Machinery Room Electrical Best Practices

Similar documents
Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

National Electrical Code

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

ELECTRICAL BULLETIN

Welcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room?

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

PART 4 ELECTRICAL STANDARDS

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Electrical Inspection Service & Distribution

CHAPTER 20 SERVICE EQUIPMENT

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

SECTION AUTOMATIC TRANSFER SWITCHES

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal

ELECTRICAL POWER SYSTEMS

PANELBOARDS & BUILDING DISTRIBUTION

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation

SECTION ISOLATED POWER SYSTEMS

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

Chapter 1 General... 5

Ammonia Refrigeration RAGAGEP

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks

SECTION AUTOMATIC TRANSFER SWITCHES

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Safety Meeting Topic #37 NFPA 70E What is it?

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

2017 NEC Presented by: Russ LeBlanc

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove

Monitoring of Electrical Equipment Failure Indicators and Alarming

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

SECTION AUTOMATIC TRANSFER SWITCHES

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS

Property risk solutions

Subcontract Agreement No.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Guide to Compliance with the Electrical Workplace Safety Standards in the United States

Electrical Safety Program

Hazardous Location Certified

Risk Mitigation of Aging Electrical Infrastructure

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?

Short Circuit Current Rating

Guide Specification Model CTG Automatic Transfer Switch

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

Electrical Energy department

PGR-8800 TECHNICAL FAQ

ANSI/NETA Standards Update

US Navy Leading the Way in Switchboard Protection

Arc Flash Protection Training - NFPA 70e Electrical Safety

Ammonia Detection System Codes and Design Specifications

Pilz Safety Lockout System (PSLS)

Overview of Significant 2017 NEC Changes

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

SEL Arc-Flash Solutions

WHY ELECTRICAL PREVENTIVE MAINTENANCE IS ESSENTIAL TO A SAFE AND PRODUCTIVE WORKPLACE

ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS

SYSCO CENTRAL PENNSYLVANIA, LLC. HARRISBURG, PENNSYLVANIA

Electric Shock Drowning

Building Electrical System Overview

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004

TABLE LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE Uncovered Parking Areas. Building Grounds. Walkways 10 feet wide or greater

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

SEL Arc-Flash Solutions

Ground Fault Protection Improvement Study

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

BASIC ELECTRICAL ENGINEERING FOR CE

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

MODEL SST 2 40 FREEZE PROTECTION THERMOSTAT MODEL SST FIXED SET POINT THERMOSTAT. Installation and Operation Manual

A. This Section includes transfer switches rated 600 V and less, including the following:

ENGINE GENERATORS AND ACCESSORIES

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

Understanding NFPA, NEC 2005 Article 409 a White Paper by Paul A. Terry, P.E.

CENTERLINE 2100 Motor Control Center (MCC) Doors and Units with Vertical Operating Handles

SECTION : MEPS IDENTIFICATION & LABELING

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

2014 National Electrical Code & NFPA 70E/Arc Flash

2009 ELECTRICAL CODE REQUIREMENTS

Wiring Diagrams Units Produced After April 20, 2009

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Installation Instructions

Element D Services Electrical

XRRS Specification Fire Ready Hood

Installation Instructions

Heat Recovery Units. EXTERNAL STATIC REQUIRED (in.h2o) (Pa) MOTOR (Bhp/Hp) (bkw/kw) SPEED (rpm)

Spring Test 6 due 04/26/2013

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

Transcription:

Machinery Room Electrical Best Practices Brad Heeres Angus-Young Associates February 8, 2007

Understand and comply with applicable codes and standards The National Electrical Code requirements for a safe electrical installation Working clearances Egress away from equipment Proper grounding and bonding NFPA 70E Standard for Electrical Safety in the Workplace Article 130 requirements for protection against arcflash hazard IEEE Standards for design and analysis of electrical distribution systems Color Book Series Red and Green Books

Understand and comply with applicable codes and standards ASHRAE 15 Ventilation requirements for machine rooms Provide 0.5 cfm/ft 2 continuous ventilation and alarm on failure Provide shutdown controls outside the machine room Feed ventilation fans from a separate circuit and provide controls outside the machine room

Understand and comply with applicable codes and standards International Institute of Ammonia Refrigeration (ANSI/IIAR-2 and Bulletin 112) Minimize the electrical equipment in the machine room Consider Class 1 Div. 2 electrical installation for circuits/equipment that may operate in an emergency Provide adequate lighting for operations Provide emergency and exit lighting with power source located outside the machine room

Good electrical equipment and machine room design is shown in this illustration Locate non-machine room panels outside of machine room Starters for compressors located in room but away from ammonia sources Separated Electrical Room Control panels readily accessible Plan for future equipment

Maintain appropriate electrical and machine room conditions Keep electrical equipment cool Ventilate electrical rooms approx. 200 CFM/kW loss Keep electrical equipment dry Provide heating if necessary Be aware of moist air passing through conduits Use supply fans not exhaust fans for electrical room ventilation Keeps contaminants out Provide 30% or MERV 7 filters

Consider medium voltage distribution when: Individual loads exceed 500HP The facility covers a large area and has distributed large loads Where the total facility load exceeds 5000 kva or utility requirements dictate

Provide ground fault protection on feeders when GFP is required on main devices NEC requires ground fault protection on 480V solidly grounded services > 1000A Phase fuses and CBs may not clear ground faults before the main trips Overcurrent protection coordination is important for safety and reliability

Electrical systems studies can improve electrical system safety and reliability Fault current studies determine appropriate equipment ratings Coordination studies ensure proper fault clearing Arc flash evaluation improves safety

Fault current studies determine appropriate equipment ratings Establishes interrupting ratings for fuses & CBs Establishes proper trip settings or fuse ratings Provides information that can be used to limit damage due to faults

Coordination studies ensure proper fault clearing Circuit breakers are set or fuses selected to: Limit fault damage to equipment and conductors Minimize nuisance trips Isolate faults

Arc flash evaluation improves safety Proper labeling indicates the level of hazard and appropriate protective gear Fuse selections or circuit breaker settings may be adjusted to reduce the hazard

Preventative maintenance improves both safety and reliability PC Process East Wall 9-28-05 Markers: Label Emissivity Background Average Std Dev Max Min L0 0.95 92.6 91.22 0.13 91.5 91.2 L1 0.95 92.6 96.89 4.30 105.1 93.3 L2 0.95 92.6 97.53 4.24 102.8 92.5 L3 0.95 92.6 96.32 4.33 101.0 90.7 L4 0.95 92.6 95.56 3.14 98.9 91.2 L5 0.95 92.6 95.89 3.88 101.2 90.7 L6 0.95 92.6 96.23 4.22 100.5 89.7 Info: File Location F:\images\IR PC Process East Wall.is2 Image Time 28-Sep-05 10:09 AM Emissivity 0.95 Background Temp 64.00 F Image Range 89.60 to 106.70 F Average Temp 93.91 F Calibration Range 32.00 to 662.00 F Lens 40948-2126, 20mm/F.8 Camera S/N FLX.05.05.004 IR PC Process East Wall.is2 Notations: 600Amp Breaker. Phase A 296 amps, Phase B 302 amps and Phase C 304 amps Comments: Use good installation practices Check for hot equipment and terminations (thermal scan) Monitor large loads like compressors and MCCs for changes in operation

Electrical best practices: Understand Codes and Standards Use good planning for new construction, additions and upgrades Properly select and adjust electrical devices Monitor the electrical system operation Properly inspect and maintain electrical equipment Follow good safety practices