ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 2 (RTU1) CESMPU025RHVAV2 Date: February 17, 201 2013 Consolidated Energy Solutions, Inc.
UNIT FEATURES CES TYPE VAV2 Unit features include: 25 Ton MultiPath Dehumidification Rooftop Unit 1 Digital scroll compressor & 1 on/off compressor (R410a) 2 Independent refrigerant circuits Hot gas reheat Outside air, return air, and bypass air damper with DDC actuators Fully modulation DDC actuators for MultiPath control Factory installed custom controls with VAV support Natural gas heat with 4stage control Gas Valve Covers 5 year compressor warranty Stainless steel drain pan sloped ptrap Direct drive BI plenum supply fan with VFD Double wall construction with foam insulation (R13) Permanent frame replaceable media filters (MERV7) 115v convenience outlet (Factory Wired) Phase & brownout protection Factory mounted disconnect Factory installed return air CO2 sensor Field installed items by EMS installer (supplied by others): Supply air temperature sensor in ductwork, space temperature and space humidity (see controls specification)
UNIT SPECIFICATIONS JOB NAME NUMBER OF UNITS AT SITE UNIT MODEL NUMBER PLACEMENT OF UNIT(S) CLIMATIC REGION ALTITUDE / STATION PRESSURE TOTAL UNIT SUPPLY AIR O/A DESIGN CONDITIONS O/A QUANTITY R/A DESIGN CONDITIONS R/A QUANTITY ALDI TYPE P7VAV2 1 (TAG RTU1) CESMPU025RHVAV2 HORIZONTAL, OUTDOOR, SEATED ON ROOF CURB TYPE 2 DESIGN 981 FT / 14.210 PSI 8000 CFM 97.0 DB F / 7. WB F 2100 CFM 75.0 DB F / 4.0 WB F 5900 CFM GROSS UNIT CAPACITY 27. MBH GROSS SENSIBLE CAPACITY 15.04 MBH LATENT CAPACITY 111.3 MBH DEHUMIDIFICATION 100.84 LB/H LEAVING COIL TEMPERATURE.51 F FAN HEAT 8.24 MBH UNIT EER / IEER RATING 11.3 / 12.7 ESP / TSP FILTER / DX COIL FACE VELOCITY UNIT WEIGHT ROOFCURB WEIGHT FAN TYPE FAN MOTOR BHP / RPM / HP 0.35 1.00 WC / 1.47 2.12 WC 384.00 FPM / 274.30 FPM 2931 LBS 250 LBS 27" DIRECT DRIVE BACKWARD CURVED PLENUM 2.92 3.99 / 1011 1110 / 7.5 VFD TYPE OF HEATING NATURAL GAS, 4STAGE INLET GAS LINE 1 MINIMUM/ MAXIMUM INLET PRESSURE.0 WC / 10.5 WC IGNITION NONSTANDING, SPARK, RELIGHT GAS INPUT / OUTPUT / EFFICIENCY 405.00 MBH / 328.10 MBH / 81% ELECTRICAL S/A MOTOR AMPS COMPRESSOR MOTORS RLA CONDENSER FAN MOTORS FLA COMBUSTION MOTORS CONTROL UNIT FULL LOAD AMP (FLA) MINIMUM CURRENT AMP (MCA) MAXIMUM OVERCURRENT (MOP) 208V / 3 PHASE / 0 HZ 1 @ 24.2 AMPS 2 @.1 AMPS 3 @ 5.4 AMPS 2 @ 1.7 AMPS 1 @ 0.9 AMPS 137 AMPS 149 AMPS 175 AMPS CES Condenser Sound Power Level 25 30 Ton 3 125 250 500 1000 2000 4000 8000 LwA Inlet 97 91 89 87 83 80 77 7 89 Outlet 98 95 88 88 84 80 77 75 90 Total 101 9 92 91 8 83 80 79 92 Tested in Accordance with AMCA 300 Revised for new fan test sound data 9/17/08 CES 25 30 Ton Condenser Sound Pressure Level 3 125 250 500 1000 2000 4000 8000 dba Inlet 79 73 72 9 5 2 59 58 71 Outlet 81 77 70 70 2 59 58 72 Total 83 79 74 73 9 5 2 1 75 Sound Pressure Level in a Hemispherical Free Field Distance (ft) = 10
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP 25 TON 0 UNOBSTRUCTED DETAIL A DETAIL B DETAIL C CES 25 TON = 3 CONDENSER FANS TOP VIEW
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP 25 TON 0 UNOBSTRUCTED CONTROL CABINET VIEW
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP 25 TON 0 UNOBSTRUCTED ACCESS DOOR VIEW
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP 25 TON 0 UNOBSTRUCTED SIDE CABINET VIEW
Type 4 Roof Curb CONSOLIDATED ENERGY SOLUTIONS, INC. NOTES: NOT TO SCALE 14" HEIGHT (OTHER HEIGHTS AVAILABLE) ALL DIMENSIONS IN INCHES DATE: REVISION: 08/08/2013 1.00
CONSOLIDATED ENERGY SOLUTIONS, INC. DATE: 08/5/2015 REVISION: 3.0 9 TO CSTB1 () SUPPLY FAN 1 HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 HEAT STAGE 4 COMPRESSOR 2 REHEAT / RECLAIM 1 REHEAT / RECLAIM 2* CONDENSER FAN 1 CONDENSER FAN 2 CONDENSER FAN 3* (When Applicable) R13 R11 24 R14 R12 R15 NC 24 R10 R9 R8 24 R7 VisoGraph Remote Display Remote Display Clear VNR Back View Red Black VNR 1 2 3 Clear Red Black Remove shield wire From both ends Belden 8771 SPACE TEMPERATURE 2 SPACE HUMIDITY OR DP 2 COMMON FOR TEMPS GND FOR HUM AND TRANS 12V HUMIDITY OR DP 2 SPC HUM White Black Shield Supply TO CSTB 1 () FUSE 5X20 70 71 72 73 74 75 7 77 78 79 80 81 82 83 84 85 8 87 88 89 90 91 92 93 109110111 112 113 114 11511117 118 119 120121122 R NOTE: VAV CONNECTIONS ARE FIELD INSTALLED. Expansion Dip Switch CAN Bus LAN Term gnd PWR ON ALARM 100 101 102 103 104 1 2 3 4 1 2 3 7 9 10 11 1 40 41 42 43 44 45 4 47 49 50 21 22 25 5152 53 54 55 5 57 58 59 0 1 28 29 8 R5 ERV CONNECTIONS ARE FACTORY INSTALLED WHEN THE UNIT IS EQUIPPED WITH AN ERV. R4 SPACE TEMP 2, BREAKROOM TEMP, OFFICE TEMP, CO2 2 AND HUMIDITY/ DEWPOINT 2 ARE OPTIONAL AND FIELD INSTALLED. VAV DAMPER VAV FAN SPEED GND FOR AO POINTS VAV BOOSTER HEAT VAV FAN ERV WHEEL ERV POWER EXHAUST ERV BYPASS ERV STORE EXHAUST R3 R2 24 R1 () () TO CSTB1 BELDON 841 14 GAUGE 3WIRE TWISTED PAIR 90 BREAKROOM TEMPERATURE BRK OFFICE TEMPERATURE OFF CO2 SENSOR 2 CO2 84 8 87 88 70 71 72 73 85 7 77 78 79 80 81 icontroller Master RS5 Slave RS5 CAN BUS REMOTE DISPLAY GND GND VNR Term GND Term 97 98 99 100 101 102 103 104 105 Term JMP1 LED1 ALARM Modem Ext. Modem Reset Internal Modem White Black Shield Supply 1 2 3 4 5 7 8 10 11 12 13 14 15 1 40 41 42 43 21 22 23 24 25 1 2 28 29 VISOGRAPH (SEE DETAIL) 1 2 3 VNR SEE TERMINAL CONNECTION DETAIL BELDON 841 14 GAUGE 3WIRE TWISTED PAIR BELDON 841 14 GAUGE 3WIRE TWISTED PAIR FIELD INSTALLED BYPASS AIR DAMPER BAD OUTDOOR AIR DAMPER OAD RETURN AIR DAMPER RAD DIGITAL COMP 1 DC1 VARIABLE FREQ DRIVE VFD GROUND FOR ANALOG OUTS GROUND FOR DIGITAL IN SMOKE DETECTOR EMR AIRFLOW SWITCH AFS CLOGGED FILTER SWITCH CFS LOAD SHED* LS () () () TO CSTB1 TO CSTB1 GND MODBUS COMMUNICATION CONNECTION EXPANSION BOARD 1 9 MAINTAIN POLARITY BLACK 18 GAUGE RED 18 GAUGE Note: USE AN ISOLATED TRANSFORMER 50VA DO NOT SHARE POWER WITH ANALOG OUTPUTS 120Vac Terminal 1 1 Detail GROUND FOR POWERED SENSORS COMMON FOR TEMP SENSORS OUTDOOR TEMPERATURE OAT 0500 PSI TRANS COMP1 SUCT INDOOR HUMIDITY RHDP SPACE TEMP SPACE SUPPLY TEMP SUPLY 1 2 3 4 5 7 8 9 10 11 12 13 14 15 1 icontroller 1 9 CO2 SENSOR CO2 MIX AIR TEMP MIX RETURN AIR TEMP RETN 07 PSI TRANS COMP 2 DISC OUTDOOR HUMIDITY ODRH 5VDC TRANSDUCERS 12VDC HUMIDITY OR DEWPOINT MAINTAIN POLARITY RED 18 GAUGE BLACK 18 GAUGE Note: USE AN ISOLATED TRANSFORMER 50VA DO NOT SHARE POWER WITH ANALOG OUTPUTS 120Vac