ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Similar documents
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

R07. Answer any FIVE Questions All Questions carry equal marks *****

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)


INSTITUTE OF AERONAUTICAL ENGINEERING

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Chapter 8 Balances on Nonreactive Processes PSYCHROMETRIC CHART

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Pressure Enthalpy Charts

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

LISTOF EXPERIMENTS. S. No. NAME OF EXPERIMENTS PAGE No.

REFRIGERATION AND AIR CONDITIONING

Chapter 10. Refrigeration and Heat Pump Systems

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Chapter 14, Problem 27.

CE311 Fall 2016 Mid-Term Exam 1

Chapter 9. Refrigeration and Liquefaction

Homework Chapter2. Homework Chapter3

Department of Mechanical Engineering ME 322 Mechanical Engineering Thermodynamics

UNIT - 3 Refrigeration and Air - Conditioning

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

A/C Cooling Load calculation and measurement

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Thermodynamics II Chapter 6 Mixtures & Psychrometry

UNIT-1 Q.1 Draw P-V and T-s diagram of Reversed Carnot cycle (2M-Apr./May-2009) Q.2 Define Ton of refrigeration and COP. (2M- Nov/Dec-2009)

Mechanical Engineering Laboratory

Drying principles and general considerations

CE311 Fall 2016 Mid-Term Exam 1

SAMPLE STUDY MATERIAL

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Week 9. Refrigeration Cycles I. GENESYS Laboratory

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Use this Construction/HVAC Glossary to answer the questions below.

UNIT-III PSYCHROMETRY. Though there are many psychometric terms, yet the following are important from the subject point of view :

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

AR/IA/UP 241 Lecture 5: Psychrometrics

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Temperature. In the HVAC area, we talk about two kinds of temperatures.

II. OBJECTIVE OF RESEARCH

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Thermodynamics: Homework A Set 7 Jennifer West (2004)

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

2. CURRICULUM. Sl. No.

SECTION THIRTEEN HEATING, VENTILATION, AND AIR CONDITIONING

SSC-JE STAFF SELECTION COMMISSION MECHANICAL ENGINEERING STUDY MATERIAL REFRIGERATION CYCLES REFRIGERATION CYCLES REFRIGERATION CYCLES

1 /35 2 /35 3 /30 Total /100

PLEASE READ AND FOLLOW THESE INSTRUCTIONS

REFRIGERATION TUTOR. OBJECTIVE: To perform test on the refrigeration tutor to determine different COPs and other performance parameters.

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

ISSN Vol.08,Issue.21, November-2016, Pages:

Armstrong Cool-Fog Systems

ω = (1) Kirby S. Chapman Ph.D.

Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Thermo-physical properties found on most psychrometric charts

HVAC (Heating, Ventilating, and Air Conditioning)

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Last exam / sista tent

(Refer Slide Time: 00:00:40 min)

Performance investigation of Air-conditioning system using ejector as expansion device

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Heat pump and energy recovery systems

Numerical Simulation of Window Air Conditioner

Air Conditioning Clinic

Compendium DES July 2016, CARN

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Air Conditioning and Refrigeration Laboratory

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

SIR C.R.REDDY COLLEGE OF ENGINEERING, ELURU DEPARTMENT OF MECHANICAL ENGINEERING ETD-II. Model Short Answer Questions And Answers

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

GRAPSI_DRAW DIGITAL PSYCHROMETRIC CHART

Transcription:

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes which are heating, cooling, humidification and dehumidification in an air conditioning unit. The air velocity, dry and wet bulb temperatures and water added/removed will be measured to check the mass and energy balances of these processes. 2. I TRODUCTIO The purpose of air conditioning equipment is to change the state of the entering air to a desired state by controlling temperature and humidity of the specified space. Air conditioning applications are divided into two types according to their purposes: i) Comfort air conditioning, ii) Industrial air conditioning. The primary function of the air conditioning is to modify the state of the air for human comfort. The industrial air conditioning meets the temperature and humidity requirements of an industrial or scientific process. In comfort air conditioning, it is necessary to control simultaneously the temperature, relative humidity, cleanliness and distribution of air to meet the comfort requirements of the occupants. According to the comfort chart as given by ASHRAE (American Society of Heating, Refrigeration and Air-conditioning Engineers), comfort condition can be obtained at 20-23 C DBT (dry bulb temperature) and (50± 20) % relative humidity in winter, and 24-27 C DBT and (50± 20) % relative humidity in summer. In order to maintain these levels, the state of air is modified at an air conditioning apparatus such that varying summer and winter loads are balanced. 3. THEORY In air conditioning, the moist air (or simply the air) is taken as a mixture of dry air (a) and water vapor (w) carried with it. At a given total air pressure and temperature, the amount of water vapor that may be in the air is limited. The mixture existing at this limit is called saturated air. If there is any excess water in the air, it separates itself from the mixture as a liquid (condensate) or solid (ice). 1

The dry bulb temperature (T db ) is the familiar temperature that can be measured by a thermometer or a thermocouple. On the other hand, the wet bulb temperature (T wb ), is related to humidity level. The humidity of moist air may be stated in either relative humidity, f or humidity ratio, w. The psychrometric charts are diagrams giving the relationship between T db, T wb, f, w and h by assuming an ambient pressure. For example, ASHRAE chart no. 5 is for 750 m. elevation (92.634 kpa barometric pressure) which may be used for Ankara (see Fig. 6). Many psychrometric processes may be represented on these charts by straight lines. Wet Bulb Temperature (T wb ) is the temperature measured when the bulb of a thermometer or the junction of a thermocouple is wetted. For unsaturated moist air, it is less than the dry bulb temperature; the difference being proportional to the relative humidity. In practice T wb is assumed to be equal to the adiabatic saturation temperature, T*, which would be reached if moisture is added in an adiabatic process until the air becomes saturated. Thus, T wb ~T*. Relative Humidity (Φ)and Humidity Ratio (w) is defined as, (1) where P w = Partial pressure of water vapor in air P ws = Saturation pressure of water at air temperature T This is a dimensionless quantity usually expressed as percentage. The humidity ratio (also called specific humidity), w, is defined as (2) where m w = mass of water vapor in moist air m a = mass of dry air Using the ideal gas relationship for dry air and water vapor gives (3) The humidity ratio of air at a given P and T may be calculated from these relationships when T * is known: (4) where 2

and T, T * = Dry and wet bulb temperatures ( C), h * f = Specific enthalpy of liquid water at T * (kj/kg w ) h g = specific enthalpy of water vapor at T (kj/kg w ) h * fg = (h g -h f ) at T* (kj/kg w ) P * ws = saturation pressure of water evaluated at T * (kpa) c pa = Constant pressure specific heat of dry air (1.0035 kj/kg a ) Note that * indicates properties which are evaluated at the adiabatic saturation (that is wet bulb) temperature T *. Enthalpy(h) The enthalpy of the moist air at any state can be read from psychrometric charts or can be calculated as : (5) Sensible Heating or Cooling (Q s ) The sensible heat transfer process is one where only energy is added or removed from the moist air. The dry and wet bulb temperatures, relative humidity change as a result of heat transfer, but there is no change in water vapor content or humidity ratio of the air.(see fig.1.) Fig. 1 Sensible Heating and Cooling Humidification or Dehumidification The process of adding water vapor to the air is called humidification. Humidification increases the humidity ratio, relative humidity, wet bulb temperature and the enthalpy, but the dry bulb temperature may slightly change or remains unchanged. The reverse process, which decreases the humidity ratio is called dehumidification. It may be achieved by absorbing the moisture at constant temperature by a descicant (see fig.2) or by cooling the moist air below its dew point temperature (see fig.3.) by using refrigeration. 3

Combined Heating and Humidification, or Cooling and Dehumidification The following combined sensible and latent process, shown in figure 3 may occur in air conditioning : 1-6 : Heating and humidification ( common in winter) 1-7 : Heating and dehumidification (with a descicant) 1-8 : Cooling and humidification (as in air washers) 1-9 : Cooling and dehumidification (common in summer) 1-9 : Cooling and dehumidification (theoretical) In figure 3, process 1-9 is actual whereas process 1-9 is theoretical. Fig. 2 Humidification and dehumidification concepts Fig. 3 Combined Processes Mass and Energy Balances At steady state, the following relations can be obtained from the mass and energy balances for a general process as shown in figure 4. Fig. 4 General Control Volume 4

The continuity equation gives : Continuity for dry air Continuity for water vapor (6) (7) The first law of thermodynamics gives (8) where & m w h w zero during sensible heating or cooling = condensate removed during dehumidification (-) water vapor injected during humidification (+) = h f at T 2 for dehumidification o h g at water vapor temperature (96 C) for humidification Q & = Rate of heat transfer, (+) for heating, (-) for cooling Note that water boils at about 96 o C at Ankara. The percentage error between the measured and theoretical values can be found by: Theoretical Value Measured Value Percentage Error= 100% (9) Theoretical Value Refrigeration Cycle Cooling the moist air with or without dehumidification is usually achieved by using a mechanical refrigeration cycle which includes a compressor, a condenser, an expansion valve(or capillary tube for small systems) and an evaporator. Fig. 5 Refrigeration Cycle In the laboratory unit, the compressor is reciprocating type run by an electrical motor which also runs the fan of the air cooled condenser. Figure 5 is the P-h chart for the 5

refrigerant, R-12. Figure shows the equipment schematics as well as P-h and T-s diagrams of a typical cycle. In reality, the compression process will be irreversible and there will be pressure losses through the evaporator, the condenser and the connecting pipes. The isentropic efficiency of the compressor is defined as: (10) The parameters that are important include the compressor discharge temperature (T 2 ), cooling capacity, power input and coefficient of performance of the cycle which may be defined as : (11) Because of the irreversibility of the expansion valve and also other parts, this COP becomes less than the ideal value of a reversible (Carnot) cycle, (12) 4. Experimental Setup The schematic layout of the set-up is shown in figure 7. Main parts of the setup are as follows : i. Preheaters : Three electrical heaters to heat the air entering ii. Boiler : To supply steam for humidifier. It is composed of a stainless steel container and three electrical heaters, which are dipped into the water iii. Cooling Coil : To cool the air with or without dehumidification iv. Rotating vane anemometer : To measure air flow rate in feet per minute v. Reheaters : Two electrical heaters after the cooling coil which reheats the cooled air before delivery to the space, if required vi. Compressor-Condenser unit : To complete the refrigeration cycle vii. Fan : For air circulation viii. Thermocouples and thermometers : For measuring dry and wet bulb temperatures 6

PROCEDURE : Before the Experiment: Check all the thermocouples and thermometers, they should show the same dry bulb and wet bulb temperatures at all locations. Start the boiler and wait until the thermometer shows 96 C. Then turn OFF the power to the boiler, to be restarted for humidification. During the Experiment: Turn the fan ON and note down the air flow. Use heating, cooling, humidification and dehumidification as required. Make the necessary measurements and note them down on the enclosed Data Sheet. At least 10-15 minutes should pass to reach a steady state after any modification on the operation is made. Measurement steps during the experiment: Start your alarm clock, to measure the condensed water and water level change in the boiler (5 Min). During this 5 min. duration, read the wet bulb and dry bulb temperature values for each state, read the temperature values related with the refrigeration cycle, read the pressure values related with the refrigeration cycle. After 5 min measure the amount of the collected condensed water and boiler level. Measure the air velocity. After the Experiment: (1) Plot the process lines on psychrometric chart. (2) Estimate the T wb at section 4, based on state 5 and the processes between states 4 and 5 (Hint: use psychrometric chart). (3) Find h, f and w from chart and from equations (1) to (5). Compare the results. (4) Make necessary calculations for a, theoretical energy and mass changes with measured ones. w and Q & at each section. Compare the (5) Draw the refrigeration (R-12) cycle on the P-h diagram provided and estimate power input to the compressor, (W c ) refrigerant flow rate ( ), isentropic efficiency(h c ) and COP. r 7

RESULTS A D DISCUSSIO S Questions For Further Discussion: i. Why using the sea level psychrometric chart for Ankara is incorrect? Estimate the error in humidity ratio and enthalpy at some selected moist air states. ii. Estimate the heat lost or gained from the duct surfaces. Will the emission of this cause significant errors in energy balances? (U sur = 1.7 W/m 2 C) (O LY FOR LO G REPORT) Section Preheater Evaporator Reheater Total Lateral Area (m 2 ) 0.72 0.6 2.28 6 iii. Comment on taking electrical heaters consumption as constant. Estimate the variation in electrical energy supplied to these heaters if the resistance is known within ± 20%, and voltage varies within ± 5%. (O LY FOR LO G REPORT) 8

Fan Compressor condenser unit Reheaters (3.6 kw) Mixer 5 Evaporator Mixer Liquid Receiver Drier T.E.V. 3 Condensate PreHeaters (2.88 kw) Steam Injection SCHEMATIC DRAWI G OF EXPERIME TAL SETUP 9 4 Rotating vane anemometer Discharge 1.44 kw 2.5 kw Boiler 2 Mixer d 1 1.44 kw Feed Water Inlet

ME 410 EXPERIMENT 3 Mass & Energy Balances in Psychrometric Processes DATA SHEET Lab Group : Date: AMBIENT Pressure 92 kpa Temperature mv (11th T.C) AIR FLOW (ft/min) Preheaters: 0.72 kw each (x3) Duct Area: 0.0875 m² Reheaters: 0.72 kw each (x2) Boiler Cross Section: 0.3 m x 0.4 m Temperature Section Dry Bulb Wet Bulb TC Readings at Section 4 (Dry-bulb) TC No. (mv) TC No. (mv) TC No. (mv) TC No. (mv) 1 & 2 1 2 9 14 3 3 4 10 15 5 7 8 12 16 13 18 Tavg Energy Input at Preheaters Energy Input at Reheaters ENERGY VALUES kw kw High side pressure of compressor Low side pressure of compressor Temperature at condenser inlet Temperature at evaporator outlet REFRIGERATION CYCLE Psi (Red Gage) Psi (Blue Gage) mv (20th TC) mv (21st TC) Measurement Time Change in boiler level Amount of condensate WATER MEASUREMNTS min mm ml Conversion Factors: 1 Psi =6.895 kpa 1 ft/min 0.00508 m/s T ( C) 23.46xT(mV) + 2.35 10

ME 410 EXPERIMENT 3 OUTLINE FOR RESULTS Table-1 Enthalpy (h), humidity ratio (w) and relative humidity (Φ) values for each section Section T db T wb From Chart From Equations Deviations ( % ) ( o C ) ( o C ) h (kj/kg) w (gr/kg) Φ (%) h (kj/kg) w (gr/kg) Φ (%) h w Φ 1 & 2 3 4 5 Table-2 Results of energy and mass balance calculations States 2 & 3 3 & 4 Process Preheating+ Humidification Cooling+ Dehumidification Measured Values Theoretical Values % Deviations Q & m (kw) w (kg/s) Q & m (kw) w (kg/s) Q & m w 4 & 5 Reheating air :.. kg/s ref :.. kg/s W & c :.. kw η :.. COP :.. 11