Catalog RoofPak Singlezone, Heating and Cooling Systems with Evaporative Condensers

Similar documents
RoofPak Applied Rooftop Systems

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

VariCool VAV Engineering Guide

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

Catalog C: RoofPak Singlezone Heating and Cooling Units. Type RPS/RFS/RCS 18 to 135 Tons MEA N. See page 3

1.1 This section applies to air handling units for HVAC Systems.

THE ULTIMATE ROOFTOP SOLUTION

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Catalog RoofPak Applied Rooftop Systems with Energy Recovery Wheels

Maverick II Commercial Rooftop Systems 15 to 75 tons

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

RoofPak Applied Rooftop Systems Air Handler

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Catalog Maverick II Commercial Packaged Rooftop Systems. Engineered for flexibility and performance

Vision and Skyline Semi-custom Air Handlers

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Catalog Rebel Commercial Packaged Rooftop Systems

Modular Supply Make-Up Air Unit

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

Technical Development Program

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

Catalog Rebel Outdoor Chilled Water Air Handling Systems

TYPICAL CPA SPECIFICATIONS

ALL PRODUCTS BROCHURE

Cultivator & Hybrid Cultivator

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

MAC N-407 Air-Cooled Chiller

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

Catalog Rebel Commercial Packaged Rooftop Systems

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Indirect Gas-Fired Make-Up Air

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

CeilMate TM Series 3 and 4 tons of cooling capacity. Ceiling Mounted Systems. Air Handler with Remote Condensing Unit Air Handler designed for R-410A

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Commercial Packaged Rooftop Systems

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

Advance Release September 2009

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

MACH N-407 Heat Pump Air-Cooled Chiller

DIVISION 15 MECHANICAL

Air-Cooled Split System Condensing Units for Remote DX Coils and Air Handlers. Models RCS 015D to 140D R-410A Refrigerant.

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Models DG and DGX

VERTICAL FAN COIL UNITS

Your Chiller Solution For Efficiency And Reliability. McQuay Dual Compressor Centrifugal Chillers 160 to 2500 Tons

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Product Specifications. Vertical Floor Consoles By First Co.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

C13-Series Engineering Guide

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

JCseries EVAPORATIVE CONDENSER. engineering data

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

VariCool VAV. (Variable Air Volume) 9 to 70 tons Variable Air Volume Water-Cooled and Chilled Water. Unique Solutions for All-Indoor HVAC Projects

Submittal Data Performance Data Electrical Data

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Energy Recovery with Cooling and Heating Model ERCH

SECTION AIR HANDLING UNIT

RHEEM PACKAGE GAS/ELECTRIC

Submittal Summary Page

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

RT-OA TM Rooftop Outdoor-Air (DOAS)

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

VertiCool Aurora Engineering Guide

The Centurion Rooftop GAS/ELECTRIC, TONS ELECTRIC/ELECTRIC, TONS

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

Mission Critical Air Conditioning Systems

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

C-Series. Unique Solutions for All-Indoor HVAC Projects

PACKAGE AIR CONDITIONER

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

Flexible & Innovative. Cooling Solutions

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

48PGD/E/F/L/M/N PG20-28

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

Transcription:

Catalog 219-2 RoofPak Singlezone, Heating and Cooling Systems with Evaporative Condensers Models: RDE/RPE 76 150 Tons RDE SWSI Airfoil (Plenum); SAF Draw-Through Cooling Coil; Filters; Steam or Hot Water Heat RPE DWDI Airfoil; SAF Blow-Through or Draw-Through Cooling Coil; Filters; Electric, Gas, Steam or Hot Water Heat

Table of Contents Introduction.... 3 A New Standard in Rooftop Systems with Evaporative Condensers...3 Agency Listed...3 Nomenclature....3 Features and Options.... 4 Energy Savings.... 6 Evaporative Condenser Energy Savings...6 Features.... 8 Refrigeration Circuit...8 Evaporative Condenser...8 Walk In Service Compartment...9 Cabinet....10 Air Handling Section...10 Electrical and Controls...10 Factory Installed and Wired Options... 11 Condensing Section....11 Air Handling Section...11 Intelligent Equipment...12 Daikin MictroTech III Rooftop Remote User Interface....13 Electrical and Controls...13 Multiple Unit Applications...13 Field-Installed Roof Curbs...13 Optional Water Treatment...14 Application Considerations.... 17 General...17 Location and Curb/Rail Support....17 Filters...17 Acoustics...18 Economizer, Return Fan and Exhaust Fan Application...19 Variable Air Volume (VAV)... 20 MicroTech III Control...20 Unit Operating Range...21 Fan Operating Range...21 Indoor Fan and Motor Heat, Blow-Through vs. Draw-Through Cooling... 22 Table of Contents Recommended Clearances....23 Service Clearance...23 Cooling Coil, Heat, and Supply Fan Service Clearance....23 Overhead Clearance...23 Ventilation Clearance...24 Control and Power Wiring...25 Altitude Adjustments...25 Furnace Performance...26 Freezing Concerns....26 Spray System....26 Hot Water and Steam Coils...26 Water Treatment...26 Condenser Water Connections...27 Selection Instructions...28 Physical Data... 31 Cooling Capacity Data... 32 Heating Capacity Data........................ 38 Gas Piping Schematic... 42 Component Pressure Drops... 43 Fan Performance Data... 44 Return Fans & Exhaust Fans...44 DWDI Supply Fans...45 SWSI Plenum Supply Fans....47 Dimensional Data... 48 Section Options and Locations...48 Typical Dimensions...51 Electrical Knockout Locations...53 Piping Entrance Locations...54 Roof Curbs... 55 Electrical Data.... 58 Supply Power Wiring....60 Unit Weights... 61 Fan Motor Weights...63 Roof Curb Weights...63 Engineering Guide Specification... 64 CAT 219-2 ROOFPAK PACKAGED SYSTEMS 2 www.daikinapplied.com

Introduction A New Standard in Rooftop Systems with Evaporative Condensers Introduction 76 through 150 tons Full factory operation test 100% make-up air, dehumidification, VAV or CV operation Modular construction and customized application flexibility Multiple fan, coil, filter and heat selections. High efficiency compressor and coil combinations Factory integrated and commissioned MicroTech III advanced DDC control system Daikin s Open Choices feature provides building automation system integration using BACnet MS/TP, BACnet IP, BACnet Ethernet, or LonTalk communication protocol options Durable, double-wall construction with access doors on both sides of each section Heavy-duty evaporative condenser designed for easy maintenance with a walk-in service compartment Blow-Through configuration for high sensible cooling and quieter operation Draw-Through configuration for high latent cooling or high humidity applications Agency Listed MEA 368-93-N Manufactured in an ISO-Certified Facility Nomenclature R P E - 150 C S E RoofPak Unit Configuration P = Blow-Through Cooling D = Draw-Through Cooling Heat Medium A = Natural Gas E = Electric S = Steam W = Hot Water Y = None (Cooling Only) Evaporative Condensers Nominal Capacity (Tons) RPE, RDE: 076, 089, 100, 110, 130, 140, 150 Cooling Coil Size S = Standard (Low Airflow) L = Large (High Airflow) Design Vintage www.daikinapplied.com 3 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Features and Options Features and Options 11 2 9 10 6 5 1 MicroTech III Control System Factory-installed and tested to minimize costly field commissioning Open Choice feature provides building automation system integration using BACnet MS/TP, BACnet IP, BACnet Ethernet, or LonTalk communication protocol options State-of-the-art keypad interface allows easy adjustment of Direct Digital Control functions, bi-directional communications, stand-alone or network operation* Optionally: add the Intelligent Equipment control solution, which provides real-time data streams for benchmarking performance, monitoring system operations and implementing remote diagnostics and control 2 Airfoil Fans More energy efficient and quieter than forward curved fans. Double width, double inlet (DWDI) or single width, single inlet (SWSI) plenum fans 3 Durable Construction Pre-painted exterior cabinet panels pass 750 hour ASTM B117 Salt Spray Test for durability Heavy-duty R-6.5 insulation minimizes heat loss for reduced energy costs Double-wall construction protects insulation and provides a wipe clean surface to inhibit microbial growth Stainless steel, sloped drain pans eliminate standing water and provide long service life Full unit base rail with heavy-duty lifting lugs provide single piece rigging of units up to 150 tons 4 SuperMod High Turndown Gas Burner Full 20:1 turndown and multiple sizes enable precise temperature control at reduced design, installation, and life-cycle costs Maintain comfortable tenant environment in VAV, 100% make-up air, and dehumidification applications 5 Hinged Access Doors On both sides of every section for easy access to all components. Single lever latch and door holders provide easy entry and support routine maintenance. Double-wall construction protects insulation during maintenance. 6 Blank Sections Available throughout the unit to factory-mount air blenders, carbon or charcoal filters, sound attenuators, humidifiers, or other specialty equipment. Allow customization for maximum system performance and efficiency. 7 Walk-in Service Compartment Ventilation fan with a manual shutter allows conditioned air into the service compartment for comfortable servicing in hot weather Lights, electrical outlet, main control panel, spray pump, water connections, and optional water treatment system Drain pan under the water piping and a raised floor grate in the pan keeps the walking area dry. Single field connections to makeup water and drain lines CAT 219-2 ROOFPAK PACKAGED SYSTEMS 4 www.daikinapplied.com

Features and Options 8 3 12 1 7 4 8 Modular Flexibility Allows you to specify the unit you want, optimized for high energy efficiency, good IAQ, and quiet operation 100% make-up air, dehumidification, CV, and VAV operation Blow-Through cooling coil configuration (shown) provides higher sensible cooling, a quiet tenant environment, and energy savings Draw-through cooling coil configuration provides higher latent cooling for make-up air systems or systems with high humidity loads Multiple filter, fan, coil, and heating options and sizes to match system requirements. Extended face area filters and coils reduce system pressure drops and improve efficiency Multiple high efficiency compressor and coil combinations match 9 Return or Exhaust Fans Return fans can provide better building pressure and ventilation control as return duct pressure drop increases. Exhaust fans can save energy as return duct pressure drop requirements decrease. 10 Factory-Mounted Variable Frequency Drives Control fan motor speed for lower fan operating costs and sound levels in VAV systems. 11 Economizer Outside air enters from both sides, improving mixing for better temperature control. DesignFlow Precision Outdoor Air Measurement and Control System accurately measures and maintains outdoor air quantity. Patented UltraSeal low leak dampers minimize air leakage, reducing energy costs. Generous face area intakes/ outlets and control dampers reduce system pressure drops, improving efficiency. 12 Evaporative Condensing Section Open design allows easy access to compressors and refrigerant piping Unique rail support system allows the roof deck and insulation to help block compressor noise from entering the building Condenser tube bundles. Replaceable, slide out, sectional, sloped stainless steel sump. Heaviest piece weighs less than 175 pounds Entire spray chamber is enclosed in stainless steel Replaceable mist eliminators Replaceable air inlet screens Vertical discharge propeller condenser fans with service guards reduce noise PVC spray system with spray pump, water treatment connections and float control automatically maintains acceptable water levels www.daikinapplied.com 5 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Energy Savings Evaporative Condenser Energy Savings Energy Savings Air cooled condensers can only reject heat to the ambient dry bulb as the condenser air passes over the condenser surface. Typical design dry bulb temperature is often considered to be 95 F. However, actual rooftop dry bulb conditions are usually much greater due to solar heat on a dark roof. See Figure 1. Evaporative condensers use a cooling spray of water that evaporates and cools the condenser air down toward the typical ambient wet bulb temperature of 75 F. SeeFigure 2. Evaporative condensers, therefore, reject heat to colder temperatures and operate at lower condensing temperatures. Therefore less compressor work and energy are required. This allows compressors in an evaporative condensing unit to operate at lower condensing temperatures and consume 25 40% less electricity than comparable air cooled units, especially at design conditions. Refer to Table 1. Figure 1: Air-Cooled Condenser Figure 2: Evaporative Condenser Table 1: Air-Cooled vs. Evaporative-Cooled Condensers Design Conditions ARI Design Conditions Ambient Temperature Condensing Unit kw per ton Condensing Temperatures Air Cooled 95 /75 F 1.15 1.20 125 135 F Evaporative Cooled 95/75 F 0.84 0.88 105 115 F Desert Design Conditions Air Cooled 110 /72 F 1.35 1.40 135 145 F Evaporative Cooled 110 /72 F 0.82 0.86 102 112 F Rooftops with Evaporative Condensers Save Money 1. Savings in Electrical Consumption Costs Both consumption and demand usually drive the electrical costs for large, non-residential customers. Electrical consumption is the total energy consumed and is usually measured in kw Hours. Several factors influence consumption, including unit efficiency, operating hours, and load profile. Daikin s Energy Analyzer computer program is the ideal tool for estimating energy consumption for a given building. 2. Savings in Electrical Demand Costs Electrical demand is the peak energy consumed in a billing cycle and is usually measured in kw. Demand costs associated with air-cooled and evaporative-cooled rooftops are relatively easy to compare. a. The 25 40% reduction in peak design condensing unit kw translates into a 25 40% savings in condensing unit demand costs. Based on utility rate structures, this can be a substantial savings. b. In addition, Daikin offers airfoil supply and return fans that reduce design bhp and air handler demand costs by up to 20%. 3. Savings in Installation Cost Rooftop ampacity and electrical service costs are proportional to design kw. A 25 40% reduction in condensing unit design kw translates into smaller and less expensive wires, disconnects and transformers that feed the rooftop units. Daikin s airfoil supply and return fans often save one or two motor sizes and further reduce the required electrical service. Typical Savings vs. Air-Cooled Rooftop Systems To illustrate the savings generated by evaporative condensing, consider a two-story shopping mall using several 125-ton VAV rooftop units and occupied 365 days a year. Assume external static pressures of 2.5" for each supply duct and 0.5" for return ducts. Table 2 through Table 4 show the Daikin RPE evaporative condenser rooftop if this mall is located in the Los Angeles, New York and Las Vegas. CAT 219-2 ROOFPAK PACKAGED SYSTEMS 6 www.daikinapplied.com

Energy Savings Table 2: Comparison of Evaporative and Air-Cooled Condensing for the Los Angeles Area Mall Figure 3: Comparable Energy Performance to Water- Cooled Chillers Conditions Air-Cooled Daikin RPE Design Ambient Dry Bulb/Wet Bulb 95 F/72 F 95 F/72 F Electrical Consumption Rate (per kw Hour) $0.15 $0.15 Electrical Demand Rate (per kw) $24 $24 Condensing Unit Efficiency (kw/ton) 1.15 0.85 Electrical Cost $30,200 $22,100 Percent Savings 27% All shopping mall energy analysis and comparison charts provided in this document have been generated using Daikin Energy Analyzer software. Table 3: Comparison of Evaporative and Air-Cooled Condensing for the New York Area Mall Conditions Air-Cooled Daikin RPE Design Ambient Dry Bulb/Wet Bulb 95 F/75 F 95 F/75 F Electrical Consumption Rate (per kw Hour) $0.11 $0.11 Electrical Demand Rate (per kw) $18 $18 Condensing Unit Efficiency (kw/ton) 1.15 0.88 Electrical Cost $17,860 $12,375 Percent Savings 31% All shopping mall energy analysis and comparison charts provided in this document have been generated using Daikin Energy Analyzer software. Table 4: Comparison of Evaporative and Air-Cooled Condensing for the Las Vegas Area Conditions Air-Cooled Daikin RPE Design Ambient Dry Bulb/Wet Bulb 110 F/72 F 110 F/72 F Electrical Consumption Rate (per kw Hour) $0.07 $0.07 Electrical Demand Rate (per kw) $8 $8 Condensing Unit Efficiency (kw/ton) 1.40 0.85 Electrical Cost $19,042 $11,351 Percent Savings 40% All shopping mall energy analysis and comparison charts provided in this document have been generated using Daikin Energy Analyzer software. Daikin Energy Analyzer Software Program Daikin Energy Analyzer is the perfect tool for quantifying the savings that can be generated by evaporative condensing. Energy Analyzer software can model energy consumption for almost any type of building based on local climate and utility costs. Using Energy Analyzer to Quantify Savings Go To The Primary System Screen (Figure 4) 1. Click On The Condensing Unit 2. Click On Air Cooled or Evap Cooled 3. Check The Defaults For access to Daikin Energy Analyzer Software, contact your local Daikin representative for a copy. To locate your Daikin representative, visit DaikinApplied.com or call (800) 432-1342. Figure 4: Energy Analyzer - Primary System Screen RPE Energy Costs are Competitive Using the 0.85 kw/ton condensing unit efficiency from the previous example, Figure 3 shows a comparison of a Daikin RPE evaporative condenser rooftop system with a 0.55 kw/ ton water-cooled chiller system. In this case, we assumed that the chiller system would have constant flow pumps and that it unloads to 0.46 kw/ton. As shown in Figure 3, the energy performance of the two systems is very comparable, with the RPE offering a significant part load advantage and the chiller offering a small full load advantage. Given that most air-conditioning systems operate at 60% load or less over the great majority of a typical year, the Daikin RPE may be the best energy savings investment. www.daikinapplied.com 7 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Features Daikin RPE and RDE units contain the same air handler construction and controls as Daikin RPS and RDT applied rooftop units. For more detail, refer to RPS Catalog 214 and RDT Catalog 217. For a copy of these catalogs, contact your local Daikin representative or visit DaikinApplied.com. Refrigeration Circuit Open condenser design allows easy service access to compressors and refrigerant piping Multiple high efficiency Copeland Discus compressors mounted on isolators with crankcase heaters, positive displacement oil pump, low oil pressure protection control, 3-leg internal motor protection and cylinder unloaders for up to 8 steps of capacity control Dual refrigerant circuits include manual shut off valves on the suction, discharge and liquid lines, accessible sight glass, filter drier and solenoid valves (expansion valves are included in the air handler section). The controls include high and low refrigerant pressure protection control switches, manual control switch, and manual pump down switch Compressors are allowed to operate down to 45 F ambient, where economizer free cooling operation takes over Evaporative Condenser Unique rail support system allows the roof deck and insulation to help block compressor noise from entering the building Condenser tube bundles are constructed of corrosionresistant copper tubes, stainless steel casing, and polymer tube sheets The sloped, stainless steel sump is divided into multiple sections that slide out for easy replacement. The heaviest section weighs less than 174 pounds The entire spray chamber is constructed of corrosionresistant stainless steel Replaceable mist eliminators between the tube bundle and condenser fans minimize water consumption Replaceable air inlet screens keep sunlight out of the sump and help prevent microbial growth Direct drive condenser fans eliminate the service expense associated with belts and sheaves Vertical discharge, propeller condenser fans with service guards reduce horizontal-radiated noise 3-phase, severe duty, totally enclosed condenser fan motors with current sensing overload protection and permanently lubricated bearings support extended product life PVC spray system includes spray pump, water treatment connections and float control that automatically maintains acceptable water levels. Replaceable, clog resistant nozzles spray water across a 150 arc and completely wet the coil surface for improved performance. Single field connections to make-up water and drain lines can reduce installed cost Features Figure 5: Standard RPE and RDE Spray System Optional Cyclone Separator Optional Water Treatment System Hand Valve See Figure 15 on page 16 for Water Treatment Enhancements NOTE: The cyclone separator is on a side stream. A hand valve controls water flow. The hand valve should be opened until the inlet pressure to the separator is about 10-20 psi as determined by the factory-installed gauge. This will yield about 15-30 gpm of blowdown whenever the blowdown solenoid opens. Hose Bib with Manual Shut Off Valve Automatic Float Controlled Intake Valve Drain Optional Bleed-Off Solenoid Valve Spray Intake Water Sump Removable Screen Pump CAT 219-2 ROOFPAK PACKAGED SYSTEMS 8 www.daikinapplied.com

Features Figure 6: Corrosion Resistant Stainless Steel Fan Decks with Severe Duty Motors and Corrosion-Resistant Fans PVC Spray Tubes Stainless Steel Spray Enclosure Figure 7: Easy Service Access Stainless Steel Sump Polymer Tube Sheets Copper Tube Bundles Walk In Service Compartment All routine refrigerant service can be performed inside the walk-in service compartment away from compressor noise and outdoor conditions Contains marine lights, electrical outlet, main control panel, spray pump, water connections, and optional water treatment system A thermostat-controlled ventilation fan turns on at 75 F and a manual shutter draws conditioned air into the service compartment for comfort. These features provide more comfort for service even in hot weather A hose bib is provided as standard in the make up water line to aid in condenser cleaning A drain pan under the water piping and a raised floor grate in the pan help keep the walking area dry Optional unit heater for cold climate use No compressor noise is generated in the work area Sight glass, filter driers, solenoid valves and charging valves are in the service compartment Figure 8: Walk-In Service Compartment Marine Lights Exhaust Fan Access Doors on Both Sides Walk In Service Compartment Replaceable Sump Easy Compressor Access Replaceable Nozzles with 150 Spray Arc Main Control Panel Charging, Suction, Discharge & Liquid Schrader Connections Optional Unit Heater Hot Gas Bypass Valves Solenoid, Sight Glass & Filter Drier Raised Floor Grate and Drain Pan Space for Water Treatment www.daikinapplied.com 9 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Features Cabinet Weather resistant skin is made of pre-painted, galvanized steel that successfully withstands a 750 hour salt spray test. The service compartment walls are double wall with R6.5 insulation sandwiched between the outer skin and inner liner. The air handler cabinet is also available with double-wall construction with R6.5 insulation Full-sized, double-wall, hinged access doors are provided on each side of the section, complete with a single lever latch Heavy gauge galvanized steel base with a formed recess sits on the gasketed curb and provides a weather-tight seal. The base also includes strategically placed lifting brackets to allow balanced cable or chain hook lifting Air Handling Section Factory piped, charged and tested refrigeration system comes complete with an aluminum fin, copper tube, DX coil with expansion valves and distributors. Each distributor tube is wrapped in plastic to help prevent refrigerant leaks DX coils feature interlaced circuiting to keep the entire coil face active during all capacity steps and eliminate the air bypass associated with face split coil designs. An intermediate drain pan collects condensate from the top half of the coil. Drain tubes run from the intermediate drain pan to the sloped, galvanized [optional stainless] steel drain pan High efficiency airfoil supply fans require less bhp and generate less noise than forward curved fans at the medium static pressures typical of large VAV units. Fans are available in both DWDI (housed) and SWSI (plenum) fan arrangements. For more information, refer to page 19 Insulated supply and return air plenums with bottom [optional horizontal] openings reduce ducted noise levels. A double wall option is available with perforated liners in these sections Figure 9: Airfoil Fans Electrical and Controls Single source power with optional, non-fused disconnect switch with control panel door interlock Individual short circuit protection for each compressor, supply fan and return fan motor. Condenser fan and exhaust fan motors are also provided with short circuit protection All control panel wiring is labeled per the wiring diagram and all 115 575 volt wiring is housed in conduit or metal raceways Daikin s Open Choices feature provides building automation system integration using BACnet MS/TP, BACnet IP, BACnet Ethernet, or LonTalk communication protocol options. This allows any building automation system (BAS) to communicate with MicroTech III over an industry standard network and obtain access to the operating status, all set points, and alarms LONMARK certified discharge air control (DAC) or space comfort control (SCC) communication options BACnet compliant communication options MicroTech III is available in several temperature control modes LONMARK certified Space Comfort Control [SCC] for single zone, constant volume applications; including 100% make-up air application LONMARK certified Discharge air temperature control [DAC] for VAV or constant volume applications. Static pressure control of the supply fan and return/exhaust fan can also be included Time clock, lead lag, morning warm up, night set back, economizer pre-cool and flexible reset are all standard Published integration instructions for both forms of communication Unit mounted keypad and 4-line by 20-character display provide an enhanced user interface Compressor head pressure control that reliably cycles the condenser fans from sump temperature down to 45 F ambient Duct high pressure safety on all VAV units Figure 10: MicroTech III Keyboard CAT 219-2 ROOFPAK PACKAGED SYSTEMS 10 www.daikinapplied.com

Factory Installed and Wired Options The RPE and RDE contain the same air handler construction and controls as the RPS and RDT units. For complete detail refer to RPS Catalog 214 and RDT Catalog 217. For a copy of these catalogs, contact your local Daikin representative or visit DaikinApplied.com. Condensing Section Compressor spring isolation with suction and discharge line vibration absorbers Extra compressor unloaders that provide 6 stages (size 76 100) or 8 stages (size 110 150) of capacity control Compressor part winding start to reduce inrush current Replaceable core filter driers Hot gas bypass on one or both refrigerant circuits Electric sump heater that helps prevent the sump from freezing in cold weather. Heat tape is also included for the sump drain and supply water lines 1.5 kw electric unit heater and ambient ON-OFF thermostat for the service compartment Air Handling Section Multiple fan and coil options optimize reliability, efficiency, sound performance and first cost for varying cfm per ton operation. Units can be selected for make-up air applications Economizer systems come standard with outdoor and return air damper leakage rates of less than 1.5 cfm/ft 2 at 1" static pressure. Economizers are available with the following value add options Patented DesignFlow minimum outdoor air measurement and control system that is independently certified to control ventilation air within +/- 5% of set point from 1,594 to 37,126 cfm of outdoor air Static air mixers that provide optimum uniformity in mixed air temperature and reduce the chances of freezestat trips and localized coil freezing Economizers are available with return or exhaust fans SWSI airfoil return fans provide better building pressure and ventilation control on ducted returns Multiple propeller exhaust fans may save energy on low-pressure drop, ceiling plenum returns (see Economizer, Return Fan and Exhaust Fan Application on page 19) Variable frequency RAF and SAF drives for VAV control (exhaust fans always include a variable frequency drive) Supply and return fan belt guards Spring isolation (with optional seismic construction) Cooling coils are available in blow-through and drawthrough arrangements to optimize the use of fan and motor heat. See Figure 21 on page 22. Factory Installed and Wired Options In blow-through arrangements (RPE only), fan energy pre-heats the mixed air temperature before entering the cooling coil, providing greater sensible capacity and colder supply air temperature for a given compressor capacity In draw-through units, fan energy re-heats the air leaving the cooling coil. Draw-through systems provide greater latent cooling capacity, lower sensible heat ratios Gas and electric heat are available on RPE units with the following options Two-pass drum and tube heat exchanger with, fully modulating, FM approved burners for 3-to-1 or 20- to-1 (patented SuperMod ) turn down and optional IRI approval. Drum and tube heat exchangers feature all stainless steel construction. Selections are available to handle up to 100 F temperature rise Low watt density, nickel chromium electric heaters with branch short circuit, automatic reset and manual reset safety 1 or 2-row hot water or jet distributing steam coils with optional valve control and optional freezestats Supply fan sound attenuators with or without mylar coating of the acoustic insulation (RPE only) Generous face area, 2" pleated, 30% efficient panel filters and/or 65 or 95% cartridge filters are available Cartridge filters can be in the final, last in air flow position for hospital or laboratory applications (RPE only) Blank sections can be added for field-installed devices such as humidifiers and integral face and bypass coils Ultraviolet Germicidal Irradiation (UVGI) lamps are available factory installed in all RDE/RPE units to cleanse cooling coils and drain pans. The UVGI lamps irradiate the cooling coil and drain pan surfaces with light in the 254-nanometer wavelength of the light spectrum (UV-C). UV-C light has been proved effective in killing most bacteria, molds and viruses in both laboratory and practical application. In addition, the continuous cleansing action of the UV-C light also serves to continuously clean the coil and drain pan, improving long-term performance and reducing coil/drain pan maintenance. Daikin equipment and UVGI lights include (ETL) safety agency certification Figure 11: DesignFlow www.daikinapplied.com 11 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Factory Installed and Wired Options Intelligent Equipment Intelligent Equipment (IE) from Daikin Applied is a secure, cloud-based controls solution that enables delivery of equipment and/or system information to customers via web or mobile devices. A power measurement module and communications gateway installed on Daikin equipment enables the unit to be directly connected to the Internet via wireless (cellular, WI-FI) or local area network (LAN), providing management, monitoring control analysis and decision-making functionality for Daikin rooftop systems and the facility. Features Remote monitoring and control of Daikin rooftop units Remote servicing capabilities Integration to the Energy Star Portfolio Manager Advanced data analytics including equipment performance, financial performance and building Comfort Index metrix based on ASHRAE Standard 55-2010 Dynamic user dashboards with photo-realistic graphics and responsive-design interface optimized for users mobile devices, tablets or PCs Secure, role-based user access Benefits Informed decision-making Increased equipment efficiency 24/7 monitoring capability Real-time equipment information Accelerated equipment payback Historical performance data Can be used with, or without, an existing building automation system (BAS) Figure 12: Intelligent Equipment Dashboards Customer Dashboard Technician Dashboard CAT 219-2 ROOFPAK PACKAGED SYSTEMS 12 www.daikinapplied.com

Factory Installed and Wired Options Daikin MictroTech III Rooftop Remote User Interface Each remote user interface is identical to its unit-mounted counterpart and offers the same functionality, including: Touch sensitive key pad with a 4 line by 20 character display format Digital display of messages in English language All operating conditions, system alarms, control parameters and schedules are monitored Features Can be wired up to 1,200 feet from unit for flexibility in placing each remote user interface within your building Unit-mounted switch enables the remote user interface during normal operation or the unit user interface for maintenance and service Benefits Allows you to access the user interface for each unit from one location, inside the building. Users need to learn one format because the remote user interface is identical to the unit-mounted version. Multiple Unit Applications For applications in which multiple units are connected in a common duct system, it is important to control all units from a common duct static pressure sensor and to control all operating units in unison. Centralized duct static pressure control can be accomplished through communication with the BAS network. Field-Installed Roof Curbs Constructed in accordance with NRCA guidelines using 12-gauge galvanized steel Fits inside the unit base around the perimeter of the air handling section and service compartment Duct frames are provided to allow duct connections to be made to the curb before the unit is placed. The unit seals to the duct frames Ship loose gasket seals between the unit and curb Separate condensing unit support rail allows an open condensing unit design and minimizes compressor noise and vibration transmission through the roof Figure 13: Remote User Interface Electrical and Controls Factory-powered service outlets complete with its own disconnect, short circuit protection and ground fault protection Smoke detectors in the supply and/or return air openings Marine lights in the supply and/or return/exhaust fan sections www.daikinapplied.com 13 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Factory Installed and Wired Options Optional Water Treatment All evaporative condensing products require water treatment systems for proper operation. The water treatment system serves the following purposes: Controls organic contamination Reduces condenser fouling and corrosion Reduces cleaning frequency and water usage Overview Daikin RPE/RDE units come with a spray system, pump, sump strainer, automatic float controlled intake, and manual blowdown as standard. Daikin evaporative condenser rooftop systems can provide as much as 44% in compressor energy savings compared to competitive air-cooled rooftop units. Until now, chemical water treatment was required to prevent scale build-up and microbial growth in the moisture laden condenser section of these units. Daikin now offers an alternative: a chemical-free water treatment system that can substantially lower the cost of water treatment, eliminate the use of hazardous chemicals and simplify the water treatment process. Figure 14: Water Treatment System Eliminates Chemical Costs This system eliminates the use of hazardous chemicals, including scale inhibitors, biocides and corrosion inhibitors. Typical yearly savings range from $1,800 to $2,700 per year for a 150 ton evaporative condenser rooftop unit. Minimizes Corrosion Daikin uses only stainless steel, copper and PVC in its evaporative condenser plumbing. Clean, chemical-free water, saturated with precipitates by this system, does not attack these materials. Blowdown and Water Consumption Controlled blowdown is required on Daikin RPE/RDE units as it should be with all evaporative condensing products. It involves draining off a portion of the highly concentrated water from the bottom of the sump and replacing it with lower concentration make-up water to prevent scale. Scale protection is required because the evaporation process leaves behind solids (scale) that will coat the heat exchanger surfaces and sump. This reduces the capacity, efficiency, and life expectancy of the equipment. Manual blowdown occurs whenever the spray pump operates and a manual valve adjusts flow. This inevitably bleeds off too much [increased water costs] or too little [risking scale build up] water. Controlled bleed off is included with the Daikin water treatment controller. The concentration of scale forming solids is measured by water conductivity and the control opens or closes a solenoid to allow the proper amount of bleed off. The conductivity set point should be adjusted based on water analysis to maintain a desired cycles of concentration. Theoretical water consumption required for proper heat rejection is 1.8 gallons per ton hour. All of this water evaporates and none goes into the sewer. An additional 0.6 to 0.9 gallons per ton hour is also required for make up and blowdown. The exact amount should be determined by water analysis. The RPE/RDE includes a float valve and solenoid that automatically refills the sump as required. Blowdown must be handled in accordance with local codes and normal procedures are as follows: Daikin non-chemical water treatment system - used blowdown water often can be drained to the storm sewer (check local codes) Field installed chemical water treatment system - used blowdown must not be drained to the storm sewer and is usually drained to the sanitary sewer (check local codes) Because most water utilities charge for both intake and sanitary sewer water flows based on intake meter readings, sanitary sewer charges may be reduced if sewer flow is proven to be less than water intake. Daikin offers both intake and blowdown water meters to document reduced sewer flow [confirm details with your local utility]. These meters are not included in the basic water treatment option. Reduces Water Consumption Costs With this system, supply water typically can be cycled through the evaporative system six times before it must be drained off to prevent scale. With chemical treatment systems, only three to four cycles are possible. This represents a water consumption savings of about 10%. CAT 219-2 ROOFPAK PACKAGED SYSTEMS 14 www.daikinapplied.com

Factory Installed and Wired Options A Cleaner Environment Daikin evaporative condenser rooftop units equipped with a chemical-free water treatment system contribute to a cleaner environment by reducing energy usage and by eliminating the introduction of hazardous chemicals into the waste stream. Reduces Sanitary Sewer Costs Savings in sanitary sewer costs can be even more dramatic. That s because this system requires no sanitary sewer usage all condenser water, including blow-down, usually can be drained to the storm sewer or used for irrigation (check local codes). This represents a 10 to 15% water cost savings if sewer flow is measured (i.e., credit is given for the water that evaporates during the cooling process) and even more if it is not. Chemical-Free Benefits As a scale inhibitor, the Daikin chemical-free system uses pulsed electromagnetic fields to neutralize the charge on particles suspended in water, causing them to attract to each other rather than to form scale on plumbing and heat transfer surfaces. The particles grow, encapsulate any microorganisms, and precipitate out of solution as a powder. A cyclone separator removes the powder from the system during the blow-down process. For microbial control, the system uses pulsed electromagnetic fields to attack the cell walls of any microorganisms that are not encapsulated. As a result, TBC is typically 75% less than with chemical treatment systems. In fact, total bacterial count (TBC) is so low that biofilms are normally prevented. Easy Maintenance The Daikin chemical-free water treatment system has no moving parts and is easy to maintain. Inspection and monitoring are only required once or twice per quarter, as follows: Check the water conductivity (and clean conductivity sensor if necessary) Check total bacteria count (TBC) Inspect general operation and controller settings LEED Point Available Chemical-free water treatment systems qualify for a LEED point under the Innovation heading, per a Credit Interpretation Request posted on the USGBC website. 12 to 18 Month Payback The superior performance of the Daikin chemical-free system costs a little more up front than a chemical feed system, tanks, and pumps. However, the water and chemical savings generally provide a 12 18 month payback, in addition to the financial benefit of cleaner water and heat transfer surfaces. Table 6 below shows typical yearly water treatment cost savings when using this system on a Daikin 150-ton evaporative condenser rooftop unit. Table 7 points out that, while there are water treatment costs associated with evaporative condensers, they are typically small compared to the total energy savings provided by a Daikin evaporative condenser unit. Table 5: Yearly Cost Savings Typical Chemical Treatment System Los Angeles New York City Water Cost $1,067 $628 Chemical Cost $2,000 $2,000 Total $3,067 $2,628 Daikin Chemical Free Treatment System Water Cost $923 $539 Chemical Cost $0 $0 Total $923 $539 Chemical-Free Savings $2,144 $2,089 Percent Savings 70% 79% Table 6: Yearly Cost Savings with Rooftop Unit Competitive Air Cooled Unit Los Angeles New York City Energy Cost $30,200 $17,860 Water Treatment $0 $0 Total $30,200 $17,860 Daikin RPE Unit with Chemical Free Treatment System Energy Cost $22,100 $12,375 Water Treatment $923 $539 Total $23,023 $12,914 RPE Cost Savings $7,177 $4,469 Percent Savings 24% 28% NOTE: All energy analysis and comparison charts provided above are estimates and have been generated using Daikin Energy Analyzer software. Actual customer results may vary. For access to the Daikin Energy Analyzer software, contact your local Daikin sales representative. www.daikinapplied.com 15 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Factory Installed and Wired Options Figure 15: Daikin Water Treatment Option Sump water coil-pipe treatment module Makeup water transformer To Spraybar Sump water transformer To Spraybar Flowmeter Cyclone seperator hand valve (hidden) Cyclone seperator Sump overflow Conductivity sensor Conductivity controller Makeup water control valve Auto purge controller Heat-tape all components from customer connection point to makeup water control valve Makeup water coil-pipe treatment module Ball valve actuators for blowdown Makeup water connection point to sump tank. Side stream connection to sump tank Cleanout Customer makeup water connection point Manual shutoff Sump Pump Blow down and drain System drain valve and actuator CAT 219-2 ROOFPAK PACKAGED SYSTEMS 16 www.daikinapplied.com

Application Considerations The RPE and RDE require many of the same application considerations as Daikin RPS and RDT units. More detail is provided in RPS Catalog 214 and RDT Catalog 217. For a copy of these catalogs, contact your local Daikin representative or visit DaikinApplied.com General Intended for normal HVAC use. Consult factory if cataloged operating range is exceeded, such as make up air. Compressor cooling below 45 F is not allowed Rig the unit in accordance with the instructions provided in the Installation Manual IM 791. Split units are available to reduce rigging weight and may be required if the total length exceeds 52 ft. For a copy of IM 791, contact your local Daikin representative or visit DaikinApplied.com Fire dampers may be required by code. They are not included Qualified Start-up of the unit in accordance with the IM 791 is required Clean off any road chemicals, such as winter salt, when the unit is received Proper water treatment must be provided before unit start-up Filters Application Considerations Filters should be replaced on a regular basis to avoid excessive pressure drop increases, especially on high efficiency cartridge filters Fan selection must consider dirty filter losses. Using a filter pressure drop midway between clean and dirty values is recommended unless maintaining minimum cfm is critical Daikin RPE units offer last in air stream final filters. They require special consideration The Daikin design uses full double-wall construction down stream of the final filters Cooling coils must be in the draw-through position. Final filters down stream of gas and electric heaters must be rated for 500 F temperatures. Maintenance personnel must use properly-rated replacement filters Location and Curb/Rail Support The structural engineer must verify that sufficient roof strength is provided Maximum unit pitch is 1/16 in. per foot. Curbs or supporting rails must be rigidly supported along the entire length of the unit to prevent deflection that results in door interference Gaskets must be installed between the curb and the unit, per IM 791 Curbs must be installed per NRCA guidelines See Roof Curbs on page 55 Avoid locating the unit near any heat source, exhaust, smoke stack, or any source of air-borne particles or chemicals Local codes must be followed regarding fastening the unit to the curb/rail and the curb/rail to the building. This is especially critical in higher risk, hurricane or seismic zones Refer to the Acoustics on page 18 to avoid noise and vibration problems Daikin curbs include supply and return opening support frames and perimeter channels that seal to the unit as it is placed on the curb. Therefore, duct connections can be made to the curb before the unit is placed www.daikinapplied.com 17 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Acoustics Ducted and radiated sound power ratings are available from your local Daikin sales representative. The designer is responsible for addressing these sound levels. The following guidelines will help to achieve the desired sound levels in the occupied space. Locate the unit as far away from sound sensitive areas as possible. Refer to the Location and Curb/Rail Support on page 17 Minimize supply and return fan TSP and select the fan as close to peak efficiency as possible. Avoid the do not select areas on the fan curve. Daikin offers several different fans per model size to allow for various design conditions. Refer to Fan Performance Data on page 44 Three different sound paths from the unit to occupants and/or neighbors must be considered: 1. Radiated path Use a concrete deck or pad when the unit must be located over sound sensitive areas. If this isn t possible, provide extra acoustical insulation under the condensing unit Only the supply and return ducts, and the essential plumbing and electrical connections should penetrate the acoustical insulation or roofing below the unit. The outside perimeter of the ducts must be sealed after they are installed If a built-up roof with metal decking is used, then the area inside the curb perimeter requires special attention: Provide an inverted 6" channel around the inside perimeter of the curb and seal to the curb Acoustical insulation must be installed above the decking and the 6" channel 2. Vibration path Locate the unit s center of gravity close to a main support beam to minimize roof deflection and vibration transmission into the building Daikin offers 2" deflection, supply and return fan spring isolation or rubber in shear isolators. The rubber in shear isolators should only be used when vibration isolation is clearly not required in the rooftop, such as when the unit is mounted on spring isolated curbs, spring isolated rails or the ground Daikin offers compressor spring isolation, including the necessary refrigerant line vibration eliminators Internal spring isolation options may be insufficient for some applications. Spring isolation of the entire unit may be required 3. Air-borne path through the supply and return openings Use 2003 ASHRAE Fundamentals Chapter 43 to help reduce ducted noise and minimize duct turbulence. Maintain straight ducts to and from the unit and avoid abrupt changes in duct size and direction. Avoid turns opposed to the fan wheel rotation. If 90 elbows are required, use turning vanes Use as much insulated return duct as possible and include at least one elbow and 15' of length. Maximum recommended velocities are 1000 1200 fpm Allow for duct break out and use oval or round duct whenever possible Insulate the first 20' of supply duct. The first 20' of rectangular duct should be routed over non-sensitive areas and avoid large aspect ratios. Maximum recommended velocities are 1800 2000 fpm Daikin offers factory-installed discharge plenums with optional perforated liners. The plenum provides several db of attenuation and discharges the air at a more uniform, relatively low velocity. Ducted supply noise can be further reduced by adding optional sound attenuators between the supply fan and the unit discharge Route the return air path through the length of the curb to add distance between the unit return opening and the building return opening CAT 219-2 ROOFPAK PACKAGED SYSTEMS 18 www.daikinapplied.com

Application Considerations Economizer, Return Fan and Exhaust Fan Application Rooftop economizer applications usually require return or exhaust fans to properly control building pressure and maintain minimum ventilation. Daikin offers both exhaust and return fan capability. They are not generally interchangeable for a given design. In general: Return air fans (RAF) should be used on ducted return systems (return ESP exceeds 0.4 0.5 in.) Properly selected propeller exhaust air fans (EAF) can successfully operate and save energy on open return systems (return ESP is less than 0.4 0.5 in.) Supply air fan (SAF) selection depends on whether a return or exhaust fan is used RAF system-saf handles only the supply ESP at design EAF system-saf handles both the supply and return ESP at design (EAF is OFF) Figure 16 illustrates why supply fan only units have problems, especially as return ESP increases. No exhaust will occur from the rooftop because the economizer section must be at a negative pressure The air balancer must adjust the outdoor air damper to generate large pressure drops at minimum ventilation settings (about 0.9" in Figure 16) Figure 17 illustrates how the addition of a return fan corrects these problems. The return fan is responsible for return system ESP and maintains a slightly positive pressure in the economizer section (about +0.1 in. in Figure 17) to allow for exhaust air control and a more suitable outside air intake pressure. Exhaust fans are very different than return fans and can not maintain proper building pressure and ventilation control as return ESP increases. The EAF is normally off during non-economizer operation. During these minimum outdoor air conditions, the system essentially acts like a supply fan only system When the exhaust fan cycles OFF, there is no device available to maintain a positive pressure for relief, the mixed air plenum pressure dramatically changes and minimum ventilation air control and space pressure control are lost An exhaust fan s performance weaknesses diminish as return ESP decreases. Properly selected and controlled propeller exhaust fans can successfully operate and save energy at reduced return ESP designs. At system operating conditions where a single fan can be used successfully, it generally will be more efficient than operating series fans under the same total load. When the exhaust fan turns off, the supply fan can more efficiently handle both the supply and return duct loads At the relatively high cfm, low static pressure conditions of exhaust/return application, exhaust fans can be selected closer to their peak design efficiency than can full return fans. This allows them to run more efficiently throughout their operating range. Therefore, when return duct losses don t dictate the use of a return air fan, exhaust fans are an efficient alternate. Figure 16: AF Only System Static Pressures with 1" Return Duct ESP $) J5). K J AJ # 5 K F FO - 52 ') J5).1 AJ 1 JA H = 5 2 ) 4 )?? K F A E @ 5 F=?A)J 5 J= JE? 2 HA IIKHA ' 1 4 BJ F -? E A H 5 A? JE - ) 4 AJKH - 52 Figure 17: RAF System Allows Proper Exhaust and Outdoor Air Control ') J5).1 AJ ) J ) 1 AJ )J IF D AHE?2 HA IIKHA ) J4). KJ A J $) J5). K J AJ ') J4).1 AJ www.daikinapplied.com 19 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Variable Air Volume (VAV) Daikin Rooftop VAV options include everything required to provide the full advantages of true shut-off VAV. Bypass VAV systems do not offer any fan energy savings at light load. Variable Frequency Drives for all indoor fans maximize part load fan efficiency and minimize fan sound generation Indoor fan volume control based on supply static pressure and building pressure Up to 2 supply duct sensors to properly respond to building diversity (such as east-west variation) Constant discharge temperature control. Shut-off VAV offers the following advantages Reduces first cost and energy due to building diversity Reduces indoor fan energy requirements at light load Provides the opportunity for efficient multiple zone control from a single unit and to match changing occupancy demands VFDs turn down in accordance with Figure 18 The benefits of Daikin airfoil fans are particularly applicable to VAV applications. Better efficiency and less noise at the medium static pressures associated with VAV Airfoil fans are much more forgiving than forward curved fans if unexpected variations in ESP occur They are non-overloading (bhp is fairly constant for a given RPM) and require less safety factor in motor selection They have steeper RPM lines (less variation in cfm for a given variation in ESP) Multiple forward curved fans are often used and they risk unstable fan paralleling at light load MicroTech III Control Supply fans are controlled to maintain constant supply duct static pressure. Run pressure-sensing tubes to the desired location (generally at the end of the main trunk) Use a second sensor when there is more than one main trunk, multiple floors, or significantly varying zones (such as east and west sides of a building) Return/exhaust fans are controlled to maintain building pressure in one of two ways. Daikin s exclusive Vanetrol supply/return fan tracking is generally preferred. Vanetrol is adjusted at system air balance to maintain proper building pressure throughout the expected loading conditions. This reduces the effect of wind, climate variation and doors opening and closing Direct building sensing control is available for exhaust fans or any return fan application that cannot predictably track the supply fan Daikin generally offers more steps of compressor capacity control than the industry norm, as well as HGBP, and these capabilities should be included on VAV applications to minimize variations in duct temperature. Figure 18: VFD Turndown CAT 219-2 ROOFPAK PACKAGED SYSTEMS 20 www.daikinapplied.com

Application Considerations Unit Operating Range Fan Operating Range The acceptable system operating range of the Daikin rooftop unit is determined by all of the following characteristics. Each of these limiting factors must be considered for proper performance and component design life. 1. Unstable fan operation 2. Maximum fan rpm 3. Maximum cabinet static pressure 4. Maximum face velocity (cooling coil is most important) 5. Minimum furnace or electric heater velocity 6. Turndown capability on VAV applications 7. Compressor operating pressures Figure 19 illustrates these limiting factors with the exception of items 6 and 7 above. The shaded area indicates the design operating range of the fan. For optimal efficiency, select fans as close to the fan s peak static efficiency line as possible. This line is the first system curve to the right of the unstable line illustrated. VAV fan selections must also allow for keeping the fan away from the do not select area at minimum design cfm. Cooling coil maximum face velocity is based on moisture blow off limitations and laboratory testing. 650 feet per minute maximum face velocity for 8 and 10 fin per inch coils. 600 feet per minute maximum face velocity for 12 fin per inch coils. Cooling coil minimum face velocity is 200 feet per minute for any coil selection. VAV systems must be designed such that this velocity is maintained at minimum airflow. Maximum design ambient wet bulb temperature varies per unit, but is at least 85 F. Evaporative condenser units are an excellent choice for high ambient applications. The minimum ambient temperature for compressor operation is 45 F. The MicroTech III Controller is set to prevent compressor operation below that temperature and use the economizer only when cooling is required at a lower ambient. Figure 19: Fan Selection Boundary Do Not Select www.daikinapplied.com 21 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Indoor Fan and Motor Heat, Blow-Through vs. Draw-Through Cooling Indoor Fan and Motor Heat The indoor fan and motor electrical consumption is a sensible cooling load approximately equal to 2.8 MBh per bhp (depending slightly on motor efficiency). This occurs at the fan. See Figure 20 and Figure 21. The fan and motor preheat the mixed air before it enters a blowthrough cooling coil. The fan and motor reheat the air leaving a draw-through cooling coil. Refer also to 2001 ASHRAE Fundamentals Handbook, Chapter 31 Figure 20: Blow-Through vs. Draw-Through Concept Fan and motor temperature rise is equal to Btuh / (1.08 cfm) and is typically about 3 F Due to fan and motor heat placement (Figure 20), blowthrough coils provide a high sensible heat ratio while draw-through coils provide more latent cooling per total ton. Blow-through coils achieve a higher sensible heat ratio because they operate with a higher coil approach temperature and a lower entering relative humidity. Conversely, draw-through coils cool air at a lower approach temperature and a higher relative humidity, increasing latent cooling Blow-through coils effectively provide colder supply air temperatures per ton of air conditioning and greater sensible heat ratio. This potentially allows a significant reduction in design cfm for buildings with high sensible heat ratios and a resulting reduction in building energy use Figure 21: Blow-Through and Draw-Through Performance Comparison MAT 3 B.T. Preheat 3 D.T. Reheat Coil EAT Is Different Coil LAT Is Different CAT 219-2 ROOFPAK PACKAGED SYSTEMS 22 www.daikinapplied.com

Application Considerations Recommended Clearances Service Clearance Allow the recommended service clearances shown in Figure 22. Provide a roof walkway along two sides of the unit for service and access to most controls. Cooling Coil, Heat, and Supply Fan Service Clearance An additional clearance of 24" is recommended adjacent to the cooling coil, heat, and supply fan sections. Outdoor Air Intakes Do not locate outside air intakes near exhaust vents or other sources of contaminated air. If the unit is installed where windy conditions are common, install wind screens around the unit, maintaining the clearances specified. This is particularly important to prevent blowing snow from entering outside air intakes. Overhead Clearance 1. Unit(s) surrounded by screens or solid walls must have no overhead obstructions over any part of the unit. 2. The area above the condenser must be unobstructed in all installations to allow vertical air discharge. 3. The following restrictions must be observed for overhead obstructions above the air handler section: a. There must be no overhead obstructions above the furnace flue or within 9 inches of the flue box. b. Any overhead obstruction shall not be within 2 inches of the top of the unit. c. A service canopy must not protrude more than 24 inches beyond the unit in the area of the outside air and exhaust dampers. d. Flue box outlet must extend above any obstructions. Figure 22: Service Clearances 72" Service Clearance on 4 sides except as indicated 24" 72" Clearance to end of unit or end of outside hood Roof Walkway Adjacent to Cooling Coil, Heat, and Supply Fan Sections. www.daikinapplied.com 23 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Ventilation Clearance Unit(s) surrounded by a screen or a 50% open area fence: 1. The bottom of the screen should be a minimum of 1 ft. above the roof surface. 2. Minimum distance from the unit to screen is the same as the recommended service clearance. 3. Minimum distance, unit-to-unit = 120 in. Figure 23: Ventilation Clearances Unit(s) surrounded by solid walls: 1. Minimum distance from the unit to the wall is 96 inches for all sizes. 2. Minimum distance from the unit to another unit is 120 inches. 3. Wall height restrictions: a. No restrictions if there is a wall on one side only, or on two adjacent sides. b. The wall height is restricted to no more than the unit height with walls on more than two adjacent sides. Maximum Allowable Overhead Canopy Area 24" Max 24" Max Flue Box 9" Min to Flue Box Typical All Sides 2" Topof Unit To Overhead Obstruction CAT 219-2 ROOFPAK PACKAGED SYSTEMS 24 www.daikinapplied.com

Application Considerations Control and Power Wiring Wiring must be done in accordance with the NEC and local code. For wire sizing instructions, see Supply Power Wiring on page 60. All units require 208-60-3, 230-60-3, 460-60-3, 575-60-3 or 380-50-3 power. Size wire in accordance with tables 310-16 or 310-19 of the National Electric Code. Wires should be sized for a maximum 3% voltage drop. Copper conductors must be used. Actual voltage at the unit connection must be within +/- 10% of nameplate voltage at all times. Daikin offers several power connection options. Single power connection with a terminal block or nonfused disconnect are normally the most economical. Systems served by emergency generators often require two power connections (with terminal blocks or non-fused disconnects). The generator normally serves only the air handler and controls portion so the condensing unit must be powered separately. Each unit is provided with a separate 115 volt convenience outlet that requires a separate power connection per the NEC. A second, 115 volt power supply is required to power the optional unit heater for the service compartment. Most units require a zone temperature sensor for night heat and other functions. The sensor must be properly placed so that its temperature reflects the zone requirements. Avoid outside walls, sunlight and close proximity to supply air or heat generating equipment. A return air sensor can be substituted for the space sensor if necessary. Altitude Adjustments Fan curve performance is based on 70 F air temperature and sea level elevation. Selections at any other conditions require the following adjustment for air densities listed in Table 7. Higher elevations generally require more RPM to provide a given static pressure but less bhp due to the decrease in air density. 1. Assume 32,000 cfm is required at 3.11" TSP. The elevation is 5000 ft. and 70 F average air temperature is selected. A 40" DWDI airfoil fan is selected. 2. The density adjustment factor for 5000 ft. and 70 F is 0.83. 3. TSP must be adjusted as follows; 3.11" / 0.83 = 3.75" 4. Locate 32,000 cfm and 3.75 on the fan curve. RPM = 900 and bhp = 27.5. The required fan speed is 900 RPM. 5. The consumed fan power at design = 27.5 bhp 0.83 = 22.8 bhp. Figure 24: RPE 105C - 135C 40 in. DWDI Airfoil Table 7: Temperature and Altitude Conversion Factors Air Temp ( F) Altitude (Feet) 0 1000 2000 3000 4000 5000 6000 7000 8000-20 1.20 1.16 1.12 1.08 1.04 1.00 0.97 0.93 0.89 0 1.15 1.10 1.08 1.02 0.99 0.95 0.92 0.88 0.85 20 1.11 1.06 1.02.098 0.95 0.92 0.88 0.85 0.82 40 1.06 1.02 0.98 0.94 0.91 0.88 0.84 0.81 0.78 60 1.02 0.98 0.94 0.91 0.88 0.85 0.81 0.79 0.76 70 1.00 0.96 0.93 0.89 0.86 0.83 0.80 0.77 0.74 80 0.98 0.94 0.91 0.88 0.84 0.81 0.78 0.75 0.72 100 0.94 0.91 0.88 0.84 0.81 0.78 0.75 0.72 0.70 120 0.92 0.88 0.85 0.81 0.78 0.76 0.72 0.70 0.67 140 0.89 0.85 0.82 0.79 0.76 0.73 0.70 0.78 0.65 www.daikinapplied.com 25 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Furnace Performance Gas heat performance data is based on standard 70 F combustion air temperature and zero feet altitude (sea level). Furnace altitude derate may be 4% per 1000 feet above 2000 feet due to lesser combustion air density. However, if design ambient is cold enough, then the combined affect of colder temperature and altitude may have an offsetting impact on combustion air density. Example: A 1000 MBh furnace at 70 F ambient and at an altitude of 5000 feet is derated (0.04 3 = 0.12). At 1000 MBh input (1000 0.12 MBh), the actual input is (1000 120 = 880 MBh) at 5000 feet. Above 6000 feet, consult factory. Freezing Concerns Freeze protection measures must be taken for any rooftop exposed to freezing conditions. The owner and building designer must take primary responsibility based on the exact climate and installation conditions. Drain all condenser water as soon as the climate allows the economizer to provide all required cooling. The optional sump heater is recommended to protect the sump if ambient temperatures can drop to freezing conditions (even at night). Spray System The spray tree and nozzles are not vulnerable to freezing because water drains out of them when the spray pump is OFF. Remove the sump drain plug whenever the unit is not in operation to prevent precipitation from building up in the sump and drain. Two freeze protection options are required to prevent the rest of the spray system from freezing. 1. An optional service vestibule heater provides primary freeze protection of the spray system enclosed in the vestibule. A thermostat turns the unit heater on when vestibule temperature drops to 40 F. 2. A sump heater is a recommended option that includes the following: An ambient thermostat-controlled insertion heater for the sump. Heat tape, insulation and thermostat for the sump drain. Heat tape, thermostat and insulation is included on the high pressure, factory water inlet piping upstream of the float control valve. An additional 10 feet of heat tape is provided to protect field connections. The installer must provide additional heat tape as required and insulate all field piping. An emergency drain solenoid opens up whenever the sump temperature drops near freezing and the spray system drains onto the roof. Hot Water and Steam Coils The RPE/RDE economizer offers better mixing capability than competitive rooftops but it cannot protect a hydronic coil from localized freezing. Optional air mixers are available to reduce air stratification and freezing concerns. Glycol is strongly recommended for hot water coils. It is the only reliable protection in the event of a power failure. Glycol s impact on coil and pump performance must be considered. An optional, non-averaging coil freezestat is offered on the downstream face of the heating coil. The outdoor dampers are shut, the fan is shut off, and the heating valve is fully opened, if freezing temperatures are experienced. The freezestat must be set somewhat above freezing temperatures to improve protection and may experience nuisance trips. It can not protect the coils during a power outage. Freeze protection strategies must not cause the cabinet temperature to exceed 150 F or motors and electrical equipment may be damaged. The field installed supply and bleed off water lines can enter the unit through the floor, inside the curb perimeter. This may provide sufficient protection depending on the temperature inside the curb. Use freeze protection if there is any concern the temperature inside the curb may fall below freezing. If no curb is provided, or field water piping enters the side of the unit, then additional measures are required such as heat tape and proper pipe insulation. Hot water and steam coil piping can enter the floor of the unit in the heat section and requires similar consideration. Water Treatment All evaporative condensers require proper water treatment. See Optional Water Treatment on page 14. The purpose of the water treatment system is to: Control organic contamination. Reduce condenser and sump scaling, fouling and corrosion. Reduce the required cleaning frequency. Proper water treatment involves two mandatory components (treatment and bleed off) and may also require a solid separator system depending on water quality. CAT 219-2 ROOFPAK PACKAGED SYSTEMS 26 www.daikinapplied.com

Application Considerations Condenser Water Connections Supply and return condenser water piping, plus field connections for chemical water treatment, are shown in Figure 25. Supply water can enter the floor of the service vestibule. Space is allowed in the vestibule for chemical tanks. Condenser bleed off (or return) connections allow easy drainage to a sanitary sewer through the floor of the vestibule. The spray operation washes particles out of the condenser air and condenser heat rejection evaporates water. This process leaves behind minerals and particles that were contained in the water. Water bleed off and water treatment are required to prevent the build up of scale, sludge and micro-organisms on the tube bundles and in the sump. These must be installed prior to unit start-up. See Optional Water Treatment on page 14. The theoretical water consumption required for proper heat rejection is 1.8 gallons per cooling ton hour. A nominal 100- ton unit, running at 50% capacity or 50 tons, evaporates 90 gallons of water per hour while rejecting condenser heat. Additional water must be added to the sump and bled off to the sanitary sewer to remove particles and minerals that accumulate in the water during operation. The required amount of bleed off varies with the water quality and is generally 0.6 to 0.9 gallons per ton hour or 33-50% of the theoretical evaporation water. Bleed off can be controlled in two ways. The RPE/RDE is provided with a manual shut off valve that can be used to adjust for a constant flow rate of bleed off water. This standard bleed off system can easily bleed off too much or too little water. Controlling bleed off with a solenoid valve, based on water conductivity or some other measure of particle concentration should be used. It is included in the RPE/ RDE water treatment option. The RPE sump also has a float control that automatically opens the supply water solenoid and replaces water lost in evaporation and bleed off. Water utility costs are usually based on the combination of water usage and sewer discharge. Only the bleed off portion of the water used by an evaporative condenser drains to the sewer (about 25-33% of total water used). Therefore, the sewer component of the cost of water may be reduced significantly if approved water meters are installed in the intake and bleed lines. The difference in meter rates reflects evaporation (water that will not go to the sewer) and this can be applied as a credit to the total water bill. Consult your local water utility for details. Figure 25: Condenser Water Piping and Connections Water Consumption To Spray System Optional Water Treatment Controller Spray Pump Manual Shut off Valves From Optional Separator Automatic Supply Water Valve (Float Controlled) Manual Drain Valve Supply to Sump Optional Freeze Protection Drain Valve Field Bleedoff or Drain Connection Hose Bib and Manual Shut off Valve Field Supply Water Connection To Spray System Recommended Water Piping Entrance Through the Curb From Sump Removable Sump Screen Sump Drain Left Open for Shipment www.daikinapplied.com 27 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Selection Instructions Building design and unit selection must allow for code compliance and installation limitations. The Daikin Rooftop unit offers excellent flexibility to meet diverse application requirements. This catalog includes summary performance tables at several operating conditions. Performance at other conditions can be estimated by interpolation but accuracy may suffer. Extrapolation often results in unreliable or damaging operating conditions and should not be used without factory guidance that is available through your local sales representative. Contact your Daikin representative for custom selections at specific design conditions. Selection Example Selection based on design criteria: 38,000 supply cfm at 2.00" ESP 36,000 return cfm at 0.75" ESP Sea level location using 60 Hertz power 95/75 F cooling ambient temperature 80/67 F cooling mixed air temperature [MAT] Total cooling loads requirements: 115 total tons 87 sensible tons Total sensible loads allow for: 50 hp SAF motor 25 hp RAF motor Gas furnace requirements: 1520 MBh of design heating 9" gas pressure available at the unit Furnace to only be used at design cfm for morning warm up and night heat An RPE unit must be used since a furnace, or electric heat, or final filters are required. Unit includes: Economizer plus return fan 65% filters plus pre-filters Cooling Selection Gross and net cooling The tables within the section Cooling Capacity Data on page 32 provide gross cooling or DX coil capacity based on DX coil entering air temperature (EAT). Net unit cooling capacity = [Gross cooling capacity] - [fan/motor heat] Fan/motor heat is critical. Refer to Indoor Fan and Motor Heat, Blow-Through vs. Draw-Through Cooling on page 22. Fan/motor heat = 2800 Btuh per bhp Fan/motor temperature rise (TR) = Btuh / (1.08 cfm) Mixed air vs. entering air temperature [MAT vs. EAT] Draw-through coil EAT = MAT Blow-through coil EAT = MAT + TR Blow-through EDB = mixed air EDB + TR Use a psychometric chart to find blow-through EWB. Selection From Capacity Tables Blow-through vs. draw-through. Refer to Indoor Fan and Motor Heat, Blow-Through vs. Draw-Through Cooling on page 22. Required sensible heat ratio < 80% [87 / 115 = 76%] An RPE is required due to the gas heat requirement. Therefore a draw-through RPE will be considered first. The RPE unit is available with both a low and high airflow DX coil. Refer to Table 8: Physical Data, RPE/RDE 076C - 150C on page 31. First select a high and low airflow coil with sufficient capacity. The RPE 110 with high airflow coil has sufficient capacity. No low airflow coil has sufficient capacity. Check coil velocity on all possible selections. High airflow face area = 76.0 square feet face velocity = 526 feet per minute. Low airflow face area = 60.8 square feet face velocity = 658 feet per minute The low airflow velocity is too much per Unit Operating Range on page 21. The RPE 110 [with high airflow coil] is sufficient per Table 16 on page 35. RPE 110 provides 117.6 total tons. RPE 110 provides 90.8 tons of sensible capacity. RPE 110 power consumption. 90.0 compressor kw (see Table 16 on page 35). 4.0 condenser fan and pump kw (see Table 20 on page 37). RPE 110 fan and motor heat must still be verified to be less than 50 = 25 bhp [per fan selection ] to be sure that net cooling capacity is sufficient. CAT 219-2 ROOFPAK PACKAGED SYSTEMS 28 www.daikinapplied.com

Application Considerations Heat Selection See Catalog 214 or 217 for hot water, steam and electric heat selection instructions. Furnace Selection See Table 24 on page 40 and Table 25 and Table 26 on page 41. Table 24 and Table 25 indicate all of the furnace output capacities available. Output capacity is the true measure of furnace capacity Output capacity = Input capacity furnace efficiency Furnace efficiency = 80% for Daikin furnaces [similar to most direct fired furnaces] Net unit heating capacity = Furnace heating capacity + fan/motor heat = Furnace heating capacity + (50 + 25) 2800 = Furnace heating capacity + 210,000 Btuh Net heating capacity must satisfy the heating load of 1520 MBh. A 1400 MBh furnace is the correct choice. 1,400,000 Btuh + 210,000 Btuh exceeds the 1,520 MBh requirement. Assuming actual bhp exceeds (1,520,000-1,400,000) / 2800 = 42.9 bhp Baffle selection is based on design airflow and Table 22 on page 38. Baffle A has the greatest air pressure drop. Use baffle A from 21,000 to 37,999 cfm. Baffle B has the next greatest air pressure drop. Use baffle B from 38,000 to 38,999 cfm. Furnace air pressure drop at design air flow Refer to Table 24 for a 1400 MBh furnace with B baffle. 0.86" = furnace air pressure drop. Minimum inlet gas pressure Refer to Table 25 for a 1400 MBh furnace. Minimum inlet gas pressure = 8.8" for the standard modulating burner. 5.0" for the 20:1 high turndown, modulating burner. Furnace air temperature rise = Output Btuh 1,400,000 / 1.08 cfm = 32.4 F Filter Selection Refer to Table 8: Physical Data, RPE/RDE 076C - 150C on page 31 and Table 29: Component Pressure Drops on page 43. Table 8 shows the filter face area options. Table 29 shows performance data for each filter option: Clean filter air pressure drop Maximum airflow Selection for 65% filter at 38,000 cfm per Table 29. The medium airflow option is required Clean air pressure drop = 0.65" 30% prefilter clean air pressure drop = 0.36" Maximum recommended, dirty filter pressure drop [PD] for these filters: 0.7" for the 30% prefilter 1.0" for the 65% filters Please note that 95% filters are not part of this selection. 95% filter, maximum recommended, dirty PD = 1.20". Average filter PD = (0.7 + 1.0 + 0.65 + 0.36) / 2 = 1.35" Daikin generally recommends selecting the supply fan based on average filter PD. This allows airflow to best match specifications. Adjustments can be made to maintain critical, minimum airflow. www.daikinapplied.com 29 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Application Considerations Fan Selection Refer to the following: Table 8: Physical Data, RPE/RDE 076C - 150C on page 31 and Table 29: Component Pressure Drops on page 43. Fan Operating Range on page 21. Fan Performance Data on page 44. Return Air Fan and Exhaust Air Fan Selection Refer to Return Fans & Exhaust Fans on page 44 for 36,000 cfm at 0.75" ESP. The 44" SWSI return fan performance requires 19.5 bhp at 810 RPM. 19.5 bhp satisfies the RAF bhp specification. Supply Fan Selection The unit is specified to have a return fan. Therefore the supply fan must only handle internal APD and supply duct ESP. See Economizer, Return Fan and Exhaust Fan Application on page 19. Internal APD per Table 28 on page 42 and Table 29 on page 43. Economizer with return fan = 0.52" High airflow, 12 fpi, DX coil air pressure drop = 0.80" Gas furnace = 0.86" Average filter air PD = 1.35" TSP = 0.52 + 0.80 + 0.86 + 1.35 + 2.00 ESP = 5.54" SWSI Plenum vs. DWDI Supply Fan Selection Each type should be considered based on maximum efficiency and customer preference. DWDI fans are available on RPE, blow-through or draw-through units and must be used due to the furnace requirement. SWSI fans are only available on RDE, draw-though units. No blow-through coils or filters No furnaces or electric heat They offer advantages with side discharge Pick the optimum SAF for 38,000 cfm and 5.54" TSP 40" DWDI = 47.8 bhp and 1085 RPM (Figure 37 on page 46) 36" DWDI = 50.1 bhp and 1288 RPM (Figure 36 on page 46) 33" DWDI = do not select The 40" fan is superior. 5% more efficient and, therefore, quieter Saves a motor size Meets the 50 hp supply fan allowance We can now verify acceptable net heating and cooling capacities. Actual supply and return fan bhp = 47.8 + 19.5 = 67.3 Acceptable for cooling (67.3 < 50 + 25) Acceptable for heating (67.3 > 42.9) CAT 219-2 ROOFPAK PACKAGED SYSTEMS 30 www.daikinapplied.com

Physical Data Table 8: Physical Data, RPE/RDE 076C - 150C Physical Data Data Unit Size 076C 089C 100C 110C 130C 140C 150C Nominal Capacity (tons) 1 79.2 89.4 98.9 119.3 130.8 141.9 152.5 Nominal Airflow (cfm) 32000 35000 35000 42000 45000 46000 46000 Type Reciprocating Quantity - hp 2-30 2-35 2-40 4-25 4-30 2-30, 2-35 4-35 Compressor Std. capacity control 100-83-67-33-0 100-75-50-25-0 100-72-44-22-0 100-75-50-25-0 Opt. capacity control 100-83-67-50-33-16-0 100-88-75-63-50-38-25-12-0 100-89-79-61- 44-32-22-11-0 100-92-83-67- 50-42-33-16-0 Condenser Fans No. - Dia. (In.) 4-26 4-26 4-26 6-26 6-26 6-26 6-26 Condenser Fan Motors No. - Hp 4-1.5 4-1.5 4-1.5 6-1.5 6-1.5 6-1.5 6-1.5 Type SWSI Airfoil No. - Dia. (In.) 1-44, 49 Supply Fans Motor hp range 5-75 Type DWDI Airfoil No. - Dia. (In.) 1-33, 36 1-33, 36 1-33, 36 1-36, 40 1-36, 40 1-36, 40 1-36, 40 Motor hp range 5-75 5-75 5-75 5-75 5-75 5-75 5-75 Type SWSI Airfoil Return Fans No. - Dia. (In.) 1-44.5 1-44.5 1-44.5 1-44.5 1-44.5 1-44.5 1-44.5 Motor hp range 5-60 5-60 5-60 5-60 5-60 5-60 5-60 Type Propeller Exhaust Fans Diameter (In.) 36 36 36 36 36 36 36 Quantity 2-3 per unit 2-3 per unit 2-3 per unit 2-3 per unit 2-3 per unit 2-3 per unit 2-3 per unit Motor hp 5 each 5 each 5 each 5 each 5 each 5 each 5 each Rows 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 Evaporator Coils FPI 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 F.A., small (sq. ft.) 53.9 53.9 53.9 60.8 - - - F.A., large (sq. ft.) 60.8 60.8 60.8 76.0 76.0 76.0 76.0 Type - Rows 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 Hot Water Coils Type - Rows 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 FPI 9 9 9 9 9 9 9 Face area (sq. ft.) 42.2 42.2 42.2 42.2 42.2 42.2 42.2 Type - Rows 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 Steam Coils FPI 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 Face area (sq. ft.) 42.2 42.2 42.2 42.2 42.2 42.2 42.2 Input (MBh) 625, 800, 812, 988, 1000, 1250, 1375, 1750, 1875, 2500 Gas Furnace 2 Nom. Output (MBh) 500, 640, 650, 790, 800, 1000, 1100, 1400, 1500, 2000 Electric Heat 3 Nom. Output (kw) 80, 100, 120, 160, 200, 240, 280, 320 Type 30% Pleated Panel Filters Area (sq. ft.) 116.1 116.1 116.1 116.1 116.1 116.1 116.1 No. - size (in.) 11-16 20 2 33-16 25 2 33-16 25 2 11-16 20 2 11-16 20 2 33-16 25 2 33-16 25 2 11-16 20 2 11-16 20 2 33-16 25 2 33-16 25 2 11-16 20 2 11-16 20 2 33-16 25 2 Type Prefilter, Standard Flow Prefilter, Medium Flow Area (sq. ft.) 56.0 56.0 56.0 64.0 64.0 64.0 64.0 4-12 24 2 4-12 24 2 4-12 24 2 No. - size (in.) Prefilters (for 12-24 24 2 12-24 24 2 12-24 24 2 16-24 24 2 16-24 24 2 16-24 24 2 16-24 24 2 Cartridge Filters) Type Prefilter, Medium Flow Prefilter, High Flow Area (sq. ft.) 64.0 64.0 64.0 80.0 80.0 80.0 80.0 No. - size (in.) 16-24 24 2 16-24 24 2 16-24 24 2 8-12 24 2 16-24 24 2 8-12 24 2 16-24 24 2 8-12 24 2 16-24 24 2 8-12 24 2 16-24 24 2 Type 65% or 95% Standard Flow 65% or 95% Medium Flow Area (sq. ft.) 56.0 56.0 56.0 64.0 64.0 64.0 64.0 Cartridge Filters No. - size (in.) 4-12 24 12 4-12 24 12 4-12 24 12 12-24 24 12 12-24 24 12 12-24 24 12 16-24 24 12 16-24 24 12 16-24 24 12 16-24 24 12 Type 65% or 95% Medium Flow 65% or 95% High Flow Area (sq. ft.) 40.0 64.0 64.0 80.0 80.0 80.0 80.0 No. - size (in.) 16-24 24 12 16-24 24 12 16-24 24 12 8-12 24 12 16-24 24 12 8-12 24 12 16-24 24 12 8-12 24 12 16-24 24 12 8-12 24 12 16-24 24 12 1. Rated in accordance with ARI Standard 360 2. Gas furnace size availability is limited by minimum airflow. See Table 24 on page 40. 3. Electric heat availability is limited by minimum airflow, See through. See Table 23 on page 40. www.daikinapplied.com 31 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Cooling Capacity Data Table 9: RPE/RDE 076C Low Airflow Coil Cooling Capacity Data Unit Data Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 855 642 49.4 844 637 51.1 832 632 52.8 75 67 917 531 50.5 906 526 52.2 893 521 53.9 71 986 419 51.6 973 415 53.3 961 410 55.1 63 857 773 49.5 846 769 51.1 834 764 52.8 24000 cfm 80 67 918 663 50.6 905 658 52.2 893 653 54.0 5 row 12 fpi 71 984 551 51.6 972 547 53.3 959 542 55.1 63 879 879 49.9 870 870 51.5 861 861 53.3 85 67 919 795 50.6 908 791 52.3 896 786 54.0 71 982 683 51.6 970 678 53.4 957 674 55.1 63 876 695 49.8 865 691 51.5 853 686 53.2 75 67 940 568 50.9 927 563 52.6 915 558 54.3 71 1007 438 51.9 995 434 53.7 63 883 847 50.0 871 842 51.6 859 836 53.3 28000 cfm 80 67 938 720 50.9 926 716 52.6 914 711 54.4 5 row 12 fpi 71 1005 591 51.9 993 586 53.7 981 582 55.5 63 924 924 50.6 915 915 52.3 905 905 54.1 85 67 942 872 51.0 931 867 52.7 918 863 54.5 71 1004 744 52.0 991 739 53.7 63 893 748 50.1 881 743 51.8 869 738 53.5 75 67 955 602 51.2 943 598 52.8 930 593 54.6 71 63 905 905 50.4 895 895 52.1 884 884 53.8 32000 cfm 80 67 955 776 51.2 943 771 52.9 930 766 54.7 5 row 12 fpi 71 63 960 960 51.2 950 950 53.0 940 940 54.8 85 67 965 945 51.4 953 939 53.1 940 932 54.9 71 DO NOT SELECT NOMINAL CAPACITY Table 10: RPE/RDE 076C High Airflow Coil Unit Data Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 884 700 50.0 873 695 51.6 861 690 53.3 75 67 947 571 51.0 935 566 52.7 923 562 54.4 71 63 888 852 50.1 879 848 51.7 866 842 53.5 28000 cfm 80 67 946 724 51.1 934 720 52.7 921 715 54.5 5 row 12 fpi 71 63 932 932 50.7 922 922 52.5 912 912 54.2 85 67 952 878 51.1 938 873 52.8 926 868 54.6 71 63 899 752 50.3 887 747 51.9 875 742 53.6 75 67 964 607 51.3 951 602 53.0 938 597 54.7 71 63 912 912 50.5 903 903 52.2 892 892 54.0 32000 cfm 80 67 963 781 51.3 951 776 53.0 937 771 54.8 5 row 12 fpi 71 63 969 969 51.4 959 959 53.1 948 948 54.9 85 67 973 952 51.5 961 946 53.2 947 939 55.0 71 63 913 803 50.5 901 798 52.2 889 793 53.9 75 67 975 641 51.5 963 636 53.2 950 631 55.0 71 63 944 944 50.9 933 933 52.7 923 923 54.4 36000 cfm 80 67 977 836 51.6 965 831 53.3 951 826 55.0 5 row 12 fpi 71 63 1001 1001 51.9 990 990 53.6 979 979 55.4 85 67 998 998 51.9 988 988 53.7 977 977 55.5 71 DO NOT SELECT NOMINAL CAPACITY CAT 219-2 ROOFPAK PACKAGED SYSTEMS 32 www.daikinapplied.com

Cooling Capacity Data Table 11: RPE/RDE 089C Low Airflow Coil Unit Data 27000 cfm 5 row 12 fpi 31000 cfm 5 row 12 fpi 35000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 962 721 62.9 951 716 64.5 939 711 66.0 75 67 1035 598 64.6 1023 593 66.2 1011 588 67.8 71 1113 473 66.5 1101 469 68.0 1089 464 69.6 63 966 870 63.0 955 865 64.5 944 860 66.1 80 67 1035 746 64.7 1024 742 66.2 1011 737 67.8 71 1111 621 66.5 1099 616 68.0 1086 612 69.6 63 990 990 63.5 980 980 65.1 971 971 66.8 85 67 1035 893 64.7 1024 889 66.3 1012 884 67.8 71 1111 769 66.5 1098 764 68.1 1085 760 69.7 63 985 775 63.5 973 770 65.0 961 765 66.5 75 67 1057 634 65.2 1045 629 66.7 1032 624 68.3 71 1136 492 67.0 1124 488 68.6 1111 483 70.2 63 991 942 63.6 979 937 65.2 968 931 66.7 80 67 1058 804 65.2 1046 799 66.8 1034 794 68.3 71 1135 661 67.0 1123 657 68.6 1109 652 70.2 63 1035 1035 64.6 1025 1025 66.2 1016 1016 67.8 85 67 1060 971 65.3 1049 966 66.9 1036 961 68.4 71 1133 830 67.1 1120 825 68.6 1107 821 70.2 63 992 816 63.6 980 811 65.2 968 806 66.7 75 67 1065 662 65.3 1053 657 66.8 1040 652 68.4 71 1142 504 67.2 1130 500 68.7 1116 495 70.3 63 1001 991 63.9 990 984 65.4 979 976 67.0 80 67 1063 848 65.4 1051 843 66.9 1038 838 68.5 71 1140 691 67.2 1128 687 68.7 1114 682 70.3 63 1060 1060 65.2 1050 1050 66.8 1040 1040 68.4 85 67 1072 1028 65.6 1059 1022 67.1 1046 1016 68.7 71 1139 877 67.2 1126 873 68.8 1113 868 70.4 DO NOT SELECT NOMINAL CAPACITY Table 12: RPE/RDE 089C High Airflow Coil Unit Data 31000 cfm 5 row 12 fpi 35000 cfm 5 row 12 fpi 39000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 995 781 63.7 983 776 65.2 971 771 66.8 75 67 1068 639 65.4 1056 634 67.0 1043 629 68.5 71 1148 497 67.3 1135 492 68.9 1122 487 70.5 63 1001 950 63.9 990 945 65.4 978 939 67.0 80 67 1067 809 65.5 1055 804 67.0 1043 799 68.6 71 1146 666 67.3 1134 662 68.9 1120 657 70.5 63 1045 1045 64.8 1035 1035 66.4 1025 1025 68.1 85 67 1070 977 65.6 1059 973 67.1 1046 968 68.7 71 1144 835 67.4 1132 831 68.9 1118 826 70.5 63 1013 833 64.2 1001 828 65.7 989 823 67.2 75 67 1087 675 65.8 1075 670 67.4 1061 665 69.0 71 63 1022 1015 64.4 1012 1009 66.0 1001 1001 67.6 80 67 1086 865 65.9 1073 860 67.5 1060 855 69.0 71 63 1085 1085 65.8 1074 1074 67.4 1063 1063 69.0 85 67 1093 1052 66.2 1082 1047 67.7 1070 1042 69.3 71 63 1018 873 64.3 1006 868 65.8 994 863 67.3 75 67 1090 701 65.9 1078 697 67.5 1064 692 69.1 71 63 1041 1041 64.7 1031 1031 66.3 1020 1020 67.9 80 67 1090 908 66.0 1078 903 67.6 1065 898 69.1 71 63 1103 1103 66.3 1093 1093 67.9 1082 1082 69.5 85 67 1102 1098 66.4 1093 1091 68.0 1081 1081 69.6 71 DO NOT SELECT NOMINAL CAPACITY www.daikinapplied.com 33 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Cooling Capacity Data Table 13: RPE/RDE 100C Low Airflow Coil Unit Data 29000 cfm 5 row 12 fpi 32000 cfm 5 row 12 fpi 35000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1072 791 77.1 1060 786 78.9 1046 780 80.8 75 67 1154 659 79.6 1140 653 81.5 1125 647 83.4 71 1240 525 82.3 1226 519 84.2 1211 514 86.3 63 1078 951 77.1 1064 945 78.9 1049 938 80.9 80 67 1153 817 79.6 1141 812 81.4 1125 806 83.4 71 1238 683 82.3 1223 677 84.2 1208 672 86.3 63 1094 1094 77.6 1083 1083 79.5 1072 1072 81.6 85 67 1153 976 79.7 1140 970 81.6 1125 964 83.6 71 1237 842 82.4 1223 836 84.3 1208 831 86.3 63 1092 832 77.6 1079 826 79.4 1065 820 81.4 75 67 1172 686 80.2 1158 680 82.1 1143 674 84.1 71 1258 538 83.0 1244 533 84.9 1228 527 86.9 63 1095 1005 77.7 1081 998 79.6 1068 993 81.5 80 67 1171 860 80.2 1156 854 82.1 1142 849 84.1 71 1257 713 82.9 1242 707 84.9 1227 702 86.9 63 1129 1129 78.8 1118 1118 80.7 1106 1106 82.8 85 67 1173 1034 80.3 1159 1028 82.2 1144 1022 84.2 71 1257 888 83.0 1243 882 84.9 1227 877 86.9 63 1096 860 77.7 1082 854 79.5 1067 848 81.5 75 67 1175 704 80.3 1160 698 82.2 1145 692 84.2 71 1262 546 83.0 1247 541 85.0 1232 535 87.0 63 1099 1042 77.9 1087 1036 79.7 1073 1029 81.7 80 67 1175 891 80.3 1160 885 82.2 1145 879 84.2 71 1259 733 83.0 1245 728 84.9 1229 722 87.0 63 1146 1146 79.3 1135 1135 81.3 1123 1123 83.3 85 67 1177 1074 80.5 1163 1068 82.4 1148 1062 84.4 71 1261 921 83.1 1246 916 85.0 1228 909 87.0 DO NOT SELECT NOMINAL CAPACITY Table 14: RPE/RDE 100C High Airflow Coil Unit Data 31000 cfm 5 row 12 fpi 35000 cfm 5 row 12 fpi 39000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1099 826 77.8 1086 820 79.6 1071 813 81.6 75 67 1180 683 80.4 1166 677 82.3 1150 671 84.3 71 1269 540 83.2 1254 535 85.2 1238 529 87.2 63 1102 995 77.9 1089 989 79.8 1075 983 81.7 80 67 1179 853 80.5 1165 847 82.4 1150 841 84.4 71 1266 709 83.2 1251 704 85.2 1235 698 87.2 63 1129 1129 78.8 1118 1118 80.7 1107 1107 82.8 85 67 1180 1022 80.6 1166 1016 82.5 1151 1010 84.5 71 1267 880 83.3 1252 874 85.2 1234 868 87.2 63 1120 878 78.5 1105 872 80.4 1090 866 82.3 75 67 1202 719 81.2 1187 713 83.0 1171 707 85.0 71 1292 559 84.0 1277 554 85.9 1261 548 87.9 63 1126 1068 78.7 1113 1061 80.6 1098 1054 82.6 80 67 1202 910 81.2 1187 904 83.1 1172 899 85.1 71 1289 749 84.0 1274 744 85.9 1258 738 87.9 63 1175 1175 80.2 1163 1163 82.2 1151 1151 84.3 85 67 1205 1099 81.4 1190 1093 83.3 1175 1087 85.3 71 1288 940 84.1 1273 935 86.0 1257 929 88.0 63 1127 919 78.7 1112 913 80.6 1097 907 82.5 75 67 1207 745 81.3 1192 740 83.2 1177 734 85.2 71 1297 570 84.2 1282 565 86.1 1266 560 88.1 63 1136 1116 79.1 1122 1109 80.9 1108 1100 82.9 80 67 1208 954 81.4 1194 948 83.3 1178 942 85.3 71 1296 779 84.1 1281 774 86.0 1264 768 88.1 63 1198 1198 81.0 1186 1186 83.0 1174 1174 85.1 85 67 1213 1155 81.7 1201 1150 83.5 1185 1142 85.6 71 1293 987 84.2 1278 981 86.1 1262 976 88.1 DO NOT SELECT NOMINAL CAPACITY CAT 219-2 ROOFPAK PACKAGED SYSTEMS 34 www.daikinapplied.com

Cooling Capacity Data Table 15: RPE/RDE 110C Low Airflow Coil Unit Data 33000 cfm 5 row 12 fpi 36000 cfm 5 row 12 fpi 39000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1257 916 82.9 1240 909 85.0 1221 900 87.2 75 67 1357 768 85.3 1340 760 87.5 1321 753 89.8 71 1463 616 88.0 1445 609 90.2 1426 602 92.5 63 1258 1096 82.9 1242 1089 85.0 1224 1081 87.2 80 67 1359 949 85.3 1341 942 87.5 1321 934 89.8 71 1461 796 88.0 1442 789 90.2 1423 782 92.5 63 1272 1269 83.3 1258 1258 85.5 1243 1243 87.8 85 67 1359 1129 85.4 1341 1122 87.6 1321 1114 89.9 71 1459 977 88.0 1441 970 90.2 1422 963 92.6 63 1277 957 83.4 1260 950 85.5 1242 942 87.8 75 67 1379 795 85.9 1361 788 88.0 1342 781 90.3 71 1483 630 88.5 1465 623 90.8 1445 616 93.1 63 1280 1153 83.5 1265 1146 85.6 1246 1137 87.8 80 67 1379 992 85.9 1360 984 88.1 1339 976 90.4 71 1482 827 88.5 1463 820 90.7 1444 812 93.0 63 1312 1312 84.2 1299 1299 86.4 1284 1284 88.8 85 67 1379 1187 86.0 1361 1180 88.2 1342 1172 90.4 71 1481 1023 88.6 1463 1016 90.8 1442 1009 93.1 63 1280 985 83.5 1263 977 85.6 1245 969 87.8 75 67 1381 812 85.9 1363 805 88.1 1344 798 90.4 71 1486 637 88.6 1468 631 90.8 1448 623 93.1 63 1286 1191 83.5 1269 1183 85.7 1250 1174 87.9 80 67 1379 1021 86.0 1362 1014 88.1 1343 1007 90.4 71 1483 845 88.5 1465 839 90.8 1445 832 93.1 63 1330 1330 84.6 1316 1316 86.8 1302 1302 89.2 85 67 1381 1227 86.1 1364 1220 88.2 1345 1212 90.5 71 1483 1055 88.7 1465 1048 90.8 1445 1041 93.2 DO NOT SELECT NOMINAL CAPACITY Table 16: RPE/RDE 110C High Airflow Coil Unit Data 38000 cfm 5 row 12 fpi 42000 cfm 5 row 12 fpi 46000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1326 1003 84.6 1309 995 86.7 1289 987 89.0 75 67 1429 830 87.2 1410 823 89.3 1390 815 91.6 71 1537 655 89.9 1518 648 92.1 1497 641 94.4 63 1332 1212 84.7 1315 1204 86.9 1293 1194 89.2 80 67 1429 1039 87.2 1411 1032 89.4 1392 1024 91.7 71 1536 864 89.8 1516 857 92.1 1495 849 94.4 63 1372 1372 85.6 1356 1356 87.9 1340 1340 90.3 85 67 1429 1246 87.3 1411 1239 89.5 1391 1231 91.8 71 1532 1071 89.9 1513 1064 92.2 1492 1057 94.5 63 1349 1057 85.2 1331 1049 87.3 1311 1041 89.6 75 67 1451 867 87.7 1432 859 89.9 1412 852 92.2 71 1559 674 90.4 1540 667 92.7 1519 659 95.0 63 1358 1285 85.4 1340 1277 87.5 1321 1268 89.8 80 67 1453 1097 87.8 1431 1089 90.0 1411 1081 92.3 71 1557 903 90.4 1537 896 92.6 1516 889 95.0 63 1417 1417 86.8 1402 1402 89.1 1386 1386 91.5 85 67 1455 1324 87.9 1436 1316 90.1 1416 1308 92.5 71 1554 1132 90.5 1535 1125 92.7 1514 1117 95.1 63 1354 1096 85.3 1335 1089 87.4 1316 1080 89.7 75 67 1456 892 87.8 1437 885 90.0 1416 877 92.3 71 1562 684 90.5 1542 678 92.7 1521 670 95.1 63 1365 1333 85.6 1347 1323 87.8 1328 1313 90.1 80 67 1454 1138 87.9 1435 1131 90.1 1414 1123 92.4 71 1559 931 90.5 1539 924 92.7 1518 917 95.1 63 1439 1439 87.4 1424 1424 89.7 1408 1408 92.1 85 67 1462 1379 88.1 1443 1370 90.3 1424 1362 92.7 71 1557 1177 90.6 1537 1170 92.8 1516 1163 95.1 DO NOT SELECT NOMINAL CAPACITY www.daikinapplied.com 35 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Cooling Capacity Data Table 17: RPE/RDE 130C High Airflow Coil Unit Data 41000 cfm 5 row 12 fpi 45000 cfm 5 row 12 fpi 49000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1460 1094 101.4 1445 1087 103.6 1427 1080 106.0 75 67 1566 905 104.4 1549 898 106.8 1531 891 109.2 71 1677 714 107.6 1660 707 110.0 1641 701 112.5 63 1463 1317 101.5 1446 1310 103.8 1432 1303 106.2 80 67 1563 1128 104.4 1548 1122 106.8 1530 1115 109.2 71 1675 938 107.6 1658 931 110.0 1640 925 112.5 63 1500 1500 102.4 1485 1485 104.9 1471 1471 107.4 85 67 1566 1353 104.6 1550 1346 106.9 1532 1339 109.4 71 1675 1163 107.7 1658 1156 110.1 1640 1150 112.5 63 1483 1147 102.0 1466 1140 104.3 1448 1132 106.7 75 67 1588 941 105.1 1571 934 107.4 1552 927 109.9 71 1700 732 108.3 1682 726 110.7 1663 719 113.1 63 1489 1390 102.2 1472 1383 104.5 1455 1375 107.0 80 67 1587 1186 105.1 1570 1179 107.5 1552 1172 109.9 71 1698 977 108.2 1680 971 110.6 1661 964 113.1 63 1544 1544 103.7 1530 1530 106.2 1515 1515 108.7 85 67 1590 1429 105.3 1574 1422 107.7 1556 1415 110.1 71 1699 1223 108.3 1682 1217 110.7 1663 1210 113.2 63 1484 1184 102.1 1467 1176 104.4 1449 1169 106.8 75 67 1590 964 105.1 1572 957 107.5 1554 950 109.9 71 1704 742 108.3 1686 736 110.7 1667 730 113.2 63 1494 1437 102.4 1478 1429 104.7 1461 1420 107.1 80 67 1590 1226 105.2 1573 1220 107.6 1554 1212 110.0 71 1700 1004 108.3 1682 998 110.7 1663 991 113.1 63 1563 1563 104.3 1550 1550 106.8 1535 1535 109.3 85 67 1595 1482 105.4 1578 1474 107.8 1560 1467 110.2 71 1698 1266 108.4 1681 1259 110.8 1662 1253 113.2 DO NOT SELECT NOMINAL CAPACITY Table 18: RPE/RDE 140C High Airflow Coil Unit Data 43000 cfm 5 row 12 fpi 46000 cfm 5 row 10 fpi 49000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1602 1177 115.9 1585 1170 118.2 1567 1162 120.7 75 67 1721 980 119.3 1703 973 121.7 1685 966 124.1 71 1846 780 122.9 1828 774 125.4 1809 767 127.9 63 1607 1413 115.9 1590 1406 118.3 1572 1397 120.7 80 67 1720 1215 119.3 1703 1208 121.7 1684 1201 124.2 71 1845 1015 122.9 1827 1009 125.3 1807 1001 127.8 63 1626 1626 116.6 1611 1611 119.1 1599 1599 121.6 85 67 1722 1450 119.4 1705 1443 121.8 1687 1436 124.3 71 1843 1250 122.9 1823 1243 125.4 1806 1236 127.9 63 1603 1203 115.9 1586 1196 118.3 1566 1187 120.8 75 67 1721 996 119.3 1703 989 121.7 1684 981 124.2 71 1848 786 122.9 1829 780 125.3 1810 773 127.8 63 1609 1449 115.9 1592 1441 118.3 1574 1433 120.8 80 67 1720 1243 119.3 1703 1236 121.7 1684 1229 124.2 71 1844 1033 122.9 1826 1026 125.3 1806 1019 127.8 63 1640 1640 117.1 1630 1630 119.4 1615 1615 122.0 85 67 1723 1489 119.4 1706 1482 121.8 1687 1474 124.3 71 1843 1280 122.9 1825 1274 125.4 1806 1267 127.9 63 1617 1240 116.4 1601 1233 118.8 1583 1226 121.2 75 67 1738 1022 119.8 1720 1015 122.1 1701 1007 124.6 71 1863 799 123.4 1847 793 125.8 1825 785 128.4 63 1625 1500 116.5 1608 1492 118.9 1590 1484 121.4 80 67 1737 1284 119.8 1719 1277 122.2 1703 1271 124.6 71 1861 1061 123.4 1843 1055 125.8 1823 1048 128.3 63 1676 1676 117.9 1663 1663 120.4 1646 1646 123.0 85 67 1742 1544 119.9 1724 1537 122.3 1705 1529 124.8 71 1861 1324 123.5 1842 1317 125.9 1823 1310 128.4 DO NOT SELECT NOMINAL CAPACITY CAT 219-2 ROOFPAK PACKAGED SYSTEMS 36 www.daikinapplied.com

Cooling Capacity Data Table 19: RPE/RDE 150C High Airflow Coil Unit Data 43000 cfm 5 row 12 fpi 46000 cfm 5 row 10 fpi 49000 cfm 5 row 10 fpi Entering Air Ambient Wet Bulb Temperature 70 75 80 DB WB TH SH KW TH SH KW TH SH KW 63 1715 1228 130.1 1699 1220 132.5 1681 1212 135.0 75 67 1848 1032 133.7 1830 1025 136.1 1812 1017 138.6 71 1986 833 137.8 1968 826 140.2 1948 818 142.7 63 1717 1463 130.1 1701 1456 132.5 1683 1448 135.0 80 67 1846 1267 133.7 1829 1260 136.1 1810 1252 138.7 71 1983 1067 137.7 1964 1060 140.2 1945 1053 142.7 63 1729 1694 130.4 1713 1686 132.8 1693 1675 135.4 85 67 1843 1500 133.8 1828 1494 136.2 1809 1486 138.7 71 1980 1301 137.7 1961 1294 140.1 1941 1287 142.6 63 1716 1253 130.1 1701 1246 132.5 1682 1238 134.9 75 67 1849 1047 133.8 1831 1040 136.2 1813 1032 138.7 71 1986 837 137.8 1967 830 140.2 1948 823 142.7 63 1721 1500 130.1 1704 1493 132.5 1687 1485 135.0 80 67 1847 1294 133.7 1830 1287 136.1 1811 1280 138.6 71 1983 1084 137.7 1964 1077 140.2 1944 1070 142.7 63 1735 1729 130.7 1721 1719 133.1 1706 1706 135.7 85 67 1847 1541 133.8 1829 1533 136.2 1811 1526 138.7 71 1980 1331 137.7 1961 1324 140.1 1941 1316 142.6 63 1737 1292 130.7 1720 1285 133.1 1702 1277 135.6 75 67 1870 1074 134.3 1849 1066 136.8 1830 1058 139.3 71 2007 851 138.4 1988 844 140.8 1968 837 143.3 63 1741 1553 130.7 1724 1545 133.1 1706 1537 135.6 80 67 1867 1336 134.3 1849 1329 136.8 1830 1321 139.3 71 2004 1113 138.4 1985 1106 140.8 1965 1099 143.3 63 1770 1770 131.7 1755 1755 134.2 1741 1741 136.8 85 67 1868 1597 134.4 1850 1589 136.9 1831 1581 139.4 71 2001 1375 138.4 1985 1369 140.7 1964 1362 143.3 DO NOT SELECT NOMINAL CAPACITY Table 20: RPE/RDE Condenser Fan and Spray Pump Power Consumption 1.5 hp Spray Pump on all units 1.8 kw per condenser fan motor Unit Size Number of Condenser Fans Spray Pump & Condenser Fan Total kw RPE 076C-100C 4 4.6 RPE 110C-150C 6 6.2 www.daikinapplied.com 37 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Heating Capacity Data Heating Capacity Data Figure 26: Steam Coil, Low Capacity Figure 28: Steam Coil, High Capacity Figure 27: Steam Coil, Medium Capacity Table 21: Saturated Steam Properties Pressure (psig) Temperature ( F) Latent Heat (Btu/lb.) 2 218.5 966.1 5 227.1 960.6 10 239.4 952.6 15 249.7 945.7 25 266.8 934.0 Table 22: Steam Valve Selection Chart Valve Size (inches) Condensate Rate, lb./hr. Steam Supply Pressurea 5 psig 10 psig 15 psig 25 psig 1 196 260 301 380 391 480 571 650 1-1/4 261 380 381 560 481 700 651 940 1-1/2 381 600 561 870 701 1090 940 1470 2 601 950 871 1390 1091 1750 1471 2350 2-1/2 951 1330 1391 1940 1751 2450 2351 3290 3 1331 2020 1941 2950 2451 3716 Based on valve pressure drop of 80% of saturated steam supply pressure. CAT 219-2 ROOFPAK PACKAGED SYSTEMS 38 www.daikinapplied.com

Heating Capacity Data Figure 29: Hot Water Valve Pressure Drop RPE/RDE 076C - 150C Figure 30: Hot Water Valve Piping Pressure Drop RPE/RDE 076C - 150C www.daikinapplied.com 39 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Heating Capacity Data Electric Heat Minimum cfm must satisfy two issues: 1. Maximum temperature rise is 60 F, therefore (minimum cfm = (MBh) (1000) / (1.085) (60). 2. Airflow must not be less than 22,000 cfm regardless of temperature rise. Table 23: Electric Heat Options Model 80 100 120 160 200 240 280 320 208 Volt MBh 204 255 306 408 510 612 714 816 230-460, 575 Volt MBh 249 312 374 499 624 748 873 998 Table 24: Gas Furnace Design Maximum Air Temperature Rise ( F) and Minimum Air Flow Baffle Position A B C Maximum Temperature Rise ( F) Minimum Airflow (cfm) Furnace Size (MBh) 500 650 790 800 1000 1100 1400 1500 2000 Maximum Temperature Rise 100 100 61 100 61 100 61 100 61 Minimum cfm 4600 5970 12000 7340 15000 10100 21000 13700 30000 Column Number* 2 3 3 3 3 4 4 7 7 Maximum Temperature Rise 63 73 52 76 50 73 34 82 49 Minimum cfm 7400 8200 14000 9800 18500 14000 38000 17000 38000 Column Number* 5 4 4 4 4 6 6 8 8 Maximum Temperature Rise 55 65 46 71 40 64 33 73 40 Minimum cfm 8400 9200 16000 10400 23000 16000 39000 19000 46000 Column Number* 10 10 10 10 10 10 10 10 10 *Column Number for Pressure Drop (See Table 26 on page 41) Table 25: Gas Burner Connection Size (inches) and Gas Inlet Pressure (in. W.C.) Description Minimum Gas Inlet Pressure (In. W.C.) Gas Pipe Connection Size Inches (N.P.T.) Furnace Size (MBh Output) 500 650 790 800 1000 1100 1400 1500 2000 Natural Gas (CFH) 625 812 1000 1000 1250 1375 1750 1875 2500 Standard Burner 7.00 7.00 7.50 7.50 9.00 7.00 8.00 8.00 9.00 20:1 Burner 5.50 7.00 6.50 6.50 6.50 5.00 5.00 5.00 6.00 Through 0.5 psi 1.00 1.25 1.25 1.25 1.25 1.50 1.50 1.50 2.00 2-3 psi 1.00 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.50 5-10 psi 1.00 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 CAT 219-2 ROOFPAK PACKAGED SYSTEMS 40 www.daikinapplied.com

Heating Capacity Data Table 26: Furnace Pressure Drop (in. W.C.) Airflow (cfm) Column Number (See Table 25 on page 38) 2 3 4 5 6 7 8 9 10 4000 0.05 6000 0.1 8000 0.17 0.14 0.08 0.07 10000 0.27 0.22 0.12 0.11 0.09 0.08 12000 0.39 0.32 0.17 0.16 0.13 0.12 0.09 0.08 14000 0.54 0.44 0.24 0.21 0.18 0.16 0.12 0.1 0.1 16000 0.7 0.57 0.31 0.28 0.24 0.2 0.15 0.13 0.12 18000 0.89 0.72 0.39 0.35 0.3 0.26 0.19 0.17 0.16 20000 1.09 0.89 0.48 0.43 0.37 0.32 0.24 0.21 0.2 22000 1.08 0.58 0.52 0.44 0.39 0.29 0.25 0.24 24000 0.69 0.62 0.53 0.46 0.34 0.3 0.28 26000 0.81 0.73 0.62 0.54 0.4 0.35 0.33 28000 0.94 0.85 0.72 0.63 0.47 0.41 0.38 30000 1.08 0.97 0.83 0.72 0.54 0.47 0.44 32000 1.23 1.11 0.94 0.82 0.61 0.53 0.5 34000 1.25 1.06 0.92 0.69 0.6 0.56 36000 1.19 1.04 0.77 0.68 0.63 38000 1.15 0.86 0.75 0.7 40000 0.95 0.84 0.78 42000 1.05 0.92 0.86 44000 1.15 1.01 0.94 46000 1.11 1.03 48000 1.2 1.12 50000 1.22 *Column Number for Pressure Drop (See Table 24 on page 40) www.daikinapplied.com 41 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Gas Piping Schematic Figure 31: Gas Piping Schematic Vent to atmosphere Gas Piping Schematic 9 22 10 11 13 11 9 15 16 *Minimum inlet pressure required varies with model and arrangement, from 5 to 9 inches wc 7 21 12 14 17 *Low Pressure 9" 14" wc standard 6 20 Modulation option 2 5 Natural gas shown. For LP gas, delete 4 16 18 19 1 4 3 *High Pressure High pressure option required for inlet gas pressure over 0.5 psig 18 19 Table 27: Gas Piping Descriptions Item Description FM/ETL/UL FM/ETL-C IRI Thru 400 MBh Over 400 MBh Thru 400 MBh Over 400 MBh 400 2000 MBh 1 Forced draft blower Standard Standard Standard Standard Standard 2 Combination air switch Standard Standard Standard Standard Standard 3 Pilot cock Standard Standard Standard Standard Standard 4 Pilot pressure regulator Standard Standard Standard Standard Standard 5 Pilot gas valve Standard Standard Standard Standard Standard 6 Pilot orifice Standard Standard Standard Standard Standard 7 Main gas orifice Standard Standard Standard Standard Standard 8 Manifold pressure tap Standard Standard Standard Standard Standard 9 High pressure switch Standard 10 Test cock Standard Standard Standard Standard Standard 11 Leak test tap cock Standard 12 Safety shutoff valve 13 Vent to atmosphere valve, N/O 14 Safety shutoff valve Combination redundant valve and pressure regulator Standard Combination redundant valve and pressure regulator Standard Standard Combination redundant valve and pressure regulator Standard Combination redundant valve and pressure regulator Safety shut off valve Safety shut off valve with proof of closure switch 15 Low pressure switch Standard 16 Main pressure regulator Combination redundant valve and pressure regulator Standard Combination redundant valve and pressure regulator Standard Standard 17 Main gas shutoff cock Standard Standard Standard Standard Standard 18 19 20 21 High pressure regulator Lubricated shutoff cock Combustion air butterfly valve Main gas butterfly valve Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional 22 Modulating operator Optional Optional Optional Optional Optional Table 28: Gravity Relief Damper Air Pressure Drop 0-100% Economizer Exhaust cfm 20000 25000 30000 35000 40000 Size 076C-150C 0.25 0.35 0.48 0.66 0.85 Note: If all exhaust must occur through the economizer gravity relief damper, and no return or exhaust fan is provided, then the building may be pressurized by the sum of the return duct pressure drop plus the gravity relief pressure. CAT 219-2 ROOFPAK PACKAGED SYSTEMS 42 www.daikinapplied.com

Component Pressure Drops Table 29: Component Pressure Drops Component Pressure Drops Outdoor/Return Air Options 1, 2 Filter Options Plenum Options Component Airflow (cfm) 26,000 30,000 34,000 38,000 42,000 46,000 50,000 0-30% outside air hood w/damper 0.11 0.14 0.18 0.23 0.28 0.34 0.40 100% outside air hood w/damper 0.03 0.03 0.04 0.06 0.07 0.08 0.09 Economizer, w/o RAF 0.15 0.20 0.26 0.32 0.39 0.46 0.54 Economizer, w/raf 0.29 0.36 0.44 0.52 0.61 0.70 0.80 30% pleated 0.11 0.13 0.15 0.18 0.21 0.24 0.27 Prefilter, standard flow 0.24 0.31 0.37 Prefilter, medium flow 0.21 0.25 0.31 0.36 Prefilter, high flow 0.15 0.18 0.22 0.26 0.30 0.34 0.39 65% cartridge, standard flow 0.43 0.55 0.68 65% cartridge, medium flow 0.35 0.44 0.54 0.65 65% cartridge, high flow 0.24 0.31 0.38 0.45 0.53 0.62 0.71 95% cartridge, standard flow 0.57 0.71 0.85 95% cartridge, medium flow 0.47 0.58 0.70 0.83 95% cartridge, high flow 0.34 0.42 0.50 0.59 0.69 0.79 0.89 Return, isolation damper 0.03 0.03 0.03 0.03 0.03 0.03 0.03 Discharge, isolation damper 0.03 0.03 0.03 0.03 0.03 0.03 0.03 Cooling Cooling diffuser 0.07 0.10 0.13 0.16 0.19 0.23 0.28 Options 3 Cooling coils See Table 30: Cooling Coil Air Pressure Drop Heating Options Hot water, 1-row 0.19 0.24 0.30 0.36 0.43 0.50 0.58 Hot water, 2-row 0.38 0.48 0.60 0.72 0.86 1.00 1.16 Steam, 1-row, 6 fpi 0.15 0.19 0.24 0.29 0.34 0.40 0.46 Steam, 1-row, 12 fpi 0.25 0.31 0.37 0.45 0.52 0.60 0.69 Steam, 2-row, 6 fpi 0.30 0.39 0.48 0.58 0.68 0.80 0.92 Electric heat 0.14 0.19 0.24 0.30 0.37 0.45 0.53 Gas heat See Table 26: Furnace Pressure Drop (in. W.C.) on page 41 1. Pressure drop through hood and damper is based on 30% of listed airflow. 2. Pressure drop through the economizer assumes that the majority of air will be passing through the return air dampers. If large quantities of outside air are required, pressure drops will increase causing airflow to decrease. 3. A diffuser is provided on units with blow-through cooling coils, final filters or hydronic heating. Table 30: Cooling Coil Air Pressure Drop Unit Size 076C 100C 110C 150C Cooling Coil Airflow (cfm) 28000 30000 32000 34000 36000 38000 40000 42000 44000 46000 48000 50000 DX, low airflow, 5-row, 10fpi 0.72 0.78 0.87 0.95 DX, low airflow, 5-row, 12fpi 0.85 0.92 1.02 DX, high airflow, 5-row, 10fpi 0.60 0.65 0.72 0.79 0.86 0.93 DX, high airflow, 5-row, 12fpi 0.71 0.77 0.85 0.93 1.01 DX, low airflow, 5-row, 10fpi 0.60 0.67 0.74 0.81 0.88 0.95 DX, low airflow, 5-row, 12fpi 0.72 0.80 0.87 0.95 1.04 DX, high airflow, 5-row, 10fpi 0.43 0.48 0.53 0.58 0.63 0.68 0.73 0.78 0.84 0.89 0.95 1.01 DX, high airflow, 5-row, 12fpi 0.52 0.57 0.62 0.68 0.74 0.80 0.86 0.92 0.98 1.05 NOTE: DX coil pressure drops are based on wet coils. Pressure drop of cooling coils not shown can be found in the Daikin selection program output. www.daikinapplied.com 43 CAT 219-2 ROOFPAK PACKAGED SYSTEMS

Fan Performance Data Return Fans & Exhaust Fans Fan Performance Data Figure 32: All Sizes (2) 36 Propeller Exhaust Fans DO NOT SELECT CLASS II FAN REQUIRED Figure 33: All Sizes (3) 36 Propeller Exhaust Fans DO NOT SELECT CLASS II FAN REQUIRED CAT 219-2 ROOFPAK PACKAGED SYSTEMS 44 www.daikinapplied.com