SFC-500 SERIES FIRE ALARM PANEL

Similar documents
FX-350 Series. Analog/Addressable Fire Alarm Panels. Installation and Operation Manual FX-350 SERIES. LT-959 Rev. 3.1 March 2012 FX-350 SERIES

SFC-200 SERIES LCD FIRE ALARM PANEL

FX-350 Series. Analog/Addressable Fire Alarm Panels. Installation and Operation Manual

INSTALLATION & OPERATION GUIDE

MR-2350/2351. Fire Alarm Control Panels. Installation and Operation Manual

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

FA-300 Series. LCD Fire Alarm Control Panel. Installation and Operation Manual

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

FX Fire Alarm Control Panel. Installation and Operation Manual

MR-2602 Two Zone Fire Alarm Control Panel

INTELLIGENT FIRE ALARM CONTROL PANEL

FX-3500RCU. Fire Alarm Control Panel. Installation and Operation Manual

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual

PFC-3002T Fire Alarm Control Panel

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA OBSOLETE

SFC-200 SERIES LED FIRE ALARM PANEL

30.45 Electric Release PDRP-2001

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Conventional Releasing Control Panel

NETWORK FIRE ALARM CONTROL PANEL. Features

FX-350/351/353 SERIES

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

Addressable Fire Alarm Control Panel

LT-6098 FR-320NetK Installation

LifeAlarm Fire Alarm Control Panels

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

FA-102T. Fire Alarm Control Panel. Installation and Operation Manual. LT-514 Rev.7 December 2009 A.C. ON SIGNAL SILENCED

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

MR-2350/2351 Series Analog/Addressable Fire Alarm Panel

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

FX-350/351 SERIES. Analog/Addressable Fire Alarm Panel. Programming Manual

good things in small packages

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

MPC-6000 / MPC-7000 / RND-2

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

CATALOG NUMBER. Features. Description

Specification/ Data Sheet

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

NetworX Series NX-870E Fire Supervision Module Installation and Startup

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

UDACT-300A. Digital Alarm Communicator Transmitter. Installation and Operation Manual. LT-888 Rev 3 June DEF 2 ABC ENTER MENU 6 GHI JKL MNO

AL800ULADA. NAC Power Extender. Installation Guide

MODEL B2 INSTALLATION MANUAL

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

FA-101U Fire Alarm Control Panel

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet

RELEASE DEVICE CONTROLS

PSN-1000 & PSN 1000(E) Installation Manual

Booster Power Supply Manual

EVO192 v3.0 Fire and Burglary What s New

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

FMR Installation Instructions. Addressable Fire System Controller

Conventional Fire Alarm Systems

21-light Remote Annunciator. Owner s Manual

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

RAX-LCD-LITE. Remote Annunciator. Installation and Operation Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Installation, Operating and Maintenance Manual

Technical Manuals Online! A B C DEF GHI JKL POWER 9 0 COMMAND YZ. User's Guide

Public Safety DAS Annunciator Panel

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

Print Specification. Publication. Instructions. Specific requirements. General requirements

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

FireNET Plus Wiring Instructions

DS7400Xi Addressable Control/ Communicator

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

AL600ULADA. NAC Power Extender. Installation Guide

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

ANNUNCIATOR FIXED MODULE

4100U City and Relay Cards Installation Instructions

FW106 Fire Alarm Control Panel

Electric Release Panel Wiring Tips

Fire Control/Communicator

SIGA-CC1 Single Input Signal Module Installation Sheet

Installation Guide. Control/Communicator

TrueAlarm Fire Alarm Systems

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

MGD-32 and AGD-048. Remote Multiplex Graphic Driver Annunciators and Adder Boards. Wiring and Installation Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Signature Series Auto-Sync Output Module (CC1S)

Transcription:

SFC-500 SERIES FIRE ALARM PANEL INSTALLATION INSTRUCTIONS LT-959SUM March 2010 Rev 2

SFC-500 Series Installation and Operation Manual Table of Contents Industry Canada and FCC Notice... 1 Notice for all SFC-500 Series Built-in UDACTs Sold in the U.S.A... 1 Introduction... 2 Features... 2 Conventions... 3 Circuits... 3 Zone/Group... 3 Display Points... 3 Wiring Styles... 3 System Components... 4 Panel Models... 4 Output Class A converter: four circuits... 5 Polarity reversal/city tie... 5 Remote Annunciator... 6 Smart Relay Module... 6 SRAM-216 Remote Annunciator... 6 Panel Components and System Accessories... 7 Analog/Addressable Devices... 8 Mechanical Installation... 9 Installing the Enclosure... 9 Installing Adder Modules... 12 Cable and Jumper Connections for Main Board and Adder Modules... 13 SOCA-204 Output Class A Converter Adder Module... 15 Polarity Reversal and City Tie Module (Model SPR-200)... 16 SRAX-532 Display Adder Module... 16 Circuits and Devices... 17 Addressable/Analog Devices... 17 Analog Devices... 18 Contact Inputs... 18 Contact Outputs... 18 Field Wiring... 19 Main Fire Alarm Board Field Wiring... 19 Loop Isolators... 19 Loop Operation... 20 Indicating (Powered Output) Circuits... 21 Indicating Circuit Wiring... 21 Dialer Wiring... 23 Polarity Reversal and City Tie Module (SPR-200) Wiring... 24 Auxiliary Power Supplies... 25 Power Supply Connections... 26 System Checkout... 27 Before turning the power ON... 27 Power-up procedure... 27 Troubleshooting... 27 Indicators, Controls and Operations... 28 Common Indicators... 29 Common Controls... 30 Single Stage Operation... 31 Two-Stage Operation... 32 Positive Alarm Sequence... 33 Enabling or Disabling the Positive Alarm Sequence... 33 If you do not wish the change the status, press the cancel key... 34 Input Types... 34 i

Table of Contents Output Types... 36 Evacuation Codes... 37 Remote Annunciators Operation... 40 Dialer Operation... 41 Appendix A: Compatible Receivers... 41 Appendix B: Reporting... 42 Ademco Contact-ID... 42 Security Industries Association SIA-DCS... 43 Appendix C: Specifications... 44 Appendix D: Power Supply and Battery Calculations... 45 Warranty & Warning Information... 47 Warning Please Read Carefully... 47 Limited Warranty... 49 Warranty Procedure... 49 Disclaimer of Warranties... 49 Out of Warranty Repairs... 50 ii

SFC-500 Series Installation and Operation Manual List of Figures Figure 1: Wallbox Dimensions / Mounting the SFC-500 - Surface... 9 Figure 2: Mounting the SFC-500 - Flush... 10 Figure 3: Flush Trim Detail... 10 Figure 4: Wallbox Dimensions / Mounting the SFC-551/SFC-553 Surface /Flush... 11 Figure 5: Installation of Adder Modules... 12 Figure 6: Main Fire Alarm Board Cable Connectors and Jumper Locations... 13 Figure 7: Main Board (3 loop model) Cable Connectors and Jumper Locations... 14 Figure 8: SOCA-204 Output Class A Converter Adder Modules... 15 Figure 9: Polarity Reversal and City Tie Module... 16 Figure 10: Addressable Loop Wiring - Class B or Style 4... 19 Figure 11: Addressable Loop Wiring -Class A or Style 6... 20 Figure 12: Indicating Circuit Class B or Style Y Wiring... 22 Figure 13: Indicating Circuit Class A or Style Z Wiring... 22 Figure 14 Dialer Wiring... 23 Figure 15: Polarity Reversal and City Tie Module Terminal Connection... 24 Figure 16: Supervision Of Auxiliary Supplies... 25 Figure 17: Main Power Supply Connections... 26 Figure 18: LCD Display, LED indicators and control buttons... 28 Figure 19: Evacuation and Alert Codes... 37 iii

Industry Canada and FCC Notice SFC-500 Series Installation and Operation Manual Notice for all SFC-500 Series Built-In UDACTs Sold in Canada Summit s SFC-500 SERIES BUILT-IN UDACT Communicator described in this manual is listed by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units for Fire Alarm Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling Systems and Services). These Communicators should be installed in accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction (AHJ). Industry Canada Notice Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alteration made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the Earth Ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This is necessary both for proper operation and for protection. CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate Notice for all SFC-500 Series Built-in UDACTs Sold in the U.S.A. Note: The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5. The Label Identification Number for this product is US:1M8AL02BFX350. The 02B represents the REN without a decimal point (e.g., 02B is a REN of 0.2B). For earlier products, the REN is separately shown on the label. Summit's SFC-500 SERIES BUILT-IN UDACT Digital Communicator described in this manual is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective Signalling Systems). These Communicators comply with the National Fire Protection Association (NFPA) performance requirements for UDACTs and should be installed in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These Communicators should be installed in accordance with this manual; the National Electrical Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ). FCC Notice This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the telco transformer of this equipment is a label that contains, among other information, a product identifier in the format US:1M8AL02BFX350. If requested, this number must be provided to the telephone company. This equipment is capable of seizing the line. This capability is provided in the hardware. Type of Service: The Communicator is designed to be used on standard device telephone lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C (or USOC FJ45S). Connection to telephone company provided coin service (central office implemented systems) is prohibited. Connection to party lines service is subject to state tariffs. Telephone Company Procedures: The goal of the telephone company is to provide you with the best service it can. In order to do this, it may occasionally be necessary for them to make changes in their equipment, operations or procedures. If these changes might affect your service or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changes necessary to maintain uninterrupted service. In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment which you have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringer equivalence number (REN); both of these items are listed on the equipment label. The sum of all of the REN s on your telephone lines should be less than five in order to assure proper service from the telephone company. In some cases, a sum of five may not be usable on a given line. If Problems Arise: If any of your telephone equipment is not operating properly, you should immediately remove it from your telephone line, as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. When practical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible. When you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC. Contact your telephone company if you have any questions about your phone line. In the event repairs are ever needed on the Communicator, they should be performed by Summit Systems Technologies or an authorized representative of Summit Systems Technologies For information contact Summit Systems Technologies at the address and phone numbers shown on the back page of this document. 1

Introduction Introduction Summit s SFC-500 Series Analog/Addressable Fire Alarm Control Panel provides a loop for 60 or 126 addressable or three loops for 378 input and output devices, four supervised Class B or A (Style Y or Z) indicating circuits, a full range of auxiliary power supplies, and extensive common control features via its integrated LCD display and push button console. Many of its features are fully configurable utilizing the built-in configuration capability via the front panel display and switches. The panel is available with an integrated dialer/modem. Optional modules include Polarity Reversal and City Tie, SRAX-532 LED Display Adder, and Class A Converter for indicating circuits. Semiflush or surface mountable enclosures can be used for retrofits and on new installations. This manual covers the following panels: Note: Installation of the SFC-500 Series Fire Alarm Control panel should be in accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the Local Authority Having Jurisdiction (AHJ). SFC-500-60-DR SFC-500-126-DR SFC-500-378-DR SFC-551-DR SFC-551-LDR SFC-553-DR SFC-553-LDR Features One Loop (60 devices) Panel with dialer, red One Loop (126 devices) Panel with dialer, red Three Loops (378 devices) Panel with dialer, red One Loop (126 devices) Panel with dialer, red One Loop (126 devices) Panel, with 32 LED display and dialer, red Three Loops (378 devices) Panel, with dialer, red Three Loops (378 devices) Panel, with 32 LED display and dialer, red The SFC-500 Series panels support a loop of 60 or 126 analog devices and up to 3 loops of 378 analog devices, including thermal, ion, photo detectors, and contact input and output devices. Drift compensation and Auto Test features are provided for analog devices. Four Power Limited Class B (Style Y) indicating circuits. Each indicating circuit may be configured as Class A (Style Z) using an output Class A converter adder module. Each indicating circuit may be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be Steady, Temporal Code, California Code, or March Time. The system provides the necessary protocols to sync strobes from major manufacturers. Two-stage, alarm verification, and waterflow retard operations available. Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and One-Man Walk Test. Subsequent Alarm, Supervisory, and Trouble operation. provides a regulated, supervised 21.1VDC auxiliary power supply @ 500mA max.; unfiltered, unsupervised 24V FWR power supply @ 1.7 A max and a resettable auxiliary power supply @ 300mA max. Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all non-disconnectable and Auxiliary Alarm Relay (disconnectable). Output for remote trouble indicator and Buzzer (RTI). RS-485 Interface for SRAM-200LCD Annunciators, SRA-300 Series Remote Annunciators, SRAM-216 and SRAM-208 Remote Annunciators and SSR-212 Smart Relay Modules (max total of 7 remote annunciators). Optional Module for City Tie and Polarity Reversal Signaling. Extensive transient protection Built-in UDACT (Digital Alarm Communicator Transmitter). Extensive and easy configuration of the panel via the integrated LCD display and keypad or laptop computer. Remote dial up (with built-in UDACT) for event log checking and/or configuration changing 2

SFC-500 Series Installation and Operation Manual Conventions Circuits Refers to a physical electrical interface for the analog loop, indicating signals or relays, and common alarm, supervisory, and trouble relay outputs. Zone/Group Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit. Groups are used extensively in the SFC-500 Series to facilitate annunciation of multiple input and output points on the 32 (up to 64) LED display and to facilitate bypassing of inputs and outputs. Display Points The SFC-500 Series provides an LCD display to annunciate the status of the system and connected devices. The FX-351 also provides up to 64 LED display points on the panel front in addition to the LCD display. Display points may be assigned to LEDs during configuration to groups of inputs or outputs. There are two LEDs for every display point: one single color (amber) and one dual color (red/amber). Wiring Styles The analog loop can be connected in Class B (Style Y) or Class A (Style D) configurations. Changing the indicating circuits to Class A requires an SOCA-204 adder board which will convert four indicating zones from Class B (Style Y) circuits to Class A (Style Z). This is done without reducing the number of circuits. Note: The Model SFC-500-60DR panels DO NOT recognize any devices with addresses higher than 60. 3

AC ON COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM PRS TUV SIGNAL SILENCE BUZZER SILENCE LAMP TE S T SPARE AC ON COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM PRS TUV SIGNAL SILENCE BUZZE R SILENCE LAMP TE S T SPARE ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1 ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1 AC ON COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1 ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1 PRS TUV SIGNAL SILENCE BUZZE R SILENCE LAMP TE S T SPARE ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1 ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1 ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1 System Components System Components Panel Models SFC-500 SERIES Addressable Fire Alarm Control Panel SFC-500 SERIES Addressable Fire Alarm Control Panel SFC-500 SERIES Addressable Fire Alarm Control Panel SYSTEM NORMAL MAY 21, 2006 02:41PM SYSTEM NORMAL MAY 21, 2006 02:41PM SYSTEM NORMAL MAY 21, 2006 02:41PM 1 2 ABC 3 DEF X 1 2 ABC 3 DEF X 4 GHI 5 JKL 6 MNO M 4 GHI 5 JKL 6 MNO M 1 2 ABC 4 GHI 5 JKL 7 8 * 0 QZ 3 DEF 6 MNO 9 WXY # X M? 7 8 * 0 QZ 9 WXY #? 7 8 * 0 QZ 9 WXY #? SFC-500-60-DR SFC-500-126-DR SFC-500-378-DR SFC-551-DR SFC-551-LDR SFC-553-DR SFC-553-LDR All SFC-500 Series Panels have the following features: Multi-zone fire alarm control panel with 2 x 20 LCD display. Style Y or Style D analog loop(s). Four Power Limited Class B (Style Y) indicating circuits (max 1.7 Amps each - 5 Amps total). Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays. Additional SRAX-532 Display Adders can be added to provide 64 annunciation points per adder. An optional SOCA-204 Class A converter module may be used to convert the indicating circuits to Class A (Style Z). Additional outputs include connections for a RTI remote trouble indicator, SPR-200 Reverse Polarity Module, an RS- 485 bus for connection of up to seven SRAM-200LCDs, SSR-212s and SRAM-300 Series annunciators. Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC filtered and regulated, and resettable auxiliary power supply. 4

SFC-500 Series Installation and Operation Manual See the table below for the specifics of each panel. Model # of points # of loops 2 line UDACT Digital Communicator (y/n) Door Color # of 32 point LED Displays Max # of LED Displays SFC-500-60-DR 60 1 y red n/a n/a SFC-500-126-DR 126 1 y red n/a n/a SFC-500-378-DR 378 3 y red n/a n/a SFC-551-DR 126 1 y red 0 2 SFC-551-LDR 126 1 y red 1 2 SFC-553-DR 378 3 y red 0 2 SFC-553-LDR 378 3 y red 1 2 Some models may not be available in all markets. Verify with your local distributor. Output Class A converter: four circuits Model Description BLK RED BLK RED - SIG2 OUT+ - SIG2 RET+ SOCA-204 Output Class A converter module (four circuits) BLK RED - SIG4 OUT+ - SIG4 RET+ BLK RED - SIG1 OUT+ - SIG1 RET+ - SIG3 OUT+ - SIG3 RET+ Polarity reversal/city tie Model Description JW1 + - + - + - CITY TIE POLARITY REVERSAL ALARM POLARITY REVERSAL SUPV SPR-200 Polarity Reversal and/or City Tie Module JW4 JW2 5

System Components Remote Annunciator Model Description SYSTEM NORMAL 18:01 MON 2010-01-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 1 2 3 ABC DEF 4 5 6 GHI JKL MNO 7 8 9 PRS TUV WXY * 0 # QZ ENTER MENU CANCEL INFO SRAM-200LCDR Remote Annunciator Module, LCD display, red painted box SFC-200 SERIES Remote Annunciator Smart Relay Module Model Description SSR-212R Smart Relay Module (12 relays) with red enclosure SFC-200 SERIES Remote Relay SRAM-216 Remote Annunciator Model Description A.C. ON COMMON TROUBLE SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE SRAM-216 16 Zone remote annunciator LAMP TEST SYSTEM RESET SRAM-216 6

SFC-500 Series Installation and Operation Manual Panel Components and System Accessories MODEL NO. SALC-252 SRAX-532 SRAM-208(R) SRAM-216(R) SRAM-316 / TZ SRAM-332 / TZ SGD-32 SGD-048 SRTI-200 SFC-200TRB SFC-UNIV-TRB SBB-301(R) SBB-302(R) SBB-303(R) SBB-308(R) SBB-312(R) MP-300 BC-160 DESCRIPTIONS 252 Point Dual Loop Addressable Adder 32 Zone Internal Display Adder (for SFC-551 and SFC-553 only) 8 LED Remote Annunciator (red) 16 LED Remote Annunciator (red) 16 LED Annunciator chassis / TZ has 16 yellow LEDs for trouble indication. Remote Annunciator with 32 bi-colored (red and yellow) LEDs. TZ version has 32 yellow LEDs for trouble indication. Graphic Annunciator Graphic Annunciator Adder Driver Board Remote Trouble Indicator, Buzzer and LED Trim Ring For Enclosure (Black) Trim Ring For Larger Enclosure (Black) Enclosure for one annunciator, white. R version is red. Enclosure for two annunciators, white. R version is red. Enclosure for three annunciators, white. R version is red. Enclosure for eight annunciators, white. R version is red. Enclosure for twelve annunciators, white. R version is red. End-of-line resistor plate, 3.9K ohm External Battery Cabinet 7

System Components Analog/Addressable Devices DESCRIPTION Ionization Smoke Detector (UL Listed) Photoelectric Smoke Detector Summit Model SII-200 SIP-200 * Multi-sensor (photoelectric with supplemental rate-of-rise heat sensor) SIM-200 Heat Detector SIH-200 BASES 4 inch Standard Base SIB-4 6 inch E-Z Fit Base SIB-6 6 inch Base with Relay SIB-6R 6 inch Base with Sounder SIB-6S 6 inch Base with Temporal Tone Sounder SIB-6TH ANCILLARY MODULES Priority Monitor Module Mini Priority Monitor Module SIM-100P SIM-101P Single Relay Output Module (1 Form C Contacts, 2 Gang Mount) 55000-820 Supervised Control Module Isolator c/w Mounting Base SIM-100S SIM-100X (Kit) 100XH (Isolator) 100XB (Base) ADDRESSABLE DUCT DETECTORS Ionization Duct Smoke Detector (UL Listed) Photoelectric Duct Smoke Detector (UL Listed) Ionization Duct Smoke Detector with relay (UL Listed) Photoelectric Duct Smoke Detector with relay (UL Listed) SIDH-200I SIDH-200P SIDH-200IR SIDH-200PR ADDRESSABLE PULL STATIONS Addressable Single Stage Single Action Pull Station Addressable Single Stage Dual Action Pull Station SPS-201ID SPS-202ID * Unit employs an integral heat sensor; however it must not be used as a regular heat detector. Refer to the product data sheet for detailed functionality, operation and application. Manual configuration for the SIM-200 is NOT PERMITTED. This device must be configured via the AUTO CONFIG. 8

SFC-500 Series Installation and Operation Manual Mechanical Installation Installing the Enclosure Install the SFC-500 Series Fire Alarm Panel enclosure as shown below. Mount the enclosure using the four mounting holes and the screws provided. Figure 1: Wallbox Dimensions / Mounting the SFC-500 - Surface Mounting Hole 11" 1.5" Mounting Hole 14.5" 20" Mounting Hole 5.4" Mounting Hole 4.5" 14.5" 9

Mechanical Installation Figure 2: Mounting the SFC-500 - Flush 11" 1.5" PLACE SFC-200TRB TRIM RING OVER BACKBOX 17" 14.5" 4 Mounting Holes for Surface Mounting Adhere trim ring to wall surface around SFC-500 backbox 20.0" 22.5" 4" 3.5" is the maximum depth for semi-flush mounting using the flush trim ring 4.5" 3.5" 14.5" 1" 1" is the minimum depth above the wall required for semi-flush mounting using the flush trim ring Figure 3 shows a cross-section of the semi-flush mounted backbox and the trim ring. Make sure to allow a minimum depth of 1 above the wall surface for proper door opening. Figure 3: Flush Trim Detail Wall Trim ring Wood stud Back box 10

SFC-500 Series Installation and Operation Manual Figure 4: Wallbox Dimensions / Mounting the SFC-551/SFC-553 Surface /Flush PLACE SFC-UNIV-TRB TRIM RING OVER BACKBOX 11" 17" 1.5" 4 Mounting Holes for Surface Mounting Adhere trim ring to wall surface around SFC-551 backbox 20.5" 26" 28.5" 4" 3.5" is the maximum depth for semi-flush mounting using the flush trim ring 4. 5 " 3.5" 14.5" 1" 1" is the minimum depth above the wall required for semi-flush mounting using the flush trim ring Note: See Figure 3 for Flush Trim Details for mounting the trim ring. 11

- - - B Installing Adder Modules Installing Adder Modules The SFC-500 Fire Alarm panels come pre-assembled with all components and boards except for Adder Modules. Module installation locations are shown in Figure 5. Refer to Figure 6 on the next page for Jumper or DIP Switch settings and see Wiring Tables and Information for wiring specifications. Figure 5: Installation of Adder Modules Reverse polarity and city tie module SPR-200. Mounted on hex spacer with two screws provided. NC NO C NC NO C NC NO C NC NO S - + C R T R T R T R T RES CO RES CO LINE2 LINE1 RS-485 AUX. RELAY ALARM RELAY TROUBLE SUPERVISORY RELAY RELAY JW7 JW2 JW6 JW5 For PC programming use UIMA Interface module not UL-864 or ULC-527 listed. Please refer to Document LT-929 for details SYSTEM NORMAL OCT 21, 2005 02:41AM AC ON COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM POWER SUPPLY JW9 1 2 4 ABC SIGNAL SILENCE BUZZER SILENCE LAMP TEST SPARE JW3 3 DEF 5 6 GHI JKL MNO 7 8 9 PRS TUV WXY * 0 # QZ P12 X M? RS-232C PORT JW4 RTI PORT Loop A JW1 4-WIRE AUX SUPPLY SUPPLY SIG 4 SIG 3 SIG 2 SIG 1 - + - + - + - + - + - + TRB TRL COM- COM+ + + UNFILTERED FWR 24VDC BLK RED BLK RED BLK RED BLK RED -SIG4 OUT+ -SIG3 OUT+ -SIG2 OUT+ -SIG1 OUT+ -SIG4 RET+ -SIG3 RET+ -SIG2 RET+ -SIG1 RET+ CLASS A converter board for indicating Circuits SOCA-204 (4 circuits) Transformer P8 P4 P3 P2 TO POWER SUPPLY Power supply board P6 P5 SPR-200 is mounted here for SFC-551 BATTERY P3 + P4 P1 SEC TX P2 AC wiring terminal + - + - BATTERY BATTERY 12

C C C - A - B SFC-500 Series Installation and Operation Manual Cable and Jumper Connections for Main Board and Adder Modules Figure 6: Main Fire Alarm Board Cable Connectors and Jumper Locations RS-232C PORT For PC programming Telephone line #1 Telephone line #2 RS-485 for annunciators Auxiliary Relay Alarm Relay Supervisory Relay Trouble Relay NC N O NC N O NC NO NC NO S - + C R T R T R T R T RES C O RES CO ALARM AU X. RELAY RS-485 LI NE 2 LINE1 RELA Y TR OU BLE SUPERVISORY RELA Y RELA Y JW7 JW2 JW6 JW5 SYSTEM NORMAL OCT 21, 2005 02 : 41 AM AC ON COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM For PC programming use UIMA Interface module not UL-864 or ULC-527 listed. Please refer to Document LT-929 for details SUP PLY JW9 1 2 POWER ABC SIGNAL SILENCE BUZZER SILENCE LAMP TEST SPARE 3 DEF 4 5 6 GHI JKL MNO 7 8 9 PR S TU V WXY * 0 # QZ P12 JW3 X M? JW4 Loop JW1 4- WIR E AUX SUPPLY SUPPLY SI G 4 SIG 3 SI G 2 SIG 1 - + - + - + - + - + - + RTI UNFILTERED PORT FWR 24 VDC TRB TRL CO M - CO M + + + BLK RED BLK RED BL K RED BLK RED Addressable Loop Auxiliary Supply Resettable Auxiliary Supply P8 P4 P3 P2 Connect to SPR-200 - Connect to SRAX-532 Connect to Remote trouble indicator Unfiltered 24V supply 13

C C C - A - B Installing Adder Modules Figure 7: Main Board (3 loop model) Cable Connectors and Jumper Locations Telephone line #1 Telephone line #2 RS-485 for annunciators Auxiliary Relay Alarm Relay Supervisory Relay Trouble Relay NC N O NC N O NC NO NC NO S - + C R T R T R T R T RES C O RES CO ALARM AU X. RELAY RS-485 LI NE 2 LINE1 RELA Y JW2 TR OU BLE SUPERVISORY RELA Y RELA Y JW7 P8 JW6 JW5 P4 SYSTEM NORMAL OCT 21, 2005 02 : 41 AM AC ON COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM For PC programming use UIMA Interface module not UL-864 or ULC-527 listed. Please refer to Document LT-929 for details SUP PLY JW9 P3 1 2 POWER ABC SIGNAL SILENCE BUZZER SILENCE LAMP TEST SPARE 3 DEF 4 5 6 GHI JKL MNO 7 8 9 PR S TU V WXY * 0 # QZ P12 P2 JW3 RS-232C PORT For PC programming X M? JW4 TRB RTI PORT TRL Loop JW1 SIG 1 SI G 2 SIG 3 SI G 4 AUX SUPPLY 4- WIR E SUPPLY UNFILTERED FWR 24 VDC CO M - CO M + + + - + - + - + - + - + - + BLK BL K BLK BLK RED RED RED RED Addressable Loops 1 2 3 Auxiliary Supply Resettable Auxiliary Supply Connect to SPR-200 - Connect to SRAX-532 Connect to Remote trouble indicator Unfiltered 24V supply 14

SFC-500 Series Installation and Operation Manual Table 1: Connectors and Jumpers on the Main Fire Alarm Board P8 P4 JW1 JW2 JW3 JW4 JW5 JW6 JW7 JW8, JW9, JW10, JW11, JW12 Cable from P1 of the SPR-200 Polarity Reversal and City Tie Module connects here. Otherwise not used. Cable from connector P1 of the SRAX-532 Display Adder Module connects here. Otherwise not used. On the Main Fire Alarm Module, this jumper is not used, open. Remove this jumper if a remote annunciator is used. Not used, open. Not used, open. Normally open. Place jumper here and power down (AC and batteries) and power back to restore Master Passcode. After reset, remove jumper and leave normally open. Normally open to BLOCK remote configuration via modem. Place jumper here to ALLOW any type of remote configuration. On the Main Fire Alarm Module, this jumper must be removed if a SPR-200 Polarity Reversal and City Tie Module is installed. Not used, open. SOCA-204 Output Class A Converter Adder Module Figure 8: SOCA-204 Output Class A Converter Adder Modules SOCA-204 Mounting hole for #6-32 screw BLK RED BLK RED -SIG4 OUT+ -SIG3 OUT+ -SIG4 RET+ -SIG3 RET+ BLK RED BLK RED -SIG2 OUT+ -SIG1 OUT+ -SIG2 RET+ -SIG1 RET+ Mounting hole for #6-32 screw Indicating circuits must be wired from the SOCA-204 to the main Fire Alarm board. For example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the Class A Converter Module to the positive and negative terminals of Indicating circuit 1 on the Main Fire Alarm board. The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and then wired back to the SIGNAL RET positive and negative. 15

Installing Adder Modules Polarity Reversal and City Tie Module (Model SPR-200) Mount the SPR-200 on the left side panel of the backbox with the two screws provided, refer to Figure 5. Figure 9: Polarity Reversal and City Tie Module P1 P2 Mounting hole for #6-32 screw Mounting hole for #6-32 screw + - + - + - CITY TIE POLARITY POLARITY REVERSAL REVERSAL ALARM SUPV JW4 The following hardware configuration must be performed before installing the SPR-200. Table 2: SPR-200 Cable and Jumper Settings ITEM SETTING P1 JW4 Cable connects to P8 (bottom left-hand corner) on the Main Fire Alarm Board. Not used. Keep jumper intact. The Alarm Transmit signal to the SPR-200 can be programmed to turn OFF when signal silence is active. This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals will resound and the City Tie Box will be retriggered. The Trouble Transmit signal to the SPR-200 can be programmed to delay AC power fail 0, 1, 2, or 3 hours if this is the only system trouble. SRAX-532 Display Adder Module The SRAX-532 Display Adder Module is used only with the SFC-551 Series Fire Alarm Panel. No jumpers or other physical configuration steps are required to install this second SRAX-532 Display Adder Module. Remove the blank cover plate from the front door and install the SRAX-532 with the clear cover in the opening with the hardware provided. Disconnect main and standby power and connect the cable of the second SRAX-532 into the open, remaining header of the existing SRAX-532. The additional LEDs will be available for configuration as LEDs 33 to 64, when the system power is restored. 16

SFC-500 Series Installation and Operation Manual Circuits and Devices Addressable/Analog Devices The SFC-500 supports up to 3 loops of addressable/analog devices. The device loop can be used to connect up to 60, 126 or 378 analog devices and addressable input or output modules on an unshielded twisted pair (UTP). The devices must be compatible with the Summit device protocol. The loop interface software continuously supervises the devices on its loop against those found during configuration for the following conditions: device missing unconfigured device responding two or more devices responding to the same address wrong device type A communication or addressing error on a device is reported as a trouble on the associated zone LED if configured. The addressable loop can be configured for class A or B operation. "T-tapping" is allowed (Refer to device installation documentation for details). A short or open on the loop will activate the common trouble sequence with a latching trouble. Devices on the loop have an optional LED which normally flashes when the device is polled and goes ON steady when the device is active (alarm for an input device or active for an output device). The flashing of the LED on polling for sensors can be suppressed during configuration. For input or output modules, the LED always flashes when polling. The software limits the maximum number of the devices which can have their LED turned ON when active to fifteen (15). Certain devices are designed to support an optional external LED, which operates when the LED on the device is activated. Remote/external LEDs must NOT be used on this system. The panel can provide up to 350mA of current to the devices on the loop. A maximum line loss of 5 volts is permitted, so the loop distance, wire size, and maximum number of devices are limited by this constraint. The device currents are as follows: DEVICE CURRENTS (ua) Device Quiescent Alarm Inrush Ionization 280 2280 1000 Photoelectric 340 4340 1000 Multi-sensor (Photoelectric/Thermal) 470 3470 1000 Heat 250 2250 1000 Priority Switch Monitor 600 4600 2500 Mini Priority Switch Monitor 600 4600 2800 Single Relay Output 850 4850 3000 Supervised Output 1000 1000 6000 Isolator 35 35 0 The devices should be installed using unshielded twisted pair (UTP). The currents above may be used to calculate the total line drop on the loop, which must not exceed 5 volts worst-case at the last device. The calculations required to determine the maximum permissible loop wiring distance with various combinations of devices is relatively complicated, and when isolators are used, includes a consideration of device inrush currents which must not exceed 20mA for a single isolator. In no case should more that twenty devices be connected to a single isolator. To simplify the calculation process, please utilize the loop calculator program located on the Summit website at http:/www.summit-st.net in order to determine maximum loop lengths, number of devices, and wire sizes etc. It is also important to note that the device LEDs present a significant extra load on the loop which must be considered in calculating permissible loop lengths, battery capacities, etc. Please refer to the device Installation 17

Circuits and Devices Instructions and other documentation provided with the addressable devices, bases, and isolators for further information. The system will automatically limit the maximum number of device LEDs which can be illuminated to 15. Analog Devices The system supports Summit SI-200 Series photo, ion, multi-sensor and thermal (heat) type analog detectors, as well as contact input and output devices. The detectors may be configured as non-verified or verified alarm inputs. To determine an alarm condition, the system polls the analog device and compares the analog value against stored thresholds for pre-alarm and alarm conditions. A range of thresholds is provided for each type of analog device (except for contact devices), corresponding to the agency approved range of threshold for a particular device type. Each device can be individually configured to a value in the range of threshold for day time and one for the night time or after hours operation; i.e. a device may be configured to a low sensitivity for day time and high sensitivity at night time. The day time threshold will be used unless the after hours operation is active. Drift Compensation The SFC-500 will automatically adjust for gradually increasing affects of dust and other accumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detector going dirty according to the gradual change in the normal clean air value received. When it can no longer compensate for an increasingly dirty detector, a dirty detector trouble is indicated for that device. Auto Test Periodically each detector is commanded to return an alarm value to test its ability to alarm. If it fails the test, a trouble is indicated on that device. This trouble is latched until system reset. Contact Inputs Contact input modules on the addressable/analog device loop may be configured as any of the following input types: non-verified alarm inputs waterflow inputs non-latching supervisory inputs latching supervisory inputs monitor inputs trouble only inputs remote switch inputs Contact Outputs Contact output modules on the addressable/analog device loop may be configured as any of the following output types: signals strobes relay outputs Analog devices may be installed with relay or sounder bases. The outputs of these bases are activated when the device active LED turns ON steady in response to an alarm. The command to activate the output is separate from the command that activates the LED and they are not subject to the same restrictions as the LED. Output modules configured as signals are not stroked by software at the current signal rate. When the system commands them to be either in alert or in evacuation, the panel will simply activate them continuously. It is possible to provide stroked operation by connecting the signal power to a conventional signal output which is stroking at the correct rate when the device is active. Depending on the device, the system can detect open and short troubles and report it as an output circuit trouble. 18

SFC-500 Series Installation and Operation Manual Field Wiring Main Fire Alarm Board Field Wiring Wire devices to the addressable loop as shown in Figure 9 for Class B (Style 4) or Figure 10 for Class A (Style 6). Refer to the Table 2 for loop wire gauges.wire devices to addressable loops 2 and 3, if available, in the same manner. Figure 10: Addressable Loop Wiring - Class B or Style 4 FIRE ALARM MAIN BOARD Loop A B + - + CLASS B WIRING - ION SMOKE DETECTOR PHOTO SMOKE DETECTOR OUTPUT MODULE HEAT DETECTOR PULL STATION Table 2: Loop Wiring Table UNSHIELDED TWISTED PAIR WIRE GAUGE LOOP TOTAL (OUT AND IN) WIRE RUN This Loop Wiring Table is for reference only and should not be used without a detailed loop calculation. AWG FEET METRES 12 20,000 6098 14 15,942 4859 16 9960 3036 18 6265 1910 Maximum Loop Current: 350 ma Maximum Loop Resistance: 35 subtract 0.2 Ohms per isolator. Maximum Loop Capacitance: 0.5 uf Maximum Number of Isolators is 40. Loop Isolators To limit the number of addressable devices compromised by a short on the addressable loop, isolators (SIM-100X, 100XH, or 100XB) may be used to isolate the affect of the short circuit. If the impact of a short circuit must be limited to only one device, an isolating base must be used for each detector. A maximum of twenty devices can be connected between isolators, or between the panel and the first isolator, as long as the maximum in-rush current for the devices on one segment of the loop does not exceed 20mA. Refer to the installation instructions for addressable devices for additional details. 19

Field Wiring Figure 11: Addressable Loop Wiring -Class A or Style 6 FIRE ALARM MAIN BOARD Loop A B + - + CLASS A WIRING - ION SMOKE DETECTOR PHOTO SMOKE DETECTOR OUTPUT MODULE HEAT DETECTOR INPUT MODULE Loop Operation When there is a short circuit on the Class A loop with isolators installed, the isolators isolate the shorted fault, the panel detects it as an open loop and generates an open loop trouble. When a Class A loop is opened there may be a few missing devices reported by the panel which will be restored once the panel has established the Class A connection. Note: When there is an "Open loop trouble" look for both open and shorts on the loop. As a guideline, the isolators which are activated in response to a short will have their LED ON; look for the short between the two isolators with their LEDs ON. 20

SFC-500 Series Installation and Operation Manual Indicating (Powered Output) Circuits Powered output circuits can be configured as signal, strobe or relay outputs. Powered output circuits are supervised while they are not active for both open circuits and shorts. The circuit will not actually be activated if there is a short trouble on the circuit. It will be activated if an open trouble is indicated. A circuit trouble activates the common trouble sequence as a non-latching trouble. Since open circuit supervision does not operate while the circuit is in alarm, if the circuit was in trouble before it was activated, it will still indicate trouble while active. The trouble condition will be re-evaluated when supervision resumes. Output circuits configured as strobes can have sync protocol for synchronization if configured. Certain strobe and strobe/horns models of the following manufacturers are supported. 1. All normal non-sychronized horns 2. Faraday 3. System Sensor 4. Wheelock 5. Secutron 6. Mircom When configured as normal, the output circuit is ON continuously when activated and does not use any sync protocol. When configured as non-silenceable strobes, the strobes cannot be silenced, but the horn can be silenced by pressing the 'signal silence' button If the strobe is configured as silenceable strobe both the horn and the strobe are silenced (stopped) by pressing the 'signal silence' button Indicating Circuit Wiring The SFC-500 Series Addressable Fire Alarm Panels supports Class B (Style Y) and Class A (Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Line resistor. Each indicating circuit provides up to 1.7Amperes, total 5Amperes of current maximum if no auxiliary power is used. Wire indicating circuits as in Figure 11 for Class B (Style y) or as in Figure 12 for Class A (Style Z). Table 3: Indicating Circuit Wiring Total signal load in amperes Maximum wiring run to last device 18 AWG 16 AWG 14 AWG 12 AWG Feet Meters Feet Meters Feet Meters Feet Meters Max loop resistance in ohms 0.06 2350 716 3750 1143 6000 1829 8500 2591 30 0.12 1180 360 1850 567 3000 915 4250 1296 15 0.3 470 143 750 229 1200 366 1900 579 6 0.6 235 71 375 114 600 183 850 259 3 0.9 156 47 250 76 400 122 570 174 2 1.2 118 36 185 56 300 91 425 129 1.5 1.5 94 29 150 46 240 73 343 105 1.2 1.7 78 24 125 38 200 61 285 87 1.0 Notes: For Class A wiring the resistance in ohms is multiplied by two. Maximum voltage drop should not exceed 1.8 volts. 21

Field Wiring Figure 12: Indicating Circuit Class B or Style Y Wiring FIRE PANEL MAIN BOARD INDICATING CIRCUIT #1 - SIG 1 + STYLE Y WIRING INDICATING CIRCUIT - 1 INDICATING CIRCUIT #2 - SIG 2 + STYLE Y WIRING INDICATING CIRCUIT - 2 BELL STROBE HORN 3.9K 1/2 WATT ELR NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY AS #1 AND #2 Figure 13: Indicating Circuit Class A or Style Z Wiring FIRE PANEL MAIN BOARD INDICATING CIRCUIT #1 SIG 1 + - BLK RED - SIG1 OUT+ -SIG1 RET+ STYLE Z WIRING INDICATING CIRCUIT 1 INDICATING CIRCUIT #2 SIG 2 + - BLK RED - SIG2 OUT+ -SIG2 RET+ STYLE Z WIRING 2 MORE INDICATING CIRCUITS NOT SHOWN INDICATING CIRCUIT 2 SOCA-204 CLASS A CONVERTER MODULE BELL STROBE NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY AS #1 AND #2 HORN 22

SFC-500 Series Installation and Operation Manual Dialer Wiring All SFC-500 Fire Alarm Panel models have a dialer on board. Terminals marked Line 1 and Line 2 must be wired as shown in Figure 14. Terminals are located in the top left hand corner of the main fire alarm board, from the top down. Refer to Figure 5 for terminal location. Figure 14 Dialer Wiring FIRE ALARM MAIN BOARD LINE-1 LINE-2 CO CO RES T R T R T R T RJ31X GREEN 1 4 RED 2 3 BROWN 7 6 GREY 8 5 TIP RING Public switch Telephone company wiring TIP RING premise telephone IF permitted R RES Line 2 is Wired as shown for Line 1 Refer to Dialer Operation Section and Appendix B for more information regarding the built-in dialer. 23

Field Wiring Polarity Reversal and City Tie Module (SPR-200) Wiring Wire the SPR-200 Polarity Reversal and City Tie Module (if used) as shown in Figure 15. Power Limited cable type FPL, FPLR or FPLP must be used. For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown. For use in Canada, the Protective Device is not required but still recommended. Figure 15: Polarity Reversal and City Tie Module Terminal Connection SPR-200 + - CITY TIE LOCAL ENERGY RATED - 24VDC FILTERED TRIP COIL - 14 Ohms, 210mA, 5mV RIPPLE NOT POWER LIMITED + - + - POLARITY REVERSAL ALARM 24VDC OPEN 12VDC AT 3.5mA 8mA MAX. SHORT POWER LIMITED POLARITY REVERSAL SUPV. 24VDC OPEN 12VDC AT 3.5mA 8mA MAX. SHORT POWER LIMITED 1 2 S 1 2 S 1 UNPROTECTED PROTECTOR PROTECTOR PROTECTED 1 2 S 1 2 S DIN RAIL CONNECTION TO EARTH GROUND 1 + - + - + USE A SHORTING WIRE WHEN THE CITY TIE IS NOT USED CONFORMS TO NEMA STANDARD SB3-1969 INTENDED FOR CONNECTION TO POLARITY REVERSAL CIRCUIT OF A REMOTE STATION RECEIVING UNIT HAVING COMPATIBLE RATINGS 2 2 - S 1 2 UNPROTECTED PROTECTED S 1 2 EITHER THE CITY TIE or POLARITY REVERSAL INTERFACE MAY BE USED, NOT BOTH. S S DIN RAIL CONNECTION TO EARTH GROUND NOTES: 1. Plug SPR-200 ribbon cable P1 into connector P8 of the Main Fire Alarm board. 2. Cut Jumper JW1 on the SPR-200 Polarity Reversal and City Tie Module in order to transmit a trouble condition from the Polarity Reversal Alarm terminals to the monitoring station. 3. Cut Jumper JW2 on the SPR-200 Polarity Reversal and City Tie Module in order to transmit a trouble condition from the Polarity Reversal Supervisory terminals to the monitoring station. 4. Remove jumper plug from JW7 on the Main Fire Alarm board. 5. For USA installation, the installer must use an Atlantic Scientific (Tel. 407-725-8000), Model #24544 Protective Device or similar UL-Listed QVRG secondary protector. 6. The Polarity Reversal interface is Power Limited and must use power limited cable type FPL, FPLR or FPLP from the SPR-200 to the Protectors. 24

SFC-500 Series Installation and Operation Manual Auxiliary Power Supplies Aux 2 Resettable Auxiliary Power (supervised, regulated) The AUX 2 resettable auxiliary power supply is supervised for shorts, therefore a short will disconnect the power until the RESET button is pressed. A trouble signal will be generated if there is a short. The circuit must be supervised for opens utilizing the End of Line Relay Model PAM-3 as shown in Figure 16. This supply is rated at 21.1VDC regulated/300ma max/1v voltage drop maximum. Auxiliary Supply (supervised, regulated) Supervised auxiliary power is used to power the remote annunciators and smart relay modules. This filtered circuit is supervised for shorts, therefore a short will disconnect the power until the RESET button is pressed. A trouble signal will be generated if there is a short. The circuit must be supervised for opens utilizing the End of Line Relay Model PAM-3 as shown in Figure 16. This supply is rated at 21.1VDC regulated/500ma max/1v voltage drop maximum. Unfiltered Supply (unsupervised, unregulated) This unregulated supply is not supervised. When required, it is recommended that the circuit be supervised for opens utilizing the (UL listed - S3403) End of Line Relay Model PAM-3 as shown in Figure 16. This supply is rated at 24VDC/1.7A max. If there is a short on this circuit, the auxiliary power does not recover automatically when the short is removed. The main power and the battery must be disconnected, then reconnected and the panel reset to re-establish the auxiliary power supply. Figure 16: Supervision Of Auxiliary Supplies FIRE ALARM MAIN BOARD AUX 2 RESETTABLE AUXILIARY POWER OR AUXILIARY SUPPLY OR UNFILTERED SUPPLY + - DETECTOR POWER SUPPLY 22VDC, 200mA MAX. CURRENT - 300mA MAX. RIPPLE VOL. 5mV (POWER LIMITED) Supervision for Auxiliary Supplies Connect auxiliary devices here* * Use this supervision set-up only if auxiliary devices are used. 6 3 4 END OF LINE RELAY 5 2 1 Class B (Style B) WIRING E.O.L. 47K Ohms Red MINI MONITOR MODULE Violet MIX-101P SIM-101P White B + Red Loop A - + - Black Black LEGEND ION SMOKE DETECTOR PHOTO SMOKE DETECTOR HEAT DETECTOR 25

Field Wiring Power Supply Connections The power supply is located directly behind and below the main board. The ratings are: TYPE RATING Electrical Input rating 120 VAC, 60Hz, 1.73A / 240VAC, 50Hz, 0.864A Battery fuse on Main module 10A, slow blow micro fuse (not replaceable) Caution: The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated continuous power without any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes. Refer to Appendix C for specifications. Note: Ensure that the AC supply is disconnected before wiring the power to the panel. Wire the AC power to the AC wiring terminals as shown in Figure 17 using the proper wire gauge. Fire alarm systems must be installed in compliance with local codes and standards and with the Authority Having Jurisdiction (AHJ) Figure 17: Main Power Supply Connections TRANSFORMER JW7 TO SPR-200 MODULE RIBBON CABLE POWER SUPPLY P3 P2 RTI PORT UNFILTERED FWR 24VDC TRB TRL COM- COM+ POWER CONNECTOR POWER SUPPLY BOARD BATTERY P3 + P4 P6 - P5 SEC TX P1 P2 Yellow Red Black Green 240VAC 50Hz 120VAC 60Hz N Ground RED BLACK RED + - + - AC WIRING TERMINALS BATTERY BATTERY Note: The SFC-500 Series panels are capable of being wired for 120 VAC or 240 VAC 50/60 Hz as shown above. A good ground connection to the Ground" terminal is essential to electrical safety, ensure proper operation, and specified noise immunity. 26

SFC-500 Series Installation and Operation Manual System Checkout Before turning the power ON To prevent sparking, do not connect the batteries. Connect the batteries after powering the system from the main AC supply. 1. Check that all adder modules are installed in the proper location with the proper connections. 2. Check all field (external) wiring for opens, shorts, and ground. 3. Check that all interconnection cables are secure, and that all connectors are plugged in properly. 4. Check all jumpers and switches for proper setting. 5. Check the AC power wiring for proper connection. 6. Check that the chassis is connected to earth ground (cold water pipe). 7. Make sure to close the front cover plate before powering the system from main AC supply. The best way to set up a panel for the first time is to avoid connecting any field wiring at first. To begin set up, power up the panel with end of line resistors connected where appropriate, then connect the battery. The panel will show System Restart Active. Press System Reset button to reset the panel. If the panel is free of trouble, connect one circuit at a time, checking for troubles each time. If a trouble occurs at any point during the set-up, correct the fault, then continue connecting the field wiring. Power-up procedure After completing the system checkout procedures outlined above, 8. Power up the panel. The "AC ON" green LED and the Common Trouble LED should illuminate, and the buzzer should sound. Press the System Reset button. Since the batteries are not connected, the trouble buzzer should sound intermittently and the common trouble LED should flash. 9. Connect the batteries while observing correct polarity: the red wire is positive (+) and black wire is negative(-). All indicators should be OFF except for normal power "AC ON" green LED. 10.Configure the Fire Alarm Control Panel as described in the System Configuration section. Troubleshooting Symptoms Circuit Trouble Remote Trouble Ground Fault Battery Trouble Walk Test Mode Common Trouble Possible Cause Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated, as well as the common trouble indicator and trouble buzzer. To correct the fault, check for open wiring on that particular circuit loop or that the Circuit Disconnect Switch is in the ON or CLOSED position. Note: Disconnecting a Circuit will cause a system trouble (off-normal position). Remote Trouble will be indicated on the main panel display for any failure reported by, or failure to communicate with a remote annunciator or other remote device. This panel has a common ground fault detector. To correct the fault, check for any external wiring touching the chassis or other Earth Ground connection. Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will cause a battery trouble. If battery trouble condition persists, replace batteries as soon as possible. If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode. If only a common trouble is indicated on the main panel and none of the above confirming trouble indicators are ON, check the following for possible fault: Check for any missing interconnection wiring. Check for any Module missing that was part of the Configuration. Check for improperly secured cabling. 27