Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip

Similar documents
Product Specifications 4 Breaker Main Disconnect Panel with Undervoltage Trip

Product Specifications 480 VAC, 175A Main Power Distribution Panel

Product Specifications 480 VAC, 70A Main Power Distribution Panel

Product Specifications Auto Restart Main Power Distribution Panel

Product Specifications Warning Light Control Cabinet

Product Specifications Fail Safe Emergency Power Off Control Panel 480V 3 Phase

Product Specifications Warning Light Control Cabinet

Product Specifications Linear Accelerator Relay Junction Box

Product Specifications MaxLumen MRI LED Diffused Lighting

Product Specifications MaxLumen MRI LED Diffused Lighting

Product Specifications MaxLumen MRI LED Diffused Lighting

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00

LiteMinder. LM Series Inverter Pure Sine Wave Modular Inverter Technology. Fast Transfer System 1.0 to 18.75KVA LED Compatible

Installation, Operation & Service Manual

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

Guide Specification Model CTG Automatic Transfer Switch

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Hazardgard. Product Profile. Engineered to perform in the harshest environments. Hazardous Location Room Air Conditioners

Standard Product. Wall-Mount Preferred-Cutout Disconnects Hoffman WATERSHED Wall-Mount Disconnects

MaxLite LED High Bay Fixtures

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

Panel Mounted Heat Exchangers by Dantherm, Inc.

MaxLite Polygon Linear LED Light

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

CURRENT LIMITING LIGHTING CONTROL PANEL Supplemental Overcurrent Protection City of Los Angeles Approved Version

GETZ MANUFACTURING PART # CYLINDER DRYER

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

AquaSaver DISPOSER CONTROL CENTER Installation Manual. Model AS-101K

INSTALLER S & OWNER S MANUAL

CONTENTS AUTOMATIC TRANSFER SWITCHES

Elevator Control ES Switch

VT SERIES VERTICAL TOASTER OPERATOR S MANUAL TABLE OF CONTENTS

Quest Power Electric Heat EHS 31 Pro

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Owner s Manual Hydro-X Vacuum Pac

Owner s Manual Phoenix FireBird

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

FOSTORIA INDUSTRIES, INC North Main Street Fostoria, OH Phone: Fax:

ASCO Series 185 Power Transfer Switches

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

A PROUD HERITAGE OF EXPERIENCE & QUALITY. Beverage Cooler VT-SC-1

DISPOSER CONTROL CENTER

Quest Power Electric Heat EHS 62 Pro

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS!

Electric Duct Heaters

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

Installation instructions for Plenum-mounted add-on electric heaters MODEL TU. MARCH 2011 version 7

Wall-Mount Preferred-Cutout Disconnects Hoffman WATERSHED Wall-Mount Disconnects

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

INSTALLATION, OPERATION AND MAINTENANCE

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

G Series SAVE THESE INSTRUCTIONS. (Model B) Convector Heater for Hazardous Locations GENERAL! INSTALLATION

Desiccant / Pump Dehumidification System. Model Operating Manual

INSTALLATION and OPERATION INSTRUCTIONS

IW-25-2 Dehumidifier Installation & Operations. Manual

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Intelligent Lighting Controller

INSTALLER S & OWNER S MANUAL

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

Installation Manual. Models 99168, 99169, 99170

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

GRUNDFOS INSTRUCTIONS CMBE. Installation and operating instructions. Drinking Water System Component NSF / ANSI 61 NSF / ANSI 372

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

SECTION (15767) - UNIT HEATERS

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Owner s Manual Phoenix Aquadry TX 200

SACKSAFOAM QUICK FILL OPERATIONS MANUAL 2019A

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

DESIGNED BY FIRE FIGHTERS FOR FIRE FIGHTERS.

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

INSTALLATION INSTRUCTIONS

Instruction Manual and Warranty

SECTION AUTOMATIC TRANSFER SWITCHES

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

Installation and Operations Manual

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL

For use with models: BP , BP , BP

OPERATIONS MANUAL & PARTS LIST. BX2 Fastracts Extractor. IPC Eagle 3650 Dodd Rd, Eagan MN

BACKUP BATTERY INSTALLATION INSTRUCTIONS

Drawing Submittal Package

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

Interrupted Ignition Series Oil Primary Control

MaxLite LED Round Pendant Highbay Series

Quest PowerHeat HFC 100 Pro

Revitalize Building Mechanical Systems (4619)

Bulletin 1608N MiniDySC Dynamic Sag Corrector

Transcription:

NOVA Energy & Automation Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip Model NEAS-XXXX-G-UVR 03 January 2012

Product Description 1. Standard Applications The Nova 3 Breaker Main Disconnect is an integrated Main Circuit Breaker Panel with Undervoltage trip specifically designed to meet the requirements Siemens medical imaging installations. The low voltage internal control panel provide a safe, low voltage interface between the imaging equipment, control, and room line voltage. Under Voltage Release Details Figure 1 Main Disconnect Panel One Line The Under voltage release mechanism trips the circuit breaker by removing power from an internal coil. Power must be present and applied to the UVR coil before the main disconnect can be energized. If power is not provided to the UVR coil the breaker will continue to trip while one attempts to turn it on. UVR coils are designed to trip when its applied voltage falls between 35 to 70% of nominal rating. The UVR mechanism is best suited for interlocking a number of other equipment safety checks, as all circuits would need to be satisfied and all normally closed contacts would be wired in series. Any one of the contacts could open thereby tripping the circuit breaker. Another benefit of the UVR is that it will not automatically restart the equipment after a power outage. It would require that a person would go to the breaker panel and manually energize it after checking to see that conditions are safe to do so. Co Author: JF 2

2. System Compatibility Siemens Medical Solutions CT: Symbia T1 and several other related installations Please select item NEAS-43100-G-UVR -A 3. Identification Siemens Medical Solutions CT: The proper distribution panel can be identified in the Siemens Constructions Drawings sheet E-102 Somatom Definition AS Power Diagram item MP NEAS-43100-G-UVR Equal to item P2E18E4100FTS with related components A, B, C, D, E, G: 277VAC U.V. trip, ground bus bar, 80A 3P feeder (to CT), 25A 1P feeder (to UPS), 480-120 transformer 4. Features/ Benefits Features Benefits Integrated design provides all of the Main Disconnect Panel s controls into an easy to configured panel with Undervoltage Trip mechanism integrated into the main Circuit Breaker Utilizes heavy duty ABB Circuit Breaker to handle inrush currents. UL and cul listed to conform to NEC. Labeled to conform to NFPA99, NFPA-70. Provides Short Circuit and Overload Protection Provides differential protection Internally derived 120 Vac Under Voltage Release Neutral Block and Ground Block Factory wired and tested. Single point main disconnect and termination point Factory wired to match Siemens equipment and tested Designed, tested, and installed on several projects worldwide Manufactured using the highest quality components for high reliability and long life Provides protection for sensitive electronic equipment Manufactured to a tolerance which exceeds the specifications of Siemens equipment. Field adjustable overload and instantaneous trip Reduced weight- all components are within a small 40lb enclosure Field adjustable ranges allow for coordination with the facility distribution coordination. Eliminated the need for multiple control panels for short circuit, overload and Emergency Power Off Reduces installation time and cost by eliminating delays in obtaining individually enclosed components and by eliminating on site assembly. Provides a standardized platform for other future modifications or upgrades. Co Author: JF 3

5. Specifications Model Application Input Voltage Input Current Output Voltage Output over current protection NEAS-43100-G-UVR-A Main Disconnect Panel for Medical Imaging Equipment 480/277 VAC, 3 Phase 5-wire: 3 Phase Conductors + Neutral + Ground NEAS-43100-G-UVR A 125 Amps 480/277 VAC, 3 Phase (follows input voltage) NEAS-43100-G-UVR 100A 3P Main 80A 3P for CT 25A 1P for UPS Control Voltage Emergency Power Off Controls Operator Controls Compatible Estop Buttons Door Mounted Devices Grounding Short Circuit Current Protection Instantaneous Trip Settings Approvals Internally derived 277VAC 250VA for Undervoltage Trip Circuit 277VAC Undervoltage release (N.O) Compatible with 120 VAC and Low Voltage EPO operator devices Normally closed contacts Siemens CT: 2 ESTOPS- 2 N.C. contacts Direct -Mount Circuit Breaker Operating Mechanism with OSHA Lockout Isolated and non isolated ground bar 25 kaic Field adjustable from 1-10x of over current rating UL/cUL Co Author: JF 4

Figure 2 Main Disconnect Panel 6. Weights and Dimensions Mounting Main Disconnect panel is provided in a steel enclosure suitable for surface, wall or flush mounting. Dimensions Height: 600mm (24 ); Width: 500mm (20 ); Depth: 150mm (6 ) (Other enclosure options and sizes are available upon request) Weight Mounting Enclosure Enclosure Sealing 18.14 kg(40lbs.) Approximate, varies with Circuit Breaker rating and size Rear wall mounting holes (4). Spaced 0.79 (20mm) from enclosure edge 16 Gauge Carbon Steel, all rounded corners and 16 Gauge Door Foamed-in place polyurethane door gasket Finish Dip coat primed, powder-coated in textured RAL 7035 Cover Interior Panel Left Hand Hinged with 2 ¼ turn latches Zinc-Plated subpanel Ratings IP 66 to UL/cUL Type 1, 12, 3R, Co Author: JF 5

Figure 3 Enclosure Dimensions: Outside, Mounting, Depth 7. Warranty This limited warranty set forth below is given by Nova Automation ( Seller ) with respect to the electrical equipment ( Product ) packaged with this limited warranty. The Product, when delivered to you in new condition in its original packaging, is warranted against defects in materials or workmanship as follows: For a period of one (1) year from the date of original purchase, defective parts or a defective Product returned to a Seller, or its authorized service providers, as applicable, and proven to be defective upon inspection, will be repaired, or exchanged for a new Product, as determined by the Seller, or the authorized service provider. This limited warranty covers all defects encountered in normal use of the Product, and does not apply in the following cases: Loss of or damage to the Product due to abuse, mishandling, alteration, accident, electrical current fluctuations, failure to follow operating, maintenance or environmental instructions prescribed by Seller, failure to follow Sellers installation instructions, or service performed by someone other than Seller or its authorized service provider. Nova assumes no responsibility for labor or freight costs incurred in connection with the installation, removal, or replacement of products determined to be defective or any consequential or incidental damages arising from the use of the product. Nova Automations entire liability on any claim of loss or damage resulting from a defective product is limited to the replacement of the product. WARRANTY IS VOID IF PRODUCT IS NOT USED FOR THE PURPOSE FOR WHICH IT WAS MANUFACTURED. Co Author: JF 6

8. Product Service and Technical Assistance Nova Automation, LLC 2722 N. Avondale Blvd Milwaukee WI 53210 PH# 262-309-2950 Website: www.novaautomation.net 9. Approvals Prepared By ([Job Title]) This document requires the following approvals Approved By ([Job Title]) ([Job Title]) Approval Date Co Author: JF 7