The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Similar documents
Low Global Warming Refrigerants For Commercial Refrigeration Systems

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Study of R161 Refrigerant for Residential Airconditioning

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Low GWP Refrigerants for Air Conditioning Applications

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Theoretical analysis of low GWP mixture R600a/ R1234ze as a possible alternative to R600a in domestic refrigerators

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Refrigerant Glide and Effect on Performances Declaration

Air-Cooled Heat Exchanger Performance for R410A

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Investigation of Evaporator Performance with and without Liquid Overfeeding

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Performance Measurement of R32 Vapor Injection Heat Pump System

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Purdue e-pubs. Purdue University

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Developments of next generation refrigerants and heat transfer

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Local Heat Transfer Characteristics of the R1234ze(E) Two Phase Flow Inside a Plate Heat Exchanger

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

*Corresponding author;

Experimental Assessment on Performance of a Heat Pump Cycle Using R32/R1234yf and R744/ R32/R1234yf

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance of CO2 Cycles with a Two-Stage Compressor

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Efficiency of Non-Azeotropic Refrigerant Cycle

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Effect of magnetic field on the performance of new refrigerant mixtures

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

POTENTIAL OF NON - AZEOTROPIC REFRIGERANT MIXTURE AS WORKING REFRIGERANT IN HOT WATER HEAT PUMPS. FJ Smit and JP Meyer

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

R32 Compressor for Air conditioning and Refrigeration applications in China

(Refer Slide Time: 00:00:40 min)

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Experimental Study on the Performance of Twisted Capillary Tube

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

The Development of the Energy-Saving Technology by the Composition Control of R407C

Dynamic Simulation of Liquid Chillers

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

A RECENT REVIEW OF REFRIGERANT R-1234YF AND R-1234ZE (E)

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Evaluation of HCFC Alternative Refrigerants

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/ in a Heat Pump Cycle Sho Fukuda fukuda@phase.cm.kyushu-u.ac.jp Nobuo Takata Shigeru Koyama Follow this and additional works at: http://docs.lib.purdue.edu/iracc Fukuda, Sho; Takata, Nobuo; and Koyama, Shigeru, "The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/ in a Heat Pump Cycle" (2012). International Refrigeration and Air Conditioning Conference. Paper 1221. http://docs.lib.purdue.edu/iracc/1221 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2229, Page 1 The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/ in a Heat Pump Cycle Sho FUKUDA 1 *, Nobuo TAKATA 1, and Shigeru KOYAMA 2 1 Interdisciplinary Graduate School of Engineering Sciences, Kyushu University Kasuga, Fukuoka, 816-8580, Japan Phone: +81-92-583-7840, Fax: +81-92-583-7833, E-mail: fukuda@phase.cm.kyushu-u.ac.jp 2 Faculty of Engineering Sciences, Kyushu University Kasuga, Fukuoka, 816-8580, Japan Phone: +81-92-583-7831, Fax: +81-92-583-7833, E-mail: koyama@cm.kyushu-u.ac.jp ABSTRACT This study presents an experimental investigation of the circulation composition in a heat pump cycle for considering the effect of its difference from the charged composition on the cycle performance prediction. The experiment was conducted with a vapor compression heat pump cycle using a compressor developed for. The tested refrigerants are R1234ze(E)/ (20/80 mass%),r1234ze(e)/ (50/50 mass%), and R1234ze(E)/ (80/20 mass%). Compared with the charged composition, the measured mass fraction of the more volatile component R1234ze(E)increases at inlet of the expansion valve. When the difference between vapor and liquid composition is large in the two-phase flow, the difference between circulation and changed composition is large enough to affect the COP evaluation. The circulation composition depends on the velocity ratio of vapor and liquid, the operating pressure of heat pump cycle, and the degree of subcool at condenser outlet. 1. INTRODUCTION Hydro-fluorocarbons (HFCs) are widely used as refrigerants in air-conditioning and refrigeration systems. At the 1997 Kyoto Conference (COP3), it was determined that the product and use of HFCs should be regulated due to their high global warming potential (GWP). In the above mentioned situation for the air-conditioning and refrigeration systems, recently, R1234ze(E) is nominated as one of the alternates of HFCs, due to its extremely low- GWP. The heating capacity of heat pump cycles using R1234ze(E) is, however, expected to be lower than that of currently most used, because of its lower vapor density and latent heat. To achieve performance equal to, much larger unit is required. In the previous studies (Koyama et al,, 2010b, 2011), drop-in experiments on heat pump cycle using mixtures of R1234ze(E)/ was carried out; was selected as the second component to increase vapor density and latent heat. It was found that mixtures of R1234ze(E)/ were strong candidates for replacing. The mixtures of R1234ze(E)/ are zeotropic and have a temperature change during the phase-change, typically called temperature glide. When the temperature glide is utilized effectively, the irreversible loss or exergy loss in heat exchangers is reduced and the cycle performance is improved (e.g., Jakobs and Kruse, 1978, Kruse, 1981, McLinden and Radermacher, 1987, Swinney et al., 1998). The temperature glide is determined by the composition and pressure of refrigerant mixture. The circulation composition is often different from the composition of charged refrigerant, because the more volatile component can circulate faster in cycles (Youbi-Idrissi et al., 2005). This means that the actual refrigerant temperature in condensers and evaporators can shift from the temperature predicted with the charged composition (i.e., nominal composition). Therefore, for predicting the cycle performance precisely, understanding the shift of circulation composition in an operating cycle from charged composition.

2229, Page 2 The present study experimentally evaluates COP with various compositions of the mixtures in a cycle to find the optimized composition of mixtures R1234ze(E)/ as low-gwp alternatives for residential or commercial heat pump systems. Additionally, the circulation composition is compared to the charged composition to clarify the effect of this difference on the cycle performance evaluation. 2. EXPERIMENTAL SETUP AND METHOD 2.1 Experimental Setup Figure 1 shows an experimental apparatus, which is a water heat source vapor compression cycle. The experimental apparatus consists of three loops of refrigerant, and cooling and heating water. The refrigerant loop is composed of a manually controlled hermetic type rotary compressor, an oil separator, a condenser, a liquid receiver, a solenoid expansion valve and an evaporator. Using constant-temperature bathes, certain temperature cooling and heating water are supplied to the condenser and the evaporator. Four mixing chambers are installed between each component in the refrigerant loop for measuring the pressure and the bulk mean temperature of refrigerant. The other four mixing chambers are installed in water loops for measuring bulk mean temperatures of water. The dimensions of the condenser and the evaporator are specified in Table 1. Those heat exchangers are both 7200 mm long counter flow double-tube type coils. The refrigerant flows in the inner micro-fin tube, while the water simulating cooling or heating load flows the annulus. Circulating subcooled liquid is sampled at the inlet of expansion valve and the mass fractions of each component are measured by the gas chromatography. 2.2 Experimental Method 2.2.1 Test conditions: Table 2 lists the experimental conditions at heating and cooling modes. The degree of superheat at evaporator outlet is fixed at 3 K for entire experimental conditions. For heating mode, water Figure1: Schematic view of experimental apparatus Table 1: Specifications of the heat exchangers Outside diameter [mm] Inside diameter [mm] Length [mm] Type of tube Condenser Outer tube 15.88 13.88 7200 Smooth tube Inner tube 9.53 7.53 7200 Micro-fin tube Evaporator Outer tube 15.88 13.88 7200 Smooth tube Inner tube 9.53 7.53 7200 Micro-fin tube

2229, Page 3 temperatures are fixed as follows. At condenser inlet and outlet, they are kept at 20 C and 45 C, respectively. At evaporator inlet and outlet, they are kept at 15 C and 9 C, respectively. Only the water flow rate is varied for changing the heating load from 1.6 kw to 2.8 kw. Similarly, for cooling mode, water temperatures at condenser inlet and outlet are kept at 30 to 45 C, respectively, and water temperatures at evaporator inlet and outlet are kept at 20 C and 10 C, respectively. In this mode, the cooling load ranges from 1.4 kw to 2.4 kw. 2.2.2 Test refrigerants: Table 3 compares properties of the test refrigerants R1234ze(E)/, and. The components ratio of R1234ze(E)/ is tested at 80/20 mass%, 50/50 mass% and 20/80 mass%. Each refrigerant charge is optimized at the point where COP takes a maximum. Using REFPROP Ver. 9 (Lemmon et al., 2010), properties of,, R1234ze(E)/ are calculated. The mixing parameters used in REFPROP Ver. 9 are optimized from the experimental phase equilibria data (Koyama et al., 2010a) in this study. 2.2.3 Test procedure: The rotation speed of the compressor and the open angle of the solenoid expansion valve are manually controlled with monitoring the heating or cooling load and the degree of superheat at the evaporator outlet. The measured values are recorded every second for 3 minutes at the steady state. Measured points are as follows: (1) input powers to the inverter and the compressor (2) refrigerant bulk mean temperature and pressure at each mixing chamber and refrigerant mass flow rate (3) water bulk mean temperature at each mixing chamber and water volumetric flow rate The uncertainties of temperature and pressure sensors are 0.05 K and 5.5/2.2 kpa (condenser/evaporator). The uncertainties of refrigerant and water flow rates are 0.47 kg/h and 1.5 L/h, respectively. 2.2.4 Measurement procedure of compositions: Preliminarily mixed liquid refrigerant is charged into the experimental apparatus. The charge line has the sampling port to measure the charged composition. At the beginning and ending of the charging, 1 cc of the liquid refrigerant is sampled from the port to an evacuated small cell sectioned by two valves and then expanded into an evacuated vessel of 100 cc internal volume. The composition of the completely vaporized sample refrigerant is measured by the gas chromatography with uncertainty less than 0.2 mass%. Other sampling port is also located just before the expansion valve in the experimental refrigerant loop, so that the circulating refrigerant can be sampled from the liquid line. By sampling the subcooled liquid from the operating refrigerant loop at the steady state, the circulation composition is measured by the same procedure using the gas chromatography. Table 2: Experimental conditions Heating mode Cooling mode Heat source temperature [ o C] 15 9 20 10 Heat sink temperature [ o C] 20 45 30 45 Degree of superheat [K] 3 Heat transfer rate [kw] (Heating/cooling heat load) 1.6~2.8 1.4~2.4 Refrigerant Table 3: Comparison of properties between test refrigerants R1234ze(E) / (mass%) 80/20 50/50 20/80 Evaporative latent heat*[kj/kg] 201.79 243.61 286.05 315.30 221.31 Liquid density* [kg/m 3 ] 1181.4 1123.3 1080.0 1055.3 1170.0 Vapor density* [kg/m 3 ] 13.7 17.5 20.6 22.1 30.6 ODP 0 0 0 0 0 GWP 140 341 541 675 2089 *Bulk temperature 0 o C

COP h [-] COP r [-] 2229, Page 4 2.3 Data Reduction Method Heat transfer rates in the condenser and evaporator are calculated from the water and refrigerant side energy balances as, Q m Cp T T m h h (1) h w, CON w, CON w, CON, out w, CON, in R CON, in CON, out Q m Cp T T m h h (2) r w, EVA w, EVA w, EVA, in w, EVA, out R EVA, out EVA, in Those heat transfer rates Q h and Q r corresponds to the capacities or the heat loads of the heating and cooling mode operations, respectively. The deviation of those heat loads was confirmed to be within 5 %. The propagated uncertainties obtained from the water side heat balance are 1.5 and 2.5 % for Q h and Q r. Considering larger uncertainties in the refrigerant enthalpies, the heat load obtained from water side energy balance was chosen to calculate COP. COP of heating and cooling modes, COP h and COP r, are obtained from the measured input power for the inverter E inv and the heat loads Q h and Q r. COP Q E (3) h r r h inv COP Q E (4) inv 3. RESULTS AND DISCUSSION 3.1 Comparison on COP and Heat Load of Various Refrigerants Figure 2 shows the relation between COP h and Q h at heating mode, where the symbols of circle, triangle, square and inversed triangle denote the results of,, R1234ze(E)/(20/80 mass%) and R1234ze(E)/(50/50 mass%), respectively. Each refrigerant has a particular heating load to maximize COP h, where symbols circled with dashed line denote the data at maximum COP h. Maximum COP h value of R1234ze(E)/(20/80 mass%) is the highest among the test refrigerants, while that of is the lowest. Figure 3 shows the relation between COP r and Q r at cooling mode, where the symbols denote the same as in Figure 2. Each refrigerant has particular cooling load to maximize COP r, in the same manner as the heating mode. Maximum COP r value of R1234ze(E)/(50/50 mass%) is the highest among the test refrigerants, different from the heating mode. This is mainly due to the significant difference of temperature distribution in evaporator. With the temperature glide of R1234ze/(50/50 mass%), temperature difference between refrigerant and water is reduced by avoiding the pinch point in the evaporator. This avoidance of the pinch point reduces the exergy loss in evaporator and contributes to the improvement in COP r. 5.6 5.4 5.2 Heating mode R1234ze/(20/80mass%) R1234ze/(50/50mass%) 5 1.5 2 2.5 Q h [kw] :Maximum COP 4.8 4.6 4.4 4.2 Cooling mode R1234ze/(20/80mass%) R1234ze/(50/50mass%) 1.5 2 2.5 Q r [kw] Figure 2: Relation between COP h and Q h obtained from water side heat balance (Heating mode) Figure 3: Relation between COP r and Q h obtained from water side heat balance (Cooling mode)

Y R1234ze(E) [-] 2229, Page 5 0.85 0.8 0.75 0.55 0.5 0.45 80/20mass% 50/50mass% Charged composition Average ΔY R1234ze(E) =0.031 ΔY R1234ze(E) =0.050 0.25 0.2 20/80mass% 0.15 0.6 0.8 1 1.2 m [kg] ΔY R1234ze(E) =0.013 Figure 4: Deviation of the circulation composition from the charged composition Table 4: Density ratio of vapor to liquid R1234ze(E) / Refrigerant 80/20mass% 50/50mass% 20/80mass% Liquid density* [kg/m 3 ] 1165.4 1105.3 1062.0 Vapor density* [kg/m 3 ] 16.3 20.5 24.2 ρ l /ρ v [-] 71.4 53.8 43.9 3.2 Difference between the Circulation Composition and the Charged Composition Figure 4 shows the deviation of the circulation composition from the charged composition at various refrigerant charge amounts. In the top, middle and bottom graphs, symbols of circle, triangle, and square denote the results of R1234ze(E)/(80/20 mass%), R1234ze(E)/ (50/50 mass%) and R1234ze(E)/(20/80 mass%), respectively. The vertical axis shows the mass fraction of R1234ze(E), Y R1234ze(E). The solid and dashed horizontal lines show the charged composition and average circulation composition. In entire the test range, the circulation composition obtained by the in-situ sampling is lower than the charged composition. This is typical behavior of composition shift mainly caused by the local composition change and the velocity ratio of vapor and liquid phase. The more volatile component evaporates more readily; conversely, the less volatile component R1234ze(E) condenses more readily. This results in the local composition change in liquid and vapor phase during the phase change. Furthermore, the vapor flow rich in the more volatile component circulates faster than that liquid phase; while, the liquid flow rich in the less volatile component R1234ze(E) tends to be delayed or detained at somewhere in the refrigerant loop. Therefore, the composition shift can be sensitive to the variation of local composition distribution and also the velocity ratio of vapor and liquid phase. Table 4 compares the density ratio of vapor and liquid of R1234ze(E)/ mixtures. This density ratio determines the velocity ratio of vapor to liquid phases. The density ratio of R1234ze(E)/ (20/80 mass%) is the lowest among the test refrigerant. This could result in the lowest composition shift of R1234ze(E)/ (20/80 mass%). 3.3 Effect of Refrigerant Charge Amount on the Composition Shift As shown in Figure 4, the composition shift seems to be slightly decreased with increasing charge amount. With increasing the charge amount, condensing pressure increases and then the degree of subcool and the length of subcool region are increased. Thus, the two-phase region is shortened, where the vapor rich in circulates faster but the liquid rich in R1234ze(E) circulates slower during the phase change process. Likewise, it appears to be that length of two-phase region in the condenser affects composition shift somewhat.

Y R1234ze(E) [-] 2229, Page 6 0.05 0.04 0.03 0.02 0.01 20/80mass% Heat exchanger 5.0m 7.2m 0 Trend curve -0.01 0.8 0.9 1 1.1 1.2 m [kg] Figure 6: Effect of heat exchanger length on the composition shift Figure 5: Variation range of local composition in vapor and liquid phase 3.4 Effect of Variation Range of Local Composition Figure 5 explains the local composition change during the phase change. For instance, at the beginning of condensation, the less volatile component R1234ze(E) condenses more readily than at the dew temperature. Hence, the concentration of R1234ze(E) becomes locally higher in condensate; on the other hand, tends to remain in vapor phase and circulates faster in the cycle. In the case of evaporator, the more volatile component evaporates more readily and the less volatile component R1234ze(E) tends to remain in liquid phase. Then, concentration of R1234ze(E) in liquid phase locally increases. The liquid phase rich in R1234ze(E) circulates more slowly. Likewise, the difference of circulation speed between each components and the local composition change are closely related. The band of arrows in Figure 5 shows the variation range of local composition change, which is determined by the equilibria of each refrigerant mixture. The variation range increases in order of 20/80 mass%, 80/20 mass% and 50/50 mass%. On the other hand, as compared in Figure 4, the composition shift increases in the order of 20/80 mass%, 80/20 mass% and 50/50 mass%. The variation range of local composition distribution corresponds to the composition shift. From this result, it is demonstrated that the composition shift strongly depends on the variation range of local composition distribution. Probably, combination of the variation range of local composition and velocity ratio appear to determine the composition shift. 3.5 Effect of Heat Exchanger Size on Composition Shift To discuss the effect of heat exchanger size on the composition shift, the condenser and evaporator of 5000 mm in length were tested additionally. In Figure 6, the hollow and black symbols are the composition shift Y R1234ze(E) of 5000 mm and 7200 mm long heat exchangers, respectively. As compared, the longer heat exchanger brings lager composition shift. This is mainly due to the longer two phase region, where the composition is changing locally. It should be noted that the liquid reservoirs or accumulators also behave to escalate the composition shift. 3.6 Concern of the Solubility Difference in the Lubricant Oil As another possibility of stimulating the composition shift, the difference in solubility of each component into the lubrication oil should be considered. POE VG68 is applied for lubrication in this study. Some literatures (e.g., Ota

COP h [-] COP h [-] 2229, Page 7 6 5.8 R1234ze/(20/80mass%) R1234ze/(50/50mass%) circulation composition 6 5.8 R1234ze/(20/80mass%) R1234ze/(50/50mass%) charged composition 5.6 5.6 5.4 5.4 5.2 5.2 5 1.5 2 2.5 3 Q h [kw] 5 1.5 2 2.5 3 Q h [kw] Figure 7: Relation between COP h and Q h evaluated at the circulation composition Figure 8: Relation between COP h and Q h evaluated at the charged/nominal composition and Araki, 2010, Matsumoto et al., 2010, Yana Motta et al., 2010) suggested that R1234ze(E) is well soluble in POE oils as R134a, whereas is poor in solubility with POE oils. Although there is no open information of the solubility on the particular POE oil with R1234ze(E)/, probably the POE oil absorbs mostly R1234ze(E) and only little. This solubility difference could be one of factors to escalate the composition shift; however, the magnitude of this effect cannot be quantified from the present experiment. 3.7 Effect of Composition Shift on COP and Capacity Evaluation Figure 7 shows the relation between COP h and heat load Q h of heating mode calculated from refrigerant side heat balance evaluated at the circulation composition by Equations (1) and (3). Circle, triangle, square and inversed triangle symbols denote the results of,, R1234ze(E)/(20/80 mass%) and R1234ze(E)/(50/50 mass%), respectively. As compared with COP h calculated from water side heat balance plotted in Figure 2, the COP h values evaluated at the circulation composition slightly increase from that evaluated at the water side heat balance. However, it does not bring significant change on the general trend. Figure 8 shows the relation between COP h and Q h evaluated at the charged composition. Symbols denote the same as in Figure 7. By evaluating at the charged composition, COP h of the zeotropic mixture obviously decreases from the value evaluated by the other methods. Since this method assumes the composition of R1234ze(E) slightly higher than the circulation composition, the refrigerant properties such as enthalpy, latent heat and specific heat are evaluated slightly closer to R1234ze(E). In consequence of this property evaluation, this method under-evaluates COP h. For the reasonable assessment of zeotropic mixtures, COP and heat loads should be evaluated at the circulating composition. 4. CONCLUSIONS The COP of four test refrigerants,,, R1234ze(E)/(20/80 mass%), and R1234ze(E)/ (50/50 mass%) has been experimentally evaluated with a heat pump cycle. Additionally, the circulation composition has been compared to the charged composition. The concluding remarks are as follows: (1) For heating operation mode, maximum COP of R1234ze(E)/(20/80 mass%) evaluated by water side heat balance is the highest among the test refrigerants. For cooling operation mode, maximum COP of R1234ze(E)/(50/50 mass%) is the highest due to avoidance of the pinch point in evaporator. (2) The circulation composition of the less volatile component R1234ze(E) is lower than the charged composition. The more volatile component is rich in the vapor, while the less volatile component is rich in the liquid locally. This local composition distribution decreases the circulation composition of R1234ze(E). (3) COP evaluated at the circulation composition is almost unchanged from COP evaluated by water side heat balance. However, the COP evaluated at the charged composition is obviously lower than those. For reasonable assessment of zeotropic mixtures, cycle performance should be evaluated by the circulation composition.

2229, Page 8 NOMENCLATURE COP coefficient of performance ( - ) Subscripts Cp isobaric specific heat (kj/kg K) CON condenser E input power (kw) EVA evaporator h enthalpy (kj/kg) h heating mode m mass flow rate (kg/s) inv inverter Q heat transfer rate (kw) R refrigerant T temperature (K) r cooling mode Y mass fraction of R1234ze(E) ( - ) w water REFERENCES Haberschill, P., Gay, L., Aubouin, P., Lallemand, M., 2002, Performance prediction of a refrigerating machine using R-407C: the effect of the circulating composition on system performance, Int. J. Energy Res., vol.26: p. 1295-1311. Jakobs, R., Kruse, H., 1978, The use of non-azeotropic refrigerant mixture in heat pumps for energy saving, Proc. IIR Commissions B2, Delft, Netherlands: p. 207-218. Koyama, S., Matsuo, Y., Fukuda S., Akasaka, R. 2010a, Measurement of vapor-liquid equilibrium of HFO1234ze(E) / HFC-32, Proc. 2010 JSRAE Annual Conference, p. 195-196. Koyama, S., Takata, N., Fukuda, S. 2010b, Drop-in experiments on heat pump cycle using HFO-1234ze(E) and its mixtures with HFC-32, Proc. Int. Refrig. A/C Conf. at Purdue, Paper no. 2514: p. 1-8. Koyama, S., Takata, N., Fukuda, S. 2011, An experimental study on heat pump cycle using zeotropic binary refrigerant of HFO-1234ze(E) and HFC-32, IEA Heat Pump Conference, Tokyo, Japan. Kruse, H, 1981, The advantages of non-azeotropic refrigerant mixtures for heat pump application, Proc. IIR Commissions D1, D2, E1, and E2, vol. 4, no. 3: p. 119-125. Lemmon, E.W., Huber, M.L., McLinden, M.O., 2010. Reference Fluid Thermodynamic and Transport Properties - REFPROP Ver. 9.0, National Institute of Standards and Technology, Boulder, CO, USA. Matsumoto, T., Kaneko, M., Tamano, M., 2010, Evaluation of various lubricants for a low global worming potential (GWP) refrigeration systems, Proc. Int. Symp. New Refrigerants and Environmental Technology 2010: p. 210-215. McLinden, M.O., Radermacher, R., 1987, Methods of comparing the performance of pure and mixed refrigerants in the vapour compression cycle, Int. J. Refrig., vol.10: p. 318-325. Ota, R., Araki, K., 2010, Properties of refrigerant/oil mixture for low GWP refrigerants, Proc. Int. Symp. New Refrigerants and Environmental Technology 2010: p. 51-55. Swinney, J., Jones, W.E., Wilson, J.A., 1998, The impact of mixed non-azeotropic working fluids on refrigeration system performance, Int. J. Refrig., vol. 21, no. 8, p. 607-616. Yana Motta, S., Vera Becerra, E.D., Spatz, M.W., 2010, Analysis of LGWP alternatives for small refrigeration (plugin) applications, Proc. Int. Refrig. A/C Conf. at Purdue, paper no. 2499: p. 1-7. Youbi-Idrissi, M., Bonjour, J., Meunier, F., 2005, Local shifts of the fluid composition in a simulated heat pump using R-407C., Appl. Therm. Eng., vol.25: p. 2827-2841. ACKNOWLEDGEMENT This work was funded by the New Energy and Industrial Technology Development Organization (NEDO) under the project of the Development of Non-Fluorinated Energy-Saving Refrigeration and Air Conditioning Systems. The financial support is gratefully acknowledged here. The authors acknowledge Dr. C. Kondou for her helpful comments and discussion on the present study.