost layer blockage and so degrading heat transfer process and so increasing the average compressor work done, and paper (Da Silva D.L., 2012) demonstrates that the frost layer growth reduces the air free flow area by 70%, which increases the air pressure drop and reduces the fan air flow rate. As a rule, the problem of frost formation and icing of heat exchange surfaces are solved during their defrosting due to periodic heating of icy surface and cleaning it from frost and ice (Vasilyev G.P., Timofeev N.A., 2010, Vasilyev G.P., 2002). However, this technology requires significant energy costs. An alternative way to protect the heat transfer surfaces from freezing is protection by chemical means, by application of a special composition on the heat exchange surface. The principle of operation of all anti-icing compositions based on their increased hydrophobicity, in other words, they do not collect water and its vapor on their surface. All known inventions, for example the Patent (Patent 2162872) and work (Shulzhenko Y. P., 1993), concerning the problem of creating an anti-icing coatings, as a main ingredient propose the use of silicon compounds as least wetting substances. Deicing compositions may contain succinic acid or succinic anhydride and a neutralizing base, in particular sodium hydroxide, potassium hydroxide or ammonium hydroxide. When mixed with water, de-icing compounds form salts of succinic acid in the reaction, which quickly release heat sufficient to melt the ice on the surface. In other cases, the anti-icing compositions also contain a glycol, which inhibits the re-formation of ice on the cleaned surface. Nowadays it is possible to spray propylene glycol based de-icing fluid on the surfaces to be protected. The next options for de-icing are: chemical composition - a solution of the alcohol with glycerol in a ratio of 10 to 1, and spraying Teflon coating on the heat exchange surface. Numerical experiments Authors of this article have conducted a series of studies aimed at determination of areas of heat exchanger, which are most likely influenced by appearance of condensation and its subsequent freezing during heat recovery of saturated air. Studies have been carried out on computer models. The purpose was to simulate condensation of moisture in the air flow during its cooling in the process of heat recovery. For modelling and conducting of numerical experiments software system ANSYS 11.0 was used. The calculations were done for the experimental model simulating two air channels exchanging heat through heat-conducting wall. General view of the model is shown on Figure-1. 6472

After that task was solved, temperature distribution on the plate from the warm air side have been obtained, which further was used as boundary condition for solving the problem of moisture condensation. Calculation results are given in Figures-3 and 4. Figure 1. General view of the experimental model. When conducting numerical experiments, calculation model presented in Figure-2 was used, representing only a half of the model divided by XY plane at the middle of the model. Figure 2. Experimental model for numerical experiments. Length - 1 m (along axis X). Height of each area of cold and warm air flow (along axis Y) - 0.059 m. Width of 0.06 m was taken (along axis Z) and conditions of symmetry were provided on its boundary. Plate thickness is 0.002 m. For hydro-gas-dynamic calculations program module ANSYS CFX was used.the calculations were carried out using the SST turbulence model until the residuals not exceeding 10-4. The boundary conditions. Warm air enters the heat exchanger (top channel, indicated with arrows) along axis X: flow rate of 3.85 m/s (calculated on the basis of volumetric flow of the fan); air temperature 23 С. Static pressure of the cooled air at the outlet of heat exchanger - 1 atm. Cold air enters the heat exchanger (bottom channel, indicated with arrows) along axis X (counter flow with warm air): flow rate of 3.85 m/s (calculated on the basis of volumetric flow of the fan); air temperature has been changing and was taken as minus 3,1 С (the average winter temperature in Moscow), minus 15 С, minus 28 С. Static pressure of the cold air at the outlet of heat exchanger - 1 atm. Plate between cold and warm air flow is made of polymer. All other walls are considered to be thermally insulated. In order to reduce the computational domain in the XY plane, symmetry conditions of flow were provided. Figure-3. Temperature distribution on a PVC plate from warm air side for the three cold air temperatures: minus 3 0 С (top); minus 15 0 С (lower right); minus 28 0 С(lower left). Figure 4. Graph of behavior of a cross-section average temperature along axis X. Green line cold air temperature of minus 3 0 С; red line of mi nus 15 0 С; blue line of minus 28 0 С. Further, as a calculation model to assess the moisture condensation only the area of warm air flow was taken, and the previously obtained temperature distributions were given as a boundary temperature condition of the corresponding wall. The experimental 6473

model for numerical experiments to assess the moisture condensation is shown in Figure-5. Force of gravity is directed down the axis Y. Figure-5. The experimental model for numerical experiments to assess the moisture condensation. Figure-7. Gas-to-liquid phase transition rate in the outlet section area. To simulate the condensation of liquid on the wall, mathematical model of multiphase flow «Droplets with Phase Change» has been chosen, wherein the carrier phase was considered to be gas (more precisely, the saturated steam), and the secondary phase - liquid droplets. Especially important is the choice of the correct time step for providing stability condition. In this case it is chosen between 10-6 s and 5*10-5 s. As a result of this choice, and assuming the length of area to be considered (1 m), each calculation lasted for more than a day. Boundary conditions accepted for numerical experiments to assess the moisture condensation. Warm air at entrance. Flow rate of 3.85 m/s; temperature 23 0 С. Relative moisture content by weight was taken 60% and was converted into a volumetric liquid fraction of total volumetric flow. Static pressure is 1 atm. The bottom wall (plane XZ) - a three-dimensional temperature distribution obtained in previous calculations for three different temperatures of cold air supply. All other walls are considered to be thermally insulated. In the XY plane, symmetry condition of flow is provided. Figures-6 through 8 present the contours of the phase distribution at the outlet section of the heat exchanger. Moisture grew evenly to the end of the area while displacing gas. Phase transition was at a maximum near the wall and in the end of the area. Figure-6. Volumetric fraction of fluid in the outlet section. Figure-8. Liquid formation rate by volume unit. Left - cross-section in the middle (x = 0.5 m); right - the outlet section (x = 1 m). Figure-6 shows that thickness of the condensate layer increases closer to the wall (to the right), while in the middle area (where there is a symmetrical flow condition) fluid is concentrated more uniformly, and Figure-7 illustrates that maximum rate of condensation is in the lower right corner of the area. Respectively, a major amount of liquid shall be accumulated there. Average condensation rate values as per discharge area for each numerical experiment carried out is given in Table-1. Figure 8 confirms that near the walls liquid is no longer formed, as it has been accumulated there. Intensive formation takes place in the middle of computational domain (of heat exchanger), where the saturated steam is. 6474

It is noticeable that closer to the heat exchanger output area, film thickness of the condensed liquid increases. Table-1. Simulation results of moisture condensation. Figure-10. Photo of the test facility. These calculations provide a detailed study of the formation of droplets of water vapor condensate while recovering air flow heat. The calculations revealed the most "condensate-dangerous" areas of heat exchanger, which are most likely influenced by appearance of condensation and its subsequent freezing. In addition to the calculation results an experiment was carried out to choose a way to protect heat exchanging surface from condensate. EXPERIMENTAL STUDY Practically, the experimental model copied the geometric dimensions of the experimental model shown in Figure 1 and consisted of two air channels (for warm air and cold air), separated with a plate of material being tested, so that the sample plate was positioned horizontally, in parallel to the movement of air in channels caused by fans. The model was equipped with sensors, fixing surface temperature of the test materials, as well as air temperatures at inlet and outlet of each channel. When conducting experimental studies on condensate formation, three samples of thermally conductive wall separating the flows of warm and cold air in the heat exchanger were tested. - sample 1 - Teflon-coated polycarbonate (PC); - sample 2 PC without coating; - sample 3 PVC without coating. Photo of the samples is shown in Figure-9, and photo of the test facility is shown in Figure-10. During the experimental study the samples were placed inside the experimental model and blown with air according to the scheme shown in Figure-11. Figure 11. Air flow scheme for the experimental study. Condensate formation on the surface of the test samples was controlled visually and photographed. Photos of test samples are shown in Figure-12. Figure-9. The three samples of thermally conductive wall to be tested. From left to right: Sample 1 - Teflon-coated PC, Sample 2 - PC without coating, Sample 3 PVC without coating. Sample 1. 6475

In this work we consider not desublimational way of frosting but condensation with later freezing, so this effect was not discussed here. It is important, that presence of a thin Teflon coating does not substantially affect thermal resistance of heat exchange surface, but can help removing condensed moisture from heat exchange surface with air flow since the contact angle becomes larger and contact surface of droplet and heat exchange surface decreases. If the velocity of air will be sufficient to blow droplets out of heat exchanger, it will reduce risk of freezing. Sample 2. CONCLUSIONS Research described in the article represents a detailed study of the formation of droplets of condensate while recovering air flow heat. The calculations revealed the most "condensate-dangerous" areas of heat exchanger, which are most likely influenced by appearance of condensation and its subsequent freezing. Experimental studies have shown, that during the condensate formation, trend towards increasing the droplet size in direction of the warm air flow can be observed, while condensate tends to the walls of a channel. These facts are in good agreement with the results of numerical experiments. ACKNOWLEDGEMENTS The Research was conducted by JSC "NIIMosstroy" with the financial support of the Ministry of Education and Science of Russia. Unique identifier of the project RFMEFI57914X0081. REFERENCES Sample 3. Figure-12. Photos of the samples with droplets of condensed moisture. Provided Figures depicture following results: 1. Condensate is formed on all test samples at both steps. 2. During the condensate formation, trend towards increasing the droplet size in direction of the warm air flow can be observed. This fact is in good agreement with the results of numerical experiments. 3. Condensed moisture tends to the walls of a channel in accordance with calculation results. 4. Presence of the Teflon coating causes a change in the size and shape of condensate droplets with the decrease of their contact surface with the sample (see Figure 12 samples 1 and 2). At the same time, as it is stated in (Jang-Seok Lee, Sung Jhee, Jin-Koo Park, Jung- Soo Kim, Kwan Soo Lee, 2005), the frost growth on the surface that has a relatively large contact angle goes faster. [1] G.I. Sultan, E. A. ElShafieea, M. G. Safana and M. A. Elraouf. 2012. «Frost Formation and Heat Transfer over Flat Plate Evaporator», Journal of Engineering and Computer Sciences, Qassim University, Vol. 5, No. 1, pp. 49-71 (January 2012/Safar 1433H). [2] Da Silva D.L. 2012. «Frost Formation on Fan- Supplied Tube-Fin Evaporators: A Visual and Numerical Analysis», International Refrigeration and Air Conditioning Conference. Paper 1164. [3] Vasilyev G.P. and Timofeev N. A. 2010. «The energy potential of air emissions of residential buildings in Moscow» AVOK: Ventilation, heating, air conditioning, heat supply and building thermal physics. No. 1. S. 24-32. [4] Vasilyev G.P. «Results of field investigations of the thermal regime of the experimental energy-efficient building» Building materials, equipment, technologies of XXI century». No. 6. C. 6476

[5] Aleskovskaya E. C. Dubinsky J. A.; Tokarev. Patent 2162872 RF IPC C09K3/18. Hydrophobic anti-icing composition. [6] Polymer roofing and waterproofing materials. Edited Shulzhenko Y. P. - M., VNIINM, (1993). [7] Jang-Seok Lee, Sung Jhee, Jin-Koo Park, Jung-Soo Kim, Kwan Soo Lee. 2005. «Frost formation on thermally conductive plastic plain plate», Proceedings of Fifth International Conference on Enhanced, Compact and Ultra-Compact Heat Exchangers: Science, Engineering and Technology. 6477