COMPARATIVE PERFORMANCE ANALYSIS OF EXPERIMENTAL FRIGORIFIC AIR CONDITIONING SYSTEM USING R-134A AND HFO-1234YF AS A REFRIGERANT

Similar documents
*Corresponding author;

Experimental Performance Analysis of an Automotive Air Conditioning and Heat Pump System using R134a with and without Internal Heat Exchanger

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

HFO-1234yf Performance in a Beverage Cooler

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

Low GWP Refrigerants for Air Conditioning Applications

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

R-404A Alternative with Low Compressor Discharge Temperature

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Study of R161 Refrigerant for Residential Airconditioning

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

η second law = Second law efficiency

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Chapter 10. Refrigeration and Heat Pump Systems

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Enhancement of COP in Vapour Compression Refrigeration System

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

CHAPTER 1 INTRODUCTION

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance Study on A Window Type Air Conditioner Condenser Using Alternative Refrigerant R407C

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

DEEPAK PALIWAL, S.P.S.RAJPUT

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

ADVANCES in NATURAL and APPLIED SCIENCES

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Waghmare Tushar Ramrao, D.S.Nakate

THERMAL ANALYSIS OF CAR AIR COOLER

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Performance investigation of Air-conditioning system using ejector as expansion device

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

A Comparison Between Refrigerants Used In Air Conditioning

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Low Global Warming Refrigerants For Commercial Refrigeration Systems

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Oyelami S., Bolaji B. O.

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Performance of CO2 Cycles with a Two-Stage Compressor

International Journal of Advance Engineering and Research Development

A study of Transient Performance of A Cascade Heat Pump System

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Refrigerant Mass and Oil Migration During Start-up Transient

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Impacts of room temperature on the performance of a portable propane air conditioner

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

EXPERIMENTAL PERFORMANCE ANALYSIS OF AN AMMONIA-WATER DIFFUSION ABSORPTION REFRIGERATION CYCLE

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Transcription:

THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 2065 COMPARATIVE PERFORMANCE ANALYSIS OF EXPERIMENTAL FRIGORIFIC AIR CONDITIONING SYSTEM USING R-134A AND HFO-1234YF AS A REFRIGERANT by Mehmet DIREK a*, Cuneyt TUNCKAL b, and Fikret YUKSEL a a Department of Energy Systems Engineering, Faculty of Engineering, Yalova University, Yalova, Turkey b Air Conditioning and Refrigeration Technology Program, Electric and Energy Department, Vocational School of Yalova, Yalova University, Yalova, Turkey Original scientific paper DOI: 10.2298/TSCI140715130D In this study, to evaluate the comparative experimental performances, a frigorific air conditioning system using HFO1234yf and R134a was developed and refrigerated air was introduced into a conditioned room. The experiment was carried out at different condenser inlet temperatures and using the refrigerants at different charges, 1250, 1500, and 1750 grams. Experiments were conducted for a standard frigorific air conditioning system using the HFO1234yf and R-134a system. Air flow was introduced to the conditioned room for 60 minutes for each performance test. The results revealed that the temperature gradient in time was comparable for both refrigerants. The results of this investigation propose utilising HFO1234yf as a replacement for the currently favoured R134a in a frigorific air conditioning system Key words: R134a, frigorific air conditioning system, HFO1234yf Introduction Starting from 2017, the European Union s F-gas regulations [1, 2] specify that new models introduced after January 1, 2011, and after 2017, all automobiles coupled with air conditioning systems, can not be manufactured using greenhouse gases that have global warming potentials (GWP) greater than 150. Since the similar performance index of HFO1234yf system has been evaluated as an alternative for the R134a system, HFO1234yf could be implemented in existing air conditioning systems using R134a. Consequently, it has a GWP of 4 and is widely being considered as a possible replacement for R134a in automotive applications [3]. Meyer [3] revealed that the cooling capacity and coefficients of performance (COP) of HFO1234yf could be made relatively equal to the baseline R134a values using only simple system modifications. Minor and Spatz [4] demonstrated that there remain several issues that are currently being investigated through on-going research and development work in order to replace R134a with HFO1234yf in automotive applications. The effects of using improved components in air conditioning systems were studied experimentally by Petitjean and Benouali [5]. They found that the condenser plays a far more significant role than the evaporator in the optimization of the HFO1234yf performance re- * Corresponding author; e-mail: mehmetdirek@hotmail.com

2066 THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 garding the conventional heat exchangers. They also showed that the HFO1234yf performance can match or even better that of R134a with correctly designed and tuned components. Lee and Jung [6] observed the conditions for mobile air conditioners, the performance of both HFO1234yf and R134a were investigated in a heat pump bench tester. The results revealed that, because of its good environmental properties and reasonable performance, HFO1234yf could potentially be seen as a long term environmentally friendly solution for use in mobile air conditioners. Navarro et al. [7] compared HFO1234yf, R134a, and R290 for an open piston compressor at different operating conditions. They detected a reduction of between 10-15% in the system s cooling capacity when using HFO1234yf to that which used R134a. Akram et al. [8] study compared the lubricity of the two refrigerants, the environmentally friendly HFO1234yf and the traditional R134a, for air conditioning compressor applications. The results demonstrated that, for gray cast iron material interfaces, HFO1234yf offered greater lubricity than R134a. Lee et al. [9] study proposed replacing R134a in applications such as mobile air conditioners, centrifugal chillers, and beverage coolers with an azeotropic mixture of R134a and HFO1234yf. This is because the COP capacity and discharge temperature of R134a is similar to that of HFO1234yf and the HFO1234yf/R134a mixture. They found that, in the HFO1234yf/R134a mixture when more R134a was added the danger of flammability decreases, while compositions with R134a above 10%, the mixture became non-flammable. Tanaka and Higashi [10] reported also that toxicity and thermodynamic properties critical temperature, critical density, and critical pressured of HFO1234yf are similar to those of R134a. SAE research program [11] concluded that HFO1234yf can be used to globally replace refrigerants used in future mobile air conditioning systems. A comparative analysis showed that ignition potential and being exposed to hydrogen floride was extremely low. A comparative analysis show that HFO1234yf is a non-ozone depleting substance with a GWP of 4 and analysis also show that risks were well below those commonly considered acceptable by the public and regulatory agencies. In this study, the performance of R134a and HFO1234yf are compared using a frigorific air conditioning system, respectively. The refrigerated air was sent into the conditioned room for both refrigerants. The experiment was carried out using the refrigerants at different charges, 1250 g, 1500 g, and 1750 g. The effects of using R134a and HFO1234yf, as a refrigerant in a frigorific air conditioning system, and their respective performances were determined comparatively. As can be seen from the relative literature concerning this topic, this is the first time a comparison of the performance parameters for a frigorific air conditioning system using HFO1234yf and R134a has been made. The originality of this paper is to compare two refrigerants transient and steady-state situations, at different charges. This study compared the refrigerants HFO1234yf and R134a in a transient scenario, and used a conditioning room to dertermine the performance of these refrigerants. Description of the experimental set-up The experimental system was made from original components of a frigorific air conditioning system, as schematically shown in fig. 1. It employed a 7-cylinder fixed-capacity swash-plate SANDEN SD 5750 W compressor at 2200 rpm, a 9500 W parallel-flow microchannel condenser, a 5750 W laminated type evaporator and thermostatic expansion valves. An experimental system was connected to a refrigerated room for the test. The room dimensions were determined as 210 cm 220 cm 220 cm. This conditioned room was insulated by 8 cm thick insulation panels.

THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 2067 All lines in the refrigeration circuit of the system were made from Cu tubing, and insulated by elastomeric material. The condenser was inserted into separate air ducts of 1.2 m length. In order to provide the required air streams in the air ducts, an axial fan was placed at the condenser ducts. These ducts also contained electric heaters located upstream of the condenser. The condenser electric heaters could be controlled between 0-2 kw. Figure 1. Schematic illustration of the experimental set-up To provide the required air temperature at the inlets of the condenser, the refrigeration circuit was charged with 1250 g, 1500 g, and 1750 g of R134a and HFO1234yf, respectively. In order to gather data for the performance evaluation of the experimental frigorific air conditioning system, some mechanical measurements were conducted on the system. The instruments and their locations are depicted in fig. 1. The features of the instrumentation can be seen in tab. 1. Table 1. Characteristics of the instrumentation Measured variable Instrument Range Uncertainty Temperature Type K thermocouple 50-400 C ±0.3% Pressure Digital monifold 0-25 bar ±0.2% Humidity Hygrometer 10-100% ±3% Air flow rate Anemometer 0.1-15 ms -1 ±3% Compressor speed Digital tachometer 10-100000 rpm ±2% The temperatures of the refrigerant and air at the inlet and exit of each component were measured by K-type thermocouples. Thermocouples for the refrigerant temperatures were soldered to the Cu tube. The refrigerant pressures at the inlet and exit of the compressor were monitored by digital manifold. The values of most of the measured variables were acquired through a data acquisition system and recorded on a computer. The air stream discharged from the evaporator duct was supplied to the refrigerated room for cool-down tests. In order to measure the compartment temperatures, a thermocouple was located at the exit of the evaporator, while another one was suspended in the air close to the left wall, and the last one was suspended in the air close to the right wall. The values of all measured variables was acquired through a data acquisition system and recorded on a computer. The data acquisition was a logging thermometer which is a nine channel and digital manifold which is also connect to two temperatures and pressure sensors. The refrigerant flow path in the experimental system is illustrated in fig. 1. The refrigerant passing through the condenser rejects heat to the ambient air stream. Then, the refrigerant condenses and leaves the condenser as sub-cooled liquid. Following this, the refrigerant flow reaches the receiver tank, which keeps the unrequired refrigerant when the thermostatic expansion valve decreases the refrigerant flow rate at low cooling loads reaches thermostatic expansion valve (TXV) located at the inlet of the evaporator. It enters the evaporator,

2068 THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 where it rejects cool air taken from the refrigerated room, and leaves the evaporator as low pressure superheated vapour. Finally, the refrigerant is directed to the compressor, which receives the low pressure refrigerant vapour and compresses it to a high pressure. The performance of HFO1234yf was tested in a standard R134a frigorific air conditioning without any alterations being made. Thermodynamic analysis The performance parameters of the experimental frigorific air conditioning system can be evaluated by applying the first law of thermodynamics to the system. Using this law for the condenser, the cooling capacity of the experimental frigorific air conditioning system can be evaluated from: Q = m ( h h ) (1) evap r evap,in evap,out where ṁ r is the refrigerant mass flow rate. Assuming that the compressor is adiabatic, the power absorbed by the refrigerant during the compression process can be expressed: W = m ( h h ) (2) comp r comp,out comp,in The COP of the frigorific air conditioning system defined as the ratio between cooling capacity and compressor power, i. e. can be determined: Q evap COP = (3) W Testing procedure In all tests condenser air flow rate was adjusted to its maximum (0.312 m 3 /s). In the summer season the temperature range is between 25 C to 40 C, respectively, in most parts of Turkey. Before performing the tests, air temperatures at the inlets of the condenser, T cond,in, were both fixed to either 25 C to 40 C, depending on the test. Meanwhile, the relative humidity of the air stream entering the outdoor coil was usually between 50-70%. Prior to the experiment, the conditioning room was set to 25 C. Following this, the system was started up. Then, the compressor of the experimental system and data acquisition system were started simultaneously. During the experiment, the evaporator and condenser operating pressure was usually between 1.6-2.5 bar and 8.5-12.5 bar, respectively. Data were collected until the steady-state was achieved, which took a time period of 60 minutes. The first experiment was conducted using the refrigerants at 1250 g charge, then 1500 g, and 1750 g, respectively. Results and discussion Figure 2 indicates the changes in the air temperatures at the outlet of the evaporator when the temperatures of the air streams entering the condenser are maintained at 25 C and refrigerants charged at 1250 g are used. As can be seen in the graph, there is a steady drop in the air temperatures when both the HFO1234yf, and R134a refrigerants are used. However, after a period of 60 minutes there is a visible difference between the air temperatures, with the air temperature using the R134a refrigerant being between 2 C and 4 C higher than that that used HFO1234yf. The air temperature that used refrigerant R134a dropped to a temperature comp

THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 2069 of 0 C after the completion of 60 minutes, while that which used refrigerant HFO1234yf had dropped to 2 C during the same period. As can be seen in fig. 3, when the air temperature inlet of the condenser is altered to 30 C, a far more visible difference can be seen in the refrigerant performances. The ability of the HFO1234yf refrigerant to reach and maintain far lower temperatures over the period of 60 minutes is significant, and extremely promising. Figure 4 demonstrates that there is a small difference between the air temperatures when the air temperature at inlet of the condenser is 40 C. The air temperature using the R134a refrigerant being between 1 2 C higher than that used HFO1234yf. Figure 2. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 25 C, 1250 g) Figure 3. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 30 C, 1250 g) Figure 5 indicates a slight alteration in the air temperatures in the first 12 minutes, the HFO1234yf refrigerant dropping slightly lower during this period, when the refrigerants charged at 1500 g are used. This change is only temporary, and the graph reveals how these two temperatures reunite following the initial 12 minutes and maintain the same decline thereafter. The graph reveals promising results. Figure 4. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 40 C, 1250 g) Figure 5. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 25 C, 1500 g)

2070 THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 Figure 6 indicates the changes in the air temperatures at the outlet of the indoor coil when the temperatures of the air streams entering the condenser are maintained at 30 C and refrigerants charged at 1500 g are used. As the condenser air inlet temperatures increases the evaporator outlet temperature of the HFO1234yf increased. The graph reveals a sharp drop in the air temperature which uses the HFO1234yf refrigerant in the first few minutes. Thereafter, the air temperature declines at a relatively stable rate over 60 minutes. It can be seen that R134a maintains a far more stable decline, and that the air temperature is always that much higher than that of HFO1234yf, this being maintained over the duration of 60 minutes. At the end of the 60 minutes period, the HFO1234yf evaporator outlet temperature had dropped to 5 C, as can be seen in the graph. Figure 7 indicates that two temperatures line reunite and maintain the same decline during the graph, when the temperatures of the air streams entering the condenser are maintained at 40 C. Figure 6. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 30 C, 1500 g) Figure 7. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 40 C, 1500 g) When the charge for both refrigerants was increased to 1750 g, the performance of HFO1234yf, and R134a were similar over the period of 60 minutes as seen in fig. 8. The HFO1234yf and R134a both dropped to below 5 C, and both refrigerants reached similar levels. Both refrigerants maintained, more or less, the same steady decrease in air temperature. The slight difference in performance over the final 10 minutes is arguably inconsequential. Figure 9 reveals the effects when the temperature entering the outdoor unit was increased to 30 C, the performance between the two refrigerants altered greatly, a difference of 7 can be seen between the refrigerants following the completion of the 60 minute period. As can be seen in the graph, when the condenser air temperature increased, the performance of the HFO1234yf refrigerant greatly increased when compared with R134a. When the air Figure 8. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 25 C, 1750 g) inlet temperature at condenser is 40 C both refrigerants gives the same decline, as it can be seen in fig. 10.

THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 2071 Figure 9. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 30 C, 1750 g) Figure 10. The variation of the air temperature at (T ind.uni. = 25 C, T outd.uni. = 40 C, 1750 g) Figure 11. The variation of the COP as a function of air temperature at the condenser inlet (1250 g) Figure 12. The variation of the COP as a function of air temperature at the condenser inlet (1500 g) Figure 13. The variation of the COP as a function of air temperature at the condenser inlet (1750 g) In figs. 11-13 it is shown that R134a the steady-state COP is generally higher than that of HFO1234yf. These values were all taken over a period of 60 minutes and were collected for three different refrigerant charges 1250 g, 1500 g, and 1750 g. When the temperature rises the COP reduces due to the cooling capacity reducing. When the refrigerant charge is increased the COP increases too. Because of this the COP gets higher on decreasing the air temperatures entering the condenser. Despite R134a performing marginally better at different charges over the 60 minute period, the performance of both refrigerants is comparable. Conclusions The transient and steady-state performance of an experimental frigorific air conditioning system has been evaluated. The cooled air was sent to the air conditioned room in order to evaluate the performance of the two refrigerants, HFO1234yf and R134a. Based on experimental data, the conditioned air temperature, COP in the system were determined and presented as a function of time, and air temperatures at the inlets of the condenser coils. As is seen in the results section, at temperatures of 25 C, gave similar performances, with HFO1234yf producing marginally better results. This is significant, when considering HF01234yf s greater environmental properties.

2072 THERMAL SCIENCE, Year 2016, Vol. 20, No. 6, pp. 2065-2072 Refrigerant HFO1234yf gave visibly better performances than R134a when the temperatures of the air streams entering the condenser were maintained at 30 C. These improved performances over R134a are promising. When the temperature rises the COP reduces due to the cooling capacity reducing. Results were comparable during this phase of the investigation. The results of this investigation propose the utilisation of HFO1234yf as a replacement over the currently favoured R134a in a frigorific air conditioning system. In order to obtain a more comprehensive performance of HFO-1234yf can be performed with water cooled condensers in future studies. Acknowledgment The authors would like to thank the University of Yalova for supporting this study through a Research Project No: 2013/BAP/063. Nomenclature COP coefficient of performance h enthalpy, [kjkg 1 ] ṁ mass flow rate, [gs 1 ] Q cooling capacity, [W] Ẇ work, [W] Subscripts comp compressor cond condenser evap evaporator in inlet ind.uni. indoor unit out exit outd.uni. outdoor unit r refrigerant ref refrigerated room References [1] ***, Regulation (EC) No 842/2006 of the European Parliament and of the Council of 17 May 2006 on Certain Fluorinated Greenhouse Gases. Official Journal of the European Communities. Retrieved online at, http://eur-lex.europa.eu/lexuriserv/lexuriserv.do?uri = OJ:L:2006: 161:0001:0011:EN:PDF [2] ***, Directive 2006/40/EC of The European Parliament and of the Council of 17 May, Relating to Emissions from Air-Conditioning Systems in Motor Vehicles and Amending Council Directive 70/156/EEC retrieved online at, http://www.bis.gov.uk/files/file30125.pdf (2006) [3] Meyer, J., HFO1234yf System Enhancements and Comparison to R134a, Proceedings, SAE Alternative Refrigerant Systems Symposium, Phoenix, Azriz, USA, 2008 [4] Minor, B., Spatz, M., HFO-1234yf low GWP Refrigerant Update, Proceedings, International Refrigeration and Air Conditioning Conference at Purdue, Paper No. 2349, West Lafayette, Ind., USA, 2008 [5] Petitjean, S., Benouali, J., R-1234yf Validation & A/C System Energy Efficiency Improvements, Proceedings, SAE Alternate Refrigerant Symposium, AARS, Scottsdale, Ariz., USA, 2010 [6] Lee, Y., Jung, D., A Brief Performance Comparison of HFO1234yf and R134a in a Bench Tester for Automobile Applications, Applied Thermal Engineering, 35 (2012), Mar., pp. 240-242 [7] Navarro, I. O., et al., Comparative Experimental Study of an Open Piston Compressor Working with HFO1234yf, R134a and R-290, International Journal of Refrigeration, 36 (2013), 3, pp. 768-775 [8] Akram, M. W., et al., Lubricity of Environmentally Friendly HFO1234yf Refrigerant, Tribology International, 57 (2013), Jan., pp. 92-100 [9] Lee, Y., et al., Performance of Non-Flammable Azeotropic HFO1234yf/HFC134a Mixture for HFC134a Applications, International Journal of Refrigeration, 36 (2013), 4, pp. 1203-1207 [10] Tanaka, K, Higashi, Y., Thermodynamic Properties of HFO_1234yf (2,3,3,3 Tetrafluoropropene), International Journal of Refrigeration, 33 (2010), 3, pp. 474-9 [11] ***, SAE International, Cooperative Research Program, Additional Risk Assessment of Alternative Refrigerant R-1234yf, Retrieved online at http://www.sae.org/standardsdev/tsb/cooperative/crp_1234-4_report.pdf, 2013 Paper submitted: July 15, 2014 Paper revised: November 4, 2014 Paper accepted: November 4, 2014