Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Similar documents
Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked HC Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked CC Series Compressor Unit R-410A Quik-Start Instructions

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

EarthLinked Freeze Protection Kit Model FP-1872 Installation Manual

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

EarthLinked Model DSH-1872 Desuperheater Kit

EarthLinked AVN Series Air Handlers Installation Manual

EarthLinked AFN Series Air Handlers Installation Manual

EarthLinked SD(A) Series

Heat Recovery Module Installation Manual for

AVS Air Handlers Prime PSC, PSD, PSDH and Classic SC, SD, and SDH

EarthLinked Series PHXTI Pool Heat Exchangers Installation Manual

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

EarthLinked STORAGE WATER HEATER / HYDRONIC BUFFER TANK MODELS GSTE-60, GSTE-80 & GSTE-119

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

MASS. MARITIME ACADEMY

Sporlan Valve Division Parker Hannifan/CIC Group

R.A.S.E.R.S System. Installation Guide

Residential Piping and Long Line Guideline

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS

Prime Series PSC Geothermal Heating and Cooling System

Temperature Control Kit Model HHK/CWK-1872

Classic Series SC Geothermal Heating and Cooling System

INSTALLATION MODULE XARIOS RANGE. UTC Climate, Controls & Security PROPRIETARY Rev B 29th mai 2013

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Platinum Split 4000 & Platinum Split 4000 Fully Ducted COLD WEATHER START KIT Installation Manual

COLD WEATHER START KIT Ceiling Mount 4000

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Classic Series SD Geothermal Heating and Cooling System

R Series Cooling Modules

EARTHLINKED GEOTHERMAL RENEWABLE ENERGY SYSTEMS MAINTENANCE GUIDE

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

Operation and Maintenance Manual

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Condensing Unit Installation and Operating Instructions

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

RCM Refrigerant Module

Prime Series PSDH Geothermal Heating and Cooling System

Service Step by Step Trouble-Shooting Check-List

INSTALLATION INSTRUCTIONS

MODEL URS-1: FACTORY RETROFIT PROGRAM

R Series Cooling Modules

Installation Manual BCS2000/3000

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Published by the California Building Performance Contractors Association

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

Condensing Unit Installation and Operating Instructions

INSTALLATION INSTRUCTIONS

an ISO 9001:2015 Registered Company

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

Installation Manual BCS 1000/1500

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

USING THE P-T CARD AS A SERVICE TOOL

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Technical Standards for the Air Conditioning and Heat Pump Professional BPI STANDARDS

Otherwise, you can continue reading the file on the following pages.

INSTALLATION INSTRUCTIONS

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

R Series Cooling Manual

Warm Case Troubleshooting Guide 9/18/2014

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

RSMSD Technical Guide

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

PL Series Premier Indoor Plenum Coils

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

C7 Series Split System Uncased Indoor Coils

EVAPORATOR COILS Installation Manual CCG, VCG, MCG M Series Coils

Air Cooled Condenser Installation and Operating Instructions

WineZone Ceiling Mount Ductless Split 15

Installation Instructions

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

HVAC Service Technicians Training Center

Transcription:

EarthLinked TXV Kit Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Air Handler Conversion 4 System Start-Up 21 TXV AVS-410-KIT (01/13) Copyright 2013 Earthlinked Technologies, Inc.

Disclaimer Proper installation and servicing of this EarthLinked Kit is essential to the Heating and Cooling Systems reliable performance. All EarthLinked systems and kits must be installed and serviced by an authorized, trained technician who has successfully completed the training class and passed the final examination. Installation and service must be made in accordance with the instructions set forth in this manual. Failure to provide installation and service by an authorized, trained installer in a manner consistent with this manual will nullify the limited warranty coverage for the system. EarthLinked Technologies shall not be liable for any defect, unsatisfactory performance, damage or loss, whether direct or consequential, relative to the design, manufacture, construction, application or installation of the field specified components. Earthlinked Technologies, Inc. 4151 South Pipkin Road Lakeland, Florida 33811 tel. 863-701-0096 fax 863-701-7796 info@earthlinked.com www.earthlinked.com CSI # 23 80 00 TXV AVS-410-KIT (01/13)

Pre-Installation Upon receipt of the TXV Kit carefully check the model number against the bill of lading. The TXV Kit is designed to improve performance of an R-410A EarthLinked air heating and cooling system utilizing an ETI AVS Series or NON-ETI direct expansion air handler.. The TXV Kit must be matched with the appropriately sized SC or SD series compressor unit and the air handler. See Figure 1 below for correctly matched components. COMPRESSOR UNIT NOMINAL CAPACITY, BTUH R-410A COMPONENT MATCHING TABLE TXV KIT MODEL AIR HANDLER MODEL AVS - -024 (24,000) TXV-024C AVS-1824-036 (36,000) TXV-036C AVS-3036-048 (48,000) TXV-048C AVS-4248-060 (60,000) TXV-060C AVS-6000-068 (68,000) TXV-072C AVS-6800* *Note: The AVS-6800 Air Handler is installed in the VERTICAL orientation ONLY. Figure 1. R410A Component Matching Table There are two steps to the field installation of the TXV Kit: 1. Air Handler conversion 2. System Start-Up TXV AVS-410-KIT (01/13) Page 3

Air Handler Conversion The TXV ASSEMBLY is illustrated in Figure 2. Familiarize yourself with the tube connections TO DISTRIBUTOR and FROM COMPRESSOR UNIT. Also note the EQUALIZER CONNECTION and the BULB TEMPERATURE SENSOR. These will be addressed in Figures 3.a. through 3o. Figure 2. TXV/CAV Assembly TXV AVS-410-KIT (01/13) Page 4

Remove the cabinet door(s) of the air handler, as appropriate. With the air handler in the vertical position, and facing the front of the air handler, follow the illustrations of Figure 3a through Figure 3o to install the TXV assembly. Figure 3a. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 5

Non-ETI Brand Air Handler Conversion Process Before ANY air handler or cased coil brand other than EarthLinked can be utilized with an EarthLinked heating and cooling system; the coil must meet the following requirement: Other brands of air handlers and coils can be utilized successfully with the EarthLinked system if they meet the above criteria, and are converted in the field, in accordance with the following procedure: Metering Device The metering device must be removed. If the distributor must be heated in order to remove the metering device, such as when the distributor and a TXV are brazed directly together (see Figure 3b), cool the feeder tubes at the distributor to prevent them from separating from the distributor during heating. (See the following paragraph, titled Distributor, before reconnection to the distributor.) If an actuator piston is utilized, it must be removed. Completely remove the actuator housing and run straight tube to the distributor inlet. If a TXV is present, it must be removed. Plumb the void with straight unrestricted tubing. Distributor The distributor is designed and manufactured with an additional pressure dropping orifice inside. It s called a nozzle. This nozzle must be eliminated. Often the nozzle is a separate piece inserted into the inlet cavity of the distributor and held with an easily removable snapring. Sometimes the nozzle is fabricated into the distributor body and must be drilled out. Drilling Out the Nozzle For system capacities of 1-1/2 to 3 tons, drill the nozzle out using a 5/16 drill bit. For system capacities of 3-1/2 to 6 tons, drill the nozzle out using a 3/8 drill bit. Hold the distributor firmly with a tool to prevent it from twisting. Do not allow drilled cuttings or debris to fall into the distributor. When the nozzle has been removed, an unobstructed view of the distribution tubes can be seen from the inlet side. When reconnecting the supply tubing to the inlet of the distributor, insert the supply tube into the drilled hole. Use a short 5/16 or 3/8 nipple to plumb into the drilled hole and make the transition to the supply line. Do not insert the tube so far that is restricts flow to the distribution tubes. Remember to cool the feeder tubes while nitrogen brazing to prevent them from separating from the distributor. Note: This will be required when nitrogen brazing the new inlet tube to the brass distributor. TXV AVS-410-KIT (01/13) Page 6

Distributor Orientation The distributor must be positioned vertically (i.e., the liquid must enter and leave the distributor vertically). Do not allow the distributor to be set at any angle other than straight up or down (see Figure 3c). Install the necessary tubing to connect to the distributor and extend through the cabinet port for the supply line connection. Once all refrigerant tubing has been connected and brazed to the EarthLinked System, the whole system may be pressure tested using nitrogen. Do not exceed 150 psig during the test. Figure 3b. Typical Air Handler/Cased Coil Before Conversion TXV AVS-410-KIT (01/13) Page 7

Figure 3c. Typical Air Handler/Cased Coil After Conversion TXV AVS-410-KIT (01/13) Page 8

Figure 3d. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 9

Figure 3e. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 10

Figure 3f. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 11

Figure 3g. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 12

Figure 3h. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 13

Figure 3i. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 14

Figure 3j. Air Handler Conversion TXV AVS-410-KIT (01/13) Page 15

Figure 3k. Thermal Bulb and Tubing Cabinet Suction Tube Hole TXV AVS-410-KIT (01/13) Page 16

Figure 3l. Horizontal Suction Line Options VERTICAL Air Handler Installation TXV AVS-410-KIT (01/13) Page 17

Figure 3m. Positioning the Thermal Bulb TXV AVS-410-KIT (01/13) Page 18

Figure 3n. Clamp the Thermal Bulb to the Suction Line Extension TXV AVS-410-KIT (01/13) Page 19

Figure 3o. Insulate the Thermal Bulb and Suction Line If it is necessary to change the installed position of the air handler in the field, a two step process is required: 1. The thermal bulb on the suction line extension must be re-located so the thermal bulb is on a HORIZONTAL section of the suction line extension, as shown in Figures 3m and 3n, with the thermal bulb located in the 3:00, 4:00, 8:00 or 9:00 o clock positions as illustrated. Wrap the thermal bulb with the insulation as shown in Figure 3o. 2. The distributor must be reoriented so that in its final installation position it is vertical (up or down) to ensure equal distribution of refrigerant to each of the coil circuits. Rotate the distributor 90º in steps, while simultaneously reconfiguring the coil feeder tubes to avoid kinking and ensure smooth refrigerant flow to the circuits. When completed, the reconfigured distributor and feeder tube arrangement should look similar to those in Figure 3c. TXV AVS-410-KIT (01/13) Page 20

System Start-Up Evacuation/Charging SC and SD Models Refer to Figure 4 and the following description: Evacuation and Initial Charge 1. Carefully vent the nitrogen charge from the compressor unit. 2. After installing and nitrogen brazing the HVAC system components and compressor unit service valves, turn the Service Valves to Full Open and pressurize the HVAC components to 150 psig with dry nitrogen and a trace of refrigerant. Valve off the nitrogen Tank from the HVAC system components and check joints with a sensitive Electronic Leak Detector to ensure they are sealed. Repair any leaks and re-test as appropriate. TXV AVS-410-KIT (01/13) Page 21

3. After venting the pressurized system, connect the Gage Block, Refrigerant Container and Hoses as shown in Figure 4. LP and HP valves are fully open. Both Service Valves are fully opened. 4. As illustrated in Figure 4, connect a good quality Digital Micron Gage to the Liquid Line Service Valve Access Port with an Isolation Hose/Valve. Connect a quality Vacuum Pump (at least 6 CFM capacity) to the Gage Block. 5. Connect the Refrigerant Hose from the Refrigerant Container to the Charging Port. 6. Initiate the system evacuation. Evacuate the system down to 230 MICRONS as read on the digital micron gage. After 230 microns has been achieved, turn off the LP and HP valves and turn OFF the vacuum pump. Reading the digital micron gage, the system pressure must not exceed 280 MICRONS WITHIN 5 MINUTES. If pressure rises to greater than 280 microns, open LP and HP valves, crack the refrigerant valve and allow just enough refrigerant into the system until 20 inches of Hg vacuum is read on the LP gage. Close the refrigerant valve, and initiate the evacuation process again and until the above conditions are met. TXV AVS-410-KIT (01/13) Page 22

Figure 4. Typical Evacuation & Initial Charge Set-up for SC and SD Compressor Models (SC model shown). 7. Close the LP and HP valves on the gage block. Disconnect the vacuum pump and the utility hose from the gage block. Isolate/protect the Digital Micron Gage from the liquid Earth Loop Service Valve until the initial refrigerant charge is complete. 8. Open the refrigerant container valve and inject liquid refrigerant into the charging port as shown in Figure 4. TXV AVS-410-KIT (01/13) Page 23

Item Comp. Unit 9. Charge with liquid refrigerant until 3 pounds of refrigerant per ton of system capacity, has entered the system. Liquid entering the system at the charging port goes directly to the system earth loops. It does not go to the compressor. Should the pressures equalize and prevent the intended charge from entering completely, terminate the process of initial charging. Note and document the amount of refrigerant. 10. When the initial refrigerant charge (see step 9 above) has entered the system, close the refrigerant container valve and disconnect the refrigerant hose from the charging port. Note and document the amount of refrigerant. 11. The system has now been initially charged. Disconnect the Digital Micron Gage. Final Charge It is critical to control the conditions under which the compressor unit operates while final charging the system. Final charging must be done in HEAT mode. Air Handler Systems If AIR heating is provided by one of the following DX air handler systems, as listed in Figure 5, the return air to the air handler during the final charging is to be maintained in the range of 70 F to 80 F. If necessary, the air can be warmed with electric supplemental heat in the air handler. (Shunt R to W2 at the terminal block.) Air Htg. Hydronic Htg. Air Clg Domestic Wtr. Htg. System Functions 1. SC Yes Yes Air heating and cooling 1 Air heating and cooling, domestic hot water 2. SC Yes Yes Yes by field installed desuperheater 1 Air heating and cooling, domestic hot water 3. SD Yes Yes Yes by desuperheater 1 Includes Desuperheater Model DSH-1872 to supplement water heating. Figure 5. Systems with DX Air Handlers TXV AVS-410-KIT (01/13) Page 24

Final charging is done in the HEAT mode as follows, with the charging set up described in Figure 6: 1. Continue measuring the refrigerant charge weight as shown in Figure 6. 2. Be sure that air entering the air handler is between 70 F and 80 F. 3. Close the HP valve. Then turn the system on in the HEAT mode. 4. Initiate final charging by opening the refrigerant container valve and the gage manifold LP valve to allow liquid refrigerant to enter the system SLOWLY as shown in Figure 6. The ACC will not allow liquid refrigerant to enter the compressor. 5. Adding liquid refrigerant will raise the liquid level in the ACC. Continue to add liquid refrigerant to the system until the liquid level has reached the middle sight glass, as shown in Figure 7. 6. When the liquid level is at the middle sight glass, as shown in Figure 7, turn the refrigerant container valve OFF. 7. When the system has run for 20 minutes (in HEAT mode), read the evaporating temperature and condensing temperature. The evaporating temperature can be read by attaching a thermocouple lead to the Earth Loop Vapor Line with electrical tape, then wrapped with ½ thick insulation. The condensing temperature can be read by attaching a thermocouple lead to the Air Handler/CC/HWM liquid line coming into the compressor unit with electrical tape, then wrapped with ½ thick insulation. Use an accurate temperature indicator. In Figure 8, locate the evaporating temperature on the horizontal axis. The corresponding condensing temperature reading should fall between the upper and lower parallel lines in Figure 8. The temperature profile in Figure 8 is valid for the air handler systems with an air flow of 400CFM per Ton. If condensing temperature is above acceptable range, the air flow is low. If condensing temperature is below the acceptable range, air flow is too high. Adjust air flow as appropriate. TXV AVS-410-KIT (01/13) Page 25

Figure 6. Typical Final Charge Set-up for SC and SD Compressor Units (SC Model shown). 8. Check the suction saturation temperature to verify that it is within ±3 F for the measured suction pressure. The suction temperature should be approximately 15 to 20 F lower than the local earth temperature. TXV AVS-410-KIT (01/13) Page 26

Figure 7. Charge at Middle Sight Glass Figure 8. EarthLinked Performance Parameters TXV AVS-410-KIT (01/13) Page 27

9. If the system is to operate in Heat Only mode, write the final refrigerant charge on the Warranty registration Card and on the inside of the compressor unit on the electrical diagram for future reference. This is the full system charge. For Heat Only Operation, do not adjust the Thermostat Expansion Valve (TXV) or the Cooling Assist Valve (CAV). These valves have been factory set and are not to be adjusted by the installer. The system is fully operational and needs no further adjustment. 10. If the system is to operate in Heat/Cool or Cool Only mode: While the system is still operating in HEAT mode, add refrigerant to the system to bring the liquid refrigerant level up to the top sight glass on the ACC. See Figure 9. Document the total weight of the refrigerant charge to the system. Figure 9. Charge at Top Sight Glass 11. The following additional steps in the system start-up process are required if the system is to operate in Heat/Cool or Cool Only modes. These following steps require that the system be run in COOL mode. TXV AVS-410-KIT (01/13) Page 28

Cooling Mode Start-Up Process These following steps are to be followed if the system is to be run in Heat/Cool or Cool Only. The process flow chart for these steps is illustrated in Figure 15. Be sure the cooling mode for the system is enabled. Start the system in COOL mode and run system until the suction pressure stabilizes. 1. Determine what the liquid refrigerant level is in the ACC by viewing it through the sight glasses. If the liquid level is at or above the lowest sight glass, wait 10 minutes and check it again. The liquid level should be dropping with time. Repeat the 10 minute cycle observations until the liquid is below the lowest sight glass or until 2 hours pass. After 2 hours, if the liquid level has not dropped below the lowest sight glass, call ETI Technical services at 1-863-701-0096. 2. When the liquid refrigerant level drops below the ACC lowest sight glass, observe the INLINE sight glass (not the ACC sight glasses) for the status of the refrigerant flow. There are three possibilities: A. INLINE sight glass is CLEAR: As illustrated in Figure 10, a clear sight glass means the refrigerant flow is liquid. Remove 1 pound of refrigerant from the system, wait 10 minutes, and observe again. Continue this until bubbles appear in the sight glass. Figure 10. Clear-Inline Sight Glass B. INLINE sight glass has MANY BUBBLES: This is illustrated in Figure 11. Wait 10 minutes and observe the sight glass again. If many bubbles are still present, repeat the 10 minute wait cycle until the bubbles become few, or you have waited 2 hours. After a 2 hour wait, and many bubbles still exist in the sight glass, the process is done. No further adjustment in cool mode is required, and the system is operational. Figure 11. Many Bubbles-Inline Sight Glass TXV AVS-410-KIT (01/13) Page 29

C. INLINE sight glass has FEW BUBBLES: This is illustrated in Figure 12. When this condition exists, the next steps are to check the superheat and adjust the TXV as necessary. Figure 12. Few Bubbles-Inline Sight Glass 3. The TXV is to be adjusted to provide 10ºF to 15ºF superheat while running in cooling mode. The first step is to utilize the access port and LP gage in Figure 13 to measure suction pressure. Next, apply a thermocouple at the compressor suction port as shown in Figure 13 by attaching the thermocouple lead with electrical tape, and wrapping with ½ thick insulation. Figure 13. Superheat Measurements for SC and SD Compressor Units (SC Model shown). TXV AVS-410-KIT (01/13) Page 30

4. Using an accurate temperature indicator, read the suction temperature at the compressor suction port. Read the suction pressure at the access port on the LP gage. 5. Enter the Pressure-Temperature Table in Figure 14 and for the suction pressure read on the LP gage, determine the saturation temperature (evaporating temperature) from the chart, interpolating if necessary. SATURATION TEMPERATURE ( F) SUCTION PRESSURE (psig) SATURATION TEMPERATURE ( F) SUCTION PRESSURE (psig) -20 26.1 70 199.2-15 30.8 75 216.1-10 35.9 80 234.0-5 41.5 85 253.0 0 47.5 90 273.0 5 54.1 95 294.1 10 61.2 100 316.4 15 68.8 105 339.9 20 77.1 110 364.6 25 86.0 115 390.5 30 95.5 120 417.7 35 105.7 125 446.3 40 116.6 130 476.3 45 128.3 135 507.6 50 140.8 140 540.5 55 154.1 145 574.8 60 168.2 150 610.6 65 183.2 Figure 14. Pressure-Temperature for R-410A 6. To determine the degrees of Superheat, subtract the saturation temperature from the suction temperature read at the compressor suction port thermocouple. The difference in the temperatures is the superheat. (Superheat, F) = (Suction Temp., F) - (Saturation temp., F) 7. If superheat is greater than 20 F, decrease the superheat by adjusting the setting on the TXV in the counter clockwise direction. 8. See Figure 15 and follow the guidelines to bring the superheat into the 10 0 F to 15 0 F range. When superheat is adjusted to within this range, the system is fully operational and needs no further adjustment. 9. Document the net weight of the refrigerant charge in the system. Net weight is equal to the final refrigerant charge minus refrigerant removed from the system. Write it down on the Warranty Registration Card and inside the compressor unit on the electrical diagram, for future reference. This is the full system charge. TXV AVS-410-KIT (01/13) Page 31

Figure 15. Cooling Mode Start-Up Process TXV AVS-410-KIT (01/13) Page 32