Applying Performance-based Fire Alarm System Design Part 4

Similar documents
Performance-based Fire Alarm System Design Introduction

Fire Pump Supervision - Part 3 by Dean K. Wilson, P.E.

Fire Pump Supervision - Part 2 by Dean K. Wilson, P.E.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Mount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION

Can You Hear Me Now?

Fire Pump Supervision - Part 1 by Dean K. Wilson, P.E.

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E.

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Not-So-Dead Air Space

Property Name & Address [ Property Name ] - [ Property Address ]

Changes in NFPA

Surviving the Survivable Cable Crunch

Fire Alarm System Fundamentals

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION

Can You Hear Me Now?

Florida Building Code 2010

Unified Fire Authority - Fire Prevention Bureau

MNEC NFPA 72 WHITE PAPER

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

NFPA Changes

FIRE & LIFE SAFTEY STANDARD

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

FIREFIGHTER II: FIRE DEPARTMENT COMMUNICATIONS COMMUNICATIONS: SKILL SHEET #2 Define and Demonstrate Fire Department Radio Procedure

NFPA 72 Code Changes vs 2013

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

1.3 REFERENCE STANDARDS

Full Service Central Station Fire Alarm Listing Evaluation

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

TENANT FLOOR WARDEN GUIDELINES

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80

Table of Contents. EMERGENCY PROCEDURES Policy 190

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

University of Maryland FIRE EVACUATION PLAN

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

2018 NICET Code Transition Changes

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

RAMBLER PARK FIRE SAFETY INFORMATION

Date Issued: December 14, 2017 Revision: 2.1

EMERGENCY PLANNING AND PREPAREDNESS

DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM

Fire Alarm System Inspection and Testing Report

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

IRVING FIRE DEPARTMENT EMERGENCY PLANS

Emergency Action Plans (OSHA ) Abstract. Introduction. Emergency Action Plan (EAP) Elements of an EAP

Nurse Call Systems & Emergency Call Systems. Overview of ANSI/UL 1069 and ANSI/UL 2560

St. Vincent s Health System Page 1 of 6

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Emergency Planning and Preparedness

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

Dutchess Community College. Emergency Action Plan. Conklin Hall College Residence

SCALES NW EMERGENCY ACTION PLAN

DAVIS POLICE DEPARTMENT

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY

Austin Independent School District Police Department Policy and Procedure Manual

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

Floor Warden Training. Thursday, May 27, 2015

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

FACILITY OF EMERGENCY PLAN. (Template)

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

For additional information please contact the Chesapeake Fire Prevention Office at or at

Fire evacuation drill

Florida Senate SB 982 By Senator Bennett

University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE FIRE MEDICAL EMERGENCY - 911

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe

Questions/Comments for Richard Roux from Webinar on 7/11/13

University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat,

Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

EC 5.10 FIRE PREVENTION MANAGEMENT

Bold items are particular to the City of Euless

TABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2

Narrative Reports As Regulated by 780 CMR, Section 903.0

Emergency Procedures for Clients

Building Emergency Response Scenario

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

ICC CODE CORNER 2015 International Fire Code

Fire Evacuation Plan Bressler Research Building. UMB POLICE or

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

Fire Evacuation Plan Davidge Hall. UMB POLICE or

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

Fire Safety Management Policy. This plan should be read in conjunction with the Health and Safety Policy.

Winnipeg Fire Department Fire Prevention Branch

Audio Verified Alarms Best Practices

Transcription:

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss a very hot topic in the arena of fire protection today, namely, performance-based building design. The graphic attached to this article offers a graphical representation of how this performance-based design process or procedure would apply to the design of a fire alarm system.

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 2 As I have stated several times, the key to understanding the whole performance-based building design arena rests with realizing that a process makes it work. So when a designer applies the concept of performance-based design to a fire alarm system, that designer will use a very methodical procedure. Such a procedure will help ensure that the fire alarm system design will meet the specific needs of the project, and also provide a comprehensive solution to whatever fire protection problems the procedure has, itself, identified. As we explained in the previous issues, the designer begins by analyzing the hazards and defining the project scope. The designer next identifies the specific fire protection goals that will apply to this project. By gathering information from the stakeholders in the project, the designer proceeds to define the stakeholder objectives. The designer applies negotiating techniques to resolve any conflicts between various stakeholder objectives and then combines the results into design objectives for the project. Next, the designer defines the performance criteria that will quantify the design objectives. With these first four steps complete and documented in the design specifications, the designer then moves on to choose the fire alarm system type that will best meet the design objectives. Choosing the type of fire alarm system presents no more of a challenge to the performancebased design process than it does to the typical prescriptive design process. The designer must decide to which type, if any, of an off-premises system the protected premises system will transmit signals. The protected building will, first of all, have a protected premises fire alarm system. Such a system, as its main purpose, will activate local audible and visible alarm notification appliances to notify the occupants that they must evacuate the protected building. A protected premises system could also interface with a supervising station fire alarm system to help make the building even

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 3 safer in the case of fire. And, a protected premises fire alarm system could provide additional features. These features might include the operation of a fire extinguishing or suppression system; the recall of elevators; the unlocking of doors; the closing of smoke barrier doors; the control of heating, ventilating, and air conditioning equipment; or the operation of smoke control systems, to name a few. Sometimes the protected premises fire alarm system provides Emergency Voice/Alarm Communications Service. This system, used in occupancies such as high rise buildings, notifies occupants to relocate to areas of refuge, rather than evacuate. It may also selectively and partially notify occupants to evacuate, while simply informing other occupants of the nature of the emergency when the fire does not immediately threaten their safety. The emergency voice/alarm system consists of a series of high reliability speakers located throughout the building. They connect to, and receive control from, the fire alarm system communication console located in an area designated as a building fire command station. From the building fire command station, individual speaker zones or the entire building can be selected to receive an alert tone followed by a voice message that gives specific instructions to the occupants. Some systems also have fire warden telephone stations on each floor, or within each fire zone, to which a fire warden would report to assume local command and pass on specific evacuation instructions. Such telephones may also allow emergency responders to communicate when the structure of the building inhibits the operation of their hand portable two-way radios. A trained building employee usually operates the fire command station until the fire department arrives, at which time the officer in charge takes over. Protected premises fire alarm systems may transmit signals to off-premises locations by means of a central station fire alarm system, a proprietary supervising station fire alarm system, a

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 4 remote supervising station fire alarm system, or by means of an auxiliary connection to a public fire alarm reporting system. A central station fire alarm system receives signals from a protected premises at a constantly attended location operated by a company that provides central station service. This operating company must be listed by either Underwriters Laboratories Inc. (UL) or Factory Mutual Research Corporation (FMRC). Central station installations must have either the UL Certificate or FMRC Placard, whichever means of verifying the character of the installation the Authority Having Jurisdiction requires. When they receive fire alarm, supervisory, or trouble signals, operators at the central station take action prescribed by NFPA 72-1999, National Fire Alarm Code. The proprietary supervising station fire alarm system provides service at large commercial or industrial occupancies. Signals transmitted over a proprietary system are received and automatically and permanently recorded at a constantly attended proprietary supervising station located either at the protected premises or at another location of the property owner. Upon receipt of fire alarm signals, supervisory signals, or trouble signals, operators at the proprietary supervising station will dispatch a runner to investigate. The operators will also retransmit fire alarm signals retransmitted to the public fire service communication center. A remote supervising station fire alarm system connects the outputs from a protected premises fire alarm system and transmits them to a remote location. NFPA 72-1999, National Fire Alarm Code, specifies that fire alarm signals must be received at the public fire service communication center, at a fire station, or at the location of the public agency that has the responsibility to receive fire alarms from the public.

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 5 If the public agency is unwilling to receive the remote station fire alarm signals, or if that agency is willing to allow another organization to receive those signals, then the signals may be received at a location acceptable to the authority having jurisdiction. Such a location must have trained personnel on duty 24 hours a day. Upon receipt of fire alarm signals, the personnel retransmit the signals to the public fire service communication center. In some cases, the public agency receiving fire alarm signals may also be willing to receive supervisory signals and trouble signals. In most cases, the system transmits supervisory signals and trouble signals to a constantly-attended location acceptable to the authority having jurisdiction. An auxiliary fire alarm system provides the interface between a protected premises fire alarm system and a public fire reporting system. If a community does not have a public fire reporting system, then a protected premises within that community cannot have an auxiliary fire alarm system. Once the fire alarm system designer has chosen the appropriate type of fire alarm system-- as with each of the previous four steps in the performance-based design process--the designer must clearly and carefully document the choice of system in the Design Specifications. This written record will allow anyone reviewing the design to develop a thorough understanding of the decision making that the designer employed throughout the design process. The designer must next select components and create a system design. And, we will focus on that important step in the next issue. IMSA member Dean K. Wilson, P.E., C.F.P.S., works as Senior Engineer in the Windsor (CT) office of the fire protection engineering and code consulting firm, Hughes Associates, Inc. (www.haifire.com). The opinions expressed in this article are strictly his own. You can reach him by phone at (860) 687-1009; by FAX at (860) 687-1308; or by e- mail at dwilson@haifire.com.