Installation, operation and care. Pellmax UB. Burner not included Replaces:

Similar documents
Installation, operation and care Firewood boiler Vedolux 40 UB

Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02

Pellet heating. Boilers & Burners.

Accumulator tank. 1000, 750 and 500 litres Aqualux Teknik Aqualux UB Aqualux 750 CU

VEDOLUX ROBUST GREEN WOOD-FIRED BOILERS

Wood firing at its simplest

Installation, operation and care. Pellet burner Replaces:

Combine. accumulators AQUALUX ACKTANK. Combine heat sources for cheap heating

Installation, operation and maintenance. Pellet burner 18/01/2011. Replaces:

Installation and maintenance Viking Bio 35 - pellet burner


Wood pellets economical and environmentally friendly. Wood pellet heating

Installation, operation and maintenance. Accumulator tank. Acc-tank 500 CU. Acc-tank 500 UB ver: Supersedes:

INSTALLATION AND OPERATING INSTRUCTIONS. Ariterm 60+

Solar heating. Free heat from the sun!

Installation and maintenance Pellet burner

Installation and maintenance Vedolux 450

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

Installation and maintenance Viking Bio 35 - pellet burner

USERS GUIDE. LOGIC+ Combi 24, 30, 35

Logic+ Combi

USERS GUIDE 24, 30. For installation guide see reverse of book

Installation and maintenance Vedolux 350

Installer manual ELK 213 Immersion heater

"Let's provide you with a superior User Experience delivering Ease-of-Mind."

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Distributed*and*installed*in*the*UK*by*

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw

INSTALLATION, OPERATION AND MAINTENANCE. ARITERM SWEDEN AB Installation, Operation & Maintenance /28

INSTALLATION AND USER S MANUAL COOKER HOOD RS-600/A-S

Drying Cabinet Installation and Operating Manual

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

Installation and Operating Manual Drying Cabinet

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

Unvented Electric Water Heater 10/15 litre Undersink

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

INSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO

LK Electric Boiler - 4,5

USER GUIDE LOGIC HEAT H

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

Wood-firing at its simplest

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

MOS GB INSTALLATION AND MAINTENANCE INSTRUCTIONS VEDEX 1000 VEDEX 1000 M10527 LEK

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Vedo

- 12, , TECHNICAL INSTRUCTIONS

LEIHDC70SC - LEIHDC70BB LEIHDC70BC. Instructions Manual.

Installation & Operating Manual ZM kW Universal Oil Heater. ZMH Ltd t/a Z M Heaters T (0)

INDEX RECOMMENDATIONS AND SUGGESTIONS... 4 CHARACTERISTICS... 5 INSTALLATION... 6 USE... 9 MAINTENANCE... 11

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

Electronically controlled instantaneous water heater. MCX: 27300, and models. Instructions for the user

Instructions Manual SHC520X - SHC700X

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

System s30. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER

INSTALLATION AND MAINTENANCE INSTRUCTIONS PELLUX PELLUX 100 H AP

Main components. Buying all components from same manufacturer or reseller it guarantees better compatible and service if something happens


Operating instructions for the DA 8-2 Extractor

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: ,

Instructions Manual CTB CTB 9407

2kW UPRIGHT FAN HEATER INSTRUCTIONS FOR USE

50L/D DEHUMIDIFIER. Model Number: IG9805 INSTRUCTIONS FOR USE

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

Pellet boiler Electronic Modulation Automatic Cleaning Grinder system Easy Installation 4 power levels: 10, 16, 25, 43 kw

Heating with wood chips

Easyfire Standalone biomass pellet boiler

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

INSTALLATION - AND USER INSTRUCTIONS

1500W Black Glass Portable Electric Panel Heater KAHTP20BLKA

Operating and assembly manual: Electric instantaneous flow heater Admiral

Solid fuel hot water boiler TKH KW INSTRUCTIONS MANUAL for usage and maintenance

Operating and installation instructions for Fire Lotus H586

HOT WASHER MODEL NO: KING150

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM

User Guide Compact-7 series

Specifications. Vacuum motor power consumption(w/hp) 1200 / 1.6. Exhaust water pump power consumption(w/hp 800 / 1.1

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

GB24 & GB30. User Manual

SWEBO Bioenergy Manual pellet burner PB50 Rev no. Date Page PBM1: (37) Installation and maintenance instructions

ELECTRIC WATER HEATER HT382E55

USER GUIDE VOGUE MAX SYSTEM

60cm Chimney Extractor

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE)

Boiler Technical Specifications (2013)

PELLUX INSTALLATION AND MAINTENANCE INSTRUCTIONS PELLUX 100 H AP

Installation, operating and servicing instructions

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Corn Flame Energy Corn Stove Model 3000

100 FLUEBOOST

User manual. JASPI COMFORT MONO 8 & 12Kw UK 1x230V. Air/water heat pump LEK

User Instructions for Remote Controlled 2kW Rotisserie Effect Fan Heater Model 1276

IMPORTANT SAFETY INSTRUCTIONS

Description of functions

Esse B MODEL Roomheater with boiler WOOD BURNING ONLY MODEL

VETO CLEANER 500 FLUE GAS CLEANER

REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER. Installation and User Guide

Transcription:

Installation, operation and care Burner not included 2011-11-11 ver: Replaces:

Contents 11.11 otes...3 General...4 Function...4 Technical data...5 System principle Pellmax with radiator and tank-in-tank water heater...6 System principle Pellmax, SolomaxVX, Elomax...7 System principle Pellmax, Aqualux 750 Sol, SolomaxVX...8 HVAC installation...9 General Expansion system Vented Unvented Fitting the flue pipe Filling Installation...10 Chimney Turbulators Burner hatch Bracket for cleaning tool Draught regulator...11 Draught regulator Adjusting the underpressure Electrical installation...12 General Wiring diagram Power supply connection Power supply to circulation pump Power supply to Viking Bio pellet burner External control/block Connection for external control/block Function Control panel...14 Commissioning and checks...14 Operation and care...15 Bleeding/topping up Draining Safety valves If there is a risk of freezing If the water boils Overheating protection Boiler temperature Pellet operation Cleaning the boiler Chimney sweeping Troubleshooting...17 Components...18 2

11.11 otes To be completed when the is installed Serial number:... Installation date:... Installer:... Tel:... Other:.................. 3

General 11.11 Read this document carefully before carrying out any installation, adjustment or service and follow the instructions. The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction. Children being supervised not to play with the appliance. Keep these instructions close to the boiler! The boiler must not be modified, changed or rebuilt. To guarantee high reliability, all installation, adjustment and ongoing service must be carried out correctly. The correct settings are important for economical heating. The type and serial number of the boiler must be quoted whenever you contact your retailer, see the rating plate. For service issues, contact your installer. Värmebaronen AB retains the right to change the specification without prior notice, as part of its policy of continuous improvement and development. You may see the following symbols in these instructions and on the product: Information that is important for optimum function. Tells you what you must or must not do in order to avoid personal injury. Tells you what you must or must not do in order to prevent damage or disturbance to the component, the burner, the process or the surroundings. For further details, see the documentation supplied with the product. Function Applications The is a pellet burner designed to be used as part of a system including an Elomax 250/450 or Aqualux accumulator tank. The boiler can also be used with other compatible accumulator tanks or a tank-in-tank water heater. The system is environmentally friendly, economical and easy to manage, and requires minimal care. Compact and effective The is compact and easy to find space for. It is only 95 cm tall, and easy to look after. Its high efficiency guarantees good fuel economy. Large ash bin The large ash bin means that you only need to empty the ash a few times a year. Easy to clean The boiler pipes are round, with no corners where soot and ash can collect. Use the supplied pipe brush to clean the pipes from the same hatch on the front of the boiler. Testing The has been tested, with the Viking Bio pellet burner, by SP, Technical Research Institute of Sweden, and meets the requirements of the E 303-5 standard. Product contents Angled flue pipe with lockable draught regulator. Cleaning tool with bracket hanger. Drain valve. Accessories Upwards flue pipe. Round flue pipe. Attachment for external control. 4

11.11 Technical data Weight: empty: filled with water: 210 300 kg kg Volume: 80 litre Design pressure: 3 bar Test pressure: 4.3 bar Design temperature: 110 C Operating temperature 30-90 C Power: 20 kw Volume of ash bin: 24 litre Voltage: 230 V~, 50 Hz Fuse: 10 A Protection class: IP21 Waterside resistance pressure drop 3 mbar 20 C: 16 mbar 10 C: 0,854 1,724 m³/h m³/h Boiler class: E303-5 3 Min. return temp. 50 C Exhaust massflow: 20kW: 15kW: 11,9 9,2 g/s g/s Flue gase 20 kw 114 C temperature at 15 kw 82 C Manufactured to: 97/23 EG Article 3.3 Technical data Legend 1. Flow pipe R 20 int. 2. Return pipe R 20 int. 3. Safety valve / Venting / Expansion vessel R 20 int. 4. Drain valve / Expansion vessel, R 15 int. 5. Cleaning hatch. 6. Pellet burner hatch. 7. Ash bin. 8. Flue pipe connection. 9. Flue pipe with draught regulator. 10. Adjustable base bolts. 11. Cable tray for burner cable. 12. Cable trays for circulation pump and power supply. 13. Control panel. 8 13 A 5 12 1033,7+20-0 Angled flue pipe (supplied) 9 578,5 205 142 181 127 147,4 Flue pipe back then up (accessory) 147,4 9 331 Flue pipe up (accessory) 9 127 200 78 955+20-0 11 6 4 7 412 56 3 A 2 10 726 1 573 220 145 156 403,5 5

Pellmax with radiator and tank-in-tank water heater 11.11 PELLMAX UB WATER HEATER / ACCUMULATOR TAK EXPASIO VESSEL CIRCULATIO PUMP VALVE SAFETY VALVE BLEED VALVE SHUT ELECTRIC BOOST VIKIG BIO PELLET BURER This diagram illustrates the system principle. The actual system will be designed according to the applicable standards and the manufacturers' instructions for their products. 6

11.11 Pellmax, SolomaxVX, Elomax EXTRA EXPASIO VESSEL EXPASIO VESSEL ELOMAX PELLMAX UB SOLOMAX VX CIRCULATIO PUMP VALVE SAFETY VALVE BLEED VALVE O-RETUR VALVE VIKIG BIO PELLET BURER This diagram illustrates the system principle. The actual system will be designed according to the applicable standards and the manufacturers' instructions for their products. 7

Pellmax, Aqualux 750 Sol, SolomaxVX 11.11 AQUALUX SOL PELLMAX UB SOLOMAX VX EXPASIO VESSEL CIRCULATIO PUMP VALVE SAFETY VALVE BLEED VALVE O-RETUR VALVE This diagram illustrates the system principle. The actual system will be designed according to the applicable standards and the manufacturers' instructions for their products. ELECTRIC BOOST VIKIG BIO PELLET BURER 8

11.11 Pipe installation The installation must comply with the applicable regulations. Contact the chimney-sweep before changing fuel. Contact your municipality to find out about restrictions on the use of solid fuels in built-up areas. The boiler room must comply with the applicable building standards. The boiler must be installed indoors in a cellar or on the ground floor. The installation site must be designed for the total boiler weight of 300 kg including water. Make sure that the flue pipe cleaning arrangements meet the applicable regulations. The boiler can support up to 300 kg of the weight of the chimney, but only 150 kg if the Position of boiler Chimney flue pipe is directed backwards in boiler room and then upwards. The installation site must be able to support this additional weight. Boiler The boiler room must have a fresh air intake with at least the same cross sectional area as the flue duct. A discharge pipe connected to the pressure-relief device is to be installed in a continuously downward and in a frost-free enviroment. Expansion system The boiler must be connected to a vented or unvented expansion system. The volume of the expansion vessel is dimensioned according to the circumstances. The guideline values for volume are approx. 5 % of the total system volume for vented systems, or 7-15 % for unvented systems. Unvented: In unvented systems, the boiler must be fitted with a type approved safety valve connected using an unisolatable pipe from the connection at the top of the boiler, as well as a bleed valve. The overflow pipe from the safety valve must be laid to a floor drain so that no splashes of hot water can occur. The opening must be visible The opening pressure of the safety valve is based on the lowest maximum pressure that any system component can withstand. Fitting the flue pipe Outlet for flue gas thermometer Vented: The distance between the top of the highest radiator and the expansion vessel must be at least 2.5 metres in order to prevent oxygen saturation of the water in the heating system. The expansion vessel is connected in a continuous and unisolatable rise from the boiler's expansion connection at the top. To prevent damage occurring if the expansion system fails, for example because of freezing, the boiler should be fitted with a type approved safety valve. Filling The best way to fill the boiler is to use a permanent filling pipe to the expansion fitting or a hose to the drain valve 9

Installation 11.11 Chimney The chimney must produce a draught strong enough to overcome resistance in the flue duct. The flue duct should be at least Ø 90 mm or equivalent. Combustion produces water vapour, which rises with the flue gases into the chimney, where it can condense and form water, potentially damaging the inside of the chimney. A low flue gas temperature does improve efficiency, but this must be balanced against the risk of condensation. Steps to reduce the risk of condensation: Check and adjust the operation of the draught regulator. Insulate the chimney in cold spaces. Remove any turbulators. Increase the burner capacity. Install a flue liner. The flue gas temperature must be checked at all times to prevent condensation forming in the chimney. Turbulators The boiler is supplied with turbulators, designed to introduce turbulence to the flue gases, thereby increasing efficiency. The turbulators increase the flue gas resistance in the boiler. Burner hatch The boiler is supplied with a hatch designed for a Viking Bio pellet burner. If the hatch can be opened without removing the pellet feed tube or disconnecting the electricity supply to the burner, a safety switch must be fitted to the hatch. Bracket for cleaning tool The bracket for the cleaning tool can be fitted to either side of the boiler or any suitable place close to the boiler. 10

11.11 Draught regulator Draught regulator The chimney draught is influenced by the temperature and by weather and wind conditions, and because the efficiency of combustion depends on the draught, the aim is to achieve a stable draught. The draught regulator is used to allow ambient air from the boiler room into the flue duct, which has the following benefits: More stable draught and flue gas temperature. Reduced downtime losses. Flue duct ventilation. Drier flue gases, reducing the risk of condensation. Adjusting the underpressure For optimum function, the right amount of air must pass through the draught regulator. If the chimney is tall or has a large cross section, an additional draught regulator may need to be installed. To adjust the underpressure when the hatch is opened, squeeze the clips holding the weight and move it along the shaft. The underpressure changes by around 0.5 Pa/mm as shown in the figure. This is an approximate value, and a draught meter must be used if you want to set the underpressure more precisely. For the Viking Bio, the draught should be 5-10 Pa. Turn to secure the hatch 11

Electrical installation 11.11 Electrical installation work must be carried out under the supervision of an authorised electrical installer. The work must comply with the applicable regulations. The main switch (20) must not be set to position 1 before the boiler has been filled with water. Power supply connection 230V~, with max. 10A fuse. B4 L1 S3 L CP X 25 Wiring diagram 10 A 21 30-90 C T 2 1 110 C T 2 1 24 1 2 230V~ 26 L B4 L1 S3 4 ALARM 23 L 4 5 20 CP X 25 Power supply to circulation pump An all-pole circuit breaker must be installed ahead of the pump. B4 L1 S3 L CP X 25 230V~ 230V~ 28 230V~ 26 27 27 Power supply to Viking Bio pellet burner 21 23 24 20 B4 L1 S3 L 230V~ CP X 25 28 230V~, 2.8 A See also the installation instructions for the burner. 33 32 25 20. Main switch. 21. Thermostat (temperature setting). 23. Indicator showing triggered overheating protection. 24. Overheating protection. 25. Terminal block. 26. Power supply connection. 27. Circulation pump connection. 28. Viking Bio pellet burner connection. 32. Strain relief. 33. Opening for cable trays for supply, burner and circulation pump cable. See numbers 11 and 12 in Technical Data. : Blue, neutral. : Yellow/green, earth. L1: Black. B4: Brown. S3: Grey. T1, T2: Safety switch on combustion chamber hatch. If the comustion chamber hatch can be opened without removing the pellet feed tube or disconnecting the electricity supply to the burner, a safety switch must be fitted to the hatch. The boiler fuse must be removed/disconnected during installation or service. 12

11.11 Switchover - controlling the charging pump System principle Viking Bio Aqualux 750 Teknik Solar panel K 2 After switchover, the boiler s thermostat can control the charging pump between the boiler and accumulator tank. The pellet burner controls the boiler temperature and must, therefore, be fitted with a boiler temperature sensor (accessory). Temperature recommendation 85 C for the start of the charging pump. Set with the boiler thermostat, 21. 70 C boiler temperature. Set on the burner. RC B The installation and switchover must take place under the supervision of a qualified electrician. See also the installation instructions for and Viking Bio. The fuse for the boiler must be removed/interrupted during installation or service. Before switchover After switchover 21 30-90 C T 2 1 4 2 4 110 C T LARM 1 Wiring diagram - Switchover 1 2 4 5 20 B 30-90 C 21 T 2 1 4 2 4 110 C T LARM 1 1 2 4 5 20 A C A B4 L1 S3 L CP X 25 B4 L1 S3 L CP X 25 28 230V~ 27 20. Main switch. 21. Thermostat, after switchover, temperature for the start of the charging pump. 25. Terminal block. 27. Circulation pump connection. 28. Viking Bio pellet burner connection. 230V~ 28 27 A. Cable between main switch and terminal CP on the terminal block. Connect according to A above. B. Cable between the thermostat s connection 2 and terminal B4 on the terminal block. Connect according to B above. C. Connect terminals B4 - L1 on the terminal block. 13

Control panel 11.11 23 20 24 22 21 20. Main switch. 21. Temperature setting, thermostat. 22. Thermometer, boiler temperature. 23. Overheating indicator. 24. Overheating protection reset. Commissioning and checks A boiler system fitted with an unvented expansion vessel must undergo an installation inspection before being put into operation. The inspection must be carried out by a person qualified for the task. The installation inspection must be documented. A further inspection is required if the boiler or the expansion vessel is replaced. After installation, check with the installer that the system is in perfect condition. Ask the installer to demonstrate the settings and functions so you know how to operate and care for the system. the system is filled with water. all connections are watertight. flue gas connections to the boiler and to the chimney are tight. the filling/drain valve has been closed properly. the safety valves are working properly. the necessary valves are open. the circulation pump is working and the direction of flow is correct. the thermostat is correctly adjusted. The pressure in a heating system varies with the temperature, so only add water if it is necessary. Always disconnect the power supply to the boiler before: opening the burner hatch draining the boiler water 14

11.11 Operation and care Bleeding/topping up Regularly check that there is enough water in the heating system. Air may remain in the heating system for a while after installation, so bleeding should be repeated a few times. After bleeding, check the pressure and add water if necessary. The volume of water changes with the temperature, affecting the pressure in the heating system. Higher temperatures increase the volume and pressure. The expansion vessel takes up the changes in volume in the system. Only add water if it is necessary. The pressure in a heating system varies with the temperature, so only add water if it is necessary. Overheating protection The overheating protection in the boiler is triggered when the boiler temperature exceeds 110 C. It is reset from the control panel. You can only reset once the boiler temperature has dropped to below 80 C. Always check the reason for overheating! Boiler temperature The boiler temperature must not be allowed to fall below 60 C. Pellet operation For reliability and efficiency, it is important to check and adjust the burner regularly. For the Viking Bio pellet burner, the draught must be -5 to -10 Pa. Draining To drain the system, connect a hose to the drain valve, 4, on the side of the boiler. Safety valves The safety valves in the installation must be exercised regularly in order to maintain the safety function. The pressure-relief device is to be operated regularly to remove lime deposits and to verify that it is not blocket. If there is a risk of freezing In severe cold weather, no part of the heating system should be turned off as this would involve a risk of burst pipes. The boiler must not be put into operation if any part of the heating system is suspected of being frozen. Call the installer. If the water boils Disconnect the power supply to the burner, then fully open the nearest hot water tap. Call the installer. 15

Operation and care 11.11 Cleaning the boiler Risk of burns. Always leave the burner to stop burning before you start cleaning. Leave the boiler to cool down. Ash and soot are formed in pellet operation, so the boiler must be regularly cleaned, if possible when the flue gas temperature has risen by around 50 C compared to when the boiler is clean. The ash bin only needs to be emptied a few times a year. All boiler cleaning takes place from the front. Ashes may contain embers for a long time after the burning cycle, so keep them in a nonflammable container with a cover. The container must be placed on non-flammable material. Whenever you clean the pellet burner, check the amount of ash in the ash bin. When the pan is full, remove it from the boiler and empty it. This is also a good time to clean the combustion chamber. Ash attachments are available for vacuum cleaners, making it easier to clean ash from the boiler and burner. Turbulator tool Cleaning hatch Collection chamber Boiler without hatches Draught regulator Upper flue gas pipes Lower flue gas pipes Ash bin Disconnect the power to the boiler. Secure the draught regulator in the closed position. Open the boiler hatches. Use the tool to remove the turbulators. Clean the flue gas pipes with the pipe brush. Vacuum the collection chamber. Replace the turbulators. Close the hatches. Release the draught regulator. Switch on the power to the boiler. Turbulators, 4 pcs. Chimney sweeping Secure the draught regulator in the closed position to prevent soot escaping into the boiler room. After cleaning the chimney, the draught regulator is removed to allow soot and ash to be removed. The best way to remove ash and soot that has fallen into the boiler is to use a vacuum cleaner through the upper flue gas pipes in the boiler. Always be careful with ash, as it may contain hot embers. 16

11.11 Troubleshooting Low room temperature Overheating protection triggered. Check the reason. Reset the overheating protection. This is a warning if it happens repeatedly, call the service engineer. Boiler temperature too low. Check the thermostat setting, adjust. Burner not working properly. Check, correct. Air in boiler or heating system or not enough water in the heating system. Check, bleed and top up the heating system as necessary. Thermostatic valves in heating system set too low. Check, adjust. Shunt control incorrectly set. Check, adjust. Circulation pump switched off. Start the circulation pump. Fuse tripped. Check the reason and correct it. Change/reset the fuse. High room temperature Thermostatic valves in heating system set too high. Check, adjust. Shunt control incorrectly set. Check, adjust. 17

Components 11.11 ref. item no. name qty. 21 120006 Thermostat 30-93 C 1 120009 Thermostat knob 1 24 120022 Overheating protection 1 20 130032 Switch 1 23 190006 Indicator 1 32 140042 Strain relief 3 25 160003 Terminal block 1 160006 End plate for terminal block 1 390255 Protective hose (m) 2.7 720200 Scoop 1 92131 Panel 1 720203 Holder for cable tray, top 1 720194 Holder for cable tray 1 22 380022 Thermometer 0-120 C 1 4 240350 Drain valve R15ext 1 232253 Turbulators 4 440002 Pipe cleaner 89 mm 1 440012 Spring steel shaft 1000 mm 1 700170 Gasket for flue pipe flange 1 700256 Cleaning tool bracket 1 700297 Flue pipe insulation 1 710260 Turbulator tool 1 7 710822 Ash bin 1 370021 Cover plate 25.4 x 65 1 370022 Cover plate 32.5 x 77 3 720195 Cover plate, lower 1 720196 Cover plate 1 720197 Left side 1 720198 Right side 1 720199 Cover 1 5 710813 Cleaning hatch compl. 1 100953 Handle 1 700292 Hatch gasket small 1 700296 Hatch insulation 1 710803 Combustion plate 1 710815 Cleaning hatch 1 6 710812 Lower hatch compl. 1 100953 Handle 2 700293 Hatch gasket large 1 700294 Hatch insulation 1 700295 Hatch insulation 1 710805 Combustion plate lower, inner 1 710811 Lower combustion plate compl. 1 710814 Large hatch 1 9 710830 Angled flue pipe compl. 1 100115 Wingnut 4 100322 Cross screw 4 440081 Draught hatch 1 710695 Gasket for flue pipe 1 710829 Front flue pipe 1 700299 Base insulation 1 710508 Lock ring 3 710799 Insulating plate for base 1 710833 Bypass retainer 1 710834 Bypass cover plate 1 720193 Rear side 1 18

Värmebaronen AB retains the right to change the specification of included components without prior notice, as part of its policy of continuous improvement and development. Varmebaronen UK 11 Back O'Hill, Stirling. FK8 1SH T 01786 849 099 F 01786 849 098 www.varmebaronen.org info@varmebaronen.org