TRUERH Series HE-67xx Humidity Element with Temperature Sensor

Similar documents
Location Requirements

A99B Series Temperature Sensors

GCS Multipoint Carbon Dioxide Gas Concentration Sampler

W43A Humidistat. Features and Benefits

MR3CCUHV Temperature/Defrost Control

HT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Standard Downrod for ceilings 8-10 feet high. Longer Downrod for ceilings 10 feet or higher

Model Smart Digital Humidistat

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

Table of Contents What to Expect with Your Installation. Ceiling Plate. Tools Needed.

A19, A28 Series Thermostats for Agricultural Buildings

TM-3100 Series Room Temperature Sensor

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

A99B Series Temperature Sensor

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

0-10 V Wall & Duct Humidistat Installation Instructions

Table of Contents What to Expect with Your Installation. Tools Needed. Motor Housing.

TECHNICAL BULLETIN. Model Smart Digital Humidistat. Installation and Owner's Manual. General Description

Table of Contents. What to Expect with. Mounting Options. Tools Needed. Preparation. Wiring. Downrod.

Installation Instructions

Viking Installation Guide

T500 Series Non-Programmable Thermostats

Model 76 Dehumidifier Control Installation Instructions

Table of Contents. What to Expect with. Mounting Options. Tools Needed. Wall Control

C7232A,B Sensor and Controller

INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM

RH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description

TEC210x-2 Series Networked Thermostats

Installation Instructions

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

TEC2100 Series Networked Thermostats

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control

L62GB BASO Safety Shutoff Device

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

TC-5231 Series, TC-5232, & TC-5241 Series

ACT2-CS Convenience Store Controller

AS570 Chill-Out Combination Sensor Installation and Operating Instructions

SC Installation, Operation & Application Guide

WIDE AREA VACUUM MODEL PF2030 WARNING: OPERATOR MUST READ AND UNDERSTAND THIS MANUAL COMPLETELY BEFORE OPERATING THIS EQUIPMENT.

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

HE220, HE260 Humidifier Installation Kit

Duct and Rough Service Carbon Monoxide Sensor

TEC3000 Series Stand-Alone and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

Installation Instructions

Digital Panel Meter K3TL. Ordering Information. Low-cost, High-quality Digital Thermometer with Built-in Microcomputer. Accessories (Order Separately)

Installation Guide. Model: IC15- MF Model: IC15- MFSilent Model: IC30- MF Model: IC30- MFSilent

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

CONSTANT SUCTION UNIT

OUTDOOR DISHWASHER INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS

Owner s Guide and Installation Manual

Crown Boiler Company

Booster Power Supply Manual

Installation Instructions

Surface-Mounted NS Series Network Sensors without LCD

136"ElectricCooktop. nstructlons _,00, JP961, JP968, JP969, ZEU769. I Iinstallation. -&WARNING - This appliance must be properly grounded.

FLT93 Installation, Operation and Troubleshooting Guide

Model NT20e Installation Guide

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

Installation Manual. Models 99168, 99169, 99170

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

Model PF 2030 Wide Area Vacuum Cleaner

DE20 INSTRUCTION MANUAL

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

Vapor-logic 3 to Vapor-logic4

Over-the-Range Microwave Oven Installation Instructions MVH130* MVH230* MVH330*

DISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

FS80-C Flow Switch. Features and Benefits. Allows user select the setting according the needs of system

Analog Room Pressure Monitor RPC Series

Some models are supplied with a protective film on steel and aluminium parts. This film must be removed before installing/using the appliance.

NS Series Network Sensors

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM

130"ElectricCooktop. nstructlons _,0, JP355, JP910, JP930, JP940, JP950. I Iinstallation. -&WARNING - This appliance must be properly grounded.

FLCH4R Garage and Utility Electric Heater

Heat Exchanger Tube Change Procedure

HE360 Humidifier Installation Kit

Installation Manual. Breeder Control Installation Manual Patented U.S. Patent No. 7,980,129 and Patents Pending

Installation. S Series Navigator Thermostatic Mixing Valve

BGH Series Hot Surface Ignition Control

IMPORTANT INSTRUCTIONS

TEC1100 Series Thermostats

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

Smart Security at Every Corner of Your Home

Speaker Wall Mount (MSP-DCCSPM)

RLD-H10P Refrigerant Leak Detector

Installation Instructions 30 French Door Built-in Wall Ovens

CD-Px Series Duct Mount CO 2 Transmitters

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

Installation Guide

Sintrol Snifter A1+ Manual. Version 1.2.2

DISHWASHER INSTALLATION INSTRUCTIONS

Transcription:

Installation Instructions HE-67xx Issue Date 0501 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation IMPORTANT: The HE-67xx Series Humidity Element with Temperature Sensor is designed for use only as an operating control. Where failure or malfunction of the HE-67xx could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of the HE-6700 must be incorporated into and maintained as part of the control system. The humidity elements are available in both a wall mount or duct probe package to suit a variety of sensing application needs. Refer to the Mounting section for a complete list of the parts included and tools required for installation. Location Requirements IMPORTANT: To avoid damage to the circuit board and components, do not mount the unit in a location where high concentrations of corrosive vapors are present. Locate the humidity element on an inside wall, free from drafts, out of direct sunlight, and where the element is not exposed to excessive vibration. Be careful not to drop the unit. Mount the wall mount element at a height of 4 to 6 ft (1.2 to 1.8 m) above the floor and with one of the two mounting direction arrows on the circuit board pointing up. (See Figure 1.) Improper orientation can result in heat-induced error. 0 to 5 VDC Output 0 to 10 VDC UP Mounting Direction Arrows Figure 1: Mounting Direction Arrows and Output Jumper Location Duct Probe Humidity Element Place the duct probe humidity element in a location that complies with the following: Position: Designed for duct mounting in any position, except with the probe tip pointed up. Duct Diameter: Recommended minimum diameter (round ducts) or width (square ducts) is 12 in. (305 mm). Air Stratification (when the unit is mounted on the discharge side of the fan): Recommended location is at least 8 ft (2.4 m) downstream from humidification equipment, where duct air and water vapor are sufficiently mixed. Avoid areas where the probe may be exposed to condensation. 2001 Johnson Controls, Inc. 1 Part No. 24-9527-7, Rev. A www.johnsoncontrols.com

Application Setup The element must be configured for the output signal required prior to installation. Proceed to the appropriate element section to change the factory setting. To set the output jumper, refer to Figure 1. Remove the cover, and position the output jumper to suit the application. Reinstall the cover. Surface To mount the unit to drywall, refer to Figure 3 and proceed as follows: Button-head Screw (2) Circuit Board Cover Duct Probe Humidity Element Refer to Figure 2 to set the output jumper for the application. Output Base No. 8 Screw (2) Horizontal Faceplate 0 to 10 VDC (Factory Set) 0 to 5 VDC Drywall Vertical Faceplate Anchor (2) Probe Base Figure 3: Mounting to Drywall Mounting Figure 2: Output Jumper Selection Parts included are: wall mount humidity element No. 8 x 1-1/4 in. pan-head tapping screw (2) plastic drywall anchor (2) horizontal and vertical faceplates Tools required are: 1/16 in. (1.5 mm) Allen wrench or T-4000-119 Allen-head adjustment tool 1. Loosen the button-head screw on both sides of the plastic cover. 2. Pull the cover off the base. 3. Use the base as a template, and mark the holes for the two anchors and the wiring. 4. Drill a 5/16 in. (8 mm) hole for the each anchor. 5. Drill a 1/2 in. (13 mm) hole in the surface where the unit will be mounted, and pull the wiring through the drilled hole. 6. Feed the wiring through the 1/2 in. (13 mm) hole and the circuit board. 7. Mount the base to the wall using the anchors and the No. 8 screws. 1/4 in. (7 mm) and 1/8 in. (3 mm) flat-blade screwdrivers drill with 5/16 in. (8 mm) and 1/2 in. (13 mm) drill bits 2 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions

Wallbox To mount the unit to a wallbox, refer to Figure 4 and proceed as follows: Note: The TE-1800-9600 Wall Plate Adaptor Kit is required for this mounting method and must be ordered separately. (See Figure 4 and Table 1.) Wallbox No. 6-32 x 7/8 in. Pan-head Machine Screw (2)* Wall Plate Adapter* Mounting Bracket* Base No. 6-32 x 5/8 in. Pan-head Machine Screw (2)* * Items in TE-1800-9600 Wall Plate Adaptor Kit Humidity Transmitter s Circuit Board Cover Horizontal Faceplate or Vertical Faceplate Figure 4: Mounting to a Wallbox 1. Attach the mounting bracket from the wall plate adaptor kit (TE-1800-9600) to the wallbox, using the two No. 6-32 x 7/8 in. pan-head screws included. 2. Feed the wiring through the mounting bracket, the wall plate adapter, the base, and the hole in the circuit board. 3. Use the No. 6-32 x 5/8 in. pan-head screws to secure the base of the humidity element to the wall plate adaptor and the mounting bracket. Duct Probe Humidity Element Parts included are: duct probe humidity element No 8 x 1 in. Phillips-head sheet metal screw (2) washer for use with conduit fitting Note: Conduit fitting and nut are not provided. Tools required are: hole saw with 1 in. (25 mm) diameter blade drill with 1/8 in. (3 mm) drill bit No. 2 Phillips screwdriver pliers gasket, sealer, or other material to seal the area between the unit and the duct TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions 3

To mount the duct probe humidity element, refer to Figure 5 and proceed as follows: Conduit Knockout (Top and Bottom of Cover) Snap-on Cover Housing No. 8 Screw (2) Duct Nut for Conduit Fitting (Not Provided) Conduit Hole Washer (Cupped Side Toward Housing) Conduit Fitting (Not Provided) Figure 5: Duct Probe Humidity Element Assembly and Mounting 1. Remove any excess insulation from the duct that prevents the probe from extending a minimum of 3 in. (76 mm) into the air stream. 2. Use the hole saw to make a 1 in. (25.4 mm) hole in the duct for inserting the probe. 3. Pull the plastic cover off the housing. 4. Insert the probe into the duct, and use the housing as a template to mark the location of the holes for the mounting screws. 5. Remove the unit, and drill a 1/8 in. (3 mm) hole for each mounting screw. IMPORTANT: Remove the unit before drilling to prevent any metal remnants from falling onto the circuit board. Seal any holes created during installation to help reduce drafts and for more accurate humidity readings. 6. Use a gasket, sealer, or other means to seal the area around the 1 in. (25.4 mm) hole between the unit and the duct. 7. Reinsert the probe, and secure the housing to the duct using the two No. 8 screws provided. Wiring! WARNING: Electrical Shock Hazard. Disconnect the power supply before wiring connections are made to prevent possible electrical shock or damage to the equipment. Observe the following when wiring either type of element: Do not run low voltage wiring in the same conduit as line voltage wiring or other conductors that supply highly inductive loads. Use 18 or 24 AWG wire. Make all wiring connections in accordance with the National Electrical Code and all local regulations. To wire a wall mount model: 1. Connect the wires to the appropriate positions on the terminal block. (See Figure 6.) Terminal Block TB1 (Humidity Transmitter Connection) PWR COM OUT Wiring Opening Terminal Block TB2 (Temperature Sensor Connection) UP UP Sensor Sensor Terminal Wiring Figure 6: Wiring the 2. Place the cover over the base, and tighten the button-head screw (shown in Figure 3) on either side of the unit to secure. 3. Choose the appropriate faceplate (vertical or horizontal), depending on the mounting position of the unit. 4. Remove the adhesive-backed paper from the faceplate, and apply to the cover. 4 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions

Duct Probe Humidity Element To wire a duct probe model: 1. Route the wires from the controller to the unit through the conduit hole in the housing. IMPORTANT: If using a conduit fitting (not provided), a washer is provided to support the fitting in the housing. If the washer is not used, the fitting could stress the plastic housing. 2. Break out the appropriate knockout from the cover (shown in Figure 5) with pliers to accommodate the wiring or conduit if used. 3. Connect the wires to the appropriate terminals of the wiring block. (See Figure 7.) 0-5V 0-10V Probe PWR COM OUT TEMP TEMP Label Output Selection Terminal Designation DATE Input 18-30 VAC, 12-30 VDC Ouput 0-5 or 0-10 VDC PART NUMBER Figure 7: Wiring the Duct Probe Humidity Element 4. Press the cover onto the base. Ordering Information Refer to Table 1 for accessories for the wall mount humidity elements (none for the duct probe models), and contact the nearest Johnson Controls representative. Troubleshooting If the humidity element is not functioning properly: 1. Verify the unit is mounted in a location that is indicative of space humidity and temperature (away from drafts, moisture, sunlight, etc.). 2. Use a humidity tester with accuracy greater than the element (±2% between 20 and 80% for 2% models; ±3% between 20 and 80% for 3% models), such as an optical dew point hygrometer, to determine the percent of Relative Humidity (RH). Note: The humidity tester and the element must sense the air at the same temperature. Before testing, be sure to wait 30 to 60 minutes for the tester to stabilize to ambient temperature and humidity. A temperature difference of as little as 1F (0.6C ) can cause a difference in measured RH of over 2.5% RH. 3. Calculate the percent of RH indicated by the element as follows: For 0 to 10 VDC output, multiply the output voltage by 10. For example: 7.5 VDC x 10 = 75% RH For 0 to 5 VDC output, multiply the output voltage by 20. For example: 3.5 VDC x 20 = 70% RH Note: ±0.9F (±0.5C ) corresponds to an error of about ±2% RH at 25 C if RH is at a high level, e.g., 70%. 4. Compare the RH readings between the humidity tester and the element. If the difference is more than the sum of the allowable errors, replace the element. See Table 2 for product specifications for the humidity elements. Table 1: Accessories for the s Product Code Number Description GRD10A-608 Plastic Guard with Baseplate and Mounting Ring T-4000-119 Allen-head Adjustment Tool (30/bag) TE-1800-9600 Wall Plate Adaptor Kit required for wallbox mounting TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions 5

Technical Data Product TRUERH Series HE-67xx Humidity Element with Temperature Sensor Power Requirements 14 to 30 VDC or 20 to 30 VAC at 50/60 Hz, Class 2 Current Draw Acceptable Wire Gauge 3 ma with no load, 25 ma maximum 16 to 24 AWG wire (18 AWG wire recommended) Humidity Element Signal: 0 to 5 VDC or 0 to 10 VDC, 1,000 ohm maximum load at 77 F (25 C) Accuracy: HE-67x2: ±2% RH for 20 to 80% RH at 77 F (25 C) ±4% RH for 10 to 20% and 80 to 90% RH at 77 F (25 C) HE-67x3: ±3% RH for 20 to 80% RH at 77 F (25 C) ±5% RH for 10 to 20% and 80 to 90% RH at 77 F (25 C) Temperature Coefficient: -0.1 to 0.05% RH/ C at 5 C (41 F) to -0.07 to -0.21% RH/ C at 65 C (149 F) Temperature Sensors Thin-film Nickel: Accuracy: ±0.34 F (0.18 C) at 70 F (21 C) Reference Resistance: 1000 ohms at 70 F (21 C) Resistance Change: Approximately 3 ohms/ F (5 ohms/ C) Silicon: Accuracy: ±1 F (0.6 C) at 70 F (21 C) Reference Resistance: 1035 ohms at 77 F (25 C) Resistance Change: Approximately 4 ohms/ F (8 ohms/ C) Thin-film Platinum: Accuracy: ±0.65 F at 70 F (±0.36 C at 21 C) Reference Resistance: 1000 ohms at 32 F (0 C) Resistance Change: Approximately 2 ohms/ F (4 ohms/ C) Electrical Connections 3-position and 2-position screw terminal blocks Ambient Operating Conditions Survival Operating Conditions Ambient Storage Conditions 32 to 140 F (0 to 60 C) 0 to 100% RH, 85 F (29.4 C) maximum dew point -20 to 140 F (-29 to 60 C) 0 to 100% RH, 85 F (29.4 C) maximum dew point -40 to 140 F (-40 to 60 C) 0 to 100% RH, 85 F (29.4 C) maximum dew point Materials Wall Mount: Beige plastic cover with metal base and metal foil face plates Duct Probe: White plastic cover with dark gray plastic housing and probe Dimensions Wall Mount (H x W x D): 1.81 x 2.12 x 3.12 in. (46 x 54 x 79 mm) Duct Probe(H x W x D): 3.28 x 3.25 x 8.27 in. (83 x 83 x 210 mm) Probe (L x D): 6.25 x 0.98 in. (159 x 25 mm) Shipping Weight 0.6 lb (0.3 kg) Agency Compliance Duct Probe Material: 94-5V flammability rated per UL 94 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Printed in U.S.A. www.johnsoncontrols.com 6 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions