INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Similar documents
Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Vertical Distribution of Air Temperatures in Heated Dwelling Rooms

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

American Society of Heating, Refrigerating and Air-Conditioning Engineers

Heat transfer and heating rate of food stuffs in commercial shop ovens

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena

Compression of Fins pipe and simple Heat pipe Using CFD

Heat Transfer in Evacuated Tubular Solar Collectors

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

INTRODUCTION OF HYBRID VENTILATION SYSTEMS OF DWELLING BUILDINGS IN LATVIA

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Numerical Analysis of Water Temperature Distribution in the Tank of. ASHPWH with a Cylindrical Condenser

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

TRANSACTIONS ON ADVANCEMENTS IN SCIENCE AND TECHNOLOGY (TASTONLINE)

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

New Convection Correlations for Cooled Ceiling Panels in Room with Mixed and Stratified Airflow

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

Performance Study of Triple Concentric Pipe Heat Exchanger

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

A Method of Heat Exchange Structure Optimization of the Cricoid Plastic Parts

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE

A Study of Drying Uniformity in a New Design of Tray Dryer

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

CFD Analysis of Co-current Spray Dryer with Swirler at Air Inlet

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

HEAT TRANSFER COEFFICIENT ENHANCEMENT IN NATURAL CONVECTION FROM HORIZONTAL RECTANGULAR FIN ARRAYS WITH PERFORATIONS

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

ENERGY EFFICIENCY BRIEF REPORT

Design And Analysis Of Centrifugal Pump

Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger

CHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger

ENSC 388: Engineering Thermodynamics and Heat Transfer

The 5 th TSME International Conference on Mechanical Engineering th December 2014, The Empress, Chiang Mai

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Human response to thermal environment in rooms with chilled beams

Typologies of Hybrid Ventilation in Schools

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

PCM-module to improve hot water heat stores with stratification: first tests in a complete solar system

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Characterization of a Heat Sink with Embedded Heat Pipe with Variable Heat Dissipating Source Placement for Power Electronics Applications

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

The impact of thermal loads on indoor air flow

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

CHAPTER 2 LITERATURE REVIEW

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Improvement on the Efficiency of Condensing Units: Analysis of the AC Precooling machine. Jillian Chodak Suzanne Murphy

Residential Building Walls and Environment in Amman, Jordan

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Key-Words: - PIR detector, simulation, temperature fields, temperature radiation, heating sensor. Fig. 1 Principle of PIR detector

Experimental study of space cooling using ceiling panels equipped with capillary mats

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Numerical study of heat pipe application in heat recovery systems

Computational simulation of road tunnel fire protection by sprinklers

Corn drying experiments by pilot dryer

Analysis of ventilation system for a microwave assisted drying unit

Study of air circulation inside the oven by computational fluid dynamics.

Thermal Comfort with Convective and Radiant Cooling Systems

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES

Structure Improvement and Flow Field Analysis of Condenser in Freeze drying Equipment

THE EFFECTS OF LEAKAGES IN ROOFS WITH VENTILATED AIR LAYERS - A CFD APPROACH. Zbynek Svoboda

Transcription:

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental and technological processes, Faculty of Physics and Mathematics, University of Latvia, Zellu Str. 8, LV-1002, Riga, Latvia. Summary. Temperature and average turbulent airflow distributions in the 3D model of a living-room are modelled using Ansys/CFX software. The heat balance of a room and its dependence on solar radiation and ventilation conditions are considered. As physical parameters of thermal comfort conditions, the airflow velocities, indoor temperatures and their gradients are analysed. The distributions are calculated according to the solar radiation source through the window and the pressure difference between opposite walls. It is shown that solar radiation has an essential influence on the heat balance of the room in a number of ways and on thermal comfort in the room. 1. INTRODUCTION The heat balance of a living-room is very important from the energy consumption point of view and the possible effect solar radiation has on it. For the first approximation this kind of heat transfer can be neglected and only heat conductivity in the boundary constructions and convection in the room with different ventilation conditions can be observed. Numerical modelling for a living-room with different boundary constructions, appropriate optimization of an arrangement of the heater and ventilation system, corresponding heat consumption, temperature and velocity fields and their influence on heat balance and thermal comfort in the room are analyzed in [1, 2]. The radiation heat transfer from the heater s surface and through the window must be taken into account for more accurate numerical results and physical interpretation. On sunny days, owing to the considerable solar heat transfer through the window, the required temperature in the room can be maintained with less heating from the central heating system. The mathematical modelling enables inclusion of the solar heat source and radiation heat transfer from the heater in the total heat consumption. Air exchange also plays a significant role in rooms inhabited by humans as a guarantee of oxygen feeding, so airflows through openings and ventilation systems are to be analysed in variants with different pressure conditions. The greater the air exchange rate the more fresh air, but also the greater the convective heat losses and amount of heating required. The other important factor to be estimated for living-rooms is thermal comfort conditions. They are generally affected by many factors like velocity of airflows, humidity, absolute temperature and amplitude of the vertical temperature gradient in the room [3]. It is therefore necessary to analyse these factors in different variants of living-rooms. 2. PROBLEM FORMULATION AND MODEL DEVELOPMENT A living-room with convective boundary conditions on border structures, heater-surface temperature and air openings is modelled. A radiation heat transfer model with an additional 640 634

solar source is included in some variants. Developed model helps to predict the features of heat transfer process in the room and distributions of characteristic quantities as well as the influence of the radiation heat transfer and the conditions of thermal comfort. Ansys CFX software [4] is used for development of 3D mathematical models and numerical calculations. The calculations have been performed for a room with dimensions 2.75 4 6m, shown in Fig.1, filled with air. The window and the wall to the exterior air are modelled in different materials with heat transmittance for the window U window =2.5 W/(m 2 K) and for the wall U wall =0.35 W/(m 2 K). Such values are chosen to simulate a room with an insulated outer wall and ordinary double-glazed window. Heat transmittance for other boundaries (walls to the adjoining rooms and to the corridor) U other is set to 1 W/(m 2 K) and it is included in heat transfer coefficient α from the surfaces using the expression α = ( 1α ) 1 st + 1 U for all solid structures. Here α st is standardised heat transfer coefficients from the surfaces (23.2 W/(m 2 K) for outside and 8.1 W/(m 2 K) for adjoining rooms. It is assumed that the surrounding rooms (upstairs, downstairs and side rooms) have the temperature T of 20 ºC, but the end wall is contiguous with a corridor or a staircase where the temperature is lower (T=15 ºC). The outdoor temperature is chosen corresponding to winter conditions (T= 10 ºC). Those values are used for the set-up of convective boundary conditions. Solar radiation through the window is modelled as a heat source on the inner window s surface. Taking into account the measurements of window solar transmittance [5], the solar heat flux density q is set to 500 W/m 2 on the inner part of the glass (Fig. 1). The angle of attack is set to 45, which corresponds to an average spring day in Latvia. For the radiation simulation the Monte Carlo model [4] with 2 10 6 histories is used. All objects except the transparent window are modelled as grey bodies with emission ε=0.9. A small cranny between the window and the wall is created to model real gaps in old window-frames, but, in the opposite wall, a ventilation opening has been created. Opening boundary conditions with constant pressure and temperature of -10ºC and 15ºC are defined on the surfaces of the crannies and ventilation opening. Pressure difference P between opposite walls is set to constant 0 and 1 Pa under-pressure or over-pressure to model different windy conditions. Surface temperature of the heater is set to constant 50 C. For all surfaces except openings non-slip boundary conditions are set. 6 m 2.75 m 45 Solar radiation, q=500 W/m 2 4 m Fig. 1. Layout of a modelled room and solar radiation source. 641 635

The airflows in the room depend both on the convection created by the temperature difference and on the air exchange between the openings in the structures. To describe the quasi-stationary behaviour of temperature and average turbulent flows, traditional differential equations are employed [6]: Reynolds averaged momentum equation; continuity equation; energy conservation equation. As a turbulence model the SST k-ω approach [4, 7] is used. The discretization was performed with tetrahedral elements of varying size; boundary layers are discretized with smaller prismatic elements. The characteristic size of finite elements is from 20 cm in the middle of the room to 0.5 mm in the vicinity of the heating element and for the openings in the walls. The total number of elements therefore reaches 7 10 5 depending on geometry. The typical meshes in the middle cross-section of the room and near the heater are shown in Fig. 2. The convective boundary conditions and the low viscosity of air essentially worsen the convergence of an iteration process. The total time required for one variant s calculations with a 3GHz computer is 2-3 days. The calculated heat imbalance between the heater power, the solar source and the losses from the outer surfaces and openings decreases below 5%. Different features of all developed modelling variants are summarized in Table 1. The variant B-1 is the basic model for a room without openings in boundary construction and without radiation heat exchange. The variant B-2 represents the same room with a Monte Carlo radiation model to create an additional heat transfer from the heater. The variant S includes also an additional solar radiation source through the window to estimate the influence of solar radiation on the heat balance of the room. The next 6 variants include air infiltration through the openings in the boundary structures with different boundary conditions on the openings. As a first series of variants the room without thermal radiation modelling is chosen variant B-zero without pressure difference ( P=0 Pa), variant B-over with 1 Pa overpressure (0 Pa on the window-frame, 1 Pa on the ventilation opening) and variant B-under with 1 Pa under-pressure (1 Pa on the window-frame, 0 Pa on the ventilation opening). The other 3 variants, S-zero, S-over and S-under, correspond to the above-mentioned variants B-zero, B-over and B-under, but are inclusive of radiation heat transfer modelling and an additional solar radiation source on the window (see Table 1). Fig. 2. Typical meshes for the modelled room in the middle cross-section and near the heater. 642 636

Table 1. Properties for various variants considered and general results of the modelling. Variant Properties/results B-1 B-2 S B-zero B-over B-under S-zero S-over S-under Radiation model - Monte Carlo Solar heat flux density (W/m 2 ) - 500 Pressure difference (Pa) - 0 +1-1 0 +1-1 Heat amount for the heater (W) 148 225 173 176 167 253 254 232 315 Solar radiation (W) - 327-326 325 327 Convection heat losses (W) - 49 38 1163 98 181 440 Air exchange rate (1/h) - 0.9 1.5 1.5 0.3 1.4 1.4 Average temperature ( C) 21.6 24.2 30.8 17.6 18.5 13.7 23.1 26.1 22.4 Vertical temperature difference ( C) 2.2 2.1 1.7 0.7 0.7 1.4 1.2 2.4 3.1 Average velocity (cm/s) 5 2 6 5 5 6 4 6 6 3. RESULTS General results for all nine developed variants are summarized in Table 1 and visualized in Fig. 3 and Fig. 4. We can consider three groups of variants to analyse results and appropriate changes: inclusion of radiation heat transfer for the room without solar source (variants B-1, B-2); inclusion of solar radiation (variants B-2, S); inclusion of air infiltration process in the room without (variants B-zero, B-over, B-under) and with (variants S-zero, S-over, S-under) thermal solar source modelling. It is possible also to extract two significant elements of the results heat balance of the room (heating powers, convection heat losses and the air exchange) and thermal comfort conditions (average velocity and temperature, vertical temperature difference). 3.1. Heat balance An average temperature in the room for the basic variant without radiation modelling (variant B-1) is 21.6 C and the heat amount taken from the heater with constant surface temperature of 50 C is only 148 W (Table 1 and Fig. 3). In fact, this variant is simplified and it is possible to neglect the radiation heat transfer in a case without any hot surfaces. Taking also into account the heat transfer by electromagnetic radiation (mainly from the heater), the heat amount is increased to 225 W for variant B-2 (Table 1 and Fig. 3), which shows the essential influence of the radiation from the hot surfaces on the total heat balance, and this kind of heat transfer cannot be ignored for accurate quantitative results. For qualitative analysis of the processes in the living-room, however, which depend on various geometrical and physical factors, the simplified variants without radiation modelling can be used [1, 2]. Air flow intensity in the room has also been reduced (Table 1 and Fig. 4.). The temperature observed in the room is more than 24ºC and it is determined also due to high emission coefficient ε=0.9 set for the 643 637

heater s surface, thereby obtained temperature level is maximal. Usually emission coefficient is lesser for the manufactured heaters and the surface temperature is not so high. Solar radiation through the window (variant S) essentially increases the average temperature in the room (Table 1 and Fig. 3) and changes the airflow structure (Fig. 4). In this case not only the heater works as a heat source, but also the floor region under direct sunlight is warmed and causes hot air masses to rise. As the indoor air temperature is higher (>30 C) than in the room without a solar radiation source, the total heat amount taken from the radiator s surface is less 173 W. It is clear that the temperature of the heating system is too high and should be reduced and regulated on sunny days. 700 600 500 400 W Heater power, W Convection losses W C Average temperature T, C 35 30 25 300 200 100 20 15 0 B-1 B-2 S B-zero B-over B-under S-zero S-over S-under Models 10 Fig. 3. Total heating power, convection losses and average temperature in the room. Actually the room has openings in the boundary structures and is not insulated, so convection heat losses owing to air infiltration should be taken into account, and this has been done in the next 6 variants. In cases when no pressure difference is set between the ventilation opening and the crannies in the window-frame (variants B-zero and S-zero), there is insignificant air circulation as a result of thermoconvection in the room and the corresponding air exchange rate is below 1 1/h. This value is sufficient for the oxygen inflow needed for human occupancy, and at the same time it does not produce great heat losses (Table 1 and Fig. 3). In this case there is a small exterior air inflow through the gaps in the window-frame, which decreases the temperature in the room and creates heat losses. Convection losses for both variants are about 100 W, but the temperature in the room of variant S-zero is more than 5 degrees higher because of an additional heat source through the window, which means an additional heat source on the floor and corresponding ascending airflow (Figs. 5b, 6b). In the case of 1 Pa overpressure set on the ventilation opening (variants B-over and S- over), air masses with a constant temperature of 1 C are inflowing into the room. This creates intensive flow near the ceiling (Figs. 5e, 6e) or in the middle of the room (Figs, 5d, 6d) and average velocities in the room are high (Table 1 and Fig. 3), which increases the heat amount taken from the radiator. Another factor, which is important from the power consumption viewpoint, is a cold exterior air inflow. In the case of overpressure in the room the air movement through the gap comes from the inside, air masses do not inflow into the room and the average temperature is higher but the heating amount is less. 644 638

(a) (b) (c) Fig. 4. Temperature contours and velocity vector field on the symmetry plane for variants B-1 (a), B-2(b) and S (c). The variants B-under and S-under describe the room with under-pressure in the room with 1 Pa pressure set on the gaps in the window-frame, which means active cold exterior air with a temperature of 10 C inflowing into the room (Figs. 5e, 5f, 6e, 6f). As a result of more intensive airflows heat transfer from the heater remarkably increases from 176 W without pressure difference to 253 W for variant B-under and from 254 W to 315 W for variant S-under (Table 1 and Fig. 3). Cold masses from the outside decrease also the average temperature in the room in comparison with variants without pressure difference (Table 1, Fig. 3). As one can see, the temperature in the room is below 14 C for the variant without additional solar source (variant B-under), in this case the room is heated by the adjoining rooms with constant 20 C. 645 639

For both variants with pressure difference 1 Pa the air exchange rate is 1.4-1.5 1/h; this causes significant convection heat loss and is energetically disadvantageous: in cases of underpressure the heat losses by convection reach 440 W for the variant S-under and more than 670 W for the variant B-under (Fig. 3), so convection heat losses for the rooms and buildings with poor and insufficient air tightness (high air exchange rate) can be greater than conduction heat losses through the building structures. This fact has been verified by many experimental measurements and appropriate modelling of a whole building [8]. (a) (b) (c) (d) (e) (f) Fig. 5. Temperature contours in the symmetry plane for variants B-zero (a), S-zero (b), B-over (c), S-over (d), B-under (e), S-under (f). 646 640

(a) (b) (c) (d) (e) (f) Fig. 6. Characteristic vector field in the symmetry plane for variants B-zero (a), S-zero (b), B- over (c), S-over (d), B-under (e), S-under (f). Average velocity v, m/s m/s C 7 Vertical temperature difference T, C 3,5 6 5 2,5 4 3 1,5 2 1 B-1 B-2 S B-zero B-over B-under S-zero S-over S-under Models 0,5 Fig. 7. Average airflow velocity and vertical temperature difference in the room. 647 641

3.2. Thermal comfort conditions Thermal conditions in the room are connected with the structure of airflow velocities, pressure difference between openings in boundary constructions and temperature distribution and thermal convection. An intensive upward airflow is thus formed at the top of the heater with maximum velocities up to 60 cm/s, and at the same time average air movement in the whole room generally does not exceed 5 cm/s. In cases without floors heated by solar radiation (variants B-1 and B-2) the vertical temperature difference owing to thermogravitation is more than 2 degrees and marked air stratification is observed (Table 1, Figs. 4a, 4b, 7). Velocities in the room decrease with the inclusion of thermal radiation (variant B-2) and the absolute temperature level increases from 21.6 C to 24.2 C. Such a temperature does not satisfy thermal comfort in modelled winter conditions. The situation becomes more inimical in the event of solar radiation, when the hot region on the floor produces notable convection and increased average velocities and the temperature level in the room is more than 30 C. In real rooms, however, there is usually a curtain, which screens out sunlight, the temperature of the heater is not so high and there is air infiltration. A complicated multiple vortex airflow structure in the room has been created in the variant with an air infiltration opening without pressure difference (Figs. 6a, 6b). It is caused mainly by air inflow from the corridor and outside with a lower temperature, hot airflow from the heater and hot air ascending from the warmed region on the floor (for variant S-zero). The average temperature is the same for the insulated room without a solar source about 23 C. Temperature difference in vertical direction is also greatly reduced (Table 1, Fig. 7). The situation changes with an overpressure of 1 Pa in the room (variants B-over and S- over) and only one main vortex is formed in the room because of active air inflow from the corridor (Figs. 5c, 5d, 6c, 6d). As the air masses move through the relatively small ventilation opening, velocities there are very high up to 1 m/s but air velocities in the other part of the room do not exceed 5-6 cm/s. Direction of the airflow vortex in the room changes as the pressure difference conditions change (variants B-under and S-under), but the air movement value does not noticeably change. In contrast with the velocities, the average temperature depends on the direction of the pressure difference. Thus, difference in absolute temperatures for variants with over and under-pressure reaches more than 4 degrees. The temperature in the room without thermal radiation modelling (variant B-under) is decreased to 13.7 C in case of under-pressure and it is not acceptable for human occupancy. We can therefore assume that it is possible to forecast that the best conditions for the modelled room can be reached in the following cases: the heater s power is regulated in accordance with the solar radiation intensity and indoor temperature; a small over-pressure (<0.3 Pa) is set in the room to exclude cold exterior air inflow. If the above-mentioned conditions are fulfilled, intensive airflows will not be formed and the average temperature in the room will be acceptable for thermal comfort conditions. 4. CONCLUSIONS A performed calculation for different modelled variants of a living-room under various conditions clearly demonstrates the influence of thermal radiation modelling on the temperature field in the room and appropriate airflows. It is necessary to use radiation modelling for accurate numerical results. The solar radiation source also has an essential influence on the heat balance and thermal comfort conditions in the room and therefore cannot be neglected. The 648 642

convective heat exchange between the living-room and the adjoining rooms and outside should be taken into account for more precise modelling. The developed variants allow estimation of temperature, airflow distributions and the tendencies of its changes, as well as heat losses through the boundary structures under different solar radiation and ventilation conditions. Obtained results show also an essential influence of some variable factors on the heat balance and the thermal comfort conditions. 3D modelling of a living-room including a solar heat source is very important for the correct representation of qualitative and quantitative heat transfer and convection processes in the living-room. NOMENCLATURE P pressure difference, Pa. q heat flux density. W/m 2. T temperature, C. U heat transmittance, W/m 2 K. Greek symbols α heat transfer coefficient from the walls, W/(m 2 K) ε emission factor, -. REFERENCES [1] Gendelis S. and Jakovičs A. Applications of 3D Mathematical Models for Improvement of Thermal Comfort Conditions in Living-Rooms. Latvian Journal of Physics and Technical Sciences. No. 3 (2005), pp. 40-52. [2] Gendelis S. and Jakovičs A. Mathematical Modelling of Living Room with Different Types of Heating and Pressure Conditions WSEAS transactions on heat and mass transfer. Issue 3 (2006), Vol. 1. [3] ISO 7730:1994. Moderate Thermal Environments Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort. International Standard. [4] Ansys Inc. ANSYS CFX User Manual. Ansys Inc., 2007. [5] Jakovičs A., Jēkabsons N. and Gendelis S. Experimental investigation of solar factor and heat transmittance for glass surfaces with and without special films. Technical report. University of Latvia, 2006. [6] Incropera F.P. and DeWitt D.P. Fundamentals of Heat and Mass Transfer. 5 th Edition. John Wiley & Sons Inc., 2002. [7] Menter, F.R. Zonal two equation k-ω turbulence models for aerodynamic flows. AIAA Paper, 93-2906, 1993. [8] Gendelis S. and Jakovičs A. Complex analysis of heat losses for buildings. Proceedings of the International Conference "Scientific Achievements for wellbeing and development of society", Rezekne, Latvia, 2004, pp. 76-83. ACKNOWLEDGEMENT: This paper is supported by the European Social Fund. 649 643