MODEL MP-S OVERSPEED UNIT SPEIFIATIONS Model Spec. ode upon delivery/add l Spec. ode( not requested, leave blank ) MP-S- - - - Hysteresis Set up Monitor Range Input Signal No. of Input Pulse Trigger Mode (Shaped Waveform circuit) 2 to 2,000 rpm RD, FK Series 0 4 to 20m AD to 255 pulse / no. of revolutions Auto 0.5V 0 Not provided 3 to 4,000 rpm 2 MS Series to 5 VD Ex.) =00 2 Manual 2.0V Provided 4 to 5,000 rpm H5 Series 3 2.0V 3 Note: In case MS is input, Short-circuited Detection is not possible. 5 to 0,000 rpm (AIRPAX o.) In case H5 Series is input, Input Abnormality detection is not possible. 6 to 5,000 rpm 7 to 20,000 rpm - - - Alarm Reset Alarm Reset Alarm Reset START-UP TIMER Function System Group* (TRP) (ALT) (NOT-OK) (TRP) (ALT) (NOT-OK) 0 Not provided 0 Auto-Reset 0 Auto-Reset 0 Auto-Reset 0 Normally De-energized 0 Normally De-energized 0 Normally De-energized A Provided Self-Hold Self-Hold Self-Hold Normally Energized Normally Energized Normally Energized 2 B 3! Warning Note) * hose the same group code on each unit used for a system as This unit should not be used for the purpose of controlling the system, because the response of "2 out of 3" or "2 out of 2" in a same rack. the is slow. should be used for the purpose of data recording.! Danger In case the Overspeed Protection System is designed to be used with this unit, use the redundant system consisting of three units (corresponding to 2 out of 3). For highest reliability, use other meters or machinery protection equipment to design the system. In case the machine protection is performed using a single meter, and that meter is experiencing a problem, it may cause severe injury or damage to the equipment. Input No. of Revolutions In case the Indicated No. of Revolutions differs from the Input Overspeed Set Point 2 points (TRP, ALT) / Indicated No. of No. of Revolutions, fill in the numbers below. Overspeed Set Range an be setup in rpm increments up to 000rpm to 00% of Revolutions When the Input No. of Revolutions is rpm, monitor range. Ratio hange rpm. Overspeed Set Accuracy ± rpm or less (Not Standard In case the magnification is or more, the accuracy resolution ABNOR. Alarm Output point (NOT-OK) Specifications) becomes worse in proportion to the magnification number. Rotation Measured LED Digital meter with 5 digits (7 segments) hangeable Range: 0.00 (Indicated No. of Revolutions / Input No. of Revolutions) 9.999 Value Overspeed Setup Value TRP : ALT : Trigger Indicator TRG. : (Red LED) However, TRP ALT. If unspecified, 50% of delivered monitor range. Shift Key Select Indicator SHIFT : (Red LED) Overspeed Relay Hysteresis an be setup within the range 0 to 50 rpm ( rpm Increments) TRP : Input RD, FK Series, MS Series, H5 Series (AIRPAX o.) ALT : Input Impedance About 5 kω If unspecified, 0 rpm when delivered. Input Voltage Range 300 Vpk-pk or less an be setup within the range 5 to 50% of F.S.(5% Increments) Min. Input Pulse Width 5 µs Setup value : Min. Indicated frequency 0 Hz Dimension(Model RD,FK) No. of Input Pulses to 255 pulse D B A D A D B External ontact Input ontact Type : Dry contact ontact for External Reset ontact for Lamp Test ontact for START-UP Timer ontact for TRP Alarm BYPASS Note: A should not be flat. Make the curve along a concentric circle. A= mm B= mm = mm D= mm Input RD-05A FK-202F A 6 B 7 2.5 (mm) D 6 Dimension of Target Recommended Set Gap Setup Value(mm).0 to.5 Digital Indicated Accuracy onversion Accuracy Pulse Output ±(0.003% of rdg. + digit) at 25 ±(0.03% of rdg. + digit) at 0 to 60 Voltage or current output proportional to monitor range. to 5VD (Output Impedance : 250Ω) 4 to 20mAD (Max. Load Resistance : 600Ω) Number of Output Point : point ±0.5% of F.S. at 25 ±2.0% of F.S. at 0 to 60 Pulse Output : Shaped pulse signal is output via a buffer amplifier. Signal Level : - to +V(P L ), +4 to 6V(P H ) Output Impedance : About 00Ω -24VD±V, 20mA (RD,FK specified) +2VD±V, 50mA (H5 specified) (Provided 9V to 27 VD s from the bass-line in the Alarm ontact Output Output Point : TRP : 2 points Instrument Rack) : ALT : 2 point Temperature Range Operating Temperature : 0 to 60 : NOT-OK : point Storage Temperature : -30 to +85 ontact apacity : Resistance Load : 250VA, 5 A Relative Humidity : 20 to 95%RH (noncondensing) : 30VD, 5A Face Plate Finish Munsell N-.0 (equiv.) ontact Type : ontact, Dry ontact Mass Max. 2.0kg Response Time : 30 ms at 300Hz or more E Marking onform to E requirements when MP-P2 is used for power supply unit. ondition TRP ontact ALT ontact Not-OK ontact Indication After PU Abnormality Detection 0 V (0mA) Input abnormal Detection Input Abnormal Indication 0 V (0mA) TRP Information Sent TRP Indication Measured Value ALT Information Sent ALT Indication Measured Value On-line Test (ontact Output Mode) On-line Test Indication Test Value On-line Test (ontact ontrol Mode) On-line Test Indication Test Value Unit Removal All ontacts Open All ontacts Open All ontacts Open 0 V (0mA) : Information Sent : Output ontrol : No relation ship 39803E.9 Revised : Dec.2009
MP- Series Monitor Specifications MODEL MP-Z ZEROSPEED UNIT Model Spec. ode upon delivery / Add l Spec. ode ( not requested, leave blank ) MP-Z- - - Hysteresis Set up Input Signal No. of Input Pulse* (shaped Waveform circuit) RD, FK Series 0 4 to 20mAD to 20 pulse / no. of revolutions 0.5V 0 Not Provided H5 Series to 5VD Ex.)=00 2.0V 3 Periods of Zerospeed setup value 2 (AIRPAX o.) 3 2.0V 2 5 Periods of Zerospeed setup value Note: In case H5Serise is input, Input Abnormality detection is not possible. - - Note) * 20 P/R or more is recommended. *2 hose the same group code on each unit used for a system as "2 out of 3" or "2 out of 2" in a same rack. Alarm Reset Alarm Reset Alarm Reset (Z) (Z2) (NOT-OK) (Z) (Z2) (NOT-OK) System Group*2 0 Auto-Reset 0 Auto-Reset 0 Auto-Reset 0 Normally De-energized 0 Normally De-energized 0 Normally De-energized A Self-Hold Self-Hold Self-Hold Normally Energized Normally Energized Normally Energized 2 B 3! Warning This unit should not be used for the purpose of controlling the system, because the response of the is slow. should be used for the purpose of data recording. In case the Zerospeed system is designed to be used with this unit, for the safety and reliability of the turning gear apparatus, use s redundant system consisting of 3 units (corresponding to 2 out of 3). For the highest reliability, it is recommended to design the system with other fast shut-down conditions. Input No. of Revolutions In case the Indicated No. of Revolutions differs from the Input Zerospeed Set Point 2 points (Z, Z2) / Indicated No. of No. of Revolutions, fill in the numbers below. Zerospeed Set Range an be setup in 0. rpm increments within the range 0.0rpm Revolutions When the Input No. of Revolutions is rpm, to 99.99rpm. Ratio hange rpm. Zerospeed Set Accuracy ± 0.0rpm or less (Not Standard In case the magnification is or more, the accuracy resolution ABNOR. Alarm Output point (NOT-OK) Specifications) becomes worse in proportion to the magnification number. Rotation Measured LED Digital meter with 5 digits (7 segments) hangeable Range: 0.00 (Indicated No. of Revolutions / Input No. of Revolutions) 9.999 Value Zerospeed Setup Value Z : Z2 : Trigger Indicator TRG. : (Red LED) However, the following conditions must be satisfied. Z Z2 Shift Key Select Indicator SHIFT : (Red LED) 0.0rpm Z,Z2 99.99rpm 0.6/Nrpm Z,Z2 N: No.of Input Pulses(pulse / revolution) If unspecified, rpm when delivered. Input Input Impedance RD, FK Series, H5 Series (AIRPAX o.) About 5 kω Zerospeed Relay Input Voltage Range 300 Vpk-pk or less Hysteresis an be setup within the range 0 to 50 rpm ( rpm Increments) Min. Input Pulse Width 5 µs Z : Min. Indicated frequency 0.0 Hz Z2 : If unspecified, rpm when delivered. No. of Input Pulses to 20 pulse Trigger Mode Manual Trigger Dimension(Model RD,FK) D B A D A D B External ontact Input ontact Type : Dry contact ontact for External Reset ontact for Lamp Test ontact for Zerospeed BYPASS Digital Indicated Accuracy ±(0.003% of rdg. + digit) at 25 ±(0.03% of rdg. + digit) at 0 to 60 Note: A should not be flat. Make the curve along a concentric circle. Input A= mm B= mm = mm D= mm Dimension of Target Recommended RD-05A FK-202F A 6 B 7 2.5 (mm) D 6 Set Gap Setup Value(mm).0 to.5 onversion Accuracy Pulse Output Voltage or current output proportional to the range 0 to 00rpm. to 5VD (Output Impedance : 250Ω) 4 to 20mAD (Max. Load Resistance : 600Ω) Output Point : point ±0.5% of F.S. at 25 ±2.0% of F.S. at 0 to 60 Pulse Output : Shaped pulse signal is output via a buffer amplifier. Signal Level : - to +V(P L ), +4 to 6V(P H ) Output Impedance : About 00Ω -24VD±V, 20mA (RD, FK specified) +2VD±V, 50mA (H5 specified) (Provided 9V to 27 VD from the bass-line in the s Instrument Rack) Zerospeed ontact Output Point : Z : 2 points Temperature Range Operating Temperature : 0 to 60 Output : Z2 : 2 points Storage Temperature : -30 to +85 : NOT-OK : point Relative Humidity : 20 to 95%RH (noncondensing) ontact apacity : Resistance Load : 250VA, 5 A Face Plate Finish Munsell N-.0 (equiv.) : 30VD, 5A Mass max. 2.0kg ontact Type : ontact, Dry ontact E Marking onform to E requierements when MP-P2 is used for power unit. ondition Z ontact Z2 ontact Not-OK ontact Indication After PU Abnormality Detection 0 V (0mA) Input Abnormal Detection Input Abnormal Indication 0 V (0mA) Zerospeed Detection Zerospeed Detection Indication Measured Value On-line Test (ontact Output Mode) On-line Test Indication Test Value On-line Test (ontact ontrol Mode) On-line Test Indication Test Value Unit Removal All ontacts Open All ontacts Open All ontacts Open 0 V (0mA) : Information Sent : Output ontrol : No relation ship 39804E2.0 Revised : Jan. 202
MODEL MP-T THRUST UNIT SPEIFIATIONS Model Spec. ode upon delivery/add l Spec. ode ( not requested, leave blank ) MP-T- 0 - Monitor Range Input Signal Frequency Response Polality* -0.5mm to 0 to +0.5mm VK-202A,FK-202F 0 D to 0.5Hz(-3dB) Direct 4 to 20mAD 0 Not Provided 2 -mm to 0 to +mm 2 VK-452A,FK-452F 2 Reverse 2 to 5VD Provided 3-2mm to 0 to +2mm 3 VK-302P Note) * 4-25mils to 0 to +25mils 4 VK-602P 5-40mils to 0 to +40mils 6-80mils to 0 to +80mils Note) When using Monitor Range 2 (-.0 to 0 to +.0mm) or 5 (-40 to 0 to +40mils), combined with input signal and Intrinsically Safe Explosion Proof onstruction, the OK Alarm Setup Point falls within the range. Therefore, use the monitor within 90% of the range. - - - /EX Polality Indication and Recorder output Toward sendor Away from sensor Direct Increase Decrease Reverse Decrease Increase Alarm Reset Alarm Reset Alarm Reset Alarm Delay Time Alarm Delay Time Sensitivity System Group*2 (TRP) (ALT) (NOT-OK) (TRP) (ALT) (NOT-OK) (TRP) (ALT) correction 0 Auto-Reset 0 Auto-Reset 0 Auto-Reset Normally 0.sec. 0. sec. A TIIS 0 Self-Hold Self-Hold Self-Hold De-energized 0 Normally De-energized 0 Normally De-energized 2 sec. 2 sec. 2 B 2 FM Normally Normally Normally 3 2 sec. 3 2 sec. 3 4 SA Energized Energized! Danger In case the Machine Protection System is designed to be used with this unit, use the redundant system consisting of three units (corresponding to 2 out of 3). For highest reliability, use other meters or machinery protection equipment to design the system. In case the machine protection is performed using a single meter, and that meter is experiencing a problem, it may cause severe injury or damage to the equipment. Alarm Set Point HH : H : L : LL : If unspecified, H-DANGER : 00% of delivered monitor range. H-ALERT : 90% of delivered monitor range. L-ALERT : 0% of delivered monitor range. L-DANGER : 0% of delivered monitor range. s an be setup within the range 0 to 50% of F.S. (0% Increments) Setup value : Alarm ontact Output Output Point : TRP : 2 points : ALT : 2 points Energized 4 3 sec. 4 3 sec. 5 ATEX 5 5 sec. 5 5 sec. 7 NEPSI Measured Value LED Digital meter with 5 digits (7 segnents) Shift Key Select Indicator SHIFT : (Red LED) Input VK-202A, FK-202F, VK-302P, VK-452A, FK-452F, VK-602P Input Impedance About 50kΩ External contact Input ontact Type : Dry ontac t ontact for External reset ontact for Lamp Test ontact for TRP Alarm BYPASS Zero Shift Adjustable within 0 to 00% of monitor range Digital Meter ±.0% of F.S. at 25 ±0.5% of F.S. at 25 onversion Accuracy ±2.0% of F.S. at 0 to 60 Note) *2 hose the same group code on each unit used for a system as "2 out of 3" or "2 out of 2" in a same rack. Voltage or current output proportional to monitor range. to 5VD (Output Impedance : 250Ω) 4 to 20mAD (Max. Load Resistance : 600Ω) Output Point : point -24VD±V, 20mA : NOT-OK : points (Provided 9V to 27 VD ontact apacity : Resistance Load : 250VA, 5A from the bass-line in the : 30VD, 5A Instrument Rack) ontact Type : ontact Dry ontact Temperature Range Operating Temperature : 0 to 60 Alarm Set Point 4 points (HH, H, L, LL) Storage Temperature : -30 to +85 Alarm Set Range -0 to +0% of monitor range Rslative Humidity : 20 to 95%RH (noncondensing) Alarm Set Accuracy ±.0% of F.S. or less Face Plate Finish Munsell N-.0 (equiv.) Alarm Set Repeatability ±0.% of F.S. or less Mass max.2.0kg Alarm Output point (NOT-OK) E Marking onform to E requirements when MP-P2 is used for power supply unit. ondition TRP ontact ALT ontact Not-OK ontact Indication After PU Abnormality Detection 0 V (0mA) Input abnormal Detection Input Abnormal Indication Measured Value TRP Information Sent TRP Indication Measured Value ALT Information Sent ALT Indication Measured Value On-line Test (ontact Output Mode) On-line Test Indication Test Value On-line Test (ontact ontrol Mode) On-line Test Indication Test Value Unit Removal All ontacts Open All ontacts Open All ontacts Open 0 V (0mA) : Information Sent : Output ontrol : No relation ship 309805E.9 Revised : Dec.2009
SPEIFIATIONS MODEL MP-P POWER SUPPLY UNIT Voltage Regular, Backup 85 to 264VA Regular 2 24VD 2 Backup 3 48VD 4 0VD Indicator OK Indicator : Green LED Output Alarm ontact Output ontact Type : P-OK (to supply power to bassline ontact apacity : 250VA, 5A in Instrument Rack) : 30VD, 5A Insulation Resistance ontact Type : contact Dry contact Normally energized Alarm Reset ontact Life Protective onstruction Model Spec. ode upon delivery / Add l Spec. ode ( not requested, leave blank ) Auto-reset 00,000 times or more (rated load) Plastic seal MP-P Regular : 26V± VD Backup : 24V±VD Between power supply & GND : 00M or more at 500VD Between power supply & alarm contact : 00MΩ or more at 500VD Between GND & alarm contact : 00MΩ or more at 500VD Dielectric Strength Between power supply & GND MP-P : 2,000VA, min. MP-P2 : 2,000VA, min. MP-P3 : 2,000VA, min. MP-P4 :,500VA, min. Power onsumption MP-P : 20VA or less MP-P2 : 00W or less MP-P3 : 00W or less MP-P4 : 00W or less Temperature Range Operating Temperature : 0 to 60 Storage Temperature : -30 to +85 Relative Humidity : 20 to 95%RH (non-condensing) Finish Panel : Munsell N-.0 (equiv.) Mass Max. 2.0kg E Marking Only as for MP-P2. 39806E.3 Revised : Apr.2004
SPEIFIATIONS MODEL MP-W INSTRUMENT RAK Model Spec. ode upon delivery/add l Spec. ode( not requested, leave blank ) MP-W - No. of Mounted Units * ombination Max. 3 Units 0 D A 2 Max. 6 Units D D 2 A A * Unit is not included. Input for Operation External Reset (normally open) Lamp Test (normally open) Start-up Timer (short circuit between terminals: START; open between terminals: STOP) TRP / Zerospeed Bypass (normally open) ontact Type : Dry contact Temperature Range Operating Temperature: 0 to 60 Storage Temperature: -30 to +85 Relative Humidity: 20 to 95%RH (non-condensing) Finish Rack: Munsell N-.0 (equiv.) Weight MP-W: max.7kg MP-W2: max.0kg E Marking onform to E requierements when MP-P2 is used for power unit. 39807E.4 Revised : Dec.202