CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

Similar documents
Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results

Practical problems of applying performance-based structural fire engineering in building design

Fire Scenarios Assessment

DS/EN DK NA:2011

Research on fire protection methods and a case study "Futurum"

This document is a preview generated by EVS

FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA

Fire Safety Concept Hotel Jumeirah

Fire Severity for Structural Design

A tool to design steel elements submitted to compartment fires - OZone V2 Part 2: Methodology and application

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

Procedure for the Approval of New Fire Detection and Alarm Technologies

Travelling Fires for CFD

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Eurocode 9 Design of aluminium structures

Effect of Foundation Embedment of PWR Structures in SSI Analysis considering Spatial Incoherence of Ground Motions

Current Research at University of Naples

WG 1: Fire Engineering V. Strategy and guidelines for damage prevention Fire design in Europe

This document is a preview generated by EVS

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

IDENTIFICATION OF NEEDS FOR IMPROVED FIRE PROTECTION BY USE OF THE EUROCODES

CEN standardization work on refrigerating systems, especially standard EN 378

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

This document is a preview generated by EVS

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES

CE marking of fire-resistant doors the right way!

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Fire Safety Fire Resistant Building Components

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES

2C10 Design for Fire and Robustness Timisoara,

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

Analysis to speed up of the start-up of steam boiler OP-380

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

This document is a preview generated by EVS

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

ECONOMIC JUSTIFICATION FOR SPRINKLER SYSTEMS

fischer Fireproof pipe installation Certified fire protection for safe fixings. MLAR MLAR Fire resistance classification R 120 according DIN EN

BUSINESS PLAN CEN/TC 142 WOODWORKING MACHINES SAFETY EXECUTIVE SUMMARY

1.1. Design fires for structural engineering

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fire Safety Concept Hotel Jumeirah

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

Heat pump supplemental heating system for motor vehicles

Y. ORMIERES. Fire risk analysis method for nuclear installations

Technical Bulletin. Fire protection requirements for cabling systems MLAR 03/2000 MDBR 12/1998. Date: 08/2006

FLIGHT UNLOADING IN ROTARY SUGAR DRYERS. P.F. BRITTON, P.A. SCHNEIDER and M.E. SHEEHAN. James Cook University

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

Edinburgh Research Explorer

Development of Seismic-induced Fire Risk Assessment Method for a Building

Mobile road construction machinery Safety- Part 1: Common requirements. Mobila väganläggningsmaskiner - Säkerhet - Del 1: Allmänna krav

ILNAS-EN 61649:2008. Weibull analysis. Analyse de Weibull. Weibull-Analyse

ON THE USE OF FIRE BRIGADE STATISTICS FOR STRUCTURAL FIRE SAFTY ENGINEERING

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

MEDIUM-DENSITY HOUSING # 7. Fire safety

9-1. Introduction to fire design

Foundations of Fire Safety in Civil Engineering

Fieldbus Non-Incendive Concept takes FISCO into Zone 2 and Division 2 hazardous areas. Phil Saward

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

WHITE PAPER.

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Fixed fire protection solutions

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Seasonal Performance and Exergy Analysis of Multi-Function Heat Pump Units

This document is a preview generated by EVS

Single Market : regulatory environment, standardisation and New Approach Pressure equipment, medical devices, metrology M/327

4 August Islington Fire Protection Transpower NZ Limited

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

fischer Fireproof pipe installation Certified fire protection for safe fixings. MLAR MLAR R 30

Impact of Air Distribution on Heat Transfer during Night-Time Ventilation

Case Study 1 Underground Car Park

Considerations in the Design of Smoke Management Systems for Atriums

DEPTH OF EMBEDMENT OF A SHEET PILE WALL

MATEC Web of Conferences

PUBLIC SUMMARY REPORT OF THE EGOLF EN 13823

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

BUSINESS PLAN CEN/TC 250 STRUCTURAL EUROCODES EXECUTIVE SUMMARY

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

EFFECT OF COMPACTION ON THE UNSATURATED SHEAR STRENGTH OF A COMPACTED TILL

FAÇADE FIRE TESTS Towards a new European standard method

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Establishing the Risk Basis of Building Size Limits

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

Sponsors: CERIB. Dr. Guillermo Rein. Department of Mechanical Engineering

Induction Billet Heaters with Enthalpy Controlled Zone Heating

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

TEHRAN LONG TERM URBAN RAIL PLAN

Transcription:

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN ABSTRACT P. Schaumann and S. Hothan University of Hannover, Institute for Steel Construction Appelstraße 9a, D-3167 Hannover, Germany This paper deals with the application of the time-equivalence-method in fire safety design. The presentation of the German regulations for industrial buildings identifies the advantages of this simplified and easy-to-use design method. Active fire protection measures, such as automatic fire alarm or sprinkler systems may be taken into account when the required fire resistance time of structural members is determined. Thus, unprotected steel structures may be used in industrial buildings under certain conditions. In order to check the range of validity, a number of calculations have been carried out using the time-equivalence-method and alternative methods. The research concerns unprotected and protected steel members. The results demonstrate that the calculation of the maximum steel temperature on the basis of the equivalent time of fire duration may only be recommended for protected steel members. Nevertheless the time-equivalence-method embedded in a probabilistic safety concept could be excellently suitable to access the required fire resistance of structural members allowing compensation of passive fire protection by active protection measures. KEYWORDS Structural fire design, steel members, time-equivalence-method, industrial buildings BASIC IDEA OF THE TIME-EQUIVALENCE-METHOD The time-equivalence-method creates a relation between the effects of heating in structural members caused by natural fires and those caused by the ISO fire curve. Concerning steel structures the equivalent time of fire exposure defines that time of ISO fire exposure, which causes the same maximum steel temperature as the corresponding natural fire. The definition of the equivalent time of fire exposure is illustrated in Figure 1. Temperature ( C) 9 8 7 6 5 4 3 2 1 Natural fire t e ISO fire max θ Gas temperature Steel temperature 5 1 15 2 25 3 Time (min) Figure 1: Equivalent time of fire exposure t e

GERMAN FIRE DESIGN CONCEPT FOR INDUSTRIAL BUILDINGS The German fire design codes for industrial buildings are based on the time-equivalence-method. This method is embedded in a probabilistic safety concept taking into account the actual fire load, the actual number of storeys, the relevant areas for heat exhaust and different additional fire safety measures like fire alarms systems, plant fire brigades or sprinklers. The regulatory frame is given by two codes: the German standard DIN 1823-1 (1998) and the German Guideline for Industrial Buildings (Guideline for Structural Fire Protection of Industrial Buildings (2)). The contents of these codes are summarised hereafter. In DIN 1823, an analytical method is provided for the evaluation of the required equivalent time of fire exposure. This value leads to the determination of a so-called fire protection class, which is the link to the Guideline for Industrial Buildings. In particular, the required fire resistance class of structural members and the maximum size of compartements are specified in this code. Figure 2 gives an overview on the contents of the fire design regulations for industrial buildings. DIN 1823 fire load building properties heat exhaust fire detection and alarming plant fire brigade sprinklers or the like required fire resistance class fire protection class fire resistance class of structural members maximum size of compartments escape routes water supply etc. Guideline for Industrial Buildings Figure 2: Connection between DIN 1823 and the Guideline for Industrial Buildings In the Guideline for Industrial Buildings, three fire safety design approaches are provided on three different levels. The first level comprises simple design tables, which contain the maximum size of the compartment in dependency of the number of storeys, the fire safety category and the fire resistance class of the structural members. The fire safety category is a special feature taking into account measures like fire alarms systems, plant fire brigades or sprinklers; it is explained in Table 1. This level needs no explicit evaluation of the required equivalent time, which is included in the table. Thus, no determination of the actual fire loads is needed. According to Table 1, unprotected steel structures may be used for single storey industrial buildings up to maximum area of 18 m 2 without special measures for fire alarm or fire fighting. If an automatic sprinkler system is installed, the maximum area may reach 1 m 2. On the second level, the evaluation method given in DIN 1823 is used on the basis of actual fire loads in the building. This method for calculating the equivalent time of fire exposure is equal to the method given in Annex E of EC1-2-2 (ENV 1991-2-2 (1995)). The characteristic value of the equivalent time of fire exposure is given by Eqn. 1

TABLE 1 MAXIMUM AREA (m 2 ) OF FIRE COMPARTMENT IN SINGLE STOREY INDUSTRIAL BUILDINGS Fire Resistance Class Safety category of Load Bearing Members K 1 without special measures for fire alarm and fire fighting R R 3 18*) 3 K 2 with automatic fire alarm system 27*) 45 K 3 with automatic fire alarm system and plant fire brigade 32 to 45*) 54 to 75 K 4 With sprinklers or the like 1 1 *) minimum area of heat exhaust openings in the roof 5 %, maximum width of building 4 m t e,k = q with q f,k f,k k (MJ / m b 2 w ) f (min) fire load density per unit floor area 2 k b (min m / MJ) conversion factor w f ( ) ventilation factor (1) The actual design value of the fire load density normally has to be estimated by experts working as fire safety consultants in co-ordination with the authority having jurisdiction. The conversion factor takes into account the thermal properties of the enclosure of the fire compartment. It ranges between 2.4 k b.7 (min m MJ). The factor k b depends on the thermal property b = ρ c λ (J/(m 2 s 1/2 K)) of the enclosure, including unit mass, specific heat and thermal conductivity of the enclosure material. The ventilation factor takes into account the ventilation conditions of the compartment, which mainly depend on vertical and horizontal openings. It ranges between.35 and 3.. The equivalent time of fire exposure t e is embedded in a probabilistic safety concept. Multiplication of t e with two factors gives the required time of fire resistance req t F (see Eqn. 2). The required fire resistance class of the structural elements is specified in dependency of the required time of fire resistance in Table 2. req t F = t e,k γ α L (min) with γ ( ) ( 1. γ 1.6) α L (.342 α 1.) ( ) L safety factor depending on the floor area of the fire compartment and the number of storeys additional factor concerning active measures of fire safety such as automatic fire alarm or sprinkler systems. TABLE 2 SPECIFICATION OF THE REQUIRED FIRE RESISTANCE CLASS Required Time of Fire Resistance (min) (2) Required Fire Resistance Class for Structural Elements < req t F 15 no requirements 15 < req t F 3 R 3 3 < req t F 6 R 6 6 < req t F R 9

It should be emphasised that no fire resistance requirements must be met for structural members if the required time of fire resistance is less than 15 minutes. That means that unprotected steel construction may be used. The level three design approach of the Guideline for Industrial Buildings may be identified as the performance-based option of the code. Fire engineering methods may be applied for evaluating the effects of fire in the building as well as the heating and the load bearing behaviour of the structure under elevated temperatures. APPLICABILITY OF THE EQUIVALENT-TIME-METHOD Objective In the context of the structural fire design for steel structures ruled by EC3-1-2 (ENV 1993-1-2 (1995)) the question arises, whether the time-equivalence-method is a suitable method for determining the maximum steel temperatures under natural fires. This question defines the objective of the investigations presented hereafter. A positive result would have two decisive advantages for the simplification of assessment methods. First, the development of gas-temperatures in the compartment in natural fires could be taken into account using a very simple approach related to the ISO-fire curve. Second, the recognised solutions for the heating of unprotected and protected steel sections given in EC3-1-2 may be applied. Method of Investigation and Parameters of the Study To check to applicability of the equivalent-time-method, maximum steel temperatures calculated according to three different approaches for natural-fire-curves are compared to each other. The three methods of taking natural-fire-curves into consideration are: EC1-2-2 Annex E The natural-fire-curve is substituted by ISO-fire curve with an equivalent time t e according to Eqn. (1). The natural-fire-curve is given by a parametric gas-temperature-time-curve according to Annex B of EC1-2-2. The natural-fire-curve is calculated by the computer model, which is based on a one-zone heat-balance-method. See Cadorin, J. f. and Franssen, J. M. (2). Applying the first method (EC1-2-2 Annex E), the equivalent time t e is given directly. In case of the other two methods the equivalent time t e is determined following the procedure given in Figure 1. H L B L / B / H = 5 / 5 / 2.5 [m] b Opening factor: O = A h / v A t Figure 3: Properties of fire compartment (basic scenario) h A v : area of vertical openings A t : total area of enclosure Fire load density per unit floor area: Q f,k = 5 MJ/m² (Office ) Enclosure of fire compartment: concrete,5 b = 1918 J /(m² s K)

Fig. 3 shows the basic properties of the fire compartment chosen for this study. For the steel element exposed to natural-fire-curves a section factor of A m /V = 15 m -1 has been chosen. Parameters varied in this study are the opening factor O ranging between.2 and.2 m.5 type of structural fire protection: unprotected and box-protection (R 3) comprising a 12.5 mm gypsum board. Results and Discussion As an example of the temperature development of an unprotected steel section, Figure 4 shows the curves for the three methods of taking natural-fire-curves into account. In this example the opening factor was chosen to O =.5 m.5. For this scenario the equivalent time t e has been calculated to 31 min according to Eqn. 1. The main difference between the ISO-fire-heating and the temperature-timecurves calculated for real natural-fire-curves is that there is no cooling phase in the ISO-curve. The steel temperatures caused by the ISO-fire-curve are higher than those according to and EC1-2-2 Annex B. The steel temperature-time-curves according to and are similar but not congruent although they are both natural-fire-curves according to the same scenario. In particular, the maximum steel temperature of the Ozone calculation is higher in this example. 12 O =.5 m.5 θa ( C) 1 8 6 4 2 A m /V=15 m -1 ISO fire Figure 4: 2 4 6 8 1 12 Fire duration (min) Temperature-time-curves of unprotected steel sections for different assumptions concerning the gas temperature The maximum steel temperatures for a variation of the opening factor in the basic scenario are shown in Figure 5. The corresponding equivalent times of fire exposure can be taken from Figure 6. For instance the maximum steel temperature due to the model for the opening factor O =.5 m.5 can be found as 82 C in Figure 5. The respective equivalent time of fire exposure can be seen in Figure 6 as 33 minutes. In addition to the maximum steel temperatures for and EC1-2-2 Annex B the recalculated maximum steel temperatures for the analytical method of EC1-2-2 Annex E are shown in Figure 5. These temperatures are calculated by inverting the method illustrated in Figure 1. The analytical method of EC1-2-2 Annex E is limited to maximum vertical openings of 25 % of the compartment s floor area. For the basic scenario this limit is reached at an opening factor of O =.1 m.5. Nevertheless the results for opening factors higher than.1 m.5 are also presented in order to compare the shape of the curves. There are noticeable differences between the maximum steel temperatures especially for small opening factors. For an opening factor of.2 m -1, the maximum steel temperatures vary between 51 C () and 92 C (EC1-2-2 Annex E). For increasing opening factors between.2 and.8 m.5, the curve of Annex B shows an increasing

trend while the maximum steel temperatures according to Annex E in general decrease. The maximum steel temperatures of the model show an increasing trend between the opening factors.2 and.5 m.5 and for higher opening factors, they decrease continuously. Maximum θa ( C) 1 9 8 7 6 5 4 3 2 1 A m /V=15 m -1 EC1-2-2 Annex E EC1-2-2 Ann. E mod..2.5.8.11.14.17.2 Opening factor (m.5 ) Figure 5: Maximum temperatures of unprotected member depending on the opening factor (basic scenario) The respective curves for the equivalent time of fire duration (see Figure 6) show the same characteristics as the curves of the maximum steel temperatures. A proposal to fit the trend of the curve of Annex E to that of Annex B was made by Schleich, J. B. (1996). Therefore the equivalent time of fire duration is multiplied with 13,7 O (O = opening factor). The results are continually increasing curves for max θ a and t e identified by EC1-2-2 Ann. E mod. (see Figure 5 and 6). 5 4 A m /V=15 m -1 EC1-2-2 Annex E EC1-2-2 Ann. E mod. te (min) 3 2 1.2.5.8.11.14.17.2 Opening factor (m.5 ) Figure 6: Equivalent time of fire exposure of unprotected member depending on the opening factor (basic scenario) It can be stated that for unprotected members concerning the different methods, the resulting equivalent times of fire duration are very different. Concerning the described results, the applicability of the time-equivalence-method on unprotected steel members located in small fire compartments must be challenged.

In the following the results for a protected member are presented. The protected steel section features a box protection with gypsum boards. The properties of the board material are: unit mass 2 = 945kg m λ =.2 W m K and specific heat = 17J kg K. ρ, thermal conductivity ( ) p p Figure 7 shows the maximum steel temperatures of the protected member. The corresponding equivalent times of fire exposure are shown in Figure 8. The differences between the maximum steel temperatures of the different curves are not higher than 1 C for any opening factor. In general the computer model produces the highest maximum steel temperatures and the method of EC1-2-2 Annex E the lowest. The curve of ranges between them except for very small opening factors (O =.2 m.5 ). All curves show a decreasing trend for increasing opening factors and they are developing nearly parallel to each other. Maximum θa ( C) 6 5 4 3 2 1 12.5 mm board A m /V=15 m -1 EC1-2-2 Annex E.2.5.8.11.14.17.2 Opening factor (m.5 ) Figure 7: Maximum temperatures of protected member depending on the opening factor (basic scenario) Concerning the corresponding equivalent times of fire exposure, the curves show the same characteristics as the temperature curves (see Figure 8). The maximum difference between the t e - curves is about 14 minutes for a very small opening factor of O =.2 m.5. c p 6 5 4 12.5 mm board A m /V=15 m -1 EC1-2-2 Annex E te (min) 3 2 1.2.5.8.11.14.17.2 Opening factor (m.5 ) Figure 8: Equivalent time of fire exposure of protected member depending on the opening factor (basic scenario)

It can be assumed that for protected steel members the time-equivalence-method produces realistic results concerning the maximum steel temperatures. CONCLUSION This paper deals with the presentation of the German fire safety design regulations for industrial buildings based on the time-equivalence-method. Active fire protection measures, such as automatic fire alarm or sprinkler systems may be taken into account when the required fire resistance time of structural members is determined. Thus, unprotected steel structures may be used in industrial buildings under certain conditions. In order to check the range of validity, a number of calculations have been carried out using the time-equivalence-method and alternative methods. The research concerns unprotected and protected steel members. The results demonstrate that the calculation of the maximum steel temperature on the basis of the equivalent time of fire duration may only be recommended for protected steel members. For unprotected steel elements the results are too unfavourable. Nevertheless it should be tried to transfer the time-equivalence-method to other types of buildings and use. For this purpose the method has to be embedded in a probabilistic safety concept allowing compensation of passive fire protection by active protection measures. REFERENCES Cadorin, J.-F. and Franssen, J.-M. (2). The One Zone Model Ozone- Description and Validation Based on 54 Experimental Fire Tests, University of Liege, Belgium. DIN 1823-1 (1998). Structural fire protection in industrial buildings Part 1: Analytically required fire resistance time, Beuth Verlag, Berlin, Germany (in German). DIN 412-2 (1977). Fire Behaviour of Building Materials and Building Components; Building Components; Definitions, Requirements and Tests, Beuth Verlag, Berlin, Germany (in German). ENV 1991-2-2 (1995). Eurocode 1 Basis of design and actions on structures, Part 2-2: Actions on structures Actions on structures exposed to fire, CEN, Brussels, Belgium. ENV 1993-1-2 (1995). Eurocode 3 Design of steel structures Part 1-2: General rules Structural fire design, CEN, Brussels, Belgium. German Guideline for Structural Fire Protection of Industrial Buildings (2). Committee Building Supervisory of ARGEBAU, Germany (Muster-Richtlinie über den baulichen Brandschutz im Industriebau - M IndBauRL, Fachkommission Bauaufsicht der ARGEBAU, Fassung März 2, in German). Schleich, J.-B. (1996). Eurocode 1 Part 2-2: Actions on structures exposed to fire, IABSE-Colloquium, Basis of design and actions on structures, Delft. IABSE, 74, 71-81.