Drum Level Instrumentation and. The ASME Boiler Code Requirements. Presented by: Jim Kolbus. Topics

Similar documents
Drum Level Instrumentation and

Thank You for Attending Today s Webinar:

THE BOOK A Guide to Boiler Drum Level Equipment and Control Concepts

Revitalize Building Mechanical Systems (4619)

Low pressure boiler* inspection and maintenance

Boiler Instrumentation

Boiler Mountings. Engr. Omar Sadath, Maritme Lecturer & Trainer, Bangladesh

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

BERMAD Fire Protection

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

SAMPLE SPECIFICATIONS

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL

TWIP Level Switches. Water Detection for Alarms, Trips, Drain Pot, Heaters, Deaerators, and Condensate Tank Applications

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION HEATING BOILERS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

Rental Boiler Specifications (Nebraska Boiler)

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

SECTION PLUMBING EQUIPMENT

2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

SECTION PLUMBING EQUIPMENT

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

Economical and simplified solutions that offer quality and optimum steam trap service.

BuildingName The Description of the Project P DOCUMENTS

Instrumentation and Controls Group

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

DIVISION FINNED WATER-TUBE BOILERS

SECTION METERS AND GAGES FOR PLUMBING PIPING

CSD-1 COMMERCIAL BOILER CONTROLS

ToThePOINT. Best Practices. Best Practice No. 1: Have your boiler inspected regularly by an authorized inspection agency. LOSS CONTROL SERVICES

RHP120 RHP300 Steam Boiler Series

Blowdown Separator & Aftercoolers Installation, Operation, & Maintenance

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

Reliable Solutions in. Level Indication & Control, Sight Flow Indication, Filtration & Separation. Working Together to Deliver

Silhouette. Feedwater Heater. Boiler Feedwater

Flo-Rite-Temp Instantaneous Steam/Water Heater

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

STR-Series Indirect-Fired Air Turnover Units

Flo-Rite-Temp Instantaneous Steam/Water Heater

YARWAY PROCESS THERMOSTATIC STEAM TRAPS SERIES 151 AND AV5

SECTION METERS AND GAUGES FOR HVAC PIPING

SECTION HUMIDITY CONTROL EQUIPMENT

Project Name: Location: Engineer: Contractor: I. GENERAL

TEMPERATURE CONTROLLERS

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

CLASS POWER ENGINEER S CERTIFICATE

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION PACKAGED HEAT TRANSFER SYSTEM

NATURAL GAS PIPING

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

DIVISION FINNED WATER-TUBE BOILERS

1. Division 23 Section "Steam and Condensate Heating Piping" for steam and condensate meters.

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

96.2% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS CON X US REMOTE CONNECT. MODBUS AND BACnet MSTP PROTOCOL

SECTION DOMESTIC WATER PIPING SPECIALTIES

Installation, Operation and Maintenance

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

Miniature Hobby Boiler Inspection and Certification Requirements

Series 151 and AV5. A wide range of process thermostatic steam traps is available to match almost any application need.

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES

Bids received after scheduled opening time will be returned to Bidder unopened.

Solution builder. in energy management.

Blowdown Separator & Aftercoolers

Steam System Best Practices Document No. 11

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

Hubbell NX500 High Efficiency Gas Condensing Water Heater

HIGH EFFICIENCY COMMERCIAL BOILERS

Eclipse Self-Check UV Scanner

Series 300 VTB. Installation Instructions

SECTION WATER HEATERS

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Liquid Drainers LIQUID DRAINERS

CTO BOOSTER SPECIFICATION

SECTION ELECTRIC WATER HEATERS

SECTION HEATING BOILER FEEDWATER EQUIPMENT

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Sterilizer Model LS2020 Series Beta Star Life Science Products of R-V Industries

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

DIVISION FINNED WATER-TUBE BOILERS

Technical Specification

MOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

INSTALLATION and OPERATION MANUAL DIRECT STEAM KETTLES MOUNTED ON ELECTRIC BOILER BASE CABINET MODELS: EMT-6 EMT-10 EMT-12 EMT-6-6 EMT-10-6 EMT-10-10

MODELS R & RH 10 THRU 20 RB SERIES ELECTRIC STEAM BOILERS

Packaged Semi-Instantaneous Steam Fired Water Heater

Transcription:

Drum Level Instrumentation and The ASME Boiler Code Requirements Presented by: Jim Kolbus Topics ASME Code Section 1 Requirements for Drum Level Instrumentation Water Columns and Water Gage Isolation Valves Prohibition of Structural Webs in Water Gage Glasses End to End Reflex Type Water Gages Magnetic Level Gages Code Design Requirements for Isolation Valves Level Switch requirements for HRSG applications Low Water Cutouts Common Code Violations Recommendations for Level Instrumentation Piping

ASME Code General Terms Direct Reading Gage Indirect Reading Gage Glass Gage Remote Level Indicator Direct Reading Gages Tubular Glass to 250 PSI Prismatic (Reflex) to 350 PSI Flat Glass (Transparent) to 2000 PSI Bi-Color to 3000 PSI

Bi-Color Water Gage Glasses Operate on the principle of light refraction Light refracts through water different than steam Displays Green to indicate the presence of water and Red for steam. Gage must be outfitted with an illuminator in order to be Code Compliant Bi-Color Water Gage Principle of Operation Steam shows RED. Water shows GREEN

Remote (Indirect) Level Indicators Conductivity Probe Type Level Indication System PLUS OTHER TECHNOLOGIES - Differential Pressure Transmitters - Guided Wave Radar Magnetic Level Gage (equipped w/ 4-20 transmitter) Remote (Indirect) Level Indicators All Differential Pressure and Guided Wave type Indirect Level Indication instruments must be installed and programmed to the manufactures instructions to prevent indication errors. Precautions must be taken to prevent adverse effects from freezing conditions on the level sensing components Insulation on all piping is recommended, except on the Condensate Pots for DP transmitters. Install cages or guards to protect personnel, if service area is confined

ASME Boiler Code Water Gage Requirements: Operating up to 400 PSIG One Direct Reading Gage Required (which must be kept continuous service) Operating over 400 PSIG Two Direct Reading Gages in service OR Two Remote (Indirect) Level Indicators On Continuous Display for the Operator and One Direct Reading Gage (Which may be Isolated but kept in serviceable condition) Code Requirements for Gage Glass Placement Level A = Lowest Permissible Water Level, at which there will be no danger of overheating the vessel

Code Requirements for Gage Glass Placement Gage Glass Visibility must not intersect Vessel connection pipe diameters Water Gage Glass Placement Explained 1. Lowest Permissible Water Level- At which level there will be no danger of overheating (Level A). 2. Water Connection for Water Column- Must be 1 below low visibility point of gage glass and at least 1 NPT. The line must be level or slope downward from column to drum. 3. Steam Connection for Water Column-Same as 2 above. Except slope down ward from drum to column. 4. Steam Connection may come out of top of vessel- Centerline of steam connection would be at point marked B. 5.The lowest visible part of water gage glass-must be at least 2 above the lowest permissible water level (Level A). 6. The highest visible part of water gage glass-must be at least 1 below center of steam connection. 7. Gage cock connections- Must not be less than 1/2 pipe size and located within gage visibility range V. (Gage cocks are no longer required by ASME Section 1.)

ASME Code References Water Columns (PG-60.2) -1 min. connection size for water column to boiler (PG-60.3.4) - 3/4 min. drain connection size (PG-60.2.3) Stainless Steel is prohibited for the construction of water colu mns (PG-12.3) Water Level Indicators (PG-60.1) * Water Gage Glass Requirements ( PG-60.1.1) * Gage Glass & Connections ( PG-60.3) * 3/4 min. connection size for Remote (Indirect) level indicators (PG-60.3.4) * Highest visible permissible water level (PG-60.3.2) * Lowest visible permissible water level ( PG-60.3.3) * Stainless Steel for Gage Glass Body (PG-12) * Magnetic Level Gage Chambers permitted up to 900 PSI (PG-12), as of 2007 * 1 Gage overlap requirement for Transparent Gages (PG-60.1), since 1996 * Transverse or Cross Web Structural Webs are prohibited from use in the construction of Transparent type Water Gage Glasses, which may obstruct the view of the level (PG60.1), as of 2009 Ball Checks in Water Gages Valves considered to be a user option, if specified, must meet the Code requirements (Automatic Shut Off Valves Appendix A-18) ASME Code References Gage Cocks (Trycocks) are not required (PG-60.4), since 1991 Many Operators continue to rely on Gage Cocks Magnetic Water Level Gage: permissible for applications up to 900 PSI External switches are not permitted for control Purposes, such as Low Water Cutouts (PG.12 and PG.60) Switches not permitted

Code Limitations for the most commonly used materials for Instrumentation (Pressure Parts) SA-278 Cast Iron to 250 PSI SB-61 Bronze to 450 PSI SA106 Carbon Steel Pipe or SA105 Forgings to 3000 PSI Specified Grades of Stainless Steel Water Columns Cast Iron Water Columns are permissible up to 250 PSI Fabricated Steel Water Columns are used for applications up to 3000 PSI Three types of Water Column Functions No Alarm for the sole purpose of supporting one or two water gage glasses Float Alarm Type Electrode (conductivity Probe) Type for Alarms and Cut Outs (Trips)

Water Columns and Tie Tubes Water Columns are not required on Power Boilers by ASME Boiler Code, but when specified, must be designed and manufactured to comply with Code Water Columns are considered to be a Standard Pressure Part or Standard Welded Part as defined in Section 1: PG-11 of the ASME Boiler Code. Therefore, a Code stamp for manufacturing is not required. The use Code recognized materials and applicable welding procedures are a must. Always Install Chain Operators for Operator and Plant Safety PG.60.1.7 requires an accessible operating mechanism from the isolation valves to the operating floor or platform

Structural Webs are Prohibited From Flat Glass Gages Designs - These Webs may mask the actual location of the water level - The risk of Masking the level is enhanced on elevated gage glass installations Flat Glass Transparent Type Water Gage Glasses Typical View of Water Level with no obstruction

End-to-End Reflex Gage Glasses Are Permitted - PG.60.1 Clarifies the use of multisection gages without overlap, due to the light refraction principle Globe Valves for Isolation and Drain In-line flow prevents sediment or condensate traps, which can lead to false level indication with traditional Globe valves Globe type valves are now permitted if the lowest edge of the seat is at least 25% of the port diameter. (Ref: PG-60.3.7) Incorrect Correct

Magnetic Water Level Gages Magnetic Level Gage (equipped w/ 4-20 transmitter) For Process For Power Boilers Code Issues and Concerns for the Use of Magnetic Level Gages on Boiler Drums Acceptable as an acceptable Indirect Reading for applications Gage up to 900 PSI (Ref: PG12.2) The Indication Scale must follow ASME guidelines (Ref: PG-60.3.2 & PG60.3.3) May not be used to support a water Gage glass, due to prohibition of stainless steel construction for water columns. Ref: PG-12.3 No accessories are permitted to be attached for control purposes (No Trip Switches). This device must be used for indication only. Ref: PG-60.1.1.4 NOTE: The use of a Magnetic Level Gage does not replace the Code requirement for a Direct Reading Water Gage Glass on any Power Boiler Drum designed to meet the ASME Section 1 Boiler Code

Concerns for the Application of Magnetic Water Gages on Boiler Drums The float design is based on the operating conditions(customer specified), not the boiler design conditions. Therefore, if the boiler is operated at a pressure lower than the planned operating pressure, the Magnetic Gage reading will be higher than the actual drum level. If the user has poor water quality, the potential exists for iron particles to attach onto the float. This will result in a heavier float, with an inaccurate level reading. Low Water Cutouts Two devices are required (Ref: CSD-1: Controls and Safety Devices for High Pressure Steam Boilers ASME) Subsection CW-140 These devices are typically activated by floats or conductivity probes The two devices must be in separate chambers or one of them may be inserted directly into the boiler

Low Water Cutouts The minimum connection pipe size is 1 and separately piped devices must have a vertical drain of no less than ¾ NPS One control must be set to activate ahead of the other one A Manual Reset function may be applied to the lower of the 2 controls, with a maximum delay of 3 minutes, after the fuel has been cut off Low Water Cutouts Time Delays: The cutout circuit may incorporate a time delay not to exceed 90 seconds or the manufacturer s recommendation (whichever is less)

Requirements for Level Switches on HRSG s The Code now requires Drain Pots to be installed in the Boiler Proper or Boiler External Piping either upstream or downstream of the Desuperheater to ensure malfunctions of the devices will not allow water to enter hot boiler components. These drain pots shall include automatic detection of water and automatic operation of the drain pot valves. Drain pots with single element level control with delay to close are an acceptable method of detecting and removing spray water. Consult Code Section PHRSG-4 for more details Example Drain Pot Installation Requirements for NFPA 85 Compliance Water Level in each drum is continuously monitored and recorded or logged (Section 8.7.2.3-1) Operators receive audible and visual alarms for low water level (Section 8.7.3.2.1-6) Duct Burner Master Fuel Trip from Low Water Level on HP Drum section (8.7.4.3-12)

Recommendations for Level Instrument Piping All piping from the drum to the water level instruments are to be insulated, for the following reasons: 1. Provide safety for plant personnel 2. Increases level accuracy 3. Reduce excess condensate formation Any slope in the piping should be downhill on the steam line & uphill on the water line from the drum. Piping from Drum to Level Instruments should be kept to a minimum < 6 Ft Common Code Violations and Concerns Isolated Inoperable Water Gages Missing Water Gage Glasses Missing Illumination from Ported type gages Inadequate display of remote Level Indicators in the control room combined with isolated gages

Common Code Violations and Concerns Continued Contaminated Water Gage Glasses that prevent viewing the actual level (meniscus line) Multiple Section Flat Glasses without the Code required overlap Poor Maintenance Practices Annual Violation Report The data Illustrates Boiler Controls as the primary source of violations Source: The National Board of Boiler and Pressure Vessel Inspectors

Drum Level Instrumentation Note: Photos are helpful for discussion Photo of Serious Installation Error Code Violation and Operation Risk to Boiler

Photo of Corrected Installation Top Questions for Users Are you having any operational issues with Water Gage Glasses on Boiler Drum applications? What instruments are installed for the display Drum Level Indication in the Control Room? Are the water level limit controls on your boiler applications working properly and tested regularly? Does the existing Drum Level Instrumentation meet the Code for the Design and Operating Pressures of your Boiler Drum?

Summary Recommendations for Drum Level Instrumentation Installations for Users Specify or Install Code Compliant Designs Examine Piping and isolation Valves Consult with the Insurance Underwriter or Plant Safety Department for plant requirements, which may exceed Code minimum Always follow the OEM maintenance instructions for the most accurate and reliable information Summary Your time and attention to this information is appreciated, along with your contributions to Operator and Plant Safety of Power Boilers Questions