Warm Case Troubleshooting Guide 9/18/2014

Similar documents
Otherwise, you can continue reading the file on the following pages.

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Installation, Operation, and Maintenance Information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied

Checking the Charge on a Heat Pump in the Winter

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Condensing Unit Installation and Operating Instructions

INSTALLATION and OPERATING. INSTRUCTIONS for. SMZP26 Series. elf-contained Freezers

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

WineZone Ceiling Mount Ductless Split 15

ThermoSaver TM Hot Gas Defrost System

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

User s Information and Installation Instructions

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Installation Manual BCS 1000/1500

User s Information and Installation Instructions

Welcome to the Ice-O-Matic on-line training modules. Ice. Pure and Simple

A/C-HEATER SYSTEM - MANUAL

ThermoSaver TM Hot Gas Defrost System

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Condensing Unit Installation and Operating Instructions

Installation Manual BCS2000/3000

Service Step by Step Trouble-Shooting Check-List

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

How to Diagnose a TXV Failurek

40KMC KMQ

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Split Floor-Mounted Cooling System Operation Care Installation Manual

YCIV Hz & Hz

Split Refrigeration Systems

Read and save these instructions

The Saturation process

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

IMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer for over 16

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

APPLICATION DATA SHEET

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-280MAH KM-280MWH SERVICE MANUAL

A Series Inertia Compressor Applications. Application Bulletin 115

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

RTP Technical Bulletin

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions

MASS. MARITIME ACADEMY

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

4A6H5042G1000A 208/230/1/ DURATION - SCROLL 3/4 208/230/1/ NO (Use BAYKSKT263) YES YES PROPELLER DIRECT

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

USING THE P-T CARD AS A SERVICE TOOL

Automatic Ice maker. Service manual MIM250

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON.

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

Ceiling Split Cooling System Installation, Operation & Care Manual WM-2500SSD WM-4500SSD WM-6500SSD WM-8500SSD

R.A.S.E.R.S System. Installation Guide

KM-630MAH KM-630MWH KM-630MRH

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

Installation Instructions

NUMBER: ISSUED: JULY 13, /336 73/23 STACKABLE CRESCENT CUBER KM-1300SWH-E SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI

AC10B FEATURES UNIT DIMENSIONS. Ducane Air Conditioner. THE DIFFERENCE IS QUALITY

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Read and save these instructions

User s Information and Installation Instructions

Horizontal/Side Discharge Condensing Units

Sporlan Valve Division Parker Hannifan/CIC Group

SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI 89/336 73/23 SELF-CONTAINED CRESCENT CUBER KM-150BAF-E KM-150BWF-E

B. A. T. Basic Appliance Training

Reach-In Refrigerators and Freezers Service Manual

INSTALLATION AND OPERATING MANUAL

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

KML F SERIES KML H SERIES

Read and save these instructions

Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice.

BasicTroubleshooting Information and Guidelines

Read and save these instructions

Installation Instructions

REF5-BB Undercounter Blood Bank Refrigerator

H29A Series Compressor Applications. Application Bulletin 139

Superheat charging curves for technicians

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

Reliability is a beautiful thing TM MODULAR CRESCENT CUBER KM-500MAH KM-500MWH KM-500MRH SERVICE MANUAL

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

Transcription:

Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last product stocking occurred, any unusual noises or abnormal operation. Ensure that all doors open freely and spring closed when released. Prior to loosening and removing condensing unit service valve caps to install refrigeration service gauges, leak check the valves to identify any refrigerant leaks from them which otherwise might not get addressed. Be prepared with the proper equipment to measure discharge pressure, suction pressure, and superheat. Measure and record the operating data requested below and determine any anomalies with the values compared to the acceptable ranges in parenthesis. Refer to the Warm Case Troubleshooting Table found on Page #2. Using the top row of the table which names each column, identify the column(s) which correspond to the appropriate abnormal reading. Then, observe the components of the case and condensing unit listed in the left vertical column of the same table. Use the table to match the measurements and observations to potential equipment problems explained in the paragraphs below. Evaluate all potential problems in the table before making a final diagnosis. In these systems, subcooling is typically not used for troubleshooting. Measurements: (Fill in blanks) Suction (Cooler: 60-65 psig; Freezer: 16-22 psig): psig Discharge - Hybrid cases only (Cooler: 250-325 psig; Freezer: 175-250 psig): psig Superheat (6 F - 14 F) *Note: Superheat readings shall be taken near the end of the operating cycle with the case operating at 1-2 F above the set point cut-out of the Carel controller. 1) Suction pressure reading: psig 2) Convert the pressure recorded in step #1 above to the R-404a saturation temperature using a refrigerant pressure/temperature chart: F 3) Measure and record the suction line temperature within 3 downstream of the TXV bulb: F 4) Calculate the evaporator superheat: F - F = F (Suct line temp Step #3) (Saturation Temp (Step #2) (Evap Superheat) Zero Zone, Inc. 110 N Oakridge Dr, North Prairie, WI 53153-9792 800-247-4496 Zero-Zone.com 1 of 5

Connection for low side pressure Location for taking suction line temperature Observations: Warm Case Troubleshooting Table Superheat Superheat Suction Suction Discharge Discharge Iced Coil 1.3 1.3 1.3 Short Cycling 1.1/1.6 1.1/1.4/1.6 1.6 1.1/1.4 1.1/1.6 Site Glass Bubbling 1.1 1.1 1.1 ( Charge) Site Glass Flashing/Foaming 1.1 1.1 1.1 Evap Fan Out 1.4 1.4 1.4 Warm Ambient 1.5 1.5 1.5 Condenser Fan Out 1.6 1.6 1.6 Dirty Condenser 1.6 1.6 1.6 Site glass indicates 1.2 1.2 1.2 1.2 1.2 1.2 moisture None of the above 2.2 2.1 2.1 2.2 2.1/2.2 Zero Zone, Inc. 110 N Oakridge Dr, North Prairie, WI 53153-9792 800-247-4496 Zero-Zone.com 2 of 5

Compressor not operating Verify correct voltage and trace the electrical circuit to contactor coil, controller (Carel), safety switches (low pressure, high pressure, and electronic unit controller EUC) and compressor. Controller and safety switches send a signal to the contactor coil to energize the compressor. If the compressor doesn t start and there is proper voltage, you will need to refer to the condensing unit manufacturer s troubleshooting guide. If the compressor is replaced, verify proper operating parameters after installation of new compressor. For further information, please use the references listed below; 1) Emerson Troubleshooting website: http://www.emersonclimate.com/en-us/resources/troubleshooting/pages/default.aspx 2) Emerson Fault Finder app: http://www.emersonclimate.com/en-us/resources/mobile_apps/pages/mobileapps.aspx. 3) Heatcraft manuals: http://www.heatcraftrpd.com/literature/literature.aspx?andfid=956. Correction to System: 1.1) A site glass which displays flashing or foaming can be the result of high superheat which could be caused by possibly a low refrigerant charge. Under normal operation, you will see occasional bubbles. If you see any constant bubbles and / or flashing or foaming, then the system might be low on refrigerant charge. Monitor the site glass to verify. Confirm that there are no restrictions in the liquid line (receiver valve partially closed, plugged drier, kinked liquid line, etc.). suction pressure, as a result of low refrigerant, will make the TXV look as though it is malfunctioning, when it is not. The TXV may be seeing a combination of liquid and vapor entering the valve, and replacing the TXV will not correct the issue in the system. Other checks for low charge are if the compressor amp draw is low or if there is a small condenser split (condensing temperature ambient temperature). Correction: Repair any leaks in the system. Add refrigerant to system to properly charge it. For Hybrid cases, the case nameplate lists the correct refrigerant charge. For Remote cases, calculate the refrigerant charge required for the line set run and add 1-1/2 pound per door for VC/VZ cases. Installers - Do not exceed receiver capacity needed for pump down operation. This is critical in situations where the liquid line solenoid valve is at the CNDU. Clear Site Glass Bubbling Flashing/Foaming Zero Zone, Inc. 110 N Oakridge Dr, North Prairie, WI 53153-9792 800-247-4496 Zero-Zone.com 3 of 5

1.2) A pink center eye on the site glass indicates the moisture level is high in the refrigerant system. Moisture can cause the expansion valve to stick and warm the expansion valve body. Correction: Replace filter/drier. 1.3) A coil that is plugged with ice may result in low superheat and might have had an insufficient defrost. Correction: The coil will need to be de-iced. Running the case through an additional defrost may de-ice a partially ice plugged coil. Water washing is generally required. Manual methods or water removal will be required for cases that use pumps and condensate evaporating pans to avoid water overflow. Troubleshoot the case defrost to ensure the case defrost is functioning properly, is programmed correctly, and has proper heater voltage. Check that all evaporator fans are functioning properly and that the evaporator has the correct superheat. 1.4) An evaporator fan that is not operating will cause the case to have low superheat and improper air flow across the evaporator. Correction: Check that the fan is plugged into the harness. Check voltage on fan harness receptacle. If no voltage is present at the harness and the other fans are operating, replace the harness. If voltage is ok on the harness, replace the fan motor. If no fans are running, troubleshoot the electrical system. 1.5) Warm ambient conditions will cause high superheat, high discharge pressure, and reduced compressor capacity. Correction: If an indoor condensing unit, verify that the store A/C unit is functioning properly and proper store conditions are maintained. Check placement of ductwork in reference to the case condensing unit. If an outdoor condensing unit, be sure there is proper air flow across the condenser. 1.6) A condenser fan that is not operating or a dirty condenser will cause high discharge pressure, reduced compressor capacity, and high superheat and improper air flow across the condenser. Correction: If the condenser is dirty, clean it and remove any obstructions from it. Check the fan blade and tighten holding screws, if required. If the condenser fan is not running, check the wiring to the condenser fan. If power is correct to the condenser fan, then replace the condenser fan motor. Expansion Valve Information: 2.1) superheat: Insufficient liquid refrigerant is being fed to the evaporator. Suction pressure will be low. superheat will cause the case temperature to be too high. Correction: Before making any adjustments, verify proper bulb attachment, bulb location, and that the TXV is not incased in ice. Also, inspect the equalizer line location and that there are no restrictions to the equalizer line. Test the TXV to make sure it is working properly. Wrap the bulb with a warm rag and verify that TXV adjusts. If the TXV does not adjust, the TXV bulb and/or valve need to be replaced. Only an experienced technician should inspect the TXV for any dirt or foreign material & if present, replace the TXV. To attempt to adjust the superheat, turn the TXV adjustment screw counterclockwise until the proper superheat is achieved. Use caution not to back out the valve past the adjustment stop. When you take the superheat readings, the case should be at 1-2 F above the set point cut-out on the Carel. Observe the case for 2 additional cycles to verify proper adjustments were made. Zero Zone, Inc. 110 N Oakridge Dr, North Prairie, WI 53153-9792 800-247-4496 Zero-Zone.com 4 of 5

2.2) superheat: Too much refrigerant is being fed to the evaporator. Suction pressure can be higher than normal. Liquid can be returning to the accumulator or compressor (liquid slugging). Correction: Before making any adjustments, verify proper bulb attachment, bulb location, and that the TXV is not incased in ice. Also, inspect the equalizer line location and that there are no restrictions to the equalizer line. Test the TXV to make sure it is working properly. Wrap the bulb with a warm rag and verify that TXV adjusts. If the TXV does not adjust, the TXV bulb and/or valve need to be replaced. Only an experienced technician should inspect the TXV for any dirt or foreign material & if present, replace the TXV. To attempt to adjust the superheat, turn the TXV adjustment screw clockwise until the proper superheat is achieved. When you take the superheat readings, the case should be at 1-2 F above the set point cut-out on the Carel. Observe the case for 2 additional cycles to verify proper adjustments were made. 2.3) Hunting: Superheat and suction pressures fluctuate. The valve feeds too much refrigerant and then not enough refrigerant. System design and operating conditions may cause the system to hunt on occasion. If hunting is moderate and there is no floodback to the compressor, the system impact is minimal and no correction is needed. Verify proper bulb attachment, bulb location, and that the TXV is not incased in ice. Verify proper superheat setting on valve. 2.4) Standard operation of a TXV The TXV meters the liquid refrigerant flow to the evaporator based on the evaporation rate of the liquid refrigerant in the evaporator. The sensing bulb on the TXV reacts to the temperature of the gas refrigerant leaving the evaporator and can adjust the liquid flow entering the evaporator. The TXV ends up controlling the superheat in the evaporator to a predetermined setting/superheat. The remote bulb pressure is equal to the evaporator pressure plus the pressure provided by the superheat spring. 2.5) Replacing a TXV A water wet rag must be wrapped around the valve when brazing the valve. Failure to do so can cause excessive heat to the internals of the valve and powerhead causing the TXV to fail. Zero Zone Service Information Zero Zone Service Documentation & Support (including specs sheets & manuals): http://www.zero-zone.com/service.php Zero Zone Display Case Customer Service Tech: 262-392-1301 or Toll-Free 800-247-4496 Zero Zone Refrigeration Systems Customer Service Tech: 262-392-1302 or Toll-Free 800-708-3735 Zero Zone, Inc. 110 N Oakridge Dr, North Prairie, WI 53153-9792 800-247-4496 Zero-Zone.com 5 of 5