TUTCO Inc. E Series Electric Single Duct VAV / Duct Heater Installation Instructions Heater Models EVH, ERH, EDH & RHE

Similar documents
HEATER E L E CT R I C DUCT RENEWAIRE EVERYWHERE EVERY GEOGRAPHY, EVERY CLIMATE, EVERY HOME, EVERY BUILDING AND EVERY APPLICATION

INSTALLATION, OPERATION & MAINTENANCE MANUAL ELECTRIC DUCT HEATER

INSTALLATION, OPERATION & MAINTENANCE MANUAL ELECTRIC DUCT HEATER

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.

Heatrix Electric Duct Heater HXOB Installation Instructions

ELECTRIC UNIT HEATER UH SERIES

Duct Heater Product Catalog

PAC SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (GEN 3, STYLE A)

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

Chromalox Electric Airduct Heaters with Fintube Heating Elements. Conduit Entrance Plate. DHRF Remote Controls Flanged Type Figure 4

M1 SERIES DUCT HEATERS

Electric Duct Heaters. IDHB & IDHC Series

Series HF custom designed flange and insert heaters.

VIFB Coil Technical Guide

Installation Instructions

HE120, HE160 Humidifier Installation Kit

VERTICAL TUBE HEATING COILS MV & VIFB MODELS

Installation and Maintenance Manual IM 1102

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Installation Instructions

VIFB Coil Technical Guide

Custom Duct Heaters. Special Applications

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

HE220, HE260 Humidifier Installation Kit

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

SECTION DUCTWORK

WARNING WARNING WARNING WARNING HEALTHY CLIMATE GERMICIDAL LIGHT AIR CLEANERS/ FILTERS

Standard Duct Heaters Open Coil

Installation Instructions

WARNING WARNING WARNING WARNING WARNING HEALTHY CLIMATE GERMICIDAL LIGHT AIR CLEANERS/ FILTERS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL IFB HEATING COILS

HE360 Humidifier Installation Kit

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Custom Duct Heaters. Special Applications

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Electric Heat Accessory Installation Instructions

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

Powers Controls Low Temperature Detection Thermostat

AG Series Electric Heaters

Ultra-sorb Models LV and LH

Powers TM Controls Accessories for Installing TH 192, TH 194 or Free Energy Band TH 193 HC Room Thermostats

TK-2001, TK-2012, TK-2201, TK-3001, TK-3201, TK-4001, TK-4012, TK-4212 TK

Electric Duct Heaters

S D HWP 77, 96. Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance. Fig. 1 Nomenclature. Fig.

TABLE OF CONTENTS page 2

SINGLE DUCT TERMINAL UNITS

Rif Cod i220-0

Installation Instructions

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Instructions. Duct Mount Accessory Q Rev: 11/

Powers Controls ET 134 Low Temperature Detection Thermostat

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT

E U R O V E N T CERTIFIED PERFORMANCE

Modular Supply Make-Up Air Unit

Installation Instructions

Compensating Installation Instructions Manual

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

Installation Instructions

MERIT SERIES Up Flow / Horizontal

Chilled Water DOAS Fan Powered Terminal Units

INSTALLATION INSTRUCTIONS

"ER" Series Electric Humidifier

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Duct and Rough Service Carbon Monoxide Sensor

4Up to 40kW per sq. ft. (24 kw per sq. ft.) 4Modulating, ON/OFF or staging 4Standard from 0.5 to 1000 kw, larger loads available

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

OPTIONAL SPRING MTG HANGING CENTRES WATER CONN'S: TWO BSP MALE. 19 mm (3/4") ELECTRICAL CONDUIT HOLES ACCESS PANEL OUT (WATER) IN 485 MOUNTING

INSTALLATION, BALANCING & MAINTENANCE

C. Samples for Initial Selection: For units with factory-applied color finishes.

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity

Installation instructions for Plenum-mounted add-on electric heaters

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Installation Operation Maintenance

Kawasaki Teryx Firestorm Heater Kit Instructions.

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL VIFB HEATING COILS

MODELS K2EU060A, K4EU090A, & K3EU120A

INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

INTA ION MODERN BAR / BATH SHOWER MIXER CP

S Y D. HWP 35, 47, 58 (c/w EC Motor & UC7 Controller) Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance

HX150 OPERATOR S MANUAL. 150 kw HEATER

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

INSTALLATION INSTRUCTIONS HIGH EFFICIENCY PACKAGED AIR CONDITIONER

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Transcription:

General for All Models TUTCO Inc. E Series Electric Single Duct VAV / Duct Heater Installation Instructions Heater Models EVH, ERH, EDH & RHE Inspect heater for any possible damage. Check all insulators for breakage and inspect heater element wire(s) for any deformation or damage that could cause a short circuit to ground. Make sure all fasteners are tight. Electrical connections such as pressure terminals should be checked for tightness. For EDH & RHE Models For EDH & RHE Models Heaters which may be installed in horizontal or vertical ducts, the following instructions must be followed for safe and optimal performance. 1. Install heater a minimum of (4) feet from heat pumps or central air conditioners. 2. Install at least (4) feet downstream from an air handler. 3. Install at least (2) feet either side from an elbow or turn. 4. Install at least (4) feet from any canvas duct connector or transition section for change in duct size. 5. Install at least (4) feet downstream from an air filter. 6. Install at least (4) feet upstream from a humidifier. * Refer to Electrical Requirements section and General Operating Requirements section for additional requirements. NOTE: RHE Models Require TUTCO Listed Remote Panels (RMC or RPE) For EDH & RHE slip in model Duct Heaters for horizontal and vertical applications the following instructions must be followed for safe and optimal performance. To install cut an opening in the duct of the appropriate size to allow the heater to slip in while maintaining a proper mounting and sealing surface. Insert the heater and use the heater box as a template for the mounting screw locations. Remove heater and drill mounting holes. Mount unit to duct using sheet metal screws. Large heaters may require hangers. Connect high and low voltage supplies as required. Note: RHE Models Require Matched Point to point connections between the Required Remote Panel and Heater Assembly. See Panel instructions for Additional Wiring details. For EDH & RHE Flange mount models insert the heater between two sections of flanged duct and bolt into place. For additional strength the duct flange(s) should be doubled as shown in Fig. 2 for EVH Models. Large heaters may require hangers. Connect high and low voltage supplies as required. For EDH & RHE models with an optional diffusor/radiant screen that must be rotated move the air diffusor/radiant screen to the opposite side such that it is on the inlet air side of the heater as represented in Fig 1 for EVH & ERH Models. For heaters with no diffuser simply flip or rotate as needed as represented in Fig. 4. For EDH & RHE model Duct Heaters (horizontal or vertical) applications the air duct should be installed in accordance with the Standards of the National Fire Protection Agency for the Installation of Air Conditioning and Ventilating Systems (Pamphlet No. 90A) and Warm Air Heating and Air Conditioning Systems (Pamphlet No. 90B). Additionally do not "Bank" heaters (side by side). If greater capacity is required, proportion smaller heaters in separate runouts. Heater control boxes must be completely accessible and located to provide ventilation at all times. 06-7121-00 REV. C Page 1 of 6

For EVH Models For EVH slip in & flanged models for use with Single Duct VAV re-heat and cooling only valves for horizontal applications the following instructions must be followed for safe and optimal performance. For re-heat valves the heater should be installed in the cut out section provided as long as it meets the minimum distance requirement of 20 inches from valve actuator to Heater inlet face (see Fig. 1 ) with the air diffusor/radiant screen on the inlet air side. If the heater must be rotated move the air diffusor/radiant screen to the opposite side such that it is on the inlet air side of the heater. For cooling only valves, or instances where no cut out is provided, cut an opening in the duct of the appropriate size that meets the 20" to actuator minimum (see Fig. 1) to allow the heater to slip in while maintaining a proper mounting and sealing surface. If the heater must be rotated move the air diffusor/radiant screen to the opposite side such that it is on the inlet air side of the heater. Insert the heater and use the heater box as a template for the mounting screw locations. Remove Heater and drill mounting holes. Mount unit to duct using sheet metal screws. Large heaters may require hangers. Connect high and low voltage supplies as required. For EVH Flange mount models insert the heater between two sections of flanged duct insuring that the air diffusor/radiant screen is on the inlet air side and bolt into place. For additional strength the duct flange(s) should be doubled as shown in Fig. 2. Large heaters may require hangers. Connect high and low voltage supplies as required. For ERH Models For ERH slip in & flanged models for use in horizontal applications the following instructions must be followed for safe and optimal performance. Note the Duct outlet to Duct Inlet ratio cannot exceed 4:1. For ERH slip in models, cut an opening in the duct of the appropriate size that meets the 20" from smaller inlet discharge minimum as shown in (see Fig. 3) to allow the heater to slip in while maintaining a proper mounting and sealing surface. If the heater must be rotated move the air diffusor/radiant screen to the opposite side such that it is on the inlet air side of the heater. Insert the heater and use the heater box as a template for the mounting screw locations. Remove Heater and drill mounting holes. Mount unit to duct using sheet metal screws. Large heaters may require hangers. Connect high and low voltage supplies as required. For ERH Flanged Models, insert the heater between two sections of flanged duct insuring that the air diffusor/radiant screen is on the inlet air side and bolt into place. For additional strength the duct flange(s) should be doubled as shown in Fig. 2. Large heaters may require hangers. Connect high and low voltage supplies as required. NOTE: For EVH & ERH refer to Electrical & General Operating Requirements sections for additional requirements. 06-7121-00 REV. C Page 2 of 6

06-7121-00 REV. C Page 3 of 6

ELECTRICAL REQUIREMENTS Refer to attached wiring diagram and wiring diagram on inside of cover. Make sure line and control voltage of system matches that noted on wiring diagram. Wire in accordance with N.E.C. and any existing local codes. Check tightness of all factory and field electrical connections. Make sure fan interlock is wired in if the Heater does not have an air flow switch. Use 90 deg. C (194 deg. F) copper wire. Control must be wired for N.E.C. Class 1 unless otherwise specified. When Heater has integral transformer for control voltage to thermostat, use thermostat with isolating contacts to prevent interconnection of class 2 outputs. Disconnect all electrical power before servicing. When servicing heater, make sure all components are repositioned in the proper location and reconnect per wiring diagram. Replacement parts must be identical to the original components. Contact factory for replacement parts. GENERAL OPERATING REQUIREMENTS For EVH & ERH Models Minimum Air Velocity: See Fig 5 & 6 Maximum Inlet Air Temp: 100 Deg. F Maximum Heater KW: 16.5 KW per Square Foot of Duct cross Section For EDH & RHE Models Minimum Air Velocity: See Fig 5 & 6 Maximum Inlet Air Temp: 110 Deg. F Maximum Heater KW: 30 KW per Square Foot of Duct cross Section All Models may be flipped and rotated as long as the diffusor/radiant screen is moved to the inlet air side where applicable except when mercury contactor option is used. NOTE: All Models must be installed at least (4) feet from any type of equipment or canvas duct and at least (2) feet on either side from an elbow or turn with the exception of a VAV valve or inlet restriction as described for EVH & ERH Models. NOTE: Minimum air flow or greater must be maintained uniformly over the entire face of the heater. The velocity of air should NEVER be lower than the specified minimum. In cases where this in not true the KW must be reduced or the velocity of air increased. NOTE: Observe at least one Heating cycle to insure that cycling of safety limit controls does not occur under normal operating conditions before leaving the installation. Technical Support Contact Tutco for any questions that you may have concerning this product. Phone: (931) 432-4141 Fax: (931) 432-4140 http://www.tutco.com/ 06-7121-00 REV. C Page 4 of 6

06-7121-00 REV. C Page 5 of 6

06-7121-00 REV. C Page 6 of 6