COMPACT FLAME CONTROLLER CFC 100

Similar documents
COMPACT FLAME CONTROLLER CFC 200 (Formerly 8.XX)

COMPACT FLAME CONTROLLER CFC 1000

COMPACT FLAME CONTROLLER CFC 2000

FLAME AMPLIFIER MODULE 3001

FLAME AMPLIFIER MODULE 3001D

Products Catalog. Flame Monitoring & Evaluation Systems

Products Catalog. Flame Monitoring & Evaluation Systems

Flame Monitors BROCHURE

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B)

UV - flame detector dual fuel burners for intermittent burner operations

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660

ABB. Measure IT Uvisor System Dual sensor flame scanner. UR460 Mod. UVIR /ER/EF/DV Flame Scanner Product Data Sheet (rev B)

UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations

UV Flame Supervision System

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev.

D-GF 150. Burner Control for Gas and Oil Burners Flame Sensor D-GF 150 D-LE 103

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

Wide Band Flame Detector KLC 20 for all kind of oil flames with intermittent burnerr operations

Eclipse 90 UV Scanner Model A Version 1

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

Technical Description Relay Module Flame Detector

Snifter ATEX22 VERSION. User Manual. Distributor

EZ-FLAME Detector USER MANUAL

Acessories BROCHURE JUNHO 2013

W-FLAME IR/UV FLAME DETECTOR

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

System Overview F300K Compact Flame Scanner. Sensors and systems for combustion engineering.

QRA10... QRA53... QRA55...

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Product Overview Combustion Technology

Manual Power relay SR853

MBCE-110/230UV Flame Sensor Module

Chemical Processes in the Combustion

Eclipse Self-Check UV Scanner

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

QRA10... QRA53... QRA55...

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

Symphony Plus Combustion instruments

QRA10... QRA53... QRA55...

S55XB and S55XBE Series Viewing Heads

Product Overview Combustion Technology

XGUARD-10/-5. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE!

INDUSTRIAL FLAME SCANNERS

Infrared Flame Detectors

FIREYE C9707A ALL FUEL SCANNER

Power Supply Display Module PSDM. Installation and Operation Manual

Gas Turbine Flame Monitoring

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE!

Infrared Flame Detectors

TYPE 85UVF/IRF Integrated Flame Scanner with Internal Flame Relay

Flame detector. The QRA4.U is for use with the following types of burner control:

HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S

Fibre Optic System D-LL 703/704

Dräger Flame 2100 Flame Detection

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

S55XB and S55XBE Series Viewing Heads

LAE10 LFE10. Use. Series 02

DATASHEET. Burner control unit FDA 601x

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12

Flame detector. The QRA4.U is for use with the following types of burner control:

Gas cooler series TC-Standard+ X2

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place

Dräger Flame 2500 Flame Detection

TYPE 95IR/95UV/95DS. Integrated Flame Scanner with Internal Flame Relay TUV SIL2 DESCRIPTION MODEL S1, S2. RoHS Compliant to EU Directive 2002/95/EC

Gas cooler series TC-Standard+

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Distributed By: M&M Control Service, INC

EUROFLAT SERIES TYPES C... S... M...

D-LX 100 All-In-One Flame Scanner

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Forced draught gas burner

Dräger Flame 2350 (UV&IR) Flame Detection

Flame detector. Building Technologies Division Infrastructure & Cities Sector

55UV5 SCANNER MODEL 1010

Document code: 1 (10) Issuing date: Status:

RS /E-EV C01 SERIES

SWARCO TRAFFIC SYSTEMS GMBH. TDD1-MW Traffic Detector User Manual TDD1-MW_BE_00

Dräger Flame 2700 (Multi-IR) Flame Detection

Snifter. User Manual. Distributor

MANUAL Overflow sensor NVF-104/34-PF

TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Rota-Sonde DC4000-L. Laser pointer for easy alignment. Remote control of the sensitivity

Laser Distance Sensor Type M Analog-Output

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

Dräger Flame 2370 (UV&IR) Flame Detection

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

SensaGuard TM Integrated Latch Installation Instructions

Line Isolation Monitor (LIM) LIM2000plus

Dräger Flame 2500 (IR3) Flame Detection

ISIS SAFETY SYSTEM Installation guide

SCHMIDT LED Measured Value Display MD Instructions for Use

U2 Combination Viewing Head and Signal Processors

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

Manual Isolating Barrier D461R1 (Revision 01)

Transcription:

COMPACT FLAME CONTROLLER CFC 100 TECHNICAL DESCRIPTION EDITION: TB CFC100 EN REV. 1 2012-03-07 IMPORTANT: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring and evaluation equipment should only be carried out by fully trained and authorized personnel. BFI Automation is pleased to support you if you do not have any experience with the equipment. Our service personnel are carrying out world wide installations, supervision and commissioning and is available upon request. For the stage of planning you can ask our sales and project engineers for any support you may need. BFI Automation is providing any kind of training for your engineers. PLEASE READ THIS LEAFLET CREFULLY AS IT CONTAINS NECESSARY IN- FORMATION FOR THE USE OF THIS EQUIPMENT. FOR MORE DETAILED IN- FORMATION PLEASE REFER TO THE OPERATING AND MAINTENANCE MA- NUAL. BFI Automation Dipl.-Ing. K.-H. Mindermann GmbH, Eggerscheidter Str. 57, 40883 Ratingen, Germany Tel. +49 2102 96 82 0, Fax +49 2102 9682 42 E-Mail: info@bfi-automation.de

Compact Flame Controller CFC 100 UV - Flame scanner with integrated flame controller - tested by German TÜV - For intermittent, continuous and 72hours operation - Recommended for gas and oil flames, also in combination - Recommended for Duct burners and heat recovery boilers - Dual channel design - Adjustable sensitivity settings via hand terminal HT100 - Analog Output 4 20 ma for flame intensity - Flame analysis via hand terminal HT100 - Optical status indication - No special cables required - Type of protection IP 65! WARNING WARNING: IMPROPER INSTALLATION OF THESE PRODUCTS MAY BE HAZARDOUS TO LIFE AND PROPERTY Function The Compact Flame Controller CFC100 is equipped with a high temperature resistant UVtube. The preamplifier generates an impulse signal which is proportional to the detected UV radiation. The subsequently thresholds adjustment is used for the discrimination and adaptation to the respective burner condition. The further functional groups integrate the signal processing for the dynamic monitoring channel, which, by means of a dark-phase monitoring, continuously checks the failure-safety of the unit. A component defect leads to an immediate switch-off of the flame-relay, which is available as a potential-free changeover contact. The switching state flame on is displayed by a yellow LED on the rear side of the unit, just as the intensity of flame, which is displayed by a flashing green LED. A flame intensity output 4 to 20 ma can be used for external displays. The safety switch-off time is fixed to 1 second.

Adjustment of Analog output 4 to 20mA Adjustments like current start value and signal window can be done with the hand terminal HT100. Mounting The correct positioning of the sight tube to the flame with less vibration is an important requirement for an optimised flame control. The assembly must ensure the primary combustion zone is inside the visible angle of the flame monitoring device for all loads. Length and diameter of the sight tube are directly related to the available flame radiation, because the visibility angle of the device is defined. The maximum length L of a sight tube is related to the tube s diameter d. d 1" 1,5" 2" L 0,5m 0,8m 1,1m The tube should be as short as possible. A diameter of 2 inch is recommended. The right adjustment is shown in the following drawing. The optical adjustment device BFI 235 is available ex stock (part-no.: P 106) The compact flame controller is delivered with a flange for quick assembly. The device is equipped with a supply for purge air which prevents the lens of contamination with dust and a subsequent damage. The optimised assembly kit consists of heating insulator, blocking valve and ball flange. These mechanical devices are also available on demand. Maintenance In case of a natural ageing depending UV tube degradation the UV tube unit can be replaced. This replacement must be done by following our UV-Tube Replacement Instructions. UV-Tube units and replacement instructions are available at BFI. Alternatively the replacement can be done at BFI factory in Germany.

flame root combustion area primary air fuel changing of frequency and amplitude in relationship to the distance of the flame root flame scanner mounting flange ball flange sight tube how to adjust in the right way 30 adjustment angle 30 max optical adjustment heating insulator right wrong 30! CAUTION CAUTION: All alignment and adjustment procedures should be used whenever parts are replaced, when the scanner has been moved, when the flame shape has altered (additional fuels, new burners, burner/register modifications), as well as on new installations.

Installation The pin configuration of the plug connector is shown in the terminal connection diagram. The flame intensity output has no potential separation from the power supply; it is related to the power supply ground. If there will be any problem in this case an isolation amplifier can be delivered on demand. A maximum shunt resistance of 500 Ω should not be exceeded. The device is immediately ready for operation after switching on the power supply.!!do not disconnect the flame controller while energized!! Connection Diagram 1 Plug configuration 2 3 PI N Internal connection Colours of BFI special cable KW6 1 white 2 brown 7 6 5 4 3 pink 4 + 24V DC green 5 0 V yellow 6 Current output 4-20 ma grey 7 switching channel 2 with external 24 V DC red Connection of compact flame controller Internal contact colour function 1 white Flame relay root x 2 brown Flame relay Flame ON x 3 pink Flame relay Flame OFF x External Bruner control ma- Anzeige Power supply 4 green Power supply +24V DC +24V DC/200mA 5 yellow Power supply GND - GND 6 grey Analog output + (4 bis 20mA) + 7 red Switching channel 2 (+24V DC ext.) (x)! CAUTION CAUTION: On all applications the compact flame controller must be tested by starting and stopping the burner several times to ensure proper operation. (e.g.: The flame relay must reliable drop out for all flame conditions.) The testing should be done with various adjacent burners ON and OFF and at various load levels. This is a requirement for proper operation.

Standard Housing Purge air Standard housing suitable for ATEX Zone II Accessories Hand Terminal HT100 Power supply 230/115V AC Swivel mount 1 inch and 2 inch flange disk Heating insulator 1 inch 3-way ball cock 1inch Pressure screw joint 5bar size 1 inch Optical adjusting device

Technical Data Spectral sensitivity Angle of view Power Supply input Current consumption Ambient temperature Current output Channel switchover Flame relay Switch thresholds Switch OFF times 185 to 260 nm chooseable 2.7 or 30 degrees 24 V DC approx. 200 ma -20...+60 degrees C 4-20 ma (Ra < 500 Ohm) Current window adjustable via hand terminal HT100 remotely via 24 V DC 1 Switch-over-contact, potential free VDE 0110, Class A max. 60 V switching voltage max. 0.5 A switching current (fused 1A) max. 30 W switching power adjustable via hand terminal HT100 fixed to 1 s Sight tube connection 1" internal thread ISO 228 Purge air connection 1/2" internal thread ISO 228 Purge air quantity 10 Nm 3 /h Electrical connection Amphenol-Tuchel-Connector C16-1 Housing dimensions Standard incl. flange 210 x 108 mm (length x diameter) Type of Protection Standard Housing IP 65, similar to NEMA 4 ATEX Zone 2 II 3 G Ex na II T4 Weight Standard 1.5 kg Electronic self-monitoring for the fail-safe function control of the device according VDE 0116, EN 230, EN 298, and TRD 411 to 414. CE-conform Rights for technical changes reserved BFI Automation 2012