FWZ Series Oil-Fired Hot Water Boilers INSTALLATION INSTRUCTIONS

Similar documents
Oil-Fired Hot Water Boilers Installation Instructions These instructions must be affixed on or adjacent to the boiler

TWZ/CT/ODV Series. Oil-Fired Hot Water Boilers (Less Tankless Heater) These instructions must be affixed on or adjacent to the boiler

Oil-Fired Steam Boilers INSTALLATION INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler WARNING

USER'S INFORMATION MANUAL

HWX GAS BOILERS USER S INFORMATION MANUAL

Gas-Fired Natural Draft Hot Water Boilers INSTALLATION INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler

USER'S INFORMATION MANUAL

Series High Efficiency Gas-Fired Hot Water Direct Vent Condensing Boilers

Crown Boiler Company

GBX GAS BOILERS USER S INFORMATION MANUAL

WBV/WV. Boilers. As an ENERGY STAR Partner, PB Heat, LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency.

Installer's Guide. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE YCC-IG EB23D1-12

WARNING FIRE OR EXPLOSION HAZARD.

APEX CONDENSING HIGH EFFICIENCY GAS-FIRED HOT WATER BOILER

User s Information Manual

USER S INFORMATION MANUAL

Alpine CONDENSING HIGH EFFICIENCY GAS-FIRED HOT WATER BOILER

ML180UH SERIES GAS FURNACE WARNING WARNING

USER S INFORMATION MANUAL

WV-DV. Series. Oil. Boilers. Installation, Operation & Maintenance Manual

USER S INFORMATION MANUAL Model: HSE 125 N/P, HSE 145 N/P Gas-fired, Condensing Boiler and Instantaneous Water Heater

EL195UH SERIES GAS FURNACE WARNING

EL195DFE SERIES GAS FURNACE WARNING

OIL-FIRED CENTRAL FURNACE

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER

BC Series II OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR US AND CANADIAN SALES

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

User s Information Manual Models: 45, ,000 Btu/hr

1. GENERAL SAFETY RULES

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS RRO SERIES CAST IRON OIL-FIRED BOILER

Installation and service must be performed by a qualified service installer, service agency or the gas supplier.

TriFire High Efficiency Oil Fired Hot Water Boiler

G61MPV SERIES GAS FURNACE WARNING

EL296UHV SERIES GAS FURNACE WARNING WARNING

TO DO IF YOU SMELL GAS

EL195UHE SERIES GAS FURNACE WARNING WARNING

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

OPERATING INSTRUCTIONS AND OWNER S MANUAL

Do not use this vent pipe or fittings for venting incinerators of any kind.

WARNING FIRE OR EXPLOSION HAZARD.

Elite. User s Information Manual. Elite and Elite VWH* All Models

Installation Requirements for Models:

WBV/WV. Series. Oil. Boilers. Installation, Operation & Maintenance Manual

USER S INFORMATION MANUAL

DOMESTIC WATER HEATER OIL FIRED

KAPPA R BOILER INSTALLATION, OPERATION INSTRUCTIONS. Gas-Fired Natural Draft Hot Water Boilers

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER

MPO IQ 87% AFUE. Limited Lifetime Warranty! control. Oil-Fired, High Efficiency, 3-Pass Water Boiler. system GREATER ENERGY SAVINGS

MC Series Gas-Fired Heating Appliance

TriFire High Efficiency Oil Fired Hot Water Boiler

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

GAS BOILERS USER'S INFORMATION MANUAL SG-135-E TO SG-495-E AAA-480 TO AAA-3000

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces

Introduction Engineering and Design Manual

CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED. Models: CMO32 CMO50

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS CL SERIES CAST IRON OIL-FIRED BOILER

MANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS:

Models TRB4075 TRB4095 TRB4110 TRB5100 TRB5115 TRB5135 TRB6130 TRB6145 TRB6165 TRB7165 TRB7180 TRB7190

INSTALLATION AND OPERATION MANUAL GAS SKILLETS MODELS: GTS-30 GTS-40

User s Information Manual

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

- Do not store or use gasoline or other

USER'S INFORMATION MANUAL ES2 GAS - FIRED

USER'S INFORMATION MANUAL

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS FOR SERIES 3

KEROSENE FORCED AIR HEATER

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

Description Model Weil-McLain part number. Vent Termination Kit for 3" Stainless Steel All

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

USER S INFORMATION MANUAL

Columbia Boiler Company

Energy Manager INSTALLATION INSTRUCTIONS. Keep these instructions with the boiler at all times for future reference

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

Fig. 1 - Unit PGD4, PGS4, WPG4

Owner s Information Manual

USER'S INFORMATION MANUAL

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

CBO-750 HYBRID-R OVEN Instructions Manual

USER S INFORMATION MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

USER'S INFORMATION MANUAL

USER S INFORMATION MANUAL

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS CL SERIES CAST IRON OIL-FIRED BOILER

User s Information Manual Models: ER152, ER202, ER252, ER302, and ER402

SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE WARNING WARNING

INSTALLATION AND SERVICE MANUAL. Hot Water Heating Boilers Domestic Hot Water Supply Boilers 399, ,000 Btu/hr Models

WBV. Boilers. As an ENERGY STAR Partner, PB Heat, LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency.

Tankless Water Heater

USER'S MANUAL PGE Single Package Rooftop

ESC ENHANCED SEALED COMBUSTION Gas - Fired Boiler

Universal Fire Tube Boiler Wall Mount Models

Crown Boiler Company

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS CL SERIES CAST IRON OIL-FIRED BOILER

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

Transcription:

D E S I G N E D T O L E A D FWZ Series Oil-Fired Hot Water Boilers INSTALLATION INSTRUCTIONS Models: FWZ060 FWZ080 FWZ100 FWZ130 FWZ160 WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury, or loss of life. For assistance or additional installer, service agency or the oil supplier. Read these instructions carefully before installing. Manufacturer of Hydronic Heating Products P.O. Box 14818 3633 I. Street Philadelphia, PA 19134 www.crownboiler.com 1

2

WARNINGS FOR THE HOMEOWNER FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler. INSPECT THE BOILER, BURNER AND CONTROLS ANNUALLY. To keep your boiler safe and efficient, have a service technician follow the Service checklist near the end of this manual. IF YOU ARE NOT QUALIFIED to install or service boilers, do not install or service this one. THE BOILER MAY LEAK WATER at the end of its useful life. Be sure to protect walls, carpets, and valuables from water that could leak from the boiler. PROTECT YOUR HOME IN FREEZING WEATHER. A power outage, safety lockout, or component failure will prevent your boiler from lighting. In winter, your pipes may freeze and cause extensive property damage. Do not leave the heating system unattended during cold weather unless alarms or other safeguards are in place to prevent such damage DO NOT BLOCK AIR FLOW into or around the boiler. Insufficient air may cause the boiler to produce carbon monoxide or start a fire. KEEP FLAMMABLE LIQUIDS AWAY from the boiler, including paint, solvents, and gasoline. The boiler may ignite the vapors from the liquids causing explosion or fire. KEEP CHILDREN AND PETS away from hot surfaces of the boiler, boiler piping, and vent pipe. CARBON MONOXIDE (CO) is an odorless, deadly gas that may be introduced into your home by any malfunctioning fuel-burning product or vent system failure. Consider installing CO alarms near bedrooms in all levels of the building to warn you and your family of potential CO exposure. WARNINGS FOR THE INSTALLER READ THIS ENTIRE MANUAL before attempting installation, start-up, or service. Improper installation, adjustment, alteration, service, or maintenance may cause serious property damage, personal injury, or death. DO NOT DISCONNECT PIPE FITTINGS on the boiler or in the heating system without first verifying that the system is cool and free of pressure and that your clothing will protect you from a release of hot water or steam. Do not rely solely on the boiler s temperature and pressure gage when making this judgment. USE PROPER PERSONAL PROTECTION EQUIPMENT when servicing or working near the boiler. Materials of construction, flue products, and fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, and/or other toxic or harmful substances that can are hazardous to health and life and that are known to the State of California to cause cancer, birth defects, and other reproductive harm. INSTALL ALL GUARDS, cover plates, and enclosures before operating the boiler. SIZE THE BOILER PROPERLY relative to the design heat load or, if using domestic hot water priority, the peak hot water load, whichever is larger. A grossly oversized boiler will cycle excessively and this will lead to premature failure of the boiler and its components. Our warranty does not apply to damage from excessive cycling. ADHERE TO ALL LOCAL CODE REQUIREMENTS. Contact your local code inspector prior to installation. In the absence of a local code, adhere to the latest editions of the Installation of Oil Burning Equipment ANSI/NFPA 31 in the USA or CAN/CSA B139, Installation Code for Oil Burning Equipment in Canada. ALL WIRING must comply with the National Electrical Code ANSI/NFPA 70 (in the USA) or the Canadian Electrical Code CSA C22.1 (in Canada) and any local regulations. 1

Table of Contents XV. Parts... 44 2

I Product Description TABLE 2.0: GENERAL SPECIFICATIONS BOILER WEIGHT TABLE 2.1: RATING DATA BOILER GPH TILE SIZE HEIGHT FT. 112 222

1-1/2" FPT SUPPLY PIPING CONNECTION TOP VIEW TEMP/PRESSURE GAUGE RELIEF VALVE AQUASTAT RELAY PORT BURNER SWING DOOR FLAME OBSERVATION 4 3 8 " 'B' MIN. FRONT SERVICE CLEARANCE (FLUEWAY CLEANING) BECKETT AFG BURNER 31 1 2 " 19" BURNER SWING DOOR CLEARANCE (FULLY OPEN) 20 FRONT VIEW 3 4 " FIGURE 2.3: GENERAL CONFIGURATION * 'A' SPANNER BAR RIGHT VIEW * 12" MIN. REAR SERVICE CLEARANCE *NOTE: THIS DIMENSION INCREASES AND IS CONTROLLED BY SMOKEPIPE ARRANGEMENT. CIRCULATOR CLEAN OUT COVER 'C' DIA. COLLAR SMOKEBOX COLLAR 21 3 8 " DRAIN VALVE 1-1/2" RETURN PIPING FLOOR LINE REAR VIEW 4

III Before Installing Installation of Oil Burning Equipment Installation Code for Oil-burning Equipment. Standard for Controls and Safety Devices for Automatically Fired Boilers such as the I=B=R - Power ( Side Wall ) Venting - Important Note Two problems arise when any oil-fired appliance is power vented: There is sometimes an accelerated rate of soot buildup on the oil burner cad-cell, spinner etc. There is a potential for severe damage to the side of the structure in the event that the boiler operates at a high smoke level. This can happen for many reasons, some of which are out of the control of both the installer and appliance manufacturer. Crown Boiler Company recommends the use of a chimney to vent the FWZ series boilers. If a power venter must be used, it is the responsibility of the installer and power vent manufacturer to engineer the power vent system. Crown Boiler Company will assume no responsibility for damage to siding, etc. from a power vented oil-fired boiler. This applies regardless of the cause of the sooting.

IV Field Assembly WARNING Installation of burners on the FWZ other than those provided by Crown, and marked for use with this boiler, may result in unreliable operation, property damage, personal injury, or loss of life. - FIGURE 4.0: BOILER FIELD ASSEMBLY

V Locating the Boiler WARNING Failure to observe the following location requirements could result in property damage, a fire, explosion or carbon monoxide (CO) hazard. - FIGURE 5.0: CLEARANCES

FIGURE 5.1: INSTALLATION OVER A COMBUSTIBLE FLOOR VI Air for Combustion and Ventilation Standard for the Installation of Oil Burning Equipment

A. For Buildings of Other than Unusually Tight Construction a. Example: An FWZ080 and a water heater are to be installed in a room measuring 6 ft - 3 in x 7 ft with an 8 ft ceiling. The water heater has an input of 30000 BTU/hr: Input of FWZ080 = 0.80 Gal/hr x 140000 BTU/Gal = 112000BTU/hr Total input in thousands of BTU/hr = (112000 BTU/hr + 30000 BTU/hr)/1000 = 142 Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft 3 - B. For Buildings of Unusually Tight Construction

FIGURE 6.0: BOILER INSTALLED IN CONFINED SPACE, ALL AIR FROM INSIDE FIGURE 6.1: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC

FIGURE 6.2: ALL AIR FROM OUTDOORS, VIA VENTILATED ATTIC FIGURE 6.3: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM 11

FIGURE 6.4: ALL AIR FROM OUTDOORS, USING HORIZONTAL DUCTS INTO BOILER ROOM 12

VII Venting WARNING Improper venting may result in property damage and/or the release of flue gases, which contain deadly carbon monoxide (CO), into the home, which can cause severe personal injury or death. Inspect existing chimney before installing boiler. Failure to clean or replace damaged pipe or tile lining will cause property damage, severe personal injury or death. Do not de-rate the appliance. Failure to fire the unit at it s designed input may cause excessive condensation upon the interior walls of the chimney. In addition, the lower input may not create enough draft to adequately evacuate the products of combustion. Standard for the Installation of Oil-Burning EquipmentStandard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning AppliancesInstallation Code for Oil-burning Equipment. Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances. The vent connector. Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances

FIGURE 7.0: TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS TABLE 7.1: MINIMUM RECOMMENDED BREECHING AND CHIMNEY SIZE BOILER 14

VIII System Piping WARNING Install boiler so that the electrical components are protected from water (dripping, spraying, rain, etc.) During appliance operation and service (circulator replacement, etc.). Operation of this boiler with continuous return temperatures below 135 f can cause severe boiler or chimney damage. Do not operate this boiler at a flow rate less than the minimum shown in Table 8.0, Column (a). Operation of this boiler in a system having significant amounts of dissolved oxygen can cause severe heat exchanger corrosion damage. Do not use toxic additives, such as automotive antifreeze, in a hydronic system. Pipe relief valve discharge to a safe location. The relief valve may discharge scalding hot water. Do not install a valve in the relief valve discharge line. Do not move relief valve from factory location. A. Standard Piping I=B=R The

heat. B. Piping for Special Situations Table 8.0 Minimum Flow Rate Requirements

FIGURE 8.1: INSTALLATION OF FACTORY SUPPLIED PIPING FIGURE 8.2: STANDARD BOILER PIPING

heater manufacturer. met. FIGURE 8.3: INDIRECT WATER HEATER BOILER SIDE PIPING

FIGURE 8.4: BYPASS PIPING FIGURE 8.5: ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER

IX Fuel Line Piping WARNING Under no circumstances can copper with sweat style connectors be used. Do not use compression fittings. Oil piping must be absolutely airtight or leaks or loss of prime may result. Some jurisdictions require the use of a fusible shutoff valve at the tank and/or the burner. In addition, some jurisdictions require the use of a fusible electrical interlock with the burner circuit. Check your local codes for special requirements.

FIGURE 9.0: ONE-PIPE GRAVITY SYSTEM FIGURE 9.1: ONE-PIPE LIFT SYSTEM 21

FIGURE 9.2: TWO-PIPE GRAVITY FEED SYSTEM (NOT RECOMMENDED) FIGURE 9.3: TWO-PIPE LIFT SYSTEM 22

X Wiring WARNING All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code (ANSI/NFPA 70). Disconnect electrical power to the boiler and heating system before servicing. Positively assure that no voltage is present. Lock electrical boxes to prevent someone from inadvertently restoring power before the heating system is safe to operate. Never defeat or jump out safety devices. Protect each boiler circuit with a properly sized over-current protection device. Make electrical connections carefully according to the boiler s wiring diagram and instructions. Wire additional field supplied safety limits, such as low water cutoffs and temperature limit devices, in series with the 120V circuit used to power the boiler. Do not alter the boiler s factory wiring when adding an additional limit device. - - T-T -

CAUTION When making low voltage connections, make sure that no external power source is present in the thermostat circuits. If such a power source is present, it could destroy the boiler s control. One example of an external power source that could be inadvertently connected to the low voltage connections is a transformer in old thermostat wiring. Do not attempt to use EnviraCOM connections for any purpose not explicitly permitted by Crown Boiler Company. Attempting to do so may result in unreliable operation and/ or damage to controls. Do not use the transformer provided on the boiler to power external devices such as zone valves. Doing so may cause damage to the transformer. 24

FIGURE 10.0: WIRING CONNECTIONS DIAGRAM FOR L7248 AQUASTAT

FIGURE 10.1: CONNECTIONS WIRING DIAGRAM FOR BURNER SPECIFIC PRIMARY CONTROL

XI Start-up and Checkout WARNING Never attempt to fill a hot empty boiler. Make sure that the area around the boiler is clear and free from combustible materials, gasoline, and other flammable vapors and liquids. Safe reliable operation of this boiler requires that the burner be checked and adjusted by a qualified oil serviceman using combustion test instruments. Failure to perform all of the checks outlined in the following procedure could result in unreliable operation, damage to the boiler not covered under warranty, property damage, or unsafe operation. All boilers equipped with burner swing door have a potential hazard which can cause severe property damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener completely when service is completed. In addition, the burner power cord will have to be disconnected from the receptacle in the front jacket. VII for more information.

FIGURE 11.0: FLUE DRAFT TAPPING POSITIVE. 2 the burner.

WARNING Attempts to use burners or burner configurations other than those shown in Table 11.1 could result in reliability problems, property damage, personal injury or loss of life TABLE 11.1a: BECKETT BURNER CONFIGURATION AND SETUP DATA L2 L1 L1 V1 V1 2 1 1 2 TABLE 11.1b: RIELLO BURNER CONFIGURATION AND SETUP DATA VSBT VSBT VSBT 2

XII Operation A. General Information B. Reading Status and Using Menu 1. 2. I I I 4.

FIGURE 12.1: BOILER CONTROL MENU STATUS MODE: =Current Status (Table 12.2) Press to enter OPERATING MODE Press and Hold,, and for at least 3 sec to enter ADJUSTMENT MODE = High Limit Setting = Current Boiler Temp. = Limit Differential = Current Set Point =Use of 2 nd Zone = High Limit Setting =Circulator Overrun =Thermal Purge Time = Limit Differential =Thermal Purge Temp =Call for Heat? (On/Off) =DHW Priority (ON/OFF) =Call for DHW? (On/Off) =Temperature Units N Error Detected by Aquastat? =Return to Status Mode Press Press or Y ERROR MODE (Visible when Lockout is Present) = Code for Error Present (Table 14.0) Y Error Detected by Aquastat? N Except as shown above, press to navigate through menu. Use,to change parameters in Adjustment Mode

TABLE 12.2: STATUS CODES OR OR OR OR FIGURE 12.3: TYPICAL OPERATING MODE DISPLAY (BOILER TEMP SHOWN) NOTE In operating mode, holding either the or button while viewing a given parameter will keep the display on the actual reading. For example, pressing while reading boiler temperature as shown in Figure 12.3 will keep the display on 180 for as long as this button is held. This makes it easier to view readings live if they are changing rapidly TABLE 12.4: OPERATING MODE PARAMETERS

TABLE 12.5: ADJUSTMENT MODE PARAMETERS OR OR 2 min F C. Using Adjustment Mode WARNING Improper adjustments to control parameters could result in unreliable boiler operation, property damage, personal injury, or loss of life. Adjustments should only be made by a qualified heating technician. I,, Use I Use the or I I Press either the or

TABLE 12.6 EXAMPLES OF THERMAL PURGE OPERATION Heat Use of From Time ( ( 1 T-T 2 min. 2 T-T 2 min. ZR 2 min. 4 on ZR Heat ( 2 min. T-T 2 min. T-T OR OR OR OR

TABLE 12.7 SUMMARY OF CIRCULATOR BEHAVIOR Parameters T-T Use of Zone ( ( OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Heat or OFF OFF Heat or OFF Heat or

XIII Service and Maintenance WARNING All boiler cleaning must be completed with the burner service switch turned off. Boilers equipped with burner swing door have a potential hazard which can cause severe property damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Disconnect the burner plug from the receptacle in the front jacket. Be sure to tighten the swing door fastener completely when service is completed. IMPORTANT Clean The Boiler Even If There Are No Significant Soot Deposits. Failure To Remove All Sulfur And Ash Deposits Annually Can Cause Severe Corrosion Damage.

WARNING The boiler must be connected to an approved chimney in good condition. Serious property damage could result if the boiler is connected to a dirty or inadequate chimney. The interior of the chimney flue must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed chimney flue is necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler s efficiency. burner. WARNING Water leaks can cause severe corrosion damage to the boiler or other system components. Repair any leaks found immediately.

Important Product Safety Information Refractory Ceramic Fiber Product Warning: The Parts list designates parts that contain refractory ceramic fibers (RCF). RFC has been classified as a possible human carcinogen. When exposed to temperatures about 1805 F, such as during direct flame contact, RFC changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled, may be hazardous to your health. AVOID Breathing Fiber Particulates and Dust Precautionary Measures: Do not remove or replace RCF parts or attempt any service or repair work involving RCF without wearing the following protective gear: 1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator 2. Long sleeved, loose fitting clothing 3. Gloves 4. Eye Protection with soap and water after contact. om other laundry and rinse washing machine after use to avoid contaminating other clothes. g in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United States and Canada. First Aid Procedures: ter for at least 15 minutes. Seek immediate medical attention if irritation persists. ed area gently with soap and water. Seek immediate medical attention if irritation persists. with clean fresh air. Seek immediate medical attention if breathing difficulties persist. Drink plenty of water. Seek immediate medical attention.

XIV Trouble Shooting A. Combustion 2 2 Water TEST PROCEDURE FOR FUEL SIDE PROBLEMS A good test for isolating fuel side problems is to disconnect the fuel system and with a 24 length of tubing, fire the burner out of an auxiliary five gallon pail of clean, fresh, warm #2 fuel oil from another source. If the burner runs successfully when drawing out of the auxiliary pail then the problem is isolated to the fuel or fuel lines being used on the installation.

B. Control System C. If Display is Blank D. If Control Shows Code E. If Control Shows Code, but Other Problem Present If no I TABLE 14.0 - ERROR CODES Error -

TABLE 14.1 - FAULTS WITHOUT ERROR CODE PRESENT Burner Off Burner Off on Burner Burner Off on Burner 41

Notes 42

Notes

XV Parts 1 1 2 2 4 4 4 4 4 4 4 4 4 4 4 1 1 1 1 1 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 12 1 1 1 1 1 1 1 1 1 1 14 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 21 22 2 2 2 24 2 2 2 44

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 4 4 4 4 2 2 2 2 2 41 2 2 2 2 2 42 2 2 2 2 2 1 1 1 1 1

1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 * 1 * 1 1 1 1 1 * 1 1 1 1 1 * 1 1 1 1 1

Manufacturer of Hydronic Heating Products P.O. Box 14818 3633 I. Street Philadelphia, PA 19134 www.crownboiler.com FWZ