TAG: RTU-2B 3B 4B 5B 6B 7B 1E MODEL: QTY. (7) 48TCED14A3A5-0B0A0 PACKAGED GAS/ELECTRIC ROOF TOP UNITS

Similar documents
Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

SUBMITTAL. Project. CLU Swenson Center. Date 01/07/2010. Mechanical Contractor. West Coast Air Conditioning. Mechanical Engineer

50KCQ Packaged Heat Pump 14 SEER 3to5NominalTons. Product Data C08613

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

RHX. Product Specifications

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

We are pleased to submit the following equipment for your approval on the above project:

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

PERFORMANCE, INNOVATION, RELIABILITY

SUBMITTAL. Project. Cross Creek Elementary School. Date. Thursday, July 23, 2015

Product Data KUWAIT SERIES

PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP 3 5 TONS (1 & 3 Phase) BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

48PGD/E/F/L/M/N PG20-28

INSTALLATION INSTRUCTIONS

582J GAS HEAT/ELECTRIC COOLING SINGLE PACKAGED ROOFTOP 14 SEER 3 TO 5 NOMINAL TONS. Product Data C (Shown with optional Louvered Hail Guard)

48KC Gas Heat/Electric Cooling Single Packaged Rooftop 14 SEER 3to5NominalTons. Product Data C08613

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

Advanced Product Data

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

ENERGY STAR COMPLIANT PACKAGE GAS HEATING/ELECTRIC COOLING, R 410A SINGLE PACKAGE ROOFTOP TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

RECORD SUBMITTAL COVER SHEET

90.1 COMPLIANT PACKAGED ROOFTOP HEAT PUMP UNITS, R 410A, TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz COOLING

VertiCool Aurora Engineering Guide

STANDARD EFFICIENCY PACKAGE A/C UNIT to 216 MBtuh

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

50TM COMBINATION HEATING/COOLING UNITS

50TJM Nominal Cooling Capacity Tons HFC R - 410A Refrigerant

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

Product Data. 50JS Single-Packaged Heat Pump Units. 1 1/2 to 5 Nominal Tons

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

50TM TFF COMBINATION HEATING/COOLING UNITS

INSTALLATION INSTRUCTIONS

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS


9 EER 1-5 Ton Vertical Packaged Wall Mount Air Conditioners

PAR5. Product Specifications

62DA,DB,DC,DD,DE,DF07-38

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Product Data. Features/Benefits. 50LJQ Single-Package Rooftop Heat Pump Units. Nominal 3 to 10 Tons

48TM GAS HEATING/ELECTRIC COOLING UNITS

DCC Commercial. Submittal Data Form. 7½ - 12½ Ton Packaged Air Conditioners Up to 11.3 EER Cooling Capacity: 88, ,000 BTU/h

1 to 5 Ton Vertical Wall Mount Air Conditioners Models AVPA

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners Up to 11.3 EER

Roof Top Packaged Unit (RTU-1) Specification

GreenPac & GreenPac HGR Air Conditioners Single stage models AVPA and HVEA and 2-stage models HVESA

Product Data. Fig. 1 - Unit 50VG -A

Model 581A COMMERCIAL GAS HEATING/ELECTRIC COOLING UNITS. Bryant Air Conditioning. Form No. PDS 581A.155.3B. 13 to 20 Tons DESCRIPTION

WPH4 Product Specifications

Input Cap. (Btuh) Stage 2

EER PACKAGE AIR CONDITIONER, 6.9 to 14.4 kw, 2 4 TONS 3 Phase, Standard CFM / Ls EER

ASHRAE 90.1 EFFICIENCY PACKAGE AIR CONDITIONER UNIT MBtuh

PGS SERIES 15 to 20 Ton

48TF GAS HEATING/ ELECTRIC COOLING UNITS

ELECTRICAL QUANTITY WEIGHT (LB)

Advanced Product Data

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

DCG Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

Multi-Path RTU-TYPE 2

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Duct Free Systems Product Data Digest ¾ to 5 Nominal Tons

50VT--C Comfort 14 SEER Single--Packaged Heat Pump System with Puron

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

PAD3. Product Specifications. 13 SEER PACKAGE AIR CONDITIONER, 2 to 5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT

INSTALLATION INSTRUCTIONS R -410A Single Package Gas Heating / Electric Cooling

Model 702A SINGLE-PACKAGED ELECTRIC HEATING COOLING UNITS. 2 to 5 Nominal Tons UNIT 702A. Form No. PDS 702A.24.3

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Advance Release September 2009

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

Cabinet Features Heavy-gauge, galvanized-steel cabinet with UV-resistant powder-paint finish Full Perimeter Rail Sloped drain pan

DCC Series. Submittal Data Form 15- & 20-TON, THREE-PHASE PACKAGED AIR CONDITIONERS UP TO 11 EER

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Product Data. Features/Benefits All in one package cooling efficiency, installation convenience and ease of accessibility allow for timesaving

DCG Commercial. Submittal Data Form

Water-Cooled Self-Contained Units

Product Data. Features/Benefits. 50GX 3-PHASE SINGLE-PACKAGED ELECTRIC COOLING UNITS 2-1/2 to 5 Nominal Tons

14 SEER, 12 EER, 8.0 HSPF, PACKAGE HEAT PUMP, 2 to 5 TONS 208/ , Single Phase

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

50HJQ004, 005, 006, 007, 008 & 012 SINGLE-PACKAGE HIGH-EFFICIENCY HEAT PUMP UNITS WITH FIELD-INSTALLED ELECTRIC HEAT

Product Catalog. Packaged Rooftop Air Conditioners Foundation Electric/Electric Tons, 50 Hz RT-PRC073B-EN. May 2018

PERFORMANCE, INNOVATION, RELIABILITY

ELECTRIC HEAT Field installed accessory heaters are available in a wide range of capacities with single point wiring connections. High Temp.

ASHRAE 90.1 EFFICIENCY PACKAGE GAS / ELECTRIC UNIT MBtuh

General Description. Operation

Submittal Summary Page

C13-Series Engineering Guide

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

Transcription:

SUBMITTAL ***FOR APPROVAL*** TAG: RTU-2B 3B 4B 5B 6B 7B 1E MODEL: QTY. (7) 48TCED14A3A5-0B0A0 PACKAGED GAS/ELECTRIC ROOF TOP UNITS Project 66 Orland Square Dr. Landlord Renovations Location Orland Park, IL Contractor Classic Air, Inc. Engineer Cartland Kraus Date June 22, 2015

Table Of Contents Prepared By: 12:07PM RTU-2B 3B 4B 5B 6B 7B 1E... 3 Unit Report... 4 Certified Drawing... 5 Performance Summary... 9 Packaged Rooftop Builder 1.39q Page 3 of 12

RTU-2B 3B 4B 5B 6B 7B 1E RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM RTU-2B 3B 4B 5B 6B 7B 1E Tag Cover Sheet Unit Report Certified Drawing Performance Report Packaged Rooftop Builder 1.39q Page 4 of 12

Unit Report Unit Report For RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM Unit Parameters Unit Model:... 48TCED14A3A5-0B0A0 Unit Size:... 14 (12.5 Tons) Volts-Phase-Hertz:... 208-3-60 Heating Type:... Gas Duct Cfg:... Vertical Supply / Vertical Return Medium Heat Round Tube Plate Fin Coils Dimensions (ft. in.) & Weight (lb.) *** Unit Length:... 7' 4.125'' Unit Width:... 4' 11.5'' Unit Height:... 4' 1.375'' *** Total Operating Weight:... 1417 lb *** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog. Lines and Filters Gas Line Size:... 3/4 Condensate Drain Line Size:... 3/4 Return Air Filter Type:... Throwaway Return Air Filter Quantity:... 4 Return Air Filter Size:... 20 x 20 x 2 Unit Configuration High Static Option (Belt Drive) Al/Cu - Al/Cu Base Electromechanical Controls Temperature Economizer w/ Barometric Relief Standard Packaging Warranty Information 1-Year parts(std.) 5-Year compressor parts(std.) 10-Year heat exchanger - Aluminized(std.) No optional warranties were selected. NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods. Ordering Information Part Number Description Quantity 48TCED14A3A5-0B0A0 Rooftop Unit 7 Base Unit High Static Option (Belt Drive) Std leak Temp Econo IV with baro relief and W7212 control None Accessories CRRFCURB003A01 VST2800 14-inch Tall Roof Curb Venstar Commercial Programmable Thermostat 7 7 Packaged Rooftop Builder 1.39q Page 5 of 12

Certified Drawing Certified Drawing for RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM Packaged Rooftop Builder 1.39q Page 6 of 12

Certified Drawing for RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM Packaged Rooftop Builder 1.39q Page 7 of 12

Certified Drawing for RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM Packaged Rooftop Builder 1.39q Page 8 of 12

Certified Drawing for RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM ROOF CURB ACCESSORY # CRRFCURB003A01 CRRFCURB004A01 A 14" [356] 24" [610] NOTES: 1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED. 2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY. 3. DIMENSIONS IN [ ] ARE IN MILLIMETERS. 4. ROOFCURB: 18 GAGE STEEL. 5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB). 6. SERVICE CLEARANCE 4 FEET ON EACH SIDE. 7. DIRECTION OF AIR FLOW. 8. CONNECTOR PACKAGE CRBTMPWR002A01 IS FOR THRU-THE-CURB GAS TYPE PACKAGE CRBTMPWR004A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS. CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING CRBTMPWR002A01 CRBTMPWR004A01 THRU THE CURB THRU THE BOTTOM POWER WIRING FITTING 3/4" [19] NPT 1 1/4" [31.7] NPT CONTROL WIRING FITTING ACCESSORY CONVENIENCE OUTLET WIRING CONNECTOR 1/2" [12.7] NPT 1/2" [12.7] NPT 1 3/4" [44.5] 6 3/64" [153.5] 53 1/2" [1358.9] 11.42" [290.0] 14 3/4" [374.7] 2 1/4" [57.2] "A" 1.00" [25.4] 12-1/2" [317.5] WIDE INSULATED DECK PANELS 26" [660.4] 1 3/4" [44.4] 9-15/16" [252.4] WIDE INSULATED DECK PANEL 4 3/16" [106.0] 32 9/16" [827.1] 1 3/4" [44.4] 81 3/4" [2076.3] SECTION THRU SIDE GAS SERVICE PLATE THRU THE CURB DRILL HOLE 2" [50.8] @ ASSEMBLY (IF REQUIRED) (SEE NOTE #8) 20-3/4" [513] INSIDE 2-3/8" [61] SEE NOTE #2 3" [76.2] 40 3/16" [1020.8] 15 13/16" [401.6] 1 3/4" [44.5] SUPPLY AIR OPENING RETURN AIR OPENING 23 1/16" [585.8] VIEW "B" CORNER DETAIL SUPPLY AIR RETURN AIR 1-3/4" TYP [44.5] 1 3/4" [44.5] 31 17/32" [800.9] 15 15/32 [392.9] GASKET (SUPPLIED WITH CURB) DUCT (FIELD SUPPLIED) UNIT 7/16" [11] NAIL (FIELD SUPPLIED) TYPICAL (4) SIDES COUNTER FLASHING (FIELD SUPPLIED) "A" 4' 2" [1270.0] 6' 6-1/4" [1987.5] 4 9/16" [115.5] 1/4" [7.0] ROOFING FELT (FIELD SUPPLIED) CANT STRIP (FIELD SUPPLIED) ROOFING MATERIAL (FIELD SUPPLIED) SEE VIEW "B" DRAWING RELEASE LEVEL: CERTIFIED DRAWING PRODUCTION UNLESS OTHERWISE SPECIFIED THIRD ANGLE DIMENSIONS ARE IN INCHES PROJECTION TOLERANCES ON: 1 DEC 2 DEC 3 DEC ANG MATERIAL - - - - THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART, WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION. SUPPLY AIR RETURN AIR RIGID INSULATION (FIELD SUPPLIED) - - - AUTHORIZATION NUMBER ENGINEERING TITLE 1029120 CURB ASY, ROOF MANUFACTURING C 6' 61/4" WAS 6' 7 1/6", 4'2' WAS 4' 2 13/16"; 18 GA WAS 16 GA.; 15 13/16" WAS 15 15/16"; NAIL FIELD SUPPLIED WAS WITH CURB 4/22/13 MMC - - 1067898 ENGINEERING REQUIREMENTS - - - - SIZE DRAWING NUMBER REV T-005, Y-002 DRAFTER CHECKER D 50HJ405012 WEIGHT: - MMC 12/16/09 - - SHEET 5 OF 5 SURFACE FINISH MODEL (INTERNAL SCALE DISTRIBUTION MFG/PURCH USE ONLY) NEXT DRAWING C REV REVISION RECORD DATE BY CHK'D APP'D ECN NO. - PURCH - N/A - Packaged Rooftop Builder 1.39q Page 9 of 12

Performance Summary Performance Summary For RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM Part Number:48TCED14A3A5-0B0A0 ARI EER:... 10.80 IEER:... 11.0 Base Unit Dimensions Unit Length:... 88.1 in Unit Width:... 59.5 in Unit Height:... 49.4 in Operating Weight Base Unit Weight:... 1167 lb Medium Heat:... 18 lb High Static Option (Belt Drive):... 15 lb Temperature Economizer w/ Barometric Relief:... 74 lb Accessories 14-inch Tall Roof Curb:... 143 lb Total Operating Weight:... 1417 lb Unit Unit Voltage-Phase-Hertz:... 208-3-60 Air Discharge:... Vertical Fan Drive Type:... Belt Actual Airflow:... 5000 CFM Site Altitude:... 0 ft Cooling Performance Condenser Entering Air DB:... 95.0 F Evaporator Entering Air DB:... 80.0 F Evaporator Entering Air WB:... 67.0 F Entering Air Enthalpy:... 31.44 BTU/lb Evaporator Leaving Air DB:... 60.5 F Evaporator Leaving Air WB:... 57.7 F Evaporator Leaving Air Enthalpy:... 24.83 BTU/lb Gross Cooling Capacity:... 148.67 MBH Gross Sensible Capacity:... 105.37 MBH Compressor Power Input:... 10.20 kw Coil Bypass Factor:... 0.254 Heating Performance Heating Airflow:... 5000 CFM Entering Air Temp:... 60.0 F Leaving Air Temp:... 94.1 F Gas Heating Input Capacity:... 180.0 / 224.0 MBH Gas Heating Output Capacity:... 147.0 / 184.0 MBH Temperature Rise:... 34.1 F Supply Fan External Static Pressure:... 0.92 in wg Options / Accessories Static Pressure Economizer:... 0.32 in wg Total Application Static (ESP + Unit Opts/Acc.):... 1.24 in wg Fan RPM:... 1176 Fan Power:... 4.70 BHP NOTE:... Selected IFM RPM Range: 1022-1240 Electrical Data Voltage Range:... 187-253 Compressor #1 RLA:... 19 Compressor #1 LRA:... 123 Packaged Rooftop Builder 1.39q Page 10 of 12

Performance Summary For RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM Compressor #2 RLA:... 22.4 Compressor #2 LRA:... 149 Indoor Fan Motor Type:... HIGH Indoor Fan Motor FLA:... 13.6 Combustion Fan Motor FLA (ea):... 0.48 Power Supply MCA:... 67 Power Supply MOCP (Fuse or HACR):... 80 Disconnect Size FLA:... 70 Disconnect Size LRA:... 392 Electrical Convenience Outlet:... None Outdoor Fan [Qty / FLA (ea)]:... 1 / 6.2 Electrical Data (Units produced on or after 02/16/2015 ) Compressor #1 RLA:... 19.6 Compressor #1 LRA:... 136 Compressor #2 RLA:... 22.4 Compressor #2 LRA:... 149 Power Supply MCA:... 68 Power Supply MOCP (Fuse or HACR):... 80 Disconnect Size FLA:... 71 Disconnect Size LRA:... 405 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics Sound Power Levels, db re 10E-12 Watts Discharge Inlet Outdoor 63 Hz 98.9 95.4 87.0 125 Hz 96.7 90.1 85.2 250 Hz 85.3 75.8 84.6 500 Hz 79.3 71.3 84.9 1000 Hz 76.4 69.7 82.2 2000 Hz 73.2 65.7 78.4 4000 Hz 76.8 66.4 75.3 8000 Hz 79.2 63.5 72.9 A-Weighted 86.2 78.2 87.0 Advanced Acoustics Advanced Accoustics Parameters 1. Unit height above ground:... 30.0 ft 2. Horizontal distance from unit to receiver:... 50.0 ft 3. Receiver height above ground:... 5.7 ft 4. Height of obstruction:... 0.0 ft 5. Horizontal distance from obstruction to receiver:. 0.0 ft Packaged Rooftop Builder 1.39q Page 11 of 12

Performance Summary For RTU-2B 3B 4B 5B 6B 7B 1E Prepared By: 12:07PM 6. Horizontal distance from unit to obstruction:... 0.0 ft Detailed Acoustics Information Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 87.0 85.2 84.6 84.9 82.2 78.4 75.3 72.9 92.4 Lw B 60.8 69.1 76.0 81.7 82.2 79.6 76.3 71.8 87.1 LwA C 54.6 52.8 52.2 52.5 49.8 46.0 42.9 40.5 60.0 Lp D 28.4 36.7 43.6 49.3 49.8 47.2 43.9 39.4 54.7 LpA Legend A Sound Power Levels at Unit's Acoustic Center, Lw B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 2.0 Fan Curve 1200 RPM 1300 RPM 1400 RPM 1.8 1100 RPM 1.6 1000 RPM 1.4 Static Pressure (in. wg.) 1.2 1.0 0.8 0.6 900 RPM 800 RPM 700 RPM 600 RPM SC RP 0.4 500 RPM 5.00 BHP 0.2 400 RPM 1.50 BHP 0.75 BHP 1.00 BHP 2.00 BHP 3.00 BHP 0.0 0.0 0.7 1.4 2.1 2.8 3.5 4.2 4.9 5.6 6.3 7.0 Airflow (CFM - thousands) RPM = 1176 BHP = 4.70 Maximum RPM = 1130 Maximum BHP = 4.70 Note: Please contact application engineering for selections outside the shaded region. SC - System Curve RP - Rated Point Packaged Rooftop Builder 1.39q Page 12 of 12

Venstar Programmable Thermostat T2800 STANDARD FEATURES: Up to 3-Occupied, 1-Unoccupied periods per day, with copy command for easy programming Accepts humidification/dehumidification control module (Venstar part number ACC0430) Auto changeover, 3-stage heat, 2-stage cool for use with gas/electric, heat pump, electric & hydronic heat Configurable for manual changeover, also configurable programmable or non-programmable Adjustable deadbands and timers 3 configurable outputs for maximum flexibility (MISC1, MISC2, MISC3) Extra 6 th and 7 th outputs (beyond our standard thermostat) Smart Fan (keeps the fan from running during unoccupied periods) Smart recovery Display shows both heating an cooling setpoints and room temperature simultaneously All programming and setpoints stored in non-volatile memory, and are never lost in power failure Service filter and service UV lamp indicators Red/Green LED shows whether thermostat is calling for heating or cooling 5-minute compressor time guard and adjustable cycle limit, both defeatable for servicing equipment Outdoor sensor ready with high and low temperature of the day Thermoglow backlit electro-luminous display and backlit color coded keys and legends Accepts accessory IR Remote Control system (Venstar part number ACC0431) Accepts accessory EZ Programmer (Venstar part number ACC0432) For accessory locking cover use (Venstar part number ACC0620) MODEL: T2800 QUANTITY: DATE: JOB NAME: LOCATION: BUYER: ENGINEER: BUYER P.O.#: