Chapter 4 Compressors Overview & System Annual Power Consumption

Similar documents
Partial Load Performance Of Refrigeration System

Chapter 1 Preface & General

Copy Right By: Thomas T.S. Wan

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Case 8 Basic Performance of Screw Compressor

Case 6 Impact of Fouling Factor and Special Material for Heat Exchanger

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Copy Right By: Thomas T.S. Wan

HVAC Water chiller selection and optimisation of operation

Case 13 Food Storage & Processing Center

PREVIEW COPY. Compressors. Table of Contents. Introduction to Compressors...3. Lesson Two Reciprocating Compressors...21

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

R07. Answer any FIVE Questions All Questions carry equal marks *****

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Vacuum Booster for Distillation Process

EN aquatech.piovan.com

Torad Rotary Spool Compressor

Ducted Propeller. Airflow Volume

Pressure Enthalpy Charts

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

Modern vacuum and overpressure generation for pneumatic conveying

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

How to Cut Chiller Energy Costs by 30%

Rotodynamic Pumps INTRODUCTION:

Refrigeration & Air Conditioning Experiment No. 5. Experiment No. 5

Water engineers and utilities are often

Refrigeration Systems and Accessories

Air-Cooled Condensers

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

1900 Series In-Line Pump

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Intermediate Refrigeration Systems for Operators

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

PUMPS FOR LIVESTOCK WATERING SYSTEMS. This Factsheet outlines the design and operation of pumps that are suited for livestock watering systems.

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

DTI Kenneth Bank Madsen Global Application Expert Food Retail

HVAC/R Refrigerant Cycle Basics

Chapter 8. Production of Power from Heat

Chapter 9. Refrigeration and Liquefaction

Air-Cooled Condensers

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

THERMAL ICE STORAGE: Application & Design Guide

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

PROJECT MANUAL GUIDE SPECIFICATIONS FOR: PFANNENBERG SERIES CC COMPACT PACKAGED CHILLERS PART 1 GENERAL

Rich Knoelke. Questions or Comments: Mulcahy Shaw Water.

REFRIGERATION AND AIR CONDITIONING

Pumps SELECTION OF A PUMP

Oil-Less Rotary Screw Compressors Variable Speed. Engineered to Save

CONTENTS. Air Conditioning Fundamentals TC S

Air Compressor Efficiency Opportunities. Industrial Energy Efficiency Workshop December 11, 2007

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Frigi Tech International, Inc Prairie Wind Lane,. Houston, Texas T: F:

Irrigation Water Pumps

CENTRAL SPLIT UNIT UNIC

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Air conditioning 23XRV

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Improving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions.

Environmentally friendly refrigeration systems for industrial use

OIL-FREE COMPRESSOR. Let s write together a new chapter in the refrigeration history.

The pump. A pump is a device that moves fluids (liquids or gases), or sometimes slurries, by mechanical action.

Oil-Less Rotary Screw Compressors

CHAPTER 3 BASIC STEAM CYCLE

BVG series Biogas and landfill gas applications

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents

Water Pumps. turbo-hydraulic pumps, positive-displacement pumps.

WHY SULLAIR? For more information on the IHI-Sullair joint venture, please visit 2,000th IHI-Sullair centrifugal

Technical Note. EHPA Quality Label Model Range Definition Version

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

The Digital Scroll Dryer

The Design Flaw in HVAC

CURRICULUM BREAKDOWN

NATURAL REFRIGERANT SYSTEMS

Understanding Process Vacuum for Process Improvement

2016 Annual Conference

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Chapter B-2. Chapter 2. Air generation and distribution. Festo Didactic TP101

2. CURRICULUM. Sl. No.

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

KELVIN Clim F497. Kelvin air conditioning

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

energydesignresources

Page 1 of Relevant Provincial Jurisdictional legislation.

CHECK VALVES INSTALLATION

DISCLOSURE THIS GUIDEBOOK WAS PREPARED BY THE IRC. NEITHER THE IRC, NOR ANY PERSON ACTING ON BEHALF OF THEM:

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

Transcription:

Chapter 4 Compressors Overview & System Annual Power Consumption Copy Right By: Thomas T.S. Wan 温 Sept. 3, 2008 All rights reserved (Cor. 07-08-12) Compressor is the heart of the refrigeration system. The character of the compressor greatly influences the performance and the power consumption of the refrigeration system. Therefore, it is important to realize the characteristics of the compressor when a refrigeration system is being designed. Also, the power consumption and economic balance are to be taken into the consideration when selecting the compressor and the major components of the system. The industrial refrigeration system is designed to control the process temperature or to keep the evaporative temperature to ensure the quality of the product being made or to meet the process requirement. In order to achieve this sole purpose, the compressor for refrigeration application shall have the following features and capabilities: (1) The compressor is to be equipped with automatic control devices for partial load operation and should be able to maintain the design temperature in the evaporator under any load variation. (2) The compressor should have wide range of part load capability. (3) The lubrication system for the compressor is not to be open to outside atmospheric to avoid contamination. (4) Oil used should be refrigeration oil. (5) Seal gas used should be enclosed and shall be the same as the refrigerant being used for the system. Compressor Characteristics: FIG. 4-1 shows the compressor group available for industrial refrigeration application. The Internally Compound reciprocating compressor is used mostly for packaged unit; Rotary compressor was used for booster duty and it is now not commonly used; Ejector type compression device and Axial Flow compressors are also not commonly used by industrial refrigeration equipment manufacturers. Therefore, these compressors are not included in this manual. FIG. 4-2 shows the characteristics of the compressors commonly used for industrial refrigeration application. The horizontal axis represents the flow or capacity and the vertical axis represents the compression head. 40

41

From the FIG. 4-2, the reciprocating compressor performance curve is almost vertical; that means the capacity variation for a reciprocating compressor is very limited, however, the compressor can handle wide range of compression head; Because of this character, reciprocating compressor is referred to as a variable head and constant volume machine. In the same diagram, the performance curve for centrifugal compressor is almost flat, that means the centrifugal compressor can handle wide range of capacity variation, but, the head change capability is limited; Because of these characters, the centrifugal compressor is referred to as a variable volume and constant head machine. The screw 42

compressor curve lies between the reciprocating and centrifugal compressors; therefore, the screw compressor is a variable head and also it is a variable volume machine. The screw compressor has the advantages of both centrifugal and reciprocating compressors; best of all, it does not have the disadvantages of both centrifugal and reciprocating machine. Table 4.1 Compressor Comparison Major Characteristics: Reciprocating Screw Centrifugal Compressor Compressor Compressor Compression Head Variable Variable Constant Capacity Constant Variable Variable Suction Volume Flow Low Medium High Motion Reciprocating Rotary Rotary Capacity Control Step Control Continuous Variable Continuous Variable From the Table 4.1, it is very obvious that the screw compressor has all the advantages as compared to other types of compressors for refrigeration application. That is the reason why screw compressors are so popular in the refrigeration industries. The size of screw compressor is getting smaller; the screw compressors took over the capacity application range which used to be covered by the reciprocating compressor. The size of screw compressor is also getting bigger, particularly the twin-rotor screw, the screw compressors penetrated the areas where the applications are traditionally covered by centrifugal machines. FIG. 4-3 shows a typical refrigeration system curve. This system curve might change due to load requirement of the process. The industrial refrigeration system operates 365 days per year unless it is scheduled for service and maintenance. The fundamental and primary duty for the compressor for the application is to be able to perform and to fulfill the requirement of evaporative temperature at the full load and to meet the partial load operation. The installations for industrial refrigeration are usually with open drive. Sometimes, a special driver such turbine or engine is used instead of motor. Therefore, this manual inclines to cover larger size open type compressors instead of hermetic machines. 43

System Annual Power Consumption: Power consumption and energy conservation are the most important considerations for industrial refrigeration systems design these days. Therefore, when designing the industrial refrigeration system, the power consumption, particularly the annual power consumption should be carefully exam. FIG. 4-4 shows the relationships between the major components of the refrigeration system and also the formula to estimate the annual energy use for the system. This formula can also be used as the justification and comparison for the selection between different compressors or systems. 44

45

The power consumption calculation for the compressor and refrigerant flow for the load (TR) are as the following (See Chapter-2): Head = (H 2 H 1 ) x 778 = ( H) x 778 = Ft. 200 Flow = -------- -- x TR NRE Flow x Head (Compressor HP) Design = ---------------------- 33000 x E ff Where: Flow: Refrigerant Flow, Lbs/Min at design point. Head: Compression Head, Ft. at design point. Compressor Overall Efficiency at design point. E ff From the FIG. 4-4, the annual power consumption is greatly depending on the power consumption of the refrigeration system at the design point (BHP) design or (KW) design ; The annual power consumption also depends on the conditions as how the system is behaved during the partial load operation; It is important that the refrigeration system is to be designed and to be operated in such way that it is able to take the advantages of reduce head (HD%) and reduce capacity (TR%); also the compressor partial load efficiency ( %) is another important factor as shown in the formula. The compressors for industrial refrigeration are practically to be operated year round. Typical operation time is about 6000 to 8000 hours per year. FIG. 4-5 shows the annual Kw-Hr power consumption evaluation for the refrigeration system with operating hours of 8000 per year; the friction HP loses and oil pump are added for this case. 46

47