The Design, Testing, and Implementation of a Halon 1301 Fire Extinguishment System for Use in the Service Lunar Adapter at KSC Launch Complex 39

Similar documents
FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

SEMICONDUCTOR FABRICATION FACILITIES

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

Explosion Venting and Suppression of Bucket Elevator Legs, G90-990

SEMICONDUCTOR FABRICATION FACILITIES

SPECIAL HAZARDS THE MOST ADVANCED TECHNOLOGY FOR PROTECTING

GASEOUS HYDROGEN SYSTEMS

Large Family Daycare Guideline

HOT WORK SAFETY PROGRAM:

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Fixed Fire Extinguishing Equipment and Systems

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

Paper Session II-C - Laser Ordnance Ignition Capability at KSC

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Managing Extreme Risk by preventing flammable gas explosions. Michael van Niekerk

Amerex Fire Suppression Systems. Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond.

(h) Pesticide Application.

Welcome to Argonite fire protection from Ginge-Kerr

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

5.07 Air Replenishment Systems

FIRE SUPPRESSION SYSTEM

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

Carbon Dioxide Fire Suppression Systems

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

Module 5: Combustion Technology. Lecture 38: Combustion Burners

Bombardier Challenger Fire Protection

Chapter 12 HOT WORK OPERATIONS. Purpose:

Industrial Explosion Suppression Technology

Flammable Liquid Storage

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

WATER MIST CONVENTION AND EXHIBITION

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

AUTOMATIC FIRE & EXPLOSION SUPPRESSION SYSTEM.

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV (702) FAX (702)

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN

Residential-based Care Facility R-4 Guideline

SPACE SHUTTLE EXTERNAL TANK GASEOUS OXYGEN VENT SYSTEM William G. Franklin NASA/John F. Kennedy Space Center, Florida

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Water Mist Fire Suppression

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828)

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. TM TM

WATERFRONT FACILITY COMPLIANCE BOOKLET

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE

MATERIAL SAFETY DATA SHEET

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

JAMES MOODY IM FLASH LIFE SAFETY AHJ

Inert Gas Fire Extinguishing System

Emergency shutdown systems. Procedures for bypassing ESD s

BOC FS125 The Fire Extinguishing Solution

Fire suppression systems for server rooms and data centres

With CV Technology products and care, you ll be better protected from dust explosions.

An Overview of Extinguishing Systems for Computer Equipment

Effective, efficient response for emergency situations Risk Management

SOUTH AFRICAN NATIONAL STANDARD

Fig. 1 - Unit PGD4, PGS4, WPG4

This policy is applicable to all DMS-owned, -leased and -managed facilities.

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

A comprehensive systems-level approach in cabin design minimizes fire potential and helps ensure passenger safety. aero quarterly qtr_04 11

Superior by Design The Kidde ADS TM FM-200 System

Xavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps

TRAINING BULLETIN September 1, 2010 PURPLE K DRY CHEMICAL EXTINGUISHER 1. INTRODUCTION

READING: ECLSS (Environmental Control and Life Support System)

***DRAFT - NOT FOR FILING***

NJSP HMRU. Module 5 B HM Operations 1

SECTION FM-200 FIRE SUPPRESSION SYSTEM

AUTOMATIC FIRE SUPPRESSION SYSTEMS

Crosswalk: Weight-Based Rating versus Performance-Based Rating

FIRE PROTECTION PROGRAM

EMERGENCY PREPAREDNESS: EVACUATIONS

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts

Fire Extinguishing System

Chapter 18 Welding Table of Contents

BETACURE 100 CO-REACTANT

Creating a safer world!

Owner s Information Manual

APPENDIX A FEES SECTION FC A01 CERTIFICATES A01.1

Certificate of Compliance Section 1 - PRODUCT AND COMPANY IDENTIFICATION

FIXED PROTECTION FOR OIL AND CHEMICAL PLANTS

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

Laboratories and Hazardous Materials. Company Overview

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

Fire Prevention Plan

Transcription:

The Space Congress Proceedings 1969 (6th) Vol. 2 - Space, Technology, and Society Apr 1st, 8:00 AM The Design, Testing, and Implementation of a Halon 1301 Fire Extinguishment System for Use in the Service Lunar Adapter at KSC Launch Complex 39 J. T. Myers Catalytic-Dow D. C. Weaver Catalytic-Dow Follow this and additional works at: https://commons.erau.edu/space-congress-proceedings Scholarly Commons Citation Myers, J. T. and Weaver, D. C., "The Design, Testing, and Implementation of a Halon 1301 Fire Extinguishment System for Use in the Service Lunar Adapter at KSC Launch Complex 39" (1969). The Space Congress Proceedings. 3. https://commons.erau.edu/space-congress-proceedings/proceedings-1969-6th-v2/session-8/3 This Event is brought to you for free and open access by the Conferences at Scholarly Commons. It has been accepted for inclusion in The Space Congress Proceedings by an authorized administrator of Scholarly Commons. For more information, please contact commons@erau.edu.

THE DESIGN, TESTING AND IMPLEMENTATIN F A HALN 1301 FIRE.EXTINGUISHMENT SYSTEM FR USE IN THE APLL/SATURN LUNAR MDULE ADAPTER AT KENNEDY SPACE CENTER LAUNCH CMPLEX 39 David C. Weaver Catalytic-Dow Titusville, Florida INTRDUCTIN Since the advent of hypergolic fuels usage at the Kennedy Space Center and the Kennedy Air Force Station, personnel safety during fueling opera tions has been provided by limiting the number of persons having access to hazardous areas to those who were essential to the operation, and by providing these people with protective clothing. With the Apollo Program, a new problem has introduced itself; the Lunar Module (LM) (Fig. 1) is actually two launch vehicles which leave the launch pad as part of the Apollo payload. Fueling of these launch vehicles takes place approximately two weeks before the launch of the Apollo/Saturn V. Personnel are required to continue servicing the LM after fueling; this requires them to be enclosed within the Saturn/ Lunar Module Adapter (SLA). Special egress equipment has been installed but will not be discussed in this presentation. To minimize the hazard of a flash fire resulting from the ignition of a spilled hypergol, a Halon 1301 (bromotriflouromethane) protection system has been designed and has been available during the launches of AS-204 and AS-504. Since im provements over the original system which was installed at Launch Complex 37 were incorporated into the design of the system for Launch Complex 39, our discussion will deal only with the Launch Complex 39 system. DESIGN The responsibility for the design of the Halon 1301 Fire Extinguishment Systems was given to the Kennedy Space Center, Design Engineering, Facilities Branch (DE-FAC). Catalytic-Dow, the facilities support contractor for NASA Kennedy Space Center perations supported DE-FAC in this assignment. Utilizing studies performed by the Explosive Research Center, in the United States Bureau of Mines, it was determined that any atmosphere will be relatively inert to an energy ignition of a spilled hypergol, if the atmosphere contains 10% by volume of Halon 1301. To extinguish a burning hypergol which had been ignited by an energy source, 20% by volume of Halon 1301 was found to be required.1 (Research by others in this field has revealed that the extinguishment of less exotic materials can be achieved by concentration no greater than 6%). Research performed by toxicologists has indicated that short-time human exposure to concentration in this range will not cause a high degree of risk to humans. A system was to be designed, therefore, that would permit occupants of the SLA to egress in relative safety in the advent of a spill, and would sustain a 20% by volume Halon 1301 atmos phere until the problem causing the spill could be corrected. Due to the precise nature of work performed within the SLA, highly conditioned air is introduced in large quantities (3,200 standard cubic feet per minute into a volume of 6,000 cubic feet). Because the Halon 1301 system was to be installed on the work platforms of the Mobile Service Structure, care was taken to utilize the lightest available material compatible with its usage. The extinguishing agent is injected as a liquid and vaporizes on leaving the delivery nozzles; therefore, further consideration was given to minimize the possibility that the low temperature discharge would directly impinge upon occupants of the SLA or damage the SLA or LM. This con sideration was required because a change of temperature of as much as 140 Fahrenheit could be experienced in the immediate vicinity of the discharge nozzles. SYSTEM DESCRIPTIN The system is made up of three basic subsystems, two of which are Halon 1301 Storage and Delivery Subsystems; the third is the Control Subsystem. Since Halon 1301 breaks down into toxic by-pro ducts when exposed to temperatures in excess of 800 centigrade, it was determined that the initial application of the agent must be rapid. Extinguishment will occur within milliseconds of achieving the required concentrations. This requirement is achieved by the first subsystem which consists of six 85-pound containers and their associated valves and piping which have been placed in groups of two, at three different locations (Figures 2 and 3). Each group enters the SLA from a different access point. The access points were selected to provide as close a uniform dispersement as possible in accordance with operational demands. The second subsystem consists of three 1-ton cylinders of the extinguishing agent, manifolded in such a way that the discharge from these cylinders enters the SLA through a common piping system which utilizes the same entrance ports as the first system. The Halon 1301 stored in the containers is pressurized with nitrogen to 600 psi, which remains constant throughout discharge (Figures 2 and 3). The piping system is so designed, a sustained rate of flow of either 2.3 or 4.6 pounds per minute can be introduced into the SLA. 8-5

The Control Subsystem is so designed that by actuating one switch, the operator can release half (255 pounds) of the rapid discharge system into the SLA and activate a flow rate of 2.3 pounds per minute from the sustaining system. The actuation of another switch can simultan eously release the total contents of the rapid discharge system, and activate the flow rate of 4.6 pounds per minute from the sustaining system. PERATINAL CNCEPTS The Halon 1301 system has been designed to have two modes of operation. The first mode (Inert Mode) is to be used if a hypergol spill is de-. tected within the SLA. After the system has been armed, by throwing a single toggle switch, the 10% switch is thrown, causing the immediate release of a 10% concentration of the halon, and a sustaining flow of approximately 2.3 pounds per second. The second mode of.operation (Extinguish Mode) will be used if a fire is detected within the SLA. After arming as de scribed previously, the Extinguish switch is thrown, releasing a 20% concentration which will extinguish the fire and initiate a flow of 4.3 pounds per second which will prevent re- ignition. Concentration versus time curves are provided in Figures 4 and 5. BIBLIGRAPHY 1. Van Dolan, R. W.: Prevention and Extinguish ment of Fires Involving Hyperbolic Propel- lants. Explosive Research Center, Bureau of Mines, Pittsburgh, Pennsylvania. July 31, 1968. 2. Hine, C. H.: Clinical Toxicologic Studies on "Freon" FE 1301. The Hine Laboratories, Inc., San Francisco, California. January 1968. TESTING In the fall of 1968, tests were conducted utilizing full scale mockups for a major portion of the test program. Test results indicated that concentration of Halon 1301 which would inert or extinguish would be obtained within 2 seconds of activation, and that the sustaining system would prevent combustion for a period of not less than 20 minutes. The rapid introduction of this quantity of Halon 1301 into the SLA did not cause critical overpressures because of the associated cooling. Sound pressure levels reached 120 decibels for periods not exceeding 20 milliseconds. While this approaches the threshold of pain, the short duration minimizes the probability of permanent ear damage. While the Halon 1301 gas is colorless and odor less, its rapid discharge causes cooling which condenses the moisture within the air and does cause limited visibility within the SLA. Visual acquisition was recorded with a high speed camera. In general, it has been determined that the present configuration of the system installed at the Kennedy Space Center Launch Complex 39 will provide a significant level of safety not heretofore possible for those personnel re quired to work in what could be an extremely hazardous environment. 8-6

SATURN V SPACE VEHICLE CMMAND MDULE SERVICE MDULE SLA LUNAR MDULE FIG. 1 SLA FREN FRM GN 2 SUPPLY i -^ -^ QtFKE K)7o 2,000 LR. SUSTAINING FKEN B-TTLES ^ 1 2 or. SM SLED

oo 00 2 I IJ n c % CNCENTRATIN F FREN ± C z o o C co 2- ^ > 70 ^j m 2 z CJ 09 o*> yo m > 73 m zc C o

25 LC-39 SLA FREN EXTINGUISHING SYSTEM (20%) o o 0 H» UJ o u 20 40 60 10 15 20 TIME/SECNDS TIME/MINUTES FIG. 5 <b 00