Application Sheet Fan coil unit with staged fan, heating and cooling coil (4 pipe) on triac output including lighting and blinds operation

Similar documents
Application Sheet Fan coil unit with staged fan, 6-way heating/cooling coil (4 pipe) on analog output

Application Sheet Chilled/heated ceiling (4 pipe) with 6-way valve on analog output

Synco-GAMMA Application Guide. Hotel buildings. Answers for infrastructure.

Heating and D.h.w. Controller RVL482 Basic Documentation

Synco-Gamma Application Guide. Retirement and nursing homes.

Wall-mounted room thermostat with LCD

Desigo TM Room Automation The unique solution for enhanced comfort and productivity

Room thermostat with 24-hour time switch and large LCD

Flush-mounted room thermostat

Application Guide siemens.com/thermostats

District heating controller

Install intelligent room automation flexibly and future-proofed

Room thermostats with LCD for wall mounting

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

Semi flush-mount communicating room thermostats

RVL479. Heating Controller. for use with a partner unit

Flush-mount room sensor KNX S-Mode / KNX LTE- Mode / KNX PL-Link

District heating controller

Synco-GAMMA Application Guide. School building class room. Answers for infrastructure.

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

Smart Thermostat RDS110

Flush-mounted room thermostats

Room Temperature Controllers

Touch Screen Flush-mount Room Thermostats with KNX Communications

Saving energy with Synco

Semi flush-mount room thermostats

RVL481. Heating Controller. including d.h.w. heating

SAUTER ecos504/505. The modular room controller for demand-controlled, integral room automation.

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

REA22 Room Temperature Controller

XC10 Extinguishing control panels

Saving energy while ensuring an enhanced room climate

RVL480. Heating Controller

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Room Temperature Controller

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

Room thermostat with KNX communications RDG400KN

Room thermostat with Auto Timer, independent DHW

Desigo Total Room Automation User Guide Version 2.1. A6V _en_a_ Building Technologies

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Optimal control for superior lighting performance

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

Duct Temperature Sensors

Answers for infrastructure. HVAC control with Synco simple and energy-efficient

TC-9102 Applications

Room thermostat with KNX communications RDG100KN

RVL470. Heating Controller. Use. Functions. Series B

Frost Units for air temperature monitoring

Room thermostats with KNX communications RDG100KN, RDG160KN, RDG165KN

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

PRELIMINARY EDITION

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

Flush-mounted room temperature controllers for VAV / CAV applications, with LCD RDU340

Room thermostats with LCD for wall mounting RDG100 RDG100T RDG110, RDG110U RDG160T, RDG160TU RDG100T/H

Room thermostat with KNX communications RDG400KN

District Heating Controller

Room thermostats with LCD RDD100..

Predator Controller Hardware Family

Fire control panels FC360

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

Tri-Stack Smart System

Fire control panels FC726 FC726-XA

DESIGO - Answers for infrastructure. Energy-efficient applications: h,x-controlled Economizer tx2. Application data sheet

Save energy while maintaining a constant room climate

FDA241, FDA221 Siemens ASD

Room Temperature Sensors

Wireless room thermostat with LCD

FC722 Fire control panel

G a

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Use of the application program. Functional description. instabus EIB Application program description. October CO Touch-Manager wave

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SAUTER flexotron800 V2 Ventilation V3.3. manual P P

System catalogue 2019 siemens.com/desigo

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

XC10 combined fire detection and extinguishing control

Input module, input/output modules

QAW70. Room Unit. Building Technologies. for use with heating controllers

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

Installer Manual KNX Touchscreen Thermostat

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

e.control Function overview

I/O ZONE 560/583 USERS GUIDE

RVP310. Heating Controller. Building Technologies HVAC Products

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

Document # R01

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FDA241, FDA221 Siemens ASD

Air conditioning plant with 1 hot water preheater, 1 spray humidifier, 1 chilled water cooling coil and 1 hot water reheater N.Q1 B2 N.X1 B1 N.

Room thermostat with independent DHW control

Fan Coil Unit (FCU) Application Guide

Transcription:

Heating with LTHW and cooling with CHW Modulating control of heating and cooling valve (4 pipe) on triac output Automatic or manual 3-speed fan control Including the control of 4 lighting zones & 2 blinds Room temperature and fan speed operation via KX PL-Link room operator unit with temperature measurement & lighting and blinds operation Plant diagram DXR2 Room automation station B1 Extract air temperature sensor Q6, Q7 2 blinds motors B3 Supply air temperature sensor R Room D1 Window contact R1 Room operator unit with D2 Presence detector temperature sensor Q1 3-speed fan YC Cooling coil valve Q2, Q3, 4 lighting zones YH Heating coil valve Q4, Q5 Function diagrams Heating/cooling valves 1-2-3 speed fan Q Fan output signal SpH Effective heating setpoint Q1.1 Fan speed 1 TR Room temperature Q1.2 Fan speed 2 Y Valve output signal Q1.3 Fan speed 3 YC Cooling coil valve SpC Effective cooling setpoint YH Heating coil valve 1/ 8

Description of functions Basic functions Options HVAC PID control for heating and cooling. The 4 pipe system provides hot and chilled water for the heating coil and the cooling coil. 3-position valves are controlled by triac outputs for cooling and heating. The fan is controlled manual on the room operator unit or automatic in 3 speeds. The temperature is measured in the room operator unit. The application allows customers to adjust the room temperature setpoints via the room operator unit including the operation of lighting and blinds. The operating modes are Comfort, Pre-Comfort, Economy and Protection. Change of operating mode via room unit, presence detector, window contact or central command. The air flow for heating and cooling is operated in sequence to the valves. Parallel operation can be configured. Lighting The application allows room users to control lighting via a standard function switching and/or The application allows customers to control lighting operation via room unit. Blinds The application allows room users to operate the blinds via the following commands: o Move up/down o Step up/down The reference model applied ensures exact positioning of the shading products. The application allows customers to control shading operation via room unit. HVAC Optimal energy efficiency by including the option for room/supply air cascade control, presence detector or window contact. Optional system alarms displayed on the management station notify building operators of possible faults. Optional trends can be activated for room sensors. Lighting Optional system alarms displayed on the management station notify building operators of possible faults (e.g. defective electronic control gear or lamps). Optional trends can be activated for room lighting. Blinds Optional system alarms displayed on the management station notify building operators of possible faults (e.g. defective actuator). Reliable, central override of local operation only for emergencies, service, and cleaning. Central weather protection function preventing damages to shading products due to high winds or frost. Optional trends can be activated for room blinds. 2/ 8

Auxiliary functions Variants Green Leaf (RoomOptiControl) function. 1 3 speed. Multisegment use of DXR2 automation stations with PWM constant (incl. spring return) or PWM thermal fan coil unit application. control can be selected for valves. Standard hot water supply chain control. The room temperature can be measured by: The application allows for control via centralized o KX PL-Link wall-mount sensor commands (e.g. scheduler program for room operating o KX PL-Link flush-mount room operator unit mode). o KX PL-Link flush-mount sensors Central optimum start control provides best room o Analog extract air temperature sensor comfort at the start of occupancy. KX PL-Link switches for lighting and blinds Central operation or reset of setpoints, timed valve operation. kick function or outside temperature dependent Presence can be detected by KX PL-Link sensor heating limit. or binary sensor. Central override functions for valves. Seasonal compensation of room temperature setpoints. Lighting The application allows for control via centralized commands (e.g. scheduler program). The application function supports runtime totalization for each lighting group for maintenance and service purposes (burn in/operation h/ EOL end of life cycle). Blinds The application allows for control via centralized commands (e.g. scheduler program or weather station). Siemens devices Legend Type of unit Data sheet Product o. Qty. DXR2 Compact room automation station, BACnet/IP, 230 V, flat housing, 1 DI, 2 UI, 3 DO relays, 4 DO triacs R1 KX PL-Link room operator unit with temperature sensor Q2, Q3 Lighting output Q4, Q5 Lighting output Q6, Q7 Blinds actuator, 2 x AC 230 V, 6 A 9204 1 1602 QMX3.P37 1 UP 510/13 2 UP 510/13 2 RL 521/23 1 YC 2-port, 3-port valve or 3-port valves with bypass, P16 4847 V..P47.. 1 Motorized 3-positioning actuator for V..P47.., AC 24 V 4864 SSP81.. 1 YH 2-port, 3-port valve or 3-port valves with bypass, P16 4847 V..P47.. 1 Motorized 3-positioning actuator for V..P47.., AC 24 V 4864 SSP81.. 1 Optional 1) Legend Type of unit Data sheet Product o. Qty. B1 Cable temperature sensor PVC 2 m, LG-i1000 1831 QAP22 1 B3 Cable temperature sensor PVC 2 m, LG-i1000 1831 QAP22 1 D1 D2 Door/window contact, white KX PL-Link presence detector with brightness sensor 1) Can be combined according to available on-board I/Os on controller. Further documents on www.siemens.com/gamma-td. 3) Type of operation (O or C). Multiple devices of the same type can be connected. S 290/11 3) UP 258D12 1-4 3/ 8

Variants Legend Type of unit Data sheet Product o. Qty. R1 a KX PL-Link wall-mount room sensor for temperature 1602 QMX3.P30 1 R1 b KX PL-Link flush-mount room operator unit 1601 QMX3.P36 1 R1 c KX PL-Link flush-mount room sensors 1411 AQR253 AQR257 YC a 2-port, 3-port valve or 3-port valves with bypass, P16 4847 V..P47.. 1 Thermal actuator, AC/DC 24 V, O, 2P, 1 m 4884 STP73 1 YH a 2-port, 3-port valve or 3-port valves with bypass, P16 4847 V..P47.. 1 Thermal actuator, AC/DC 24 V, O, 2P, 1 m 4884 STP73 1 1 4/ 8

Connection diagram B1 T R1 R1a, b, c D2 T + - T + - + - D1 *D2a B3 T BACnet IP BACnet IP AC 230 V L 1 2 3 Y1 G Y2 M Y1 G Y2 M *Q1 YC YH L AC 230 V YC a YH a Q2 Q3 CE+ CE- 2x CE+ CE- 2x Q4 Q5 CE+ CE- M 1~ 2x Q6 Q7 3L 1 2 3L 1 2 3L 1 2 4 5 L AC 230 V *3 rd party device 5/ 8

Application configuration Equipment Values/Range Template settings On-board output Fan speed 1-stage; Q14; ormally open 2-stage; Q14, Q24; ormally open 3-stage; Q14, Q24, Q34; ormally open Cooling coil valve position Water; Y1, Y2; 3-position Water; Y1; Pulse width modulation thermal Water; Y1; Pulse width modulation spring return DX; Y1; ormally open DX; Y1, Y2; ormally open Heating coil valve position Water; Y3, Y4; 3-position Water; Y4; Pulse width modulation thermal Water; Y4; Pulse width modulation spring return Electric 1-stage; Y4; ormally open Electric 2-stage; Y3, Y4; ormally open Electric modulating; Y4; Pulse width modulation constant period KX PL-Link devices Room operator unit device 1 QMX3.P37; General HVAC; 4x dimming QMX3.P37; General HVAC; 2x dimming, 2x blinds QMX3.P37; General HVAC; 4x toggle, 2x blinds Lighting device 1 Lighting device 3 Blinds device 1 RL 512/23 - JB 512C23; 1x lighting, switching RL RS 510/23 - JB 510C23; 2x lighting, switching UP 510/03; 2x lighting, switching UP 510/13; 2x lighting, switching RS 525/23 - JB 525C23; 1x lighting, dimming UP 525/03; 1x lighting, dimming UP 525/13; 1x lighting, dimming RL 512/23 - JB 512C23; 1x lighting, switching RL RS 510/23 - JB 510C23; 2x lighting, switching UP 510/03; 2x lighting, switching UP 510/13; 2x lighting, switching RS 525/23 - JB 525C23; 1x lighting, dimming UP 525/03; 1x lighting, dimming UP 525/13; 1x lighting, dimming RS 520/23 - JB 520C23; 1x blinds RS 520/23 - JB 520C23; 1x awnings UP 520/03; 1x blinds UP 520/03; 1x awnings UP 520/13; 1x blinds UP 520/13; 1x awnings RL 521/23 - JB 521C23; 2x blinds RL 521/23 - JB 521C23; 2x awnings 3-stage; Q14, Q24, Q34; ormally open Water; Y1, Y2; 3-position Water; Y3, Y4; 3-position QMX3.P37; General HVAC; 4x toggle, 2x blinds UP 510/13; 2x lighting, switching UP 510/13; 2x lighting, switching RL 521/23 - JB 521C23; 2x blinds 6/ 8

Optional configuration Equipment Values/Range Template settings On-board input Room temperature (B1) X1; LG-i1000 Supply air temperature (B3) X2; LG-i1000 Presence detector 2 (D2 a) X1, ormally open Window contact (D1) D1; ormally closed KX PL-Link devices Sensor device 1 4 (D UP 258D12 Default values Parameter Values/Range Template settings Temperature setpoints Cooling setpoint for Comfort 0 50 C 24 C Delta cooling setpoint for Pre-comfort 0 10 K 1 K Cooling setpoint for Economy 0 50 C 35 C Cooling setpoint for Protection 0 50 C 40 C Heating setpoint for Comfort 0 50 C 21 C Delta heating setpoint for Pre-comfort 0 10 K 1 K Heating setpoint for Economy 0 50 C 15 C Heating setpoint for Protection 0 50 C 12 C Room operator unit Room unit, display temperature one Display room temperature Display room temperature Room unit, display windows status Yes, o o Room unit, display heat./cool. status Yes, o Yes Enable operation: room temp. setpoint Yes, o Yes Room unit, room temp. setpoint display Absolute temperature setpoint Relative setpoint shift Enable operation: fan speed setpoint Yes, o Yes Enable operation: presence button Yes, o o Enable operation: temporary Comfort Yes, o o Enable operation: room op. mode Yes, o o Enable operation: Green Leaf Yes, o Yes Relative setpoint shift Engineering ABT Site engineering tool is required to configure the DXR2 automation stations. See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and workflow tutorials. Option combination according to available on-board I/Os on controller. B1 (optional extract air temperature sensor) to be configured under,room temperature in order to serve for room temperature control. D2 a (on-board presence detector) to be configured in ABT Site under Presence detector 2 for maximum combination of optional devices. Type of operation (O or C). Multiple devices of the same type can be connected. 7/ 8

Management station Sample presentation of a fan coil unit application with lighting and blinds operation on the Desigo CC management station. Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.siemens.com/buildingtechnologies 2015 Siemens Switzerland Ltd Subject to change 8/ 8