TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

Similar documents
TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

TraceNet TM TCM2 CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE

TRACENET TM TN SERIES

TraceNet ECM Series Control System

CONTROL AND MONITORIN

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

HTC-915-CONT. Heat-Trace Control system

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

TRACENET TM GENESIS. Installation, Operation & Maintenance Guide CONTROL AND MONITORING SYSTEM

920 Series. A dry contact relay is provided for alarm annunciation back to a distributed control system (DCS).

Dual-point heat-tracing control system

910 Series Single-point heat-tracing control system

NGC-40 Advanced Heat-Tracing Control System

RAYCHEM NGC-30 COMPONENTS

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

Heating Cable. Description

Temperature Controllers

ACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM PRODUCT OVERVIEW. ACS-30 System

TraceNet TC Series Control System

Heating Cable. Description

C910 Series. Single-point heat-tracing control system

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM PRODUCT OVERVIEW

Variable Frequency Drive SERIES MP800 VFD

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM. product overview

02/11/2015

02/11/2015

NXM2G Installation and Operating Manual

Across-the-Line SERIES MP300 Combined Manual and Automatic

DGC-500 DIGITAL GENSET CONTROLLER

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

Series Temperature Controller Instruction Sheet

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Sitron s CF Line of Flow Switch Monitors

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Two-Channel Gas Controller

Model A2100 Series Annunciator

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Soft Start Series MP700 Solid State, Reduced Voltage

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Electric Heat Tracing INSTALLATION, MAINTENANCE, & TROUBLESHOOTING

ITAS / ITAS-EXT / ITLS / ITLS-EXT

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Moulded case circuit brakers

Process & TeMPerATUre UniversAl input DigiTAl MeTers

ITC 1 & 2 Circuit Heat Trace Controller Line or Ambient Sensing

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

UDC100 Universal Digital Controller Specifications

Nov 08 PRODUCT SPECIFICATION SHEET

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

ITC 1 & 2 Circuit Heat Trace Controller Line or Ambient Sensing

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

1.7. Insulation fault evaluators EDS460/490 EDS461/491

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

Intelligent addressable fire alarm control panel

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Model A1700 Series Annunciator

I/A Series 716C 1/16 DIN Temperature Controller

Frequently asked questions: Intelligent Transmitter Series

POCKET GUIDE 2011 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS

Engineering Guideline. pac- Carriers Type Universal

Oakton TEMP 9500 Advanced Multiparameter Controller

DGC-1000 DIGITAL GENSET CONTROLLER

Series Digital Controller Instruction Sheet

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

BC3250. Blowdown Controller

Intelligent Single Loop Fire Alarm Control Panel

OMC Ex interface unit. Manual. Version 1.2 August Author: Observator Instruments

Series 155. Mass Flow Computers TECHNICAL SPECIFICATIONS

UDC 700 Universal Digital Controllers and Indicator Specifications

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

DigiTrace NGC-family

FireNET Plus Wiring Instructions

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

LC2200 Level Controller Installation and Maintenance Instructions

Intelligent 2 & 4 Loop Fire Alarm Control Panels

NGC-20-C-E and NGC-20-CL-E

Gas Controller Module GC-06

ECO N DATE DESCRIPTION OF CHANGE CHG

Advanced Autoclave Controller with Recording + 4 Channel Mapping + Pressure Indication with PC Software & Printer Module

EMS510 PS-1 COMPLIANT OPACITY/DUST MONITOR

Insulation fault evaluator EDS460-DG

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform

ACCS-30. Multipoint commercial heat-tracing control system

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

Carbon Monoxide Transmitter

1.7. Insulation fault evaluators EDS460/490 EDS461/491

ACCURATE ELECTRONICS INC

Transcription:

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to maintaining critical process temperatures. While mechanical thermostats have been used successfully for many heat tracing applications, a more complete control and monitoring solution is necessary for most industrial heat tracing applications. Advancements in microprocessor-based technology have made electronic control and monitoring units both cost effective and reliable. Electronic control and monitoring systems ensure accurate temperature measurements, conserve energy and extend system life. A versatile electric heat tracing control and monitoring network is key to reducing operating cost in plants. Research has shown that the following features are a prerequisite within many industrial heat tracing applications 1 : Monitor electric heat trace circuit operating and ground/earth leakage currents Selectable control method (On/Off, On/ Off With Soft Starr, Proportional, Ambient Proportional) on a per circuit basis Programmable alarm set points, with alarm acknowledgment and reset capability Programmable trip set-points for each circuit Temperature sensor status indication Unique circuit identifier Communication to host computer via RS485 serial communication. Push to Test ground/earth leakage test feature on a per circuit basis Ground/earth leakage interruption capability Note: 1. For equipment in explosive atmospheres, to avoid elctrostatic discharge, clean the viewing window with a damp cloth only. If the equipment is not installed and operated within the specifications and limitations indicated by Thermon, then the protection provided by the equipment may be voided. TCM18 PANEL CERTIFICATIONS/APPROVALS TraceNet systems are approved/certified for installation and operation in ordinary and Zone 2 hazardous (classified) locations. TRACENET TCM18 SYSTEM SPECIFICATIONS Environmental: Hazardous Locations, Indoor and Outdoor - Solid State Relays Ordinary Locations, Indoor and Outdoor - Power Distribution and Mechanical Relays and/or Solid State Relays Operating Ambient Range: -40 C to 55 C Enclosures: IP54 TraceNet Supply Voltage: 100-240 Vac, 50/60 Hz Heat Tracing Voltages: 100-600 Vac User Interface: 44mm x 127mm backlit LCD display Maximum Number of Circuits: 72 within one TC series control panel Temperature Sensors per Circuit: One or Two 100 W Platinum, 3-wire RTD's Current Switching Devices: Solid State Relay * : 1-pole up to 30 Amps 2-pole up to 15 Amps per pole Mechanical Relay: Per design requirements Control Methods: Process Sensing: On/Off, On/Off With Soft Start, Proportional Ambient Sensing: On/Off, On/Off With Soft Start, Ambient Proportional (APC) Control Temperature Range: -129 C to 600 C Alarm Settings (per circuit): Low/High Temperature Low/High Current High Ground/Earth Leakage Current RTD and Relay Faults Loss of Communication Secondary Alarm Settings (with trip option): High Temperature, High Heater Current, Ground / Earth Leakage Current Networking Communications: Dual RS 485 Ethernet/Bluetooth/Wireless (requires optional communication module) Auxiliary Output Power: 24 Vdc at 0.5 Amp External Alarm Relays: Three, sealed dry contacts rated @ 0.4 Amp, 24 Vdc Two, solid state rated at 350 ma (24 Vdc) per PM6 * Additional panel types are available. Contact Thermon for details. ** Rating based on heat sinks installed external to panel. Relay ratings have a reduced rating when sinks are used internal to panel. Multiple single pole relays may be used for phase to phase and three phase circuits. Higher voltage rating relays are also available as an option. FMG 12.0018x Ex nac IIC T4 II 3 G Ex nac IIC T4 FM13ATEX0073X 1

SPECIFICATION GUIDE Typical Thermon TraceNet TM TCM18 System (See Page Numbers Listed Below for Additional Information on Each Component) TCM18 (p 3) PM6 (p 4) THERMON The Heat Tracing Specialists 2

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM TCM18 CONTROL AND MONITORING MODULE The TCM18 is a multicircuit microprocessor-based temperature control and monitoring module developed specifically for heat tracing. This module provides control and monitoring capabilities via digital information display for a maximum of eighteen heat trace circuits. This module can be configured for either process sensing control (with either one or two RTD inputs for each circuit) and/or ambient sensing control (with the option of one or two RTD inputs). TCM18 COMMUNICATION The TCM18 has two RS485 ports which communicate via Modbus ASCII or RTU protocol. One port can communicate to TraceView Network Explorer or to compatible DCS system. The second port is provided for an auxiliary RS485 communication to an optional Ethernet or wireless communication module. The TCM18 provides circuit information and programming capability through the LCD digital display and a dedicated touchpad on the front of each module. TCM18 RATINGS/SPECIFICATIONS Control and monitoring capacity...18 heat tracing circuits Nominal module supply voltage...120-240 Vac 50/60Hz Input current...1.5 Amp max. Power consumption... 70 watts Mimimum ambient temperature... -40 C Storage ambient temperature... -40 C to 85 C Data retention...non-volatile EEPROM Power clamp function... programmable from 20% to 100% Temperature input..up to 36 3-wire platinum 100 Ω RTDs Temperature control range... -129 C to 600 C Control band... programmable in increments of 1 degree High operating current alarm and trips..0.1 to 100 Amps Low operating current alarm...0.1 to 100 Amps Ground leakage alarm and trips...20 to 225 ma (in 1 ma increments) Alarm relays Three sealed dry contacts, rated @ 0.4-amps resistive at 24 Vdc/Vac Auxiliary output power... 24 Vdc at 0.5 Amps Self-test frequency... programmable from 2 to 99 hours Communication... Modbus ASCII/RTU via Dual RS 485 ports Communication rate... up to 57600 Baud Certifications...ATEX Pollution category...2 TCM18 CONNECTION PORTS TCM18 PRODUCT FEATURES Module operates in a wide range of ambient conditions. Each heat tracing circuit allows input from single or dual RTD inputs. User friendly four line heated LCD display for circuit and alarm information with input from a dedicated touchpad. Conformally coated electronics for use in panels in indoor and outdoor locations. Low and high temperature alarm and additional programmable high temperature trip functions. Low and high heater current alarm and trip functions. High ground/earth leakage current alarm and trip functions Internal test functions for ground/earth leakage functionality. Includes On-Off, On-Off with Soft Start, Proportional, and APC (Ambient Proportional Control) modes. Auxiliary 24 Vdc output for powering optional communication modules or other auxiliary devices. Equipment has been evaluated and found suitable for Overvoltage Category II over the stated range of module supply voltage, in accordance with IEC-61010-1:2010. TCM18 DIMENSIONAL DATA Auxiliary Power Out External Fuse Auxilary Input/Remote Acknowledge 190 mm 114 mm Power Input Alarm Output Terminals PM6/RM6 Input Cable Ports RTB6 Input Cable Ports RS485 Ports 482 mm 3

SPECIFICATION GUIDE PM6 POWER MODULE The PM6 serves as the power switching module, using solid state relays and links the heat tracing power circuit to the TCM18 control and monitoring module via ribbon cable. PM6 DIMENSIONAL DATA 41 mm PM6 PRODUCT FEATURES Operates in a wide range of ambient conditions. Single or dual pole solid state switching. Nickel plated terminal construction. Black anodized aluminum heat sink capable of dissipating the heat generated for up to a total of 180 Amps continuous. Standardly supplied with polycarbonate touch safe cover for increased operator touch safety. Includes a ground/earth leakage circuit test loop which allows the operator to conduct a functionality test on each circuit. Measures ground/earth leakage and heater operating currents. 483 mm External Panel Mount 483 mm Internal Panel Mount 105 mm 267 mm 70 mm 105 mm 25 mm 328 mm PM6 COMPONENT SPECIFICATIONS Circuit control capacity...up to six heat trace circuits Single pole relay switching capacity...30 Amps at 240 Vac* Dual pole relay switching capacity...15 Amps at 240 Vac* Relay power connection... 40-Pin header ribbon cable Ground/earth leakage test connection... 10-Pin header ribbon cable Maximum storage temperature... 85 C Minimum storage temperature... -40 C Oper. ambient temp. range... -40 C to 70 C Power terminal connections... 0.5 to 10mm 2, 630Vac Printed circuit board... conformally coated Alarm...two 24 Vdc @ 350 ma each * Rating based on heat sinks installed external to panel. Relay ratings have a reduced rating when sinks are used internal to panel. Higher voltage rating relays are also available as an option. PM6 CONNECTION DIAGRAM Ground/Earth Leakage Current Transformer Operating Heater Current Transformer 10-Pin Ribbon Cable Connector 40-Pin Ribbon Cable Connector Solid State Relay Input AC Voltage Output AC Voltage to Heater 24 Vdc Alarm Output THERMON The Heat Tracing Specialists 4

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM RTB6 RTD INTERFACE MODULE The RTB6 is a DIN rail mountable six RTD sensor input module which links the field RTD wiring to the TCM18 control and monitoring module via ribbon cable. RTB6 DIMENSIONAL DATA 41 mm 127 mm 7 7 mm RTB6 PRODUCT FEATURES Operates in a wide range of ambient conditions. DIN rail mountable. Conformally coated printed circuit board for use in panels located in indoor and outdoor environments. RTB6 CONNECTION DIAGRAM 26-Pin Ribbon Cable Connector RTB6 COMPONENT SPECIFICATIONS Maximum storage temperature...85 C Minimum storage temperature...-40 C Oper. ambient temp. range...-40 C to 70 C Terminal connections...up to 2.5 mm 2 Maximum RTD capacity... 6 RTD Inputs 5

SPECIFICATION GUIDE RM6 RELAY INTERFACE MODULE The RM6 is a DIN rail mountable six circuit relay interface module for linking individual solid state or mechanical relays via ribbon cable to the TCM18 module. The RM6 comes with individual terminal strips which allow the interconnection of individually mounted ground/ earth leakage and heater operating current sensing transformers as well as the ground/earth leakage circuit fault test loop. RM6 DIMENSIONAL DATA 127 mm 77 mm RM6 PRODUCT FEATURES Operates in a wide range of ambient conditions. DIN rail mountable. Conformally coated printed circuit board for use in panels located in indoor and outdoor environments. 52 mm RM6 COMPONENT SPECIFICATIONS Maximum storage temperature... 85 C Minimum storage temperature... -40 C Oper. ambient temp. range... -40 C to 70 C Terminal connections... up to 2. 5 mm 2 Earth leakage test connection...10-pin header ribbon cable Relay connection...40-pin header ribbon cable RM6 CONNECTION DIAGRAM 40-Pin Ribbon Cable Connector 10-Pin Ribbon Cable Connector 24Vdc Alarm Output Heater Operating Current Transformer Connections Ground/Earth Leakage Current Transformer Connections 24 Vdc Input Ground/Earth Leakage Circuit Functionality Test Connections Relay Control Voltage THERMON The Heat Tracing Specialists 6

TRACENET TVNE The TCM18 communicates via Modbus RTU or ASCII protocol through its RS485 ports at programmable rates up to 57600 Baud to the Thermon TVNE electric tracing circuit monitoring software. TVNE provides centralized electric tracing information such as: Heat tracing circuit status Temperatures, heater operating and earth/ground current alarm/trip events Event history Data trending Maintenance and troubleshooting guidance TVNE additionally provides the operator the ability to: Change set points as well as alarm and trip values Reconfigure system control parameters Provide heat tracing management reports Load shed circuits on a priority level basis View up to ten (10) files (.dwg or.pdf) for isometric drawings, sketches, and/or identifying photos as well as operator notes fore each controller circuit. DCS COMMUNICATIONS The TCM18 can also communicate via Modbus RTU or ASCII protocol through its RS485 ports at programmable rates up to 57600 Baud to the plant DCS. The same operating data and control capabilities that are available through TVNE are also accessible in the plant control room at the DCS.

PRODUCT REFERENCE LEGEND TCM - 1836YU - SSD - 120S130 - H2 - ND - P/N TraceNet TC Series 1 Monitoring and Control Module(s) M = Standard Control Module MN = Nuclear Control Module Heat Trace Circuits 18 36 54 72 RTD Inputs 18 36 54 72 108 144 Panels A = Ambient Sensing Panels Only P = Process Sensing Panels Only Y = Ambient and Process Sensing Panels Distribution ND = No Distribution MBx/BF y/z = Main Breaker/Breaker Frame/Number of Breakers Amperage Rating for Relays Heat Trace Relays S1 = Solid State Single Pole S2 = Solid State Two Pole M1 = Mechanical Single Pole M2 = Mechanical Double Pole Thermon Part Number Location O = Ordinary Locations H2 = Ex Explosive Atmospheres Alarm Relays U = 24 Vdc/Vac @ 0.5 Amps Rated for Ordinary and Ex Explosive Atmospheres Enclosure Type SS = Stainless Steel Type 4X/IP54 PS = Painted Steel Type 4/IP54 SSP = Stainless Steel Type 4X/IP54 (with purge) PSP = Painted Steel Type 4/IP54 (with purge) X = Custom 2 Notes: 1. Other accessory modules from the TraceNet TN Series, such as the TSM1/TSM1L and PS70, may be available for use in TC Series panels. Contact the manufacturer for details. 2. Contact Thermon for additional information. Enclosure Size mm H x mm W x mm D A = 914 x 762 x 406 B = 1219 x 914 x 406 C = 1524 x 914 x 406 D = 1524 x 914 x 610 E = 1524 x 1219 x 610 F = 1829 x 914 x 406 G = 1829 x 914 x 610 H = 1829 x 1524 x 610 I = 1829 x 1829 x 610 X = Custom 2 Trace Heater Voltages 100 Vac 120 Vac 200 Vac 208 Vac 220 Vac 230 Vac 240 Vac 277 Vac 480 Vac 600 Vac

European Headquarters Boezemweg 25 PO Box 205 2640 AE Pijnacker The Netherlands Phone: +31 (0) 15-36 15 370 Corporate Headquarters 100 Thermon Dr. PO Box 609 San Marcos, TX 78667-0609 USA Phone: +1 512-396-5801 Form TEP0131U-0118 Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.