WORKING DRAFT OF COMMITTEE MEETING OUTPUT

Similar documents
NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf

SECTION AUTOMATIC TRANSFER SWITCHES

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

SECTION AUTOMATIC TRANSFER SWITCHES

B. Section Transfer Switches: Automatic transfer switch.

SECTION GENERATOR PARALLELING CONTROLS

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

A. This Section includes transfer switches rated 600 V and less, including the following:

First Revision No. 20-NFPA [ Section No ]

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

David Stymiest, PE, CHFM, CHSP, FASHE cell Copyright 2014, Smith Seckman Reid, Inc.; All rights reserved

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

SECTION AUTOMATIC TRANSFER SWITCHES

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

Guide Specification Model CTG Automatic Transfer Switch

CONTENTS AUTOMATIC TRANSFER SWITCHES

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

ENGINE GENERATORS AND ACCESSORIES

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

16620 EMERGENCY POWER SYSTEMS

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

First Revision No. 1-NFPA [ Chapter 2 ]

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

26 of 128 9/23/2014 9:25 AM

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

Committee on NFPA 85


Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

UFGS (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

EMERGENCY POWER SYSTEMS

Public Input No. 3-NFPA [ Chapter 2 ]

Remove the "Exception" text to be consistent with direction provided in the MOS.

Spectron LSN (Life Safety Network) Suggested Specifications

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:


2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method.

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)


Step by Step Detailed Procedure Expected Result Observations Verify power off at all loads on emergency power. Verify all loads have power.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Fire Pump Supervision - Part 2 by Dean K. Wilson, P.E.

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

DIESEL Engine Fire Pump Controllers Features

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

NFPA 37 Public Comment Responses Page 1 of 32

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION 16346G METAL-CLAD EMERGENCY GENERATOR PARALLELING SWITCHGEAR MEDIUM VOLTAGE

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system.

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Comment No. 1-NFPA [ Section No ]

SECTION ISOLATED POWER SYSTEMS

SECTION EMERGENCY POWER SYSTEMS

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

FACILITY CONNECTION STANDARD

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

DGC-1000 DIGITAL GENSET CONTROLLER

FLOAT BATTERY CHARGERS

Committee Input No. 60-NFPA [ Sections , ]

File Name Description Approved. This doc shows the changes to take place in this revision. Changes are marked in comments titled "GLOBAL".

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Changes in NFPA

SECTION ENCLOSED CONTROLLERS

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Transcription:

WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF FIRST DRAFT REPORT Document: NFPA 110 (EPS-AAA) Revision Cycle: A2018 Meeting Date(s): September 7, 2016 Activity: Input Stage This is a working draft, prepared by NFPA staff, to record the output generated at the Technical s First Draft Meeting. It includes draft copies of the First Revisions and any Global Revisions. It is being made available to members for the purpose of facilitating early review, particularly for those members who may be seeking input from their respective organizations in preparation for the Letter Ballot of the.

of 39 9/21/2016 10:12 AM First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code,2015 edition. NFPA 790, Standard for Competency of Third-Party Field Evaluation Bodies, 2014 edition NFPA 70, National Electrical Code, 2017 edition Submitter Full Name: Christopher Coache Organization: National Fire Protection Assoc Submittal Date: Tue Sep 20 12:14:25 EDT 2016 : The references were added since the definitions have been extracted from other NFPA standards. Response Message: Page 1 of 39

of 39 9/21/2016 10:12 AM First Revision No. 30-NFPA 110-2016 [ New Section after 3.3.5.2 ] 3.3.X Field Evaluation Body (FEB). An organization or part of an organization that performs field evaluations of electrical or other equipment. [ 790, 2014] 3.3.X Field Labeled (as applied to evaluated products). Equipment or materials to which has been attached a label, symbol, or other identifying mark of an FEB indicating the equipment or materials were evaluated and found to comply with requirements as described in an accompanying field evaluation report. [ 70, 2017] Submittal Date: Wed Sep 07 18:40:55 EDT 2016 : The new definitions are necessary for the terms added in the new exception for Section 5.2.5. Response Message: Page 2 of 39

of 39 9/21/2016 10:12 AM First Revision No. 2-NFPA 110-2016 [ Section No. 4.4 [Excluding any Sub-Sections] ] This standard recognizes two levels of for equipment installation, performance, and maintenance requirements. Submittal Date: Wed Sep 07 11:25:46 EDT 2016 : The editorial change clarifies the intent of the statement. Response Message: Public Input No. 51-NFPA 110-2016 [Section No. 4.4 [Excluding any Sub-Sections]] Page 3 of 39

of 39 9/21/2016 10:12 AM First Revision No. 29-NFPA 110-2016 [ Section No. 5.2.5 ] 5.2.5 The EPS shall be installed in accordance with NFPA 70, National Electrical Code. Exception: When a listing process is not available for the engine-generator assembly, a Field Evaluation Body acceptable to the authority having jurisdiction shall be permitted to affix a field label. Submittal Date: Wed Sep 07 18:25:13 EDT 2016 Response Message: The exception was added since there currently is no listing process for medium voltage stationary engine-generator assembly. Page 4 of 39

of 39 9/21/2016 10:12 AM First Revision No. 3-NFPA 110-2016 [ Section No. 5.3.5 ] 5.3.5 The ambient air temperature in the EPS equipment room or outdoor housing containing Level I rotating equipment shall be stabilize at not less than 4.5 C (40 F) when the equipment is not operating. Submittal Date: Wed Sep 07 13:38:17 EDT 2016 Response Message: The revision clarifies the intent of the section. The temperature requirement is only relevant when the EPS is not operating. Public Input No. 45-NFPA 110-2016 [Section No. 5.3.5] Public Input No. 25-NFPA 110-2016 [Section No. 5.3.5] Page 5 of 39

of 39 9/21/2016 10:12 AM First Revision No. 4-NFPA 110-2016 [ Section No. 5.6.2 ] 5.6.2 Prime Mover Ratings. Proper derating factors, such as altitudes, ambient temperature, fuel energy content, accessory losses, and site conditions as recommended by the manufacturer of the generator set engine shall be used in determining whether or not brake power meets the connected load requirements. Submittal Date: Wed Sep 07 13:52:47 EDT 2016 Response Message: The authoritative source for actual derating factors is the manufacturer of the prime mover, not the assembler of a generator set. Public Input No. 43-NFPA 110-2016 [Section No. 5.6.2] Page 6 of 39

of 39 9/21/2016 10:12 AM First Revision No. 5-NFPA 110-2016 [ Section No. 5.6.3.6.1 ] 5.6.3.6.1 A battery charger driven by the prime mover shall not be required for Level 2 generators, provided the automatic battery charger has a high-low rate capable of fully charging the starting battery during running conditions as specified in 5.6.3.6. within the time frame required by this standard while powering all loads connected to the starting batteries. Submittal Date: Wed Sep 07 13:55:05 EDT 2016 Response Message: An AC powered battery charger is less reliable than a mechanically driven DC alternator because the AC-powered system has several single points of failure including the incremental wiring, ac protective devices, and the charger itself. So, for critical applications it is reasonable to require both DC power sources in the system. Generators often have significant DC loads when they are operating, in addition to the starting battery recharge duty. This addition makes it clear that the charger for critical applications must be capable of continuous operation with all loads attached. Public Input No. 26-NFPA 110-2016 [Section No. 5.6.3.6.1] Page 7 of 39

of 39 9/21/2016 10:12 AM First Revision No. 6-NFPA 110-2016 [ Section No. 5.6.4.2 [Excluding any Sub-Sections] ] For otto or diesel cycle prime movers, the type and duration of the cranking cycle shall be as specified in Table 5.6.4.2. Table 5.6.4.2 Starting Equipment Requirements Starting Equipment Requirements Level 1 Level 2 (a) Battery unit X X (b) Battery certification X NA (c) Cycle cranking X or O O (d) Cranking limiter time-outs Cycle crank (3 cycles) 75 sec 75 sec Continuous crank 45 sec 45 sec (e) Float-type battery charger X X dc ammeter X X dc voltmeter X X (f) Recharge time 24 hr 36 hr (g) Low battery voltage alarm contacts X X X: Required. O: Optional. NA: Not applicable. Submittal Date: Wed Sep 07 13:58:10 EDT 2016 Response Message: The cranking cycle was changed to only specify "O". Something that is either required or optional will be taken to mean it is optional. Public Input No. 50-NFPA 110-2016 [Section No. 5.6.4.2 [Excluding any Sub-Sections]] Page 8 of 39

of 39 9/21/2016 10:12 AM First Revision No. 7-NFPA 110-2016 [ Section No. 5.6.4.7 ] 5.6.4.7 All chargers shall include the following characteristics, which are to be accomplished without manual intervention (i.e., manual switch or manual tap changing): (1) At its rated voltage, the charger shall be capable of delivering energy into a fully discharged battery unit without damaging the battery. (2) The charger shall be capable of returning the fully discharged battery to 100 percent of its ampere-hour rating within the time specified in Table 5.6.4.2, item (f). (3) As specified in Table 5.6.4.2, item (e), meters with an accuracy within 5 percent of range shall be furnished. (4) The charger generator set or charger shall be permanently marked with the following: (5) Allowable range of battery unit capacity which can be recharged within the time requirements of Table 5.6.4.2. (6) Nominal output current and voltage (7) Sufficient battery-type data to allow replacement batteries to be obtained (8) The battery charger output and performance shall be compatible with the batteries furnished. (9) Battery chargers used in Level 1 systems shall include temperature compensation for charge rate. Submittal Date: Wed Sep 07 14:00:22 EDT 2016 Response Message: The marking requirements in (4)(a), (b), and (c) are modified to make the requirement more clear. Temperature compensation is added because battery failure is the most common reason for failure of a generator set to start and pick up loads. Improper charge rate is the most common reason for premature battery failure because proper charge rate is temperature dependent, and without temperature compensation there isn't a good way to assure that a proper charge rate is achieved. Public Input No. 27-NFPA 110-2016 [Section No. 5.6.4.7] Page 9 of 39

0 of 39 9/21/2016 10:12 AM First Revision No. 8-NFPA 110-2016 [ Section No. 5.6.5.1 ] 5.6.5.1 A control panel shall be provided and shall contain the following: (1) Automatic remote start capability (2) Run-off-automatic mechanical switch (3) Shutdowns as required by 5.6.5.2 (3) (4) Alarms as required by 5.6.5.2 (4) (5) Controls as required by 5.6.5.2 (5) Submittal Date: Wed Sep 07 14:24:26 EDT 2016 : Mechanical was added to ensure direct mechanical control for manual generator starting. Response Message: Public Input No. 28-NFPA 110-2016 [Section No. 5.6.5.1] Page 10 of 39

1 of 39 9/21/2016 10:12 AM First Revision No. 9-NFPA 110-2016 [ Section No. 5.6.5.2 ] Page 11 of 39

2 of 39 9/21/2016 10:12 AM TWO CHANGES TO BE MADE: in 2.c. change sentence to read: Automatic: Allow prime mover to start or stop by operating a remote contact. In legend to table change to read: S: Shutdown of EPS 5.6.5.2 Page 12 of 39

3 of 39 9/21/2016 10:12 AM Where a control panel is mounted on the energy converter, it shall be mounted by means of antivibration shock mounts, if required, to maximize reliability. An automatic control and safety panel shall be a part of the EPS containing the following equipment or possess the following characteristics, or both: (1) Cranking control equipment to provide the complete cranking cycle described in 5.6.4.2 and required by Table 5.6.4.2 (2) Panel-mounted control switch(es) marked run off automatic to perform the following functions: (3) Run: Manually initiate, start, and run prime mover (4) Off: Stop prime mover or reset safeties, or both (5) Automatic: Allow prime mover to start by closing a remote contact and stop by opening the remote contact (6) Controls to shut down and lock out the prime mover under any of the following conditions: (7) Failing to start after specified cranking time (8) Overspeed (9) Low lubricating-oil pressure (10) High engine temperature (An automatic engine shutdown device for high lubricating-oil temperature shall not be required.) (11) Operation of remote manual stop station (12) Individual alarm indication to annunciate any of the conditions listed in Table 5.6.5.2 and with the following characteristics: (13) Battery powered (14) Visually indicated (15) Have additional contacts or circuits for a common audible alarm that signals locally and remotely when any of the itemized conditions occurs (16) Have a lamp test switch(es) to test the operation of all alarm lamps (17) Controls to shut down the prime mover upon removal of the initiating signal or manual emergency shutdown (18) The ac instruments listed in 5.6.9.9 Table 5.6.5.2 Safety Indications and Shutdowns Level 1 Level 2 Indicator Function (at Battery Voltage) CV S RA CV S RA (a) Overcrank X X X X X O (b) Low water temperature X NA X X NA O (c) High engine temperature pre-alarm X NA X O NA NA (d) High engine temperature X X X X X O (e) Low lube oil pressure X X X X X O (f) Overspeed X X X X X O (g) Low fuel main tank X NA X O NA O (h) Low coolant level X O X X O X (i) EPS supplying load X NA NA O NA NA (j) Control switch not in automatic position X NA X X NA X (k) High battery voltage X NA NA O NA NA (l) Low cranking voltage X NA X O NA O (m) Low voltage in battery X NA NA O NA NA (n) Battery charger ac failure X NA NA O NA NA (o) Lamp test X NA NA X NA NA (p) Contacts for local and remote common alarm X NA X X NA X (q) Audible alarm silencing switch NA NA X NA NA O (r) Low starting air pressure X NA NA O NA NA (s) Low starting hydraulic pressure X NA NA O NA NA (t) Air shutdown damper when used X X X X X O Page 13 of 39

4 of 39 9/21/2016 10:12 AM Level 1 Level 2 Indicator Function (at Battery Voltage) CV S RA CV S RA (u) Remote emergency stop NA X NA NA X NA CV: Control panel mounted visual. S: Shutdown of EPS indication. RA: Remote audible. X: Required. O: Optional. NA: Not applicable. Notes: (1) Item (p) shall be provided, but a separate remote audible signal shall not be required when the regular work site in 5.6.6 is staffed 24 hours a day. (2) Item (b) is not required for combustion turbines. (3) Item (r) or (s) shall apply only where used as a starting method. (4) Item (i) EPS ac ammeter shall be permitted for this function. (5) All required CV functions shall be visually annunciated by a remote, common visual indicator. (6) All required functions indicated in the RA column shall be annunciated by a remote, common audible alarm as required in 5.6.5.2(4). (7) Item (g) on gaseous systems shall require a low gas pressure alarm. (8) Item (b) shall be set at 11 C (20 F) below the regulated temperature determined by the EPS manufacturer as required in 5.3.1. Submittal Date: Wed Sep 07 14:33:15 EDT 2016 Response Message: The change to the start command is in response to changes in the 2017 National Electrical Code. The word "indication" was struck from table legend for clarity. Public Input No. 48-NFPA 110-2016 [Section No. 5.6.5.2] Page 14 of 39

5 of 39 9/21/2016 10:12 AM First Revision No. 10-NFPA 110-2016 [ Section No. 5.6.5.5 ] 5.6.5.5 The cranking cycle shall be capable of being initiated by any of the following: (1) Manual start initiation as specified in 5.6.5.2 (2)(a). (2) Loss of normal power at any automatic transfer switch (ATS) considered a part of the EPSS. Prime mover shall start upon closing of a remote switch or contacts and shall stop, after appropriate time delays, when switch or contacts are opened. (3) Clock exerciser located in an ATS or in the control panel. (4) Manually operated (test) switch located in each ATS that simulates a loss of power and causes automatic starting and operation until this switch is reset, to cause the engine circuit to duplicate its functions in the same manner commercial power is restored after a true commercial power failure. Submittal Date: Wed Sep 07 14:38:38 EDT 2016 Response Message: Remote start circuits for most generator sets will accept either a N.O. or a N.C. contact, so the requirement shouldn't be tied to just the N.O. case. For example, a NC remote contact must be used when projects require fail-safe genset start/stop wiring. Public Input No. 49-NFPA 110-2016 [Section No. 5.6.5.5] Page 15 of 39

6 of 39 9/21/2016 10:12 AM First Revision No. 12-NFPA 110-2016 [ Section No. 5.6.5.6 [Excluding any Sub-Sections] ] All installations shall have be provided with a least one remote manual stop station of a type to prevent inadvertent or unintentional operation tamperproof emergency stop switch located outside the room housing the prime mover, where so installed, or elsewhere on the premises where the prime mover is located outside the building. Submittal Date: Wed Sep 07 15:21:49 EDT 2016 : This revision clarifies the use and location of the stop station required by NFPA 110. Response Message: Page 16 of 39

7 of 39 9/21/2016 10:12 AM First Revision No. 11-NFPA 110-2016 [ Section No. 5.6.9.9 ] 5.6.9.9 The generator instrument panel for Level 1 applications shall contain the following: (1) An ac voltmeter(s) for each phase or a phase selector switch (2) An ac ammeter(s) for each phase or a phase selector switch (3) A frequency meter (4) A voltage-adjusting feature to allow ± 5 percent voltage adjustment (5) An ac kw meter indicating total load on the generator set Submittal Date: Wed Sep 07 14:44:57 EDT 2016 Response Message: In a generator set application an engine has very limited overload capability, and without a kw meter there is no easy way for an operator to visually see when loads are approaching the limits of the engine. Because ammeters don't consider power factor, they don't actually indicate impending overload on an engine. Level 1 systems should have this critical feature. kw meters are now a standard feature in most generator set products used in Level 1 systems. Public Input No. 29-NFPA 110-2016 [Section No. 5.6.9.9] Page 17 of 39

8 of 39 9/21/2016 10:12 AM First Revision No. 13-NFPA 110-2016 [ Section No. 6.2.2.1 ] 6.2.2.1 * Undervoltage-sensing devices shall be provided to monitor all ungrounded lines of the primary the normal source of power as follows: (1) When the voltage on any phase falls below the minimum operating voltage of any load to be served, the transfer switch shall automatically initiate engine start and the process of transfer to the EPS. (2) * When the voltage on all phases of the primary the normal source returns to within specified limits for a designated period of time, the process of transfer back to primary to normal power shall be initiated. Submittal Date: Wed Sep 07 15:59:13 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Public Input No. 3-NFPA 110-2016 [Section No. 6.2.2.1] Page 18 of 39

9 of 39 9/21/2016 10:12 AM First Revision No. 14-NFPA 110-2016 [ Section No. 6.2.3 ] 6.2.3* Interlocking. Mechanical interlocking or an approved alternate method shall prevent the inadvertent interconnection of the primary normal power supply and the EPS, or any two separate sources of power. Submittal Date: Wed Sep 07 16:08:59 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Page 19 of 39

0 of 39 9/21/2016 10:12 AM First Revision No. 15-NFPA 110-2016 [ Section No. 6.2.5 ] 6.2.5* Time Delay on Starting of EPS. A time-delay device shall be provided to delay starting of the EPS. The timer shall prevent nuisance starting of the EPS and possible subsequent load transfer in the event of harmless momentary power dips and interruptions of the primary source. Submittal Date: Wed Sep 07 16:11:25 EDT 2016 Response Message: The word "harmless" was removed from the sentence. If there are momentary power dips and interruptions with the primary source, we don't really know if they will be harmless. It could be harmless to some loads, but not harmless to others. Public Input No. 54-NFPA 110-2016 [Section No. 6.2.5] Page 20 of 39

1 of 39 9/21/2016 10:12 AM First Revision No. 32-NFPA 110-2016 [ Section No. 6.2.8 ] 6.2.8* Time Delay on Retransfer to Primary Source. An adjustable time-delay device with automatic bypass shall be provided to delay retransfer from the EPS to the primary normal source of power and to allow the primary source to stabilize before retransfer of the load. Submittal Date: Fri Sep 09 14:14:50 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Page 21 of 39

2 of 39 9/21/2016 10:12 AM First Revision No. 33-NFPA 110-2016 [ Section No. 6.2.9 ] 6.2.9 Time Delay Bypass If EPS Fails. The time delay shall be automatically bypassed if the EPS fails. 6.2.9.1 The transfer switch shall be permitted to be programmed for a manually initiated retransfer to the primary normal source to provide for a planned momentary interruption of the load. 6.2.9.2 If used, the arrangement in 6.2.9.1 shall be provided with a bypass feature to allow automatic retransfer in the event that the EPS fails and the primary normal source is available. Submittal Date: Fri Sep 09 14:20:07 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Page 22 of 39

3 of 39 9/21/2016 10:12 AM First Revision No. 34-NFPA 110-2016 [ Section No. 6.2.11.1 ] 6.2.11.1 Transfer switches shall transfer the connected load to the EPS and immediately return to primary normal power automatically in case of an EPS failure. Submittal Date: Fri Sep 09 14:21:56 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Page 23 of 39

4 of 39 9/21/2016 10:12 AM First Revision No. 35-NFPA 110-2016 [ Section No. 6.2.12 ] 6.2.12 Test Switch. A test means shall be provided on each ATS that simulates failure of the primary normal power source and then transfers the load to the EPS. Submittal Date: Fri Sep 09 14:23:50 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Page 24 of 39

5 of 39 9/21/2016 10:12 AM First Revision No. 36-NFPA 110-2016 [ Section No. 6.2.16.1 ] 6.2.16.1 Interlocking. Reliable mechanical interlocking or an approved alternate method shall prevent the inadvertent interconnection of the primary normal power source and the EPS. Submittal Date: Fri Sep 09 14:25:48 EDT 2016 Response Message: The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPA documents. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also the conventional term used in the electrical power industry and by most equipment manufacturers on their products and literature describing this power source and the transfer switch position. Page 25 of 39

6 of 39 9/21/2016 10:12 AM First Revision No. 16-NFPA 110-2016 [ Section No. 6.3 ] 6.3 Load Switching (Load Shedding) Requirements for Paralleled Generator Sets. When two or more engine generator sets are paralleled for emergency power, the paralleled system is the source, and system logic shall be arranged to inhibit connection of EPS-damaging loads manage the loads to maintain power quality. 6.3.1 Each transfer switch shall have a continuous current rating and interrupting rating for all classes of loads to be served. 6.3.2 The transfer switch shall be capable of withstanding the available fault current at the point of installation. 6.3.3 The transfer of loads to the EPS shall be sequenced as follows: (1) First-priority loads shall be switched to the emergency bus upon sensing the availability of emergency power on the bus. (2) Each time an additional engine generator set is connected to the bus, a remaining load shall be connected in order of priority until all emergency loads are connected to the bus. (3) The system shall be designed so that, upon failure of one or more engine generator sets, the load is automatically reduced, starting with the load of least priority and proceeding in ascending priority, so that the last load affected is the highest-priority load. Submittal Date: Wed Sep 07 16:13:28 EDT 2016 Response Message: The title "Load Switching (Load Shedding)" was too specific and only described 6.3.3.(3). Section 6.3 and the underlying text are about the requirements for transfer switches used with paralleled generator sets. The last part of the sentence was changed to clarify that the system logic is managing the loads, whether it's priority pickup (when gensets are coming on line), or load shed (if a genset fails). This revision also clarifies that the paralleled system is the source, so that ATS ratings can be correctly chosen. The requirements in 6.3.1 and 6.3.2 are deleted since they are already covered 6.1.4 and 6.1.5. Public Input No. 47-NFPA 110-2016 [Section No. 6.3] Public Input No. 30-NFPA 110-2016 [Section No. 6.3 [Excluding any Sub-Sections]] Public Input No. 31-NFPA 110-2016 [Sections 6.3.1, 6.3.2] Page 26 of 39

7 of 39 9/21/2016 10:12 AM First Revision No. 18-NFPA 110-2016 [ Section No. 7.9.13 ] 7.9.13 Automatically actuated valves shall not be permitted in the fuel oil supply or fuel oil return lines for Level 1 Emergency Power Supply Systems. Submittal Date: Wed Sep 07 16:36:23 EDT 2016 Response Message: Based on reliability of fusible links or other automatically actuated valves, NFPA 110 Level 2 generators that do not support life safety systems should be allowed to use automatically actuated valves to protect network or IT infrastructure from fire. Public Input No. 57-NFPA 110-2016 [Section No. 7.9.13] Page 27 of 39

8 of 39 9/21/2016 10:12 AM First Revision No. 19-NFPA 110-2016 [ Section No. 7.11.6 ] 7.11.6* For systems in seismic risk areas, the EPS, transfer switches, distribution panels, circuit breakers, and associated controls shall be capable of performing their intended function during and after being subjected to the anticipated seismic shock. Submittal Date: Wed Sep 07 16:41:04 EDT 2016 Response Message: The revision is made to align the seismic requirements in this document with the International Building Codes (IBC). The IBC requires that generator sets and their support equipment, transfer switches, and switchgear be able to operate after a seismic event. Public Input No. 46-NFPA 110-2016 [Section No. 7.11.6] Page 28 of 39

9 of 39 9/21/2016 10:12 AM First Revision No. 20-NFPA 110-2016 [ Section No. 7.12.3 ] 7.12.3 The wiring between the EPS output terminals and the first distribution overcurrent protective device terminals within the EPSS shall be located at a minimal distance to ensure system reliability and safety. Submittal Date: Wed Sep 07 17:03:30 EDT 2016 : This section is redundant with 7.12.1. Response Message: Page 29 of 39

0 of 39 9/21/2016 10:12 AM First Revision No. 21-NFPA 110-2016 [ Section No. 7.13.4.3 [Excluding any Sub-Sections] ] A load shall be applied for a 2-hour, full-load test. The building load shall be permitted to serve as part or all of the load, supplemented by a load bank of sufficient size to provide a load equal to 100 percent of the nameplate kw rating of the EPS, less applicable derating factors for site conditions. With full load applied, the coolant temperature of the generator set shall stabilize at a constant value relative to outdoor ambient temperature at least 30 minutes prior to completion of the test. Submittal Date: Wed Sep 07 17:06:48 EDT 2016 Response Message: In general, a 2-hour full load test is sufficient to verify that a generator will carry rated load successfully. However, in order to verify that high load levels will not cause eventual cooling system failure, the coolant temperature should be observed to stabilize prior to stopping the test. Public Input No. 34-NFPA 110-2016 [Section No. 7.13.4.3 [Excluding any Sub-Sections]] Page 30 of 39

1 of 39 9/21/2016 10:12 AM First Revision No. 22-NFPA 110-2016 [ Section No. 7.13.4.5 ] 7.13.4.5 All safeties specified in 5.6.5 and 5.6.6 shall be tested on site as recommended by the manufacturer. Exception No. 1 : It shall be permitted for the manufacturer to test and document overcrank, high engine temperature, low lube oil pressure and overspeed safeties prior to shipment. Exception No. 2: Where the safety functions are proven to be failsafe as demonstrated by monitoring of normal conditions on engine metering and demonstration that a failed sensor or circuit will not cause shutdown of the engine, further testing of the safeties is not required. Submittal Date: Wed Sep 07 17:09:09 EDT 2016 Response Message: Engines that utilize analog sensors and verify the operation of protective functions by setting trip points at normal operating values of parameters demonstrate proper safety shutdown operation. Public Input No. 35-NFPA 110-2016 [Section No. 7.13.4.5] Page 31 of 39

2 of 39 9/21/2016 10:12 AM First Revision No. 23-NFPA 110-2016 [ Section No. 8.4.2 ] 8.4.2* Diesel generator Generator sets in service shall be exercised at least once monthly, for a minimum of 30 minutes, using one of the following methods: (1) Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer (2) Under operating temperature conditions and at not less than 30 percent of the EPS standby nameplate kw rating 8.4.2.1 The date and time of day for required testing shall be decided by the owner, based on facility operations. 8.4.2.2 Equivalent loads used for testing shall be automatically replaced with the emergency loads in case of failure of the primary source. 8.4.2.3* Diesel-powered EPS installations that do not meet the requirements of 8.4.2 shall be exercised monthly with the available EPSS load and shall be exercised annually with supplemental loads at not less than 50 percent of the EPS nameplate kw rating for 30 continuous minutes and at not less than 75 percent of the EPS nameplate kw rating for 1 continuous hour for a total test duration of not less than 1.5 continuous hours. 8.4.2.4 Spark-ignited generator sets shall be exercised at least once a month with the available EPSS load for 30 minutes or until the water temperature and the oil pressure have stabilized. 8.4.2.4. 1 The date and time of day for required testing shall be decided by the owner, based on facility operations. 8.4.2.4.2 Equivalent loads used for testing shall be automatically replaced with the emergency loads in case of failure of the primary source. Submittal Date: Wed Sep 07 17:18:00 EDT 2016 Response Message: Load level on natural gas generator sets can be qualified in the same way that they are for diesel generator sets, with the primary difference being that the required exhaust gas temperature level is different, and it takes considerably less load to reach that temperature. Separate paragraphs for diesel and natural gas generator sets are not needed. Preventing damage/degradation in the engine is not the only concern with generator sets: operating them at load helps to drive moisture out of the electrical portions of the system so they are less likely to fail. So, even if the gas genset may run a few more hours a year than might be allowed with the current rules, the effect on the generator is beneficial. Public Input No. 37-NFPA 110-2016 [Section No. 8.4.2] Page 32 of 39

3 of 39 9/21/2016 10:12 AM First Revision No. 24-NFPA 110-2016 [ Section No. 8.4.9.7 ] 8.4.9.7 * Where the test required in 8.4.9 is combined with the annual load bank test, the first 3 hours shall be first portion of the test shall be at not less than the minimum loading required by 8.4.9.5 and, the remaining last hour shall be at not less than 75 percent of the nameplate kw rating of the EPS, and the duration of the test shall be in accordance with 8.4.9.1 and 8.4.9.2. Submittal Date: Wed Sep 07 17:29:19 EDT 2016 : This revision simplifies and clarifies the requirements of this section. Response Message: Public Input No. 15-NFPA 110-2016 [Section No. 8.4.9.7] Page 33 of 39

4 of 39 9/21/2016 10:12 AM First Revision No. 31-NFPA 110-2016 [ Section No. A.3.3.4 ] A.3.3.4 Emergency Power Supply System (EPSS). When multiple generators are connected together on a common bus, the common bus is considered to be the system source. See Annex B for diagrams of typical systems. Submittal Date: Fri Sep 09 11:42:23 EDT 2016 Response Message: Recognizing the system bus for multiple generator systems will clarify design requirements for things such as grounding and bonding of the system, and selective coordination of the distribution system connected to the generator source. Public Input No. 24-NFPA 110-2016 [Section No. 3.3.4] Page 34 of 39

5 of 39 9/21/2016 10:12 AM First Revision No. 25-NFPA 110-2016 [ Section No. A.5.1.1(1) ] A.5.1.1(1) The grade of diesel fuel selected for use in a prime mover should be based on recommendations from the diesel engine manufacturer and ASTM D 975, Standard Specification for Diesel Fuel Oils. Where possible, the The purchaser of fuel for the prime mover should specify a diesel fuel that does not contain biodiesel, which can accelerate the degradation of the diesel fuel if stored longer than 6 months. If diesel fuel is stored outside for long-term storage, it can be necessary to use a winter or arctic grade of diesel fuel or to take precautions such as insulating and heat-tracing fuel tanks and lines to ensure that fuel will flow to the prime mover under the coldest possible conditions. Submittal Date: Wed Sep 07 17:32:10 EDT 2016 : Biodiesel is not recommended in a standby generator set. Response Message: Public Input No. 38-NFPA 110-2016 [Section No. A.5.1.1(1)] Page 35 of 39

6 of 39 9/21/2016 10:12 AM First Revision No. 26-NFPA 110-2016 [ Section No. A.5.6.4.6 ] A.5.6.4.6 It is intended that the battery charger be factory-built, adjusted, and approved for the specific type, construction, and capacity of the battery. For lead-acid batteries, the battery charger should be tested for the specific gravity, type, and concentration of grid alloys, such as high or low gravity, high or low antimony, calcium, or none. Submittal Date: Wed Sep 07 17:50:30 EDT 2016 : Section 5.6.4.6 relates to battery chargers not to batteries. Response Message: Public Input No. 39-NFPA 110-2016 [Section No. A.5.6.4.6] Page 36 of 39

7 of 39 9/21/2016 10:12 AM First Revision No. 27-NFPA 110-2016 [ Section No. A.6.2.15 ] A.6.2.15 ATSs can be provided with accessory controls that provide a signal to operate remote motor controls that disconnect motors prior to transfer and to reconnect them after transfer when the residual voltage has been substantially reduced. Another method is to provide in-phase monitors within the ATS in order to prevent retransfer to the primary source until both sources are nearly synchronized. A third method is to use a programmed neutral position transfer switch. See Section 230.95 of NFPA 70, National Electrical Code. Submittal Date: Wed Sep 07 18:01:31 EDT 2016 Response Message: NEC Section 230.95 describes ground fault protection which has nothing to do with transfer switch operation when switching inductive loads. Public Input No. 41-NFPA 110-2016 [Section No. A.6.2.15] Page 37 of 39

8 of 39 9/21/2016 10:12 AM First Revision No. 28-NFPA 110-2016 [ Chapter C ] Annex C Informational References C.1 Referenced Publications. The documents or portions thereof listed in this annex are referenced within the informational sections of this standard and are not part of the requirements of this document unless also listed in Chapter 2 for other reasons. C.1.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 edition. NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, 2014 edition. NFPA 54, National Fuel Gas Code, 2015 edition. NFPA 56, Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping Systems, 2014 edition. NFPA 58, Liquefied Petroleum Gas Code, 2014 edition. NFPA 70, National Electrical Code, 2014 edition. NFPA 70B, Recommended Practice for Electrical Equipment Maintenance, 2013 edition. NFPA 99, Health Care Facilities Code, 2015 edition. NFPA 101, Life Safety Code, 2015 edition. NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems, 2016 edition. C.1.2 Other Publications. C.1.2.1 ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036. ANSI/NEMA C 84.1, Standard for Electric Power Systems and Equipment Voltage Ratings (60 hertz), 2006 2011. C.1.2.2 ASCE Publications. American Society of Civil Engineers, 1801 Alexander Bell Drive, Reston, VA 20191. ASCE/SEI 7, Minimum Design Loads for Buildings and Other Structures, 2010. C.1.2.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshocken, PA 19428-2959. ASTM D 975 D975, Standard Specification for Diesel Fuel Oils,2011b 2015c. ASTM D 1835 D1835, Standard Specification for Liquefied Petroleum (LP) Gases, 2011 2013. C.1.2.4 IEEE Publications. IEEE, Three Park Avenue, 17th Floor, New York, NY 10016-5997. ANSI/IEEE 493, Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems, 2007. C.1.2.5 NEMA Publications. National Electrical Manufacturers Association, 1300 North 17th Street, Suite, 1847 900, Rosslyn Arlington, VA 22209. ANSI/ NEMA MG 1, Standard for Motors and Generators, 2009 2016. ANSI/ NEMA MG 2, Safety Standard and Guide for Selection, Installation and Use of Electric Motors and Generators, 2001, Revision 1, 2007 2014. C.1.2.6 NHC Publications. National Hurricane Center, 11691 SW 17th Street, Miami, FL 33165-2149. SLOSH (Sea, Lake and Overland Surges from Hurricanes) Model. C.1.2.7 U.S. Government Publications. FEMA 543, Design Guide for Improving Critical Facility Safety from Flooding and High Winds, 2007. FEMA 577, Design Guide for Improving Hospital Safety in Earthquakes, Floods, and High Winds, 2007. C.2 Informational References. The following documents or portions thereof are listed here as informational resources only. They are not a part of the requirements of this document. Page 38 of 39

9 of 39 9/21/2016 10:12 AM C.2.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 72, National Fire Alarm and Signaling Code, 2013 edition. C.3 References for Extracts in Informational Sections. (Reserved) Submittal Date: Wed Sep 07 18:07:23 EDT 2016 : References are changed to current SDO names, addresses, standard names, numbers, and editions. Response Message: Public Input No. 2-NFPA 110-2015 [Chapter C] Page 39 of 39