QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Similar documents
TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

microfast quick response Pendent sprinkler VK302 (K5.6)

standard response elo upright sprinkler

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

micromatic standard response Upright sprinkler VK100 (K5.6)

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

micromatic Standard response Horizontal Sidewall sprinkler

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

Microfast quick response Fusible element hsw sprinkler

TECHNICAL DATA. Page 1 of 6

standard response fusible link sidewall sprinkler VK112 (K5.6)

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

TECHNICAL DATA OBSOLETE

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

micromatic Standard response Horizontal Sidewall sprinkler

standard response Fusible Link Upright sprinkler VK204 (K8.0)

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

microfast quick response extended coverage hsw sprinkler vk606

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

standard response elo upright and pendent sprinklers (storage-density/area)

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

microfast sr/qr extended coverage pendent sprinkler

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

standard response large orifice dry

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

standard response/ quick response extended coverage

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

TECHNICAL DATA. Page 1 of 5

quick response horizontal sidewall sprinkler vk360 (K8.0)

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

quick response Sprinkler 105a October 25, 2010

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

micromatic standard response stainless steel sprinklers

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

standard/quick response extended coverage light and ordinary hazard elo sprinklers

TECHNICAL DATA vk470 (K3.0)

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

freedom residential pendent sprinkler vk466 (K5.2)

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

standard response dry horizontal sidewall sprinklers

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

microfast and microfasthp quick conventional sprinklers

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

STANDARD/quick. Sprinkler 42o. August 8, 2011

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

December 14, 2015 Page 1 of 7 TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

mirage standard response concealed pendent sprinkler vk492 (K5.6)

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

Transcription:

Page 1 of 6 1. DESCRIPTION Viking Quick Response Extra-Large Orifice Pendent Sprinkler VK377 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design requirements. The special Polyester, and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive environments and are listed/approved as indicated in the Approval Charts. The extra-large orifice provides greater flows at lower pressures than standard orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hydraulically calculated sprinkler systems, which require high densities of water. Viking Quick Response Extra-Large Orifice Sprinklers may eliminate the need for a fire pump or reduce the size of the pump if it is required. On existing systems, replacing large orifice sprinklers with extra-large orifice sprinklers may provide the higher densities required to allow an increase in the hazard classification of an occupancy. Viking quick response sprinklers may be ordered and/or used as open sprinklers (glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions below. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 VdS Approved: Certificate G413049, G413051 LPCB Approved: Certificate 096e/14 Refer to the Approval Charts and Design Criteria for requirements that must be followed. 3. Specifications: Available since 1993. Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread size: See Approval Charts Nominal K-factor: 11.2 U.S. (161.3 metric*) Glass-bulb fluid temperature rated to -65 F (-55 C) Overall Length: 2-5/16 (58.7 mm) * Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Material Standards: Sprinkler Frame: Brass UNS-C84400 Deflector: Brass UNS-C26000 Bulb: Glass, nominal 3 mm diameter Pip Cap and Insert Assembly: Copper UNS-C11000, or Leaded Bronze (UNS-C31600 or UNS-C31400) and Stainless Steel UNS-S30400 Compression Screw: Brass UNS-C36000 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap-ENT plated Finishes and temperatures: Finish: Brass Chrome White Polyester Black Polyester ENT Suffix: A F M-/W M-/B JN Temperature: 155 F (68 C) 175 F (79 C) 200 F (93 C) 286 F (141 C) -- Suffix: B D E G -- Ordering Information: (Refer to Table 1 and the current Viking List Price Book.) Replaces Form No. F_030993 Rev 18.2 (Revised ordering information.)

Page 2 of 6 4. INSTALLATION Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards. 5. OPERATION During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinkler Model VK377 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly. Sprinkler Base Part No. NPT Inch TABLE 1: ORDERING INFORMATION Instructions: Using the sprinkler base part number, (1) add the suffix for the desired Finish (2) add the suffix for the desired Temperature Rating. Size 1: Finishes 2: Classifications and Temperature Ratings BSP mm Description Suffix 1 Classification Nominal Rating Bulb Color Max. Ambient Ceiling Temperature 3 08337 3/4 20 Brass A Ordinary 155 F (68 C) Red 100 F (38 C) B 17489 1/2 15 Chrome F Intermediate 175 F (79 C) Yellow 150 F (65 C) D White Polyester 4,5,6 M-/W Intermediate 200 F (93 C) Green 150 F (65 C) E Black Polyester 4,5,6 M-/B High 286 F (141 C) Blue 225 F (107 C) G ENT 4,5,6 JN Example: 08337MB/W = VK377 with White Polyester Finish and 155 F (79 C) Nominal temperature rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F (38 C) meaning if the area will experience temperatures above the maximum ambient rating, you shall use a higher temperature-rated sprinkler. Accessories Sprinkler Wrenches (see Figure 1): A. Standard Wrench: Part No. 05118CW/B (available since 1981). B. Socket Wrench (for recessed or coated sprinklers): Part No. 11663W/B 2 (available since 2001). Sprinkler Cabinet: A. Up to 6 sprinklers: Part number 01724A (available since 1971). B. 6-12 Sprinklers: Part number 01725A (available since 1971). Footnotes 1. Where - is shown, insert the desired Temperature Rating suffix. 2. Requires a 1/2 ratchet which is not available from Viking. 3. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 4. UL Listed as corrosion resistant. 5. FM Approved as a corrosion proofing coating for installation in corrosive environments. 6. The corrosion resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. Suffix

Page 3 of 6 Base Part Number 1 SIN Sprinkler Style Approval Chart 1 - UL Quick Response Extra-Large Orifice Pendent Sprinkler VK377 Maximum 175 PSI (12 Bar) WWP Thread Size Nominal K-Factor Overall Length Listings and Approvals 3 (Refer also to Design Criteria below.) NPT BSP U.S. metric 2 Inches mm culus 4,5 NYC VdS LPCB 08337 VK377 Pendent 3/4 20 mm 11.2 161.3 2-5/16 58.7 A1Y, B1Z, B2X, A2W See Footnote 6. A1 A1 17489 VK377 Pendent 1/2 15 mm 11.2 161.3 2-5/16 58.7 -- -- A1 A1 Approved Temperature Ratings A - 155 F (68 C), 175 F (79 C), 200 F (93 C), and 286 F (141 C) B - 155 F (68 C), 175 F (79 C), and 200 F (93 C) Approved Finishes 1 - Brass, Chrome, White Polyester 7, Black Polyester 7, and Black PTFE 7 2 - ENT 7 Escutcheons W - Standard surface-mounted escutcheons only X - Standard surface-mounted escutcheons or recessed with the Micromatic Model E-1 Escutcheon. Y - Standard surface-mounted escutcheons or the Microfast Model F-1 Adjustable Escutcheon Z - Standard surface-mounted escutcheon or the Viking Microfast Model F-1 Adjustable Escutcheon or recessed with the Viking Micromatic Model E-1, E-2, or E-3 Recessed Escutcheon Footnotes 1. Base part number shown. For complete part number, refer to Viking s current price schedule. 2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3. This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4. Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5. culus-listed only for use in wet pipe sprinkler systems (or preaction systems qualifying as wet systems). 6. Meets New York City requirements, effective July 1, 2008. 7. culus Listed as corrosion-resistant. DESIGN CRITERIA - UL Also refer to the Approval Chart above. culus Listing Requirements: Quick Response Extra-Large Orifice Pendent Sprinkler VK377 is culus Listed for installation in accordance with the latest edition of NFPA 13 for standard pendent spray sprinklers: Designed for use in hazard occupancies up to and including Ordinary Hazard Group II with a minimum operating pressure of 7 psi (0.5 bar). Also culus Listed for use in High-Piled Storage Occupancies as defined in NFPA 13 with a minimum operating pressure of 7 psi (0.5 bar). Listed only for use in wet pipe sprinkler systems (or preaction systems qualifying as wet systems). The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Page 4 of 6 Base Part Number 1 SIN Sprinkler Style Approval Chart 2 - FM Quick Response Extra-Large Orifice Pendent Sprinkler VK377 Maximum 175 PSI (12 Bar) WWP Thread Size Nominal K-Factor Overall Length FM Approvals 3 NPT BSP U.S. metric 2 Inches mm (Refer also to Design Criteria below.) 08337 VK377 Pendent 3/4 20 mm 11.2 161.3 2-5/16 58.7 A1X Approved Temperature Ratings A - 155 F (68 C), 175 F (79 C), 200 F (93 C), and 286 F (141 C) Approved Finish Escutcheons 1 - Brass and ENT 4 X - Standard surface-mounted escutcheons Footnotes 1. Base part number shown. For complete part number, refer to Viking s current price schedule. 2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3. This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4. FM approved as corrosion proofing for corrosive environments. DESIGN CRITERIA - FM Also refer to the Approval Chart above. FM Approval Requirements: Quick Response Extra-Large Orifice Pendent Sprinkler VK377 is FM Approved as a quick response pendent Non-Storage sprinkler, and as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including 2-0 and 8-9). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM Installation guidelines may differ from UL and/or NFPA criteria. IMPORTANT: Always refer to Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. B 7/16" (11 mm) Nominal Pipe Engagement A 2-5/16" (59 mm) 3/4" NPT (20 mm) OR 1/2" NPT (15 mm) 1-1/4" (32 mm) Figure 1: Sprinkler Wrenches Figure 2: Sprinkler Dimensions

Page 5 of 6 Celing Opening Size: Minimum: 2-5/16ʺ (59 mm) Maximum: 2-1/2ʺ (64 mm) 2-1/8" (54 mm) 2-1/8" (54 mm) 1-3/4" (45 mm) 1-1/8" (29 mm) Minimum 2" (51 mm) 1-1/8" (29 mm) Maximum Minimum Maximum E-1 Escutcheon E-2 (shown) or E-3 Escutcheon 2-1/8" (54 mm) 1-1/2" (38 mm) 2" (51 mm) 1-3/4" (45 mm) Minimum Maximum F-1 Escutcheon Surface Mount Escutcheon Figure 3: Installation Dimensions with Viking Escutcheons

Page 6 of 6 1. Install the escutcheon inner ring onto the sprinkler threads then carefully slide the wrench** sideways around the protective cap. 2. Push the wrench upwards to ensure engagement with the wrench flats. Install the sprinkler and escutcheon inner ring into the pipe fitting. Figure 4: Recessed Installation **A 1/2ʺ ratchet is required (not available from Viking). Replaces Form No. F_030993 Rev 18.2 (Revised ordering information.)