Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Similar documents
Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

Global Journal of Engineering Science and Research Management

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Gandhinagar Institute of Technology Mechanical Engineering (Thermal Engineering) Semester II. Design of Heat Exchange Equipments [ ]

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Experimental analysis of condensation heat transfer enhancement of steam at low pressures using modified twisted tape insert

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

2. HEAT EXCHANGERS MESA

Falling Film Heat Exchangers for Solar Water Heaters

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Solar air heater duct having triangular protrusions As roughness elements on absorber plate

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

PERFORMANCE ENHANCEMENT OF AIR CONDITIONER *

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

a Heat Exchanger using FEA Tool

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

TRANSACTIONS ON ADVANCEMENTS IN SCIENCE AND TECHNOLOGY (TASTONLINE)

Performance Optimization of the Evaporative Condenser Design

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Development of Small-diameter Tube Heat Exchanger: Circuit Design and Performance Simulation

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

FUNDAMENTAL BASIS AND IMPLEMENTATION OF SHELL AND TUBE HEAT EXCHANGER PROJECT DESIGN: EVAPORATOR STUDY

Analysis of CPU cooling using liquid with different type of heat sinks

Thermal Performance of a Loop Thermosyphon

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

Experimental correlation of falling film condensation on enhanced tubes with HFC134a; low-fin and Turbo-C tubes

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Performance Study of Triple Concentric Pipe Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Compression of Fins pipe and simple Heat pipe Using CFD

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Pool boiling heat transfer enhancement on porous surface tube

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

ANALYSING THE EFFECTIVENESS OF THE HEAT EXCHANGER BY INCREASING OVERALL HEAT TRANSFER COEFFICIENT

American International Journal of Research in Science, Technology, Engineering & Mathematics

HEAT TRANSFER COEFFICIENT ENHANCEMENT IN NATURAL CONVECTION FROM HORIZONTAL RECTANGULAR FIN ARRAYS WITH PERFORATIONS

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

EXPERIMENTAL EVALUATION OF CONDENSATION HEAT TRANSFER COEFFICIENT OF R-417A IN HORIZONTAL TUBES

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Experimental Study on the Performance of Twisted Capillary Tube

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

FLIGHT UNLOADING IN ROTARY SUGAR DRYERS. P.F. BRITTON, P.A. SCHNEIDER and M.E. SHEEHAN. James Cook University

Operation of a Two-Phase Reverse Loop Thermosyphon

A study of Transient Performance of A Cascade Heat Pump System

Induction heating with the ring effect for injection molding plates

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

A Review on Comparative Study of Thermal Performance of Artificially Roughened Solar Air Heaters

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Performance Evaluation of Hybrid Solar Water Heating System Using Wire Screen Packed Solar Air Heater

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

HEAT TRANSFER ENHANCEMENT IN SHELL AND TUBE HEAT EXCHANGERS USING INSERTS

Waghmare Tushar Ramrao, D.S.Nakate

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Transcription:

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System Kwanghee Seo 1) and Taewan Kim 2)* 1) KEPCO Engineering & Construction Company. INC., 269 Hyeoksin-ro, Gimcheon-si, Gyeongsangbuk-do 39660, Republic of Korea. 2) Incheon National University, 119 Academy-ro, Yeonsu-gu, Incheon 22012, Republic of Korea. * Corresponding Author Abstract The Passive Auxiliary Feedwater System (PAFS) with nearly- heat exchangers is one of passive safety features of APR+ (Advanced Power Reactor Plus) which provides the auxiliary feedwater by means of natural circulation with condensation. It is feasible to increase the heat transfer capacity of the PAFS by employing a ly coiled heat exchanger due to additional secondary flow effect by centrifugal force. In addition, a compact and flexible design can be achieved in a fixed volume by using the ly coiled heat exchanger, which is one of the most important merits of implementing this heat exchanger. In this paper, the ly coiled heat exchanger has been employed for the PAFS instead of nearly- heat exchanger. In order to evaluate the heat transfer performance of the ly coiled heat exchanger, an in-tube condensation heat transfer correlation by Wongwises has been introduced into the system analysis code, MARS-KS. A comparative numerical study was conducted for both heat exchangers. The result shows that ly coiled heat exchanger has 20% higher heat transfer efficiency than existing nearly- heat exchanger. shows a high efficiency in heat transfer and allows a compact design. In this paper, a fundamental feasibility study on using the ly coiled heat exchanger for the PAFS has been conducted on the basis of an analysis using the system code, MARS-KS [4]. In order to perform the analysis, an empirical correlation has been implemented into the MARS-KS code and the ly coiled heat exchanger has been compared with the nearly- heat exchanger in terms of heat transfer performance and design parameters. DESIGN FEATURE OF APR+ PAFS The PAFS replaces a conventional active feedwater system and plays a role in the ultimate heat sink for decay heat through natural circulation. Fig. 1 shows a schematic diagram of the PAFS for the APR+ [1]. As shown in Fig. 1, The PAFS consists of a steam supply line, a passive condensation heat exchanger (PCHX), a return-water line, and a passive condensation cooling tank (PCCT). Keywords: Passive, Helically coiled tube, Heat exchanger, PAFS INTRODUCTION The Passive Auxiliary Feedwater System (PAFS) is one of passive safety features of APR+ (Advanced Power Reactor Plus). The PAFS provides the auxiliary feedwater by means of natural circulation with condensation. Since the natural circulation with condensation within the PAFS is the most important mechanism to remove the heat from the SG, the condensation heat transfer characteristics of a heat exchanger with nearly- tubes is one of the dominant factors to decide the performance of the PAFS. Therefore, both experimental and analytical investigations on the performance of the heat exchanger of the PAFS have been conducted to finalize the prototype design [1-3]. Meanwhile, the heat transfer enhancement can be achieved by increasing heat transfer coefficient and/or by increasing surface area. Various heat exchangers including micro-fin tubes, ly coiled heat exchangers, and so on, have been developed and implemented for industrial applications. Especially, it is known that a ly coiled heat exchanger Figure 1. Schematic diagram of the PAFS in the APR+ Table 1 shows the design parameters of the PAFS [2]. The design parameters of the PCHX tube listed in Table 1 are based on single tube. The length of tube is determined as 8.4 m considering heat removal capacity per tube and prevention of water hammering [1]. Especially in order to prevent water 940

hammering PCHX tube has been designed according to the regulatory guide of US NRC [5]. The PCCT has been designed to include enough amount of water for eight-hour operation without external water supply. Since the PCHX is designed with long nearly- tubes, the shape of the PCCT should be oblong in order to contain rather long tube. Table 1. Design parameter of the PAFS Parameter Specification PCHX Tube PCCT Inner/outer diameter Length Number of tubes Material Fluid Operating condition Flow rate Pool height Pool length Pool width 44.8 mm / 50.8 mm 8.4 m 240 STS 304 Steam 3.22 MPa / 239.1 0.295 kg/s 8.9 m 13.4 m 6.7 m DESIGN STUDY OF THE HELICALLY COILED TUBE HEAT EXCHANGER Condensation Heat Transfer and Comparison of Correlations : Since only a few studies have been conducted on the condensation heat transfer inside a ly coiled tube, it was decided to evaluate the characteristics of each correlation suggested by previous studies and to implement the most reasonable one to this feasibility study. The considered correlations and main parameters for each experiment are listed in Table 2 and Table 3. Wongwises and Polsongkram [6] have experimentally investigated two-phase condensation heat transfer and pressure drop of a ly coiled concentric tube-in-tube heat exchanger. The correlation suggested by Wongwises and Polsongkram takes into consider the effect of the geometric parameter d/d of a ly coiled tube. El-Sayed Mosaad et al. [7] carried out an experimental study to investigate condensation heat transfer and pressure drop characteristics of a ly coiled double tube with R-134a. 1 Wongwises and Polsongkram [6] Table 2. Helically coiled tube condensation model Correlation Model,,,, 2 El-Sayed Mosaad et al. [7],,, Wongwises [6] El-Sayed [7] Out dia Table 3. Helically coiled tube condensation experiment condition In dia Pitch Coil dia Helix angle (º) d/d Sat Temp ( ) Mass flux (kg/s m 2 ) 9.52 /23.2 8.3 /21.2 35 305 3.3 0.027 40 /50 400 ~ 800 R-134a 9.54 7.39 25.6 213 3.4 0.034 32 95 ~ 710 R-134a Fluid Fig. 2 depicts the heat transfer coefficient calculated by means of the correlations with respect to Reynolds number. The correlation by Shah [8] is a default condensation heat transfer coefficient in MARS-KS for turbulent film condensation. The figure indicates that the correlation by Wongwises and Polsongkram predicts higher condensation heat transfer coefficient than Shah correlation. Whereas El-Sayed Mosaad correlation underpredicts the condensation heat transfer coefficient than Shah correlation at high Reynolds number region (over 20,000). However, Shao Li [9] experimentally showed that the condensation heat transfer coefficient of the ly coiled tube is higher than straight tube by 4-13.8% and Wongwises and Polsongkram obtained 33-53% higher condensation heat transfer coefficient with ly coiled tube. Considering the results from previous studies and the Reynolds number dependency of the correlations, it is decided that Wongwises and Polsongkram correlation is more reasonable for this feasibility study for ly coiled condensation heat exchanger. 941

20000 Heat transfer coefficient (W/m 2 -K) 18000 16000 14000 12000 10000 8000 6000 4000 2000 Wonwises and Polsongkram El-Sayed Mosaad et al. Shah 0 0 10000 20000 30000 40000 50000 Reynolds number Figure 2. Heat transfer coefficient over Reynolds number Determination of Design Parameters : Basically the design parameters of the current PCHX of the PAFS are employed for the evaluation of the performance of each heat exchanger. The inner and outer diameters of the tube are 44.8 mm and 50.8 mm, respectively. The material of the tube is assumed as stainless steel 304. In order to maintain the similarity of heat transfer and pressure drop in tube, d i/d and helix angle in the experiment by Wongwises and Polsongkram are employed. The diameter and pitch of the helix in Fig. 3 are calculated by means of the following equations: di D. r (1) P = 2 D tan( α). (2) Table 4. Design parameter of ly coiled tube Figure 3. Helically coiled tube design parameter COMPARISON OF HEAT REMOVAL CAPACITY WITH HORIZONTAL TUBE HEAT EXCHANGER Development of MARS-KS Model for Analysis The MARS-KS code which is a best-estimate system analysis code based on two-fluid model, was utilized for the evaluation of the heat removal capacity and the operational performance for and type condensation heat exchanger. In order to model the condensation within a ly coiled tube, Wongwises and Polsongkram correlation has been implemented into the MARS-KS code. The geometry of the and type heat exchanger was modeled as depicted in Fig. 4 and Fig. 5, respectively. The PCTX was modeled as a single tube and the PCCT was described by two pipe components which allow internal natural circulation within the PCCT. 203 Value Specification Inner dia (di) 44.8 mm PAFS PIPE 200 PIPE 210 Outer dia (do) 50.8 mm di/d ratio (r) 0.027 Wongwises and Helix angle (α) 3.3 º Polsongkram [6] Dia. of coil (D) 1,659 mm (1) Pitch (P) 157 mm (2) 101 108 103 106 PIPE 130 Figure 4. Node diagram of tube heat exchanger 942

203 0.7 PIPE 200 PIPE 210 steam quality (x) 0.6 0.5 0.4 0.3 0.2 0.1 101 108 103 106 PIPE 130 0.0 0 1 2 3 4 5 6 7 8 9 Figure 5. Node diagram of ly coiled tube heat exchanger Figure 7. Steam quality variation ANALYSIS RESULT Fig. 6 shows the tube internal heat transfer coefficient which represents condensation heat transfer coefficient. Condensation heat transfer decrease as the flow moves toward the end of the tube for both tube types because of the decrease of quality of steam At the inlet of the tube, ly coiled tube shows 3.0% higher heat transfer coefficient comparing tube. However, as steam flows along the tube, the condensation heat transfer coefficient of ly coiled tube becomes smaller than that of the tube because more amount of steam is condensed at the inlet part so that steam quality in the ly coiled tube decreases faster than that in the tube as depicted in Fig. 7. Fig. 8 shows integrated heat removal rate along with the tube length. As indicated, in order to remove 480 kw, the length of the tube should be 8.0 m, whereas ly coiled tube requires only 6.3 m to remove same heat. This result reveals that the heat exchanger tube length can be reduced by 20% when a heat exchanger is replaced by a ly coiled heat exchanger. HTC (W/m 2 K) 35000 30000 25000 20000 15000 10000 0 2 4 6 8 Figure 6. Heat transfer coefficient variation power (W) 550000 500000 450000 400000 350000 300000 250000 200000 150000 0 1 2 3 4 5 6 7 8 9 Figure 8. Heat removal capacity according to tube length CONCLUSIONS In this paper, a feasibility study on a ly coiled heat exchanger for PAFS has been conducted. The heat transfer characteristics of the ly coiled heat exchanger have been evaluated by means of the MARS-KS analysis introducing an in-tube condensation heat transfer model for a ly coiled tube. It was found from the study that the heat transfer capacity is increased by applying a ly coiled heat exchanger so that the heat exchanger with reduced size can be implemented in order to remove the same amount of heat from a system. Further experimental and analytical investigations are needed to obtain more reliable condensation heat transfer correlation or to develop a dedicated condensation heat transfer correlation for PAFS operating condition. In addition, more studies on the effects of geometric parameters (helix angle and circle diameter to tube inner diameter ratio, so on), taking into account of pressure drop effect, of ly coiled tube are required for optimum arrangement design. 943

REFERENCES [1] B.U. Bae, et al., Design of condensation heat exchanger for the PAFS (Passive Auxiliary Feedwater System) of APR+ (Advanced Power Reactor Plus), Annals of Nuclear Energy, 46, 134 (2012). [2] B.U. Bae, et al., Validation experiment for the cooling capability of passive auxiliary feedwater system (PAFS) with PASCAL facility, Proceeding of the 20 th International Conference on Nuclear Engineering (2012). [3] Y.J. Cho, et al., Analytical studies of the heat removal capability of a passive auxiliary feedwater system (PAFS), Nuclear Engineering and Design, 248, 306 (2012). [4] Thermal Hydraulic Safety Research Department, MARS Code Manual Volume I: Code Structure, System Models, and Solution Methods, KAERI/TR-2812/2004, Korea Atomic Energy Research Institute (2009). [5] Y B. Griffith, Screening reactor steam/water piping systems for water hammer, NUREG/CR-6519 (1997). [6] S. Wongwises, M. Polsongkram, Condensation heat transfer and pressure drop of HFC-134a in a ly coiled concentric tube-in-tube heat exchanger International Journal of Heat and Mass Transfer, 49, 4386 (2006). [7] M. El-Sayed Mosaad, et al., Heat transfer and pressure drop of R-134a condensation in a coiled, double tube, Heat and Mass Transfer, 45, 1107 (2009). [8] M.M Shah, A general correlation for heat transfer during film condensation inside pipes, International Journal of Heat and Mass transfer, 22, 547 (1979). [9] L. Shao, et al., Condensation heat transfer of R-134a in straight and ly coiled tube-in-tube heat exchangers, J. Hydrodynamics, Ser. B.9,677 (2009). [10] A. Cavallini, et al., Heat transfer and pressure drop during condensation inside enhanced tube, International Journal Refrigeration, 23, 4 (2000). 944