DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Similar documents
Low Global Warming Refrigerants For Commercial Refrigeration Systems

January 16 th, 2014 New York City

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

AHRI Standard 751 (SI) 2016 Standard for Performance Rating of Thermostatic Refrigerant Expansion Valves

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

HFO-1234yf Performance in a Beverage Cooler

Study of R161 Refrigerant for Residential Airconditioning

Development of Environmentally Benign Heat Pump Water Heaters for the US Market

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Otherwise, you can continue reading the file on the following pages.

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

R-404A Alternative with Low Compressor Discharge Temperature

LOW COST HEAT PUMP WATER HEATER (HPWH)

Low GWP Refrigerants for Air Conditioning Applications

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Transcritical CO2 Bottle Cooler Development

Waste Heat Recovery Analysis of CO 2 Refrigeration Systems

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Evaluation of HCFC Alternative Refrigerants

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

A Comparison Between Refrigerants Used In Air Conditioning

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

New High Performance, Low GWP Refrigerants for Stationary AC and Refrigeration

R-407A R-448A R-449A

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Experimental Evaluation of a Residential Refrigerator with a Novel Rotating Heat Exchanger as an Evaporator

INFLUENCE OF REFRIGERANT CHARGE AND AIR INLET TEMPERATURES ON THE PERFORMANCE OF AN AUTOMOTIVE AIR CONDITIONING SYSTEM

Affordable ENERGY STAR Residential CO 2 HPWH for the US Market

Experimental Performance of R-1234yf as a Dropin Replacement for R-134a in Domestic Refrigerators

Low GWP Refrigerants for Air Conditioning and Chiller Applications

CHAPTER 1 INTRODUCTION

Oxyvap Evaporative Cooling Applications

R32 Compressor for Air conditioning and Refrigeration applications in China

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR AC AND REFRIGERATION

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

A RECENT REVIEW OF REFRIGERANT R-1234YF AND R-1234ZE (E)

Ammonia. Background on ammonia as a refrigerant

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

A Treatise on Liquid Subcooling

Evaluation of Mechanical Dehumidification Concepts (Part 2)

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Heat Pump Water Heater Technology Development. EEBA High Performance Home Summit Ed Vineyard Oak Ridge National Laboratory

THE USE OF HYDROCARBONS PROPANE AND ISOBUTANE IN REFRIGERATION SYSTEMS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature

*Corresponding author;

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

REFRIGERANT CHANGEOVER

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

New Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Chapter 10. Refrigeration and Heat Pump Systems

Effect of magnetic field on the performance of new refrigerant mixtures

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Refrigeration Training System

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Seminar 34 Refrigerants Today, Tomorrow, and Beyond

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Development Of A Low-Cost Heat Pump Water Heater For Residential Applications

Heat Pump Clothes Dryer Model Development

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

Comparative Performance of HFO Blends in a Condenser

Investigation of Evaporator Performance with and without Liquid Overfeeding

System Considerations for Refrigerant Blends with Temperature Glide

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Transcription:

Numbers of Abstract/Session (given by NOC) - 1 - DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER Richard W. Murphy Van D. Baxter Edward A. Vineyard Randall L. Linkous Research and Development Staff, Oak Ridge National Laboratory, Oak Ridge, Tennessee, USA * Abstract: This paper describes a laboratory evaluation of the relative performance of a residential integral electric heat pump water heater operating with two working fluids: (1) Refrigerant 134a (R-134a), the standard design working fluid, and (2) Refrigerant 1234yf (R- 1234yf), a potential replacement option with similar thermodynamic and transport properties, but with a substantially lower estimated global warming potential. The US 24-Hour Simulated Use and First-Hour Rating Tests were performed on the unit employing the nameplate charge of R-134a. After replacement of the R-134a by R-1234yf (with no changes to the hardware or software), heat-up tests were conducted to determine the appropriate R-1234yf charge. Finally, the 24-hour Simulated Use and First-Hour Rating Tests were repeated with R-1234yf. The first-hour rating calculated from the data for the R- 1234yf case was found to be the same as that for the R-134a case, but the energy factor for the R-1234yf case was about 6% lower than that for the R-134a on this drop-in basis. It is suggested that modification of the thermostatic expansion valve would allow a closer approach to the R-134a system energy factor. Key Words: heat pump water heater, low GWP refrigerants, drop-in tests, energy factor, first-hour rating 1 INTRODUCTION The hydrofluoroolefin (HFO) compound R-1234yf has been suggested (Calm 2008) as a near drop-in replacement for the hydrofluorocarbon (HFC) compound R-134a because the two compounds have very similar thermodynamic and transport properties, based on the REFPROP database (Lemmon et al. 2007)-- especially for mobile air conditioning situations. Although R-1234yf is mildly flammable, it has an estimated global warming potential (GWP) of 4 (over a 100-year time horizon on a scale normalized to GWP=1 for carbon dioxide), substantially lower than the corresponding GWP of 1410 attributed to R-134a. Therefore, it has been suggested that substitution of R-1234yf for R-134a in existing equipment designs might be a viable method of reducing global warming concerns. If refrigerant is * Notice: This manuscript has been authored by UT-Battelle, LLC, under Contract No. DE-AC05-00OR22725 with the U.S. Department of Energy. The United States Government retains and the publisher, by accepting the article for publication, acknowledges that the United States Government retains a non-exclusive, paid-up, irrevocable, world-wide license to publish or reproduce the published form of this manuscript, or allow others to do so, for United States Government purposes.

Numbers of Abstract/Session (given by NOC) - 2 - (unintentionally) released from such equipment to the atmosphere, the resultant direct global warming impact would be reduced by the substitution of R-1234yf for R-134a. However, if such substitution resulted in any decrease in equipment energy efficiency or capacity performance under normal operating conditions, the attractiveness of R-1234yf as a potential working fluid replacement could be reduced. Lower energy efficiency for electrically powered equipment, including heat pump water heaters or other heating, ventilating, air-conditioning, or refrigeration (HVAC/R) systems, would lead to a larger indirect global warming contribution. Such an effect could be much larger over the expected life of the equipment than that from an unintentional release of the entire system refrigerant charge for most stationary HVAC/R systems. In addition, a reduction in capacity could reduce the acceptability of the energy-efficient equipment in the marketplace. Several residential electric heat pump water heaters rated as Energy Star (http://www.energystar.gov) under U.S. Department of Energy regulations [first-hour rating (FHR) 50 gal (189 l) and energy factor (EF) 2.0, among other requirements] employ R- 134a as their working fluid. The purpose of this study was to determine the efficiency and capacity performance of an unmodified production model of one of these units operating with R-1234yf relative to that with the baseline R-134a. If performance is not significantly reduced, if safety and reliability impacts are negligible, and if the combined cost of the replacement refrigerant and any associated hardware or software modifications is not significantly greater than that of the current technology, then consideration of the alternative refrigerant based on global warming concerns may be justified. If, on the other hand, performance penalties are substantial, safety or reliability considerations are problematic, significant hardware or software alterations are required, or refrigerant costs are considerably higher, such an alternative may not be attractive. 2 BASELINE R-134A TESTING The tested model employed a vapor compression system with a top-mounted compressor and evaporator/fan assembly, a thermostatic expansion valve, and a tank-wrapped condenser coil as the primary water-heating mechanism. It also incorporated a tankmounted electrical resistance water-heating capability as a backup mechanism when called for by conditions. After verifying the nameplate charge of R-134a in the unit, First-Hour Rating Tests and 24-Hour Simulated Use Tests (United States Government 2010) were conducted to determine its baseline FHR and EF. The results very closely matched the corresponding Energy Star-listed values for this model. 3 REPLACEMENT R-1234YF CHARGE-DETERMINATION TESTING 3.1 Preparations After leak-checking procedures and removal of the standard charge of R-134a (leaving the associated oil in the unit because of its reported compatibility with R-1234yf), the refrigerant system was evacuated to high vacuum with a vacuum pump. No hardware or software modifications were made to the unit to accommodate the alternate refrigerant. However, because the properties of R-1234yf were (similar, but) not identical to those of R-134a, a matrix of preliminary heat-up tests at selected charge levels was conducted over a range of ambient air temperatures (10.0 to 43.3 C) to establish the correct R-1234yf charge within the limits of the standard hardware and software. These tests employed the same supply water temperature and water flow rate specified for the 24-Hour Simulated Use Test (United States Government 2010), but were of shorter duration to accelerate screening efforts over the various charge levels and ambient air temperatures. Specifically, the heat-up test procedure

Numbers of Abstract/Session (given by NOC) - 3 - consisted of setting the water thermostat at its maximum set point, allowing the unit to heat the tank water to this set point temperature (thereby terminating the heating activity), conducting a water draw sufficient to activate the unit s upper electric resistance (backup) heating element, terminating the draw, and (following resistance element deactivation) allowing the unit s heat pump system to return the tank water to the set point temperature. For the tests, time-scanned instrumentation was installed on the unit to provide not only temperature, humidity, power, flow, and pressure data consistent with the methods prescribed for the 24-Simulated Use Test (United States Government 2010), but also relevant refrigerant temperature and pressure data from the vapor compression system. From this data several parameters were deduced and employed as figures-of-merit to assess charge adequacy. The desired refrigerant evaporator exit superheat was that which would maximize effective heat transfer in the evaporator (maximizing evaporator saturation pressure and temperature) while minimizing the likelihood of refrigerant liquid entering the compressor under any condition over the entire system design operating range. The desired refrigerant condenser exit subcooling was that which would maximize effective heat transfer in the condenser (minimizing condenser saturation pressure and temperature) while minimizing the likelihood of refrigerant vapor entering the thermostatic expansion valve under any condition over the entire system design operating range. The desired recovery energy consumption and recovery time were the minimum values required to raise the average tank water temperature from a fixed lower intermediate value to a fixed higher intermediate value. Such recovery characteristics were intended to reflect energy efficiency and capacity attributes that would ultimately be realized in the EF and FHR determinations from the more protracted rating tests. The liquid volume of the standard R-134a mass charge was calculated, using the REFPROP database (Lemmon et al. 2007), at condenser operating conditions corresponding to the maximum water temperature setting. This value served as the beginning volume estimate for the appropriate R-1234yf charge. The corresponding mass charge estimate was determined from the liquid density of (the less-dense) R-1234yf at the same condensing temperature, again based on the REFPROP database (Lemmon et al. 2007). To avoid starting with an overcharged condition and excess recovery procedures, the initial charge of R-1234yf was chosen to be about 87% of the estimated appropriate mass charge 3.2 Tests After the initial charge was weighed into the unit, heat-up tests were conducted at four different ambient air temperatures. As shown in Figure 1, the minimum evaporator exit superheat (in non-dimensionalized form relative to the R-134a baseline value at 10 C ambient air temperature) was encountered at the lowest ambient air temperature, but frost formation on the evaporator prevented proper operation at this condition. The minimum condenser exit subcooling (in non-dimensionalized form relative to the R-134a baseline value at 10 C ambient air temperature) at 10 C is shown in Figure 2 to be about 0.89. Both the frost formation and the relatively low subcooling level were interpreted to be indications of a refrigerant undercharge situation. Because of the frozen evaporator at the lowest ambient temperature with the starting charge, emphasis was placed on monitoring evaporator performance as refrigerant charge was gradually increased.

Numbers of Abstract/Session (given by NOC) - 4 - non-dimensional minimum evaporator exit superheat 5 4 3 2 1 ambient air temperature 43.3 C 32.2 C 19.7 C 10.0 C 10.0 C with frost 0 0.8 0.9 1.0 1.1 1.2 1.3 non-dimensional refrigerant mass charge Figure 1: Evaporator superheat versus charge for various ambient air temperatures 1.5 non-dimensional minimum condenser exit subcooling 1.4 1.3 1.2 1.1 1.0 0.9 0.8 0.8 0.9 1.0 1.1 1.2 1.3 non-dimensional refrigerant mass charge Figure 2: Condenser subcooling versus charge for 10 C ambient air temperature

Numbers of Abstract/Session (given by NOC) - 5 - The charge (represented on the abscissas of Figures 1 and 2 in non-dimensionalized form relative to the estimated appropriate mass charge of R-1234yf) was then increased to about 0.92, and the heat-up tests were repeated. Although superheat decreased and subcooling increased after the refrigerant addition as expected, frost was again observed on the evaporator surface at the lowest ambient air temperature condition. The next refrigerant increment brought the total relative charge to about 0.98, within 2% of the original estimate for the appropriate charge. The associated heat-up tests showed no frost formation on the evaporator, identifying this as the minimum acceptable charge. As with the initial charge, the minimum evaporator exit superheat was achieved at the lowest ambient air temperature (10 C). However, under these conditions, although the subcooling value reached 100% of the corresponding value for the unit operating with the standard R- 134a charge, the observed minimum evaporator exit superheat was about 60% above the corresponding R-134a system value. In addition, the normalized (relative to the R-134a baseline value at 10 C ambient air temperature) recovery energy consumption and recovery time, given in Figure 3, were approximately 14% and 15%, respectively, greater than the corresponding R-134a system values. non-dimensional recovery energy consumption or time 1.2 1.1 1.0 0.9 0.8 0.9 1.0 1.1 1.2 1.3 non-dimensional refrigerant mass charge energy time Figure 3: Recovery energy consumption/time versus charge for 10 C ambient air temperature In order to possibly (a) reduce the evaporator superheat (and, consequently, improve its heat transfer effectiveness), (b) reduce the recovery energy consumption, and (c) reduce the recovery time, more refrigerant was added. Stepwise addition of R-1234yf (up to a total charge about 22% in excess of the original estimate for the appropriate charge) produced no significant change in the minimum evaporator exit superheat (see Figure 1), but did produce a significant increase (for non-dimensional charges above 1.04) in the minimum condenser exit subcooling (see Figure 2) to about 39% above the corresponding R-134a system value. As shown in Figure 3, the heat pump recovery energy consumption and time decreased somewhat as the non-dimensional charge increased from 0.98 to 1.10, but their

Numbers of Abstract/Session (given by NOC) - 6 - rate of decrease was much lower in the charge range from 1.10 to 1.22--ending with about 107% and 106% of the R-134a system values, respectively, at the highest charge. The close proximity of the two lines in Figure 3 reflects the fact that the average power draw for the unit during the recovery period was almost identical for the R-1234yf-charged system as it was for the R-134-charged system. 3.3 Analysis From these results, it was judged that further refrigerant charge increases were not likely to produce significant reductions in minimum evaporator exit superheat, recovery energy consumption, or recovery time. Because the unit employed a non-adjustable superheat type thermostatic valve as its expansion device, it was expected that this component was limiting the minimum evaporator exit superheat. Because this valve was intended for operation with the original working fluid, its bulb was charged with R-134a. We calculated the pressure differential across the valve diaphragm when the net force from this pressure differential just counteracted that from the spring/diaphragm assembly for the superheat and evaporating temperature determined in the baseline R-134a unit tests (where both the system and the thermostatic expansion valve bulb were charged with R-134a). This value represented the differential pressure required to provide a given controlled flow area within the valve orifice. Then we employed this pressure differential to estimate the superheat that would provide the same differential (and, therefore, the same controlled flow area) in the same valve (bulb charged with R-134a) operating with an R-1234yf-charged refrigeration system at the same evaporating temperature. The calculations showed that the superheat estimated on this basis was about 32% greater than the value determined for the R-134a/R-134a baseline. Although this calculation addresses the variations in saturation pressures between the two working fluids, other properties also impact thermostatic expansion valve performance. In particular, the liquid density of R-1234yf is approximately 11% smaller than that of R-134a at the representative operating condensing temperature indicating that, with all other things equal, less mass flow would be allowed through the valve (at the same controlled flow area) for the R-1234yf case than for the R-134a case, likely providing less complete wetting of the evaporator and greater superheat. Although complete and simultaneous accounting for all such effects was beyond the scope of this study, it is suggested that the remainder of the approximately 60% excess superheat with the R-1234yf-charged system over that of the R- 134a-charged system observed in the present tests is likely associated with other property differences. Similar calculations for the situation with R-1234yf both in the valve bulb and in the refrigeration system gave a corresponding superheat (with the same representative evaporating temperature) within 0.1% of the R-134a/R-134a base value. This result suggests that the same thermostatic expansion valve hardware might be successfully used with a R-1234yf-charged refrigeration system if the bulb working fluid were replaced with R- 1234yf although, to account for the somewhat different liquid density or other properties of R-1234yf relative to those of R-134a, the orifice size might also need to be changed. 4 PERFORMANCE TESTING 4.1 Results To complete performance characterization of the unit with the standard hardware and software components, both a First-Hour Rating Test and a 24-Hour Simulated Use Test were conducted with the 122% R-1234yf charge. The resultant FHR was found to match the value previously determined for the same unit operating with the standard charge of R-134a. This result was expected since the primary determinants of FHR for this unit were the

Numbers of Abstract/Session (given by NOC) - 7 - characteristics associated with the water tank (volume, mixing characteristics, etc.) and the upper resistance heating element (location, power, activation period, etc.) none of which were altered by the refrigerant replacement. The resultant EF was determined to be approximately 6% lower than the value determined previously for the same unit operating with the standard charge of R-134a. Some operational parameters that differed during the 24-hour Simulated Use Test employing R-1234yf from those observed during the same test using R-134a were: evaporator exit superheat (higher), condenser exit subcooling (higher), evaporator temperatures (lower), compressor energy consumption (higher), and refrigeration system heating capacity (lower). 4.2 Interpretation It is postulated that the mismatch between the R-134a-charged thermostatic expansion valve and the R-1234yf-charged refrigeration system caused underutilization of the evaporator (increased dry regions, increased exit superheats, depressed evaporator temperatures). It may also have led to a slightly overcharged condition in the condenser (added liquid leg backup and increased condenser exit subcooling) in the attempt to reduce the evaporator exit superheat. The combination of various effects likely led to increased compressor energy consumption and reduced refrigeration system heating capacity. 5 CONCLUSIONS Simply replacing the standard working fluid R-134a with alternative working fluid R-1234yf in this unit reduced the associated EF by about 6%, but did not significantly affect the associated FHR. If, in addition, the thermostatic expansion valve bulb Refrigerant 134a working fluid were replaced by R-1234yf working fluid, the correct refrigeration system charge could probably be established so as to produce approximately the same evaporator exit superheat. However, it is possible that the size of orifice in the thermostatic expansion valve would also have to be changed to accommodate adequate flows of the lower liquid density R-1234yf working fluid. It appears that such measures may then allow the energy factor performance of the unit employing R-1234yf to more closely approach that of the standard unit charged with R-134a. 6 REFERENCES Calm, J.M. 2008. The next generation of refrigerants Historical review, considerations, and outlook, International Journal of Refrigeration, Vol. 31, pp. 1123-1133. Lemmon E.W., M.L. Huber, and M.O. McLinden. 2007. NIST Standard Reference Database 23: Reference Fluid Thermodynamic and Transport Properties-REFPROP, Version 8.0, National Institute of Standards and Technology Standard Reference Data Program, Gaithersburg, Maryland. United States Government. 2010. Uniform Test Methods for Measuring the Energy Consumption of Water Heaters, Code of Federal Regulations, Title 10, Chapter II, Volume 3, Part 430, Subpart B, Appendix E. 7 ACKNOWLEDGMENT The R-1234yf working fluid employed in this study was graciously supplied by E.I. du Pont de Nemours and Company.