Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

Similar documents
TOTAL SYSTEM EFFICIENCY: AN INTRODUCTION TO CONDENSING BOILERS. David Grassl PE Mechanical Engineer Principal

Trials Tribulations & Rewards High T Heating Systems

Medium Mass Boilers. Maxim Power VT

CLEARFIRE HIGH-MASS CONDENSING FIRETUBE BOILER 500 TO 2,000 MBH

Now Available with PVC & Polypropylene Vent Configurations

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

ULTRA HIGH EFFICIENCY CONDENSING BOILERS MILLION BTU/HR

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

CONDENSING, MODULATING, HOT WATER SUPPLY, POOL, AND HYDRONIC HEATING BOILERS

Using ECM Smart Circulator Pumps in Primary Pump Applications in Hydronic Systems

TOTAL SYSTEM EFFICIENCY: CONDENSING BOILER SYSTEM MYTH BUSTING. David Grassl PE Mechanical Engineer Principal

CCLEARFIRE CONDENSING FIRETUBE BOILER DESIGNED FOR MAXIMUM HYDRONIC SYSTEM EFFICIENCY 500 TO 3,300 MBTU

The electrical wattage needed by the circulator is:

Application of Air Source Variable Refrigerant Flow in Cold Climates

Presented by Steve Connor August 26, Boiler Choices: The What, When & Why

Ohio Energy. Workshop HH. Strategies & Technologies to Improve the Boiler Room Efficiency. Wednesday, February 21, p.m. to 3:15 p.m.

Best Practices for Condensing Boilers

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

clearfire Large capacity condensing boilers 4,000 to 12,000 MBTU/hr

TANKLESS WATER HEATER HEATING SOLUTIONS

HYDRONIC SOLUTIONS. More than just hydronic boilers, we offer the most efficient integrated hydronic solutions on the market.

CONTENTS. B. System Design and Performance Requirements

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

90% Efficiency without Boiler Replacement TRUE GREEN SOLUTIONS NEW. Patent Pending. EcoFlex 90 + System Modulating Fan-Powered Economizer

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

Massachusetts Energy Efficiency Partnership. 5. High Efficiency Systems for Large Boilers

Summary of 60-Day Notice: Heating Efficiency

Versa- Hydro. up to 96% Efficient

The world s standard in efficiency. CBEX FIRETUBE

Sizing water heaters to provide sufficient hot water efficiently LEARN THREE METHODS YOU SHOULD BE USING TO DESIGN EFFICIENT SYSTEMS

CONDEXA PRO EXCELLENCE AND VERSATILITY

Outdoor Reset Control Theory FULL versus PARTIAL reset

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

- Essay Control Functions and Benefits

THERMAL ICE STORAGE: Application & Design Guide

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

Domestic Hot Water Heaters and Boilers FTIIIC-6

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12

FTIIIC-10. Domestic Hot Water Heaters and Boilers

KN-SERIES GAS-FIRED DIRECT VENT CAST IRON BOILERS KN-6 KN-10 KN-20

BTEC Standard

Seasonal Efficiency Longevity Part-Load Efficiency Condensing Operation Fast ROI MODULEX BOILERS MLX-1060 MLX-909 MLX-757

Residential Water Heating

Technical Document Condensing hot water boilers

RTC. Stainless Steel Condensing Floor Standing Boilers Technical data sheet. High efficiency commercial heating

A Treatise on Liquid Subcooling

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Energy-Efficiency Options for Residential Water Heating

The ultimate in air handling units: directly and indirectly fired

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

September 11, 2012 Ministry of Economy, Trade and Industry

The ultimate in air handling units: directly and indirectly fired

An Introduction to True Modular Boiler Systems

Intelligent ways to save fuel heating your Commercial building. Caravan Modular Boiler System. CHS Multiple Boiler System

Accomplish Maximum Green Results in Commercial Buildings #

FXLF-4. High Efficiency Water Heaters and Boilers

PROFIRE -E SERIES BURNERS

The ultimate in air handling units: directly and indirectly fired

Applications and Piping Strategies for Condensing Boilers - Introduction

Cclearfire HIGH EFFICIENCY, COMPACT CONDENSING BOILER 500-3,300 MBTU

Socialized Efficiency

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Benchmark. High-Efficiency Boilers. AERCO.com

The Economics of Drying.

Ve r s a - Hyd ro. 96% Efficient. The cost effec t i ve. ersa-hydro

HCLEARFIRE. High-efficiency, modular steam boiler HP

The ultimate in air handling units: directly and indirectly fired

Variable Refrigerant Flow (VRF) Systems

Considerations for INDUSTRIAL COMBUSTION

Radiant Mixing Block

7 sizes: 55,000, 80,000, 110,000, 155,000, 199,000, 285,000 & 399,000 Btuh. One of a kind design from the inside, out!

GAS CONDENSING TECHNOLOGY

MODEL M5M. High-Efficiency Packaged Watertube Boiler MMBTU

Hot Water Makers. Efficiency at its Best

Energy Conservation. Chapter 16

STATE SUPER HIGH EFFICIENCY Up To 96% Thermal RESIDENTIAL PREMIER POWER-VENT MODELS

Greenstar The World's Best Selling Condensing Boiler System

A Manufacturer s Guide to High Performance CSA P.9 Tested Combos

New Features RIELLO ARRAY. v2.0. High Efficiency Condensing Boiler MBH.

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

Highlights MBH 95% efficiency ENERGY STAR Qualified Low NOx emissions Space-saving design. 95% Efficient. Modulating Technology

A TRUE GAME CHANGER - The Vortex Heat Recovery Center CONDENSING EFFICIENCIES FOR TRADITIONAL BOILERS & HEATERS

A M E M B E R O F T H E K E N D A L L G R O U P

Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1

HIGH EFFICIENCY COMMERCIAL BOILERS

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Don t Turn Active Beams Into Expensive Diffusers

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Qualifies for up to $ 1500 Energy Tax Credit! CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES

Air Conditioning Clinic

Sustainable Techniques in Refrigerated Space

The Brute MagnaTech. A Perfect Balance of Size, Form, and Function. Commercial, High Efficiency Condensing Boiler and Volume Water Heater

HEAT EXCHANGER FORMULAS & EXAMPLE

CONTROLLED CHILLED BEAM PUMP MODULE

ADVANCED HEATING AND HOT WATER SYSTEMS

ecodry Figure 1 - Process Diagram ecodry B General Process Description

FXLF-9. High Efficiency Water Heaters and Boilers

The EnduroTi HIGH MASS. Superior Construction: COMMERCIAL CONDENSING BOILER. Stainless Steel Titanium Blend. 10 : 1 Turndown Ratio

Up To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY

Transcription:

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014 Today, hydronic boilers are producing greater efficiencies than previously thought possible, all due to the advancements of condensing technology. It is the science behind condensing that many people do not take the time to understand, which can lead to misunderstandings and the perpetuation of myths. One of the largest areas of confusion concerns high turndown. Several manufacturers promote ultra-high turndown as the solution to efficiently meeting low seasonal, partial load demands. By understanding condensing boiler operation and the basics of thermodynamics, one will realize that an extremely high-turndown burner on a hydronic condensing boiler does not promote the highest system efficiency, but actually can make the system less efficient. Conventional vs. Condensing Operation The way systems are engineered and operated today varies from the way they were designed in the past. Most heating systems were steam, not hydronic. Steam system operation is very different from a hydronic system, so the two should not be viewed in the same way. Hydronic systems provide many advantages to reduce energy consumption; however they must be operated and controlled properly to ensure a system achieves high efficiency. Below is an example system in which several key factors are presented. Observe the effect each factor plays on operational efficiency. This exercise will help you make an informed decision about proper equipment selection. Selecting the right equipment will provide an efficient, reliable system that has the lowest lifecycle cost of operation. Operating Conditions and Assumptions System set point = 130 F Constant speed pumping 40 F design delta T - Retur n temperature target of 90 F Single boiler system = 1500 MBH input 94% ef ficiency when condensing = 1410 MBH output 88% ef ficiency when not condensing = 1320 MBH output Excess air levels at normal operation = 5% O 2 (30% excess air) Fuel = Natural gas Best non-condensing ef ficiency that can be obtained is 88% Turndown comparison = a 5:1 turndown boiler vs. a 20:1 turndown boiler with the same nominal high fire efficiency. 1

Understanding the Flue Gas Dew Point It is widely understood that in a traditional steam boiler and with high-temperature firetube hot-water boilers, higher excess air is required at low fire. This ensures clean, safe, stable combustion at lower firing rates but also results in lower combustion efficiency at these rates. Since these boilers are larger and commonly operate at higher firing rates, this was considered a good trade-off. FG Dew Point Temperature F %O2 (Excess Air) vs. Flue Gas Dew Point (Natural Gas) 140 200% 135 180% 130 160% 125 140% 120 120% 115 100% 110 80% 105 60% 100 40% 95 20% 90 0% 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 Dew Point (F) X Air (%) Graph illustrates the effect of excess air with high turndown on flue gas dew point. With today s hydronic condensing boilers, the rules have changed. New premix burner technology has led to the development of burners that provide a proportionate air:fuel ratio across the entire firing range and provides a reasonable turndown. This allows for no loss in combustion efficiency and contributes to what is referred to as an inverse efficiency characteristic, wherein the condensing boiler can be more efficient at low fire rather than at high fire. Moving beyond a reasonable turndown, compromises must often be made. The compromise is that excess air must be added at higher turndown to protect the premix burner materials from overheating while still ensuring clean and stable combustion. Remember, during normal combustion, adding excess air reduces efficiency. While adding excess air lowers combustion efficiency, the effects are even more detrimental when operating condensing boilers. Because condensing boilers extract latent energy from the flue gas, we need to look at the impact excess air has on the flue gas dew point. The boiler s return water operating temperature relative to this flue gas dew point is the most essential factor in achieving condensing efficiency (greater than 90%). As the excess air level increases, the flue gas dew point decreases. A normal excess air level for a natural gasfired condensing boiler is around 5% O 2 (or 30% excess air). This correlates to a flue gas dew point of 127 F. Therefore, in order to begin to achieve condensing performance, the return water temperature must be below 127 F. If additional excess air is added with the goal of improving turndown, notice what happens. By increasing the excess air level as required to 10% O 2 (or 80% excess air) in this example, the flue gas dew point now drops to 117 F. In order to achieve the same level of condensing performance, the return water must be below 117 F. Condensing is the process by which boilers extract the latent heat that is in the combustion gas. So the lower the return water temperature is below the flue gas dew point, the more condensing that can occur and the higher the efficiencies can be. Return water temperature is not the only factor, but does play a major role in the boilers ability to extract the available latent heat energy. Unlike steam systems, hydronic systems rely on mechanical pumping and since the boilers must maintain a constant system supply water temperature, the return water temperature will increase at reduced firing rates. It is critical to understand that excess air must be increased to achieve the ultra-high turndown and the result is that the flue gas dew point is decreased, making it more difficult, if not impossible, to condense. By trying to save energy with the ultra-high turndown burner, we actually 2 move further away from the flue gas dew point, which

dramatically decreases a condensing boiler s efficiency. Let s take a closer look. Load Matching with Hydronic Pumping Contrasting steam systems, wherein the steam flow is self-motivating, hydronic systems rely on circulating pumps to deliver heat energy to the load. The delivery of heat energy or the energy output ( T) is a function of the energy input and the pump flow rate. The first law of thermodynamics is: Energy in = Energy out We can use this law to demonstrate how changes in boiler input energy as a result of ultrahigh turndown will effect T given a constant pump flow rate: Energy Input = Water flow rate (GPM) x specific heat x (T water out - T water in) = GPM x 500 x (DT) (simplified calculation) Let s review our example: Energy in = 1500 MBH (at high fire) Water flow rate = 75 GPM Based on a design of 40 F delta T with the boiler at high fire For the sake of simplicity, our example assumes no losses output or efficiency. T water out (set point) = 130 F T water in = variable At high fire: 1500 MBH = x DT DT = 1500 MBH 40 F At 5:1 turndown (20% of input): 300 MBH = [70 GPM x 500] x DT DT = 300 MBH 8 F At 20:1 turndown (5% of input): Constant speed pumping scenario Boiler Input Firing rate GPM T Supply temp Return temp 1500 MBH 100% 75 40 130 F 90 F 94% 300 MBH 20% 75 8 130 F 122 F 94% 75 MBH 5% 75 2 130 F 128 F 88% 3 Efficiency

75 MBH = [70 GPM x 500] x DT DT = 75 MBH 2 F Example 1: Return temperature at 5:1 turndown (20% firing rate) is approximately 8 F Example 2: Return temperature at 20:1 turndown (5% firing rate) is approximately 2 F When utilizing constant speed pumping, the hydronic boiler operating with 5:1 turndown will provide a system delta T of approximately 8 degrees at low fire. Contrast this with the 20:1 turndown boiler where the resulting delta T across the system is approximately 2 degrees. Not only is there less efficient heat transfer with the 20:1 boiler, but the return temperature has been elevated above the flue gas dew point (127 F) and taken the boiler out of condensing mode. Since condensing efficiencies are significantly higher with colder return water temperatures, the elevated return water temperature drops the efficiency approximately a 6%. What effect does this have on the 5:1 operational efficiency? At 5:1 turndown, the return water now comes back at 122 F. The efficiency of the 5:1 turndown boiler at 122 F return water and low fire is approximately 94%. Even though there was an increase in the return water temperature because the boiler remained below the flue gas dew point, it is still condensing and maintaining high-efficiency operation. To Cycle or Not to Cycle? One argument for ultra-high turndown boilers is, We prevent energy-wasting short cycling by keeping the boiler on. While valid for larger non-condensing boilers, this argument does not apply to today s modular systems. Optimally, boiler systems should be designed to cycle no more than two to three times per hour. In practice, five or fewer cycles per hour is considered acceptable. Let s contrast two scenarios, shutting down vs. ultra-high turndown. The amount of BTUs lost per on/off cycle of the 5:1 sample boiler compared to the loss of idling at 20:1 turndown are substantially less. Taking an average of two cycles per hour and assuming the boiler is off for 10 minutes each cycle, we can calculate, based on the mass of the boiler, pre- and post-purge durations, the water temperature and the BTU loss per on/off cycle. In this case, we calculate approximately 190 BTUs per cycle or 380 BTUs per hour. Rather than cycling off, if we allow the boiler to inefficiently operate in a non-condensing mode, this drop in efficiency equates to 6% or 4,500 BTU/hr. Allowing the ultra-high-turndown boiler to idle for 20 minutes per hour to prevent cycling, actually loses 1,500 BTU s. The ultra-high turndown boiler has lost four times the energy as the boiler that off cycled twice. The Ideal Hydronic Solution Modular Approach To maximize efficiency, it is important to right-size hydronic boilers for peak and low-load conditions to look at the overall impact the boiler design and control strategy have on the system. 4

Consider adding one or more boilers for several reasons, including redundancy and load matching to provide the correct system turndown. By staging a multi-boiler system, individual condensing boilers can be set to operate at low fire, thereby making better use of the inverse efficiency characteristics. Designing for system turndown: Select the smallest boiler first: this boiler should be sized to handle the low load conditions at the low firing rate. (5:1 in our example) The formula is: Min MBH = cycles/hr (SV x 8.33 x DT deviation) Where: Min BTU/hr = minimum desired input (required system turndown) Cycles per hour = # of tolerable on/off cycles Designing for 30 minutes of run time under zero load conditions will equal 2 cycles per hour SV = system volume (gallons) 8.33 = density of water DT deviation = maximum allowable tolerance above and below set point Example: Min BTU/hr = minimum desired input (required system turndown) Cycles per hour = 2 SV = 2,000 gallons 8.33 = density of water DT deviation = 10 degrees (±5 degrees) Min BTU/h = 2(2,000 x 8.33 x 10) Min BTU/h = 333,200 A boiler with a minimum output of 333,200 BTU/hr is an appropriate selection to minimize short cycling while maintaining high system operational efficiency. To learn more about hydronic boilers or for help designing a hydronic boiler system, visit cleaverbrooks.com. There is a hydronic boiler solution for almost any commercial application. 5