www. ElectricalPartManuals. com Annunciator unit Features Self-contained microprocessor-based annunciator unit with 64 alarm channels Application

Similar documents
Annunciator Unit SACO 16 D1. Product Guide

Annunciator unit. Application

Analog Annunciator Unit SACO 16 A3. Product Guide

REA 105 Arc Protection Module. Operator s Manual

SACO 16D3 Annunciator unit. User s manual and Technical description

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series

Universal fault annunciator for panel mounting

VAMP 121. Arc protection unit. User manual

AO Annunciator Module

1. General Safety Block diagram Description of operation Connections Commissioning...11

Window facia fault annunciators

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

VAMP 120 & 121. Arc flash detection units. Product picture

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Installation / Monitoring Technique

SPEF 3A2 C. Fault indicator. User s manual and Technical description SPEF 3A2 C. f n SPA. Serial port. RS AA Ser.No.

Parameterisable compact fault annunciator with permanent display

MSM - Expansion modules

Installation, Operating and Maintenance Manual

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Panel Mounted Fault Annunciator Series

System 9000TS Sequence of Events Recorder

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Model A1600 Series Annunciator

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

TCM-2 Thyristor Control Module DATA SHEET

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

ME 3011C / Alarm Indication / Quick Reference Guide

Signal Processing System ME30 infobox

SFC-200 SERIES LED FIRE ALARM PANEL

System 9000TS Event Recorder

Model A1700 Series Annunciator

Pioneer-R16 Gas Monitor Operator s Manual

Vocia VACIE. Reference Guide

VACIE REFERENCE GUIDE REVISION 1.2.6

Independent Zone Control (I.Z.C.)

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION

Standard Devices. Electronic Alarm Indication Systems. ME 3011b

M1000 Alarm Annunciator

FireNET Plus Wiring Instructions

APPLICATION DATA SHEET

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

ORION Mini-Rep INSTALLATION MANUAL

AIS750 Series Alarm Annunciator

X11CA COMPUTER ANNUNCIATORS

20 Light Remote Annunciator

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

INPUT / OUTPUT MINI MODULES

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

The EN54 Part 2 & 4 Fire System

ME 3011 compact. Electronic Alarm Indication Systems. Power Station Control Systems. Automation Equipment. Power Distribution Control Systems

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Model A2100 Series Annunciator

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

THE SOLUTION. MSM-Product family OPERATING MANUAL. A fault annunciator of the. BSM Basic fault annunciator for panel mounting. INFOwww.ees-online.

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Technical Manual. Level Alarm Unit CARLA & WIDS

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

SIRA srl. Installation and user manual. Consolle/Digit Remote LCD Annunciator. Remote LCD Annunciator INSTALLATION & USERS MANUAL.

ESP TECHNOLOGIES LIMITED

Process Alarm Solutions

Operating Instructions

SALES SUPPORT DOCUMENT

Integrated Security Solutions

System 9000TS Sequence of Events Recorder

Monitoring Devices 11/1

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

A T L A S - SolarClimatic Test Cabinet SC 2000 MHG

Application, Installation, Operation & Maintenance Manual

Intelligent addressable fire alarm control panel

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Addressable Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

ZXSe Range Data Sheet

GROUP OF COMPANIES. MERLIN STEALTH Electric Fence Energizer. Users Manual

Annuciator Logic Controllers

Fire control panels FC360

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

The EN54 Part 2, 4 and 13 Fire System

AIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)

APPLICATION DATA SHEET

M2500 Engine Controller Installation Manual

DRAFT 20 October 2014

D1000 Arc-fault Protection System

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Arc Fault Protection System D1000

Series 725 Programmable Alarm Annunciator

DIGITAL ALARM UNIT Model ALU-AP

Transcription:

Features Self-contained microprocessor-based annunciator unit with 64 alarm channels pplication larm channels activated by normally open or normally closed contact Small and large stand-alone annunciator applications Large centralized or distributed annunciator systems with event reporting Fully field-programmable by means of a portable programming module or via the serial interface Sixteen output relays, i.e. 14 for group realarms, one for an audible device and one for the self-supervision system The annunciator unit is used in a variety of applications requiring supervision of alarm and signalling contacts in power plants, substations and industrial process installations. The alarm unit is also approved for use in off-shore installations and marine applications. Further, the annunciator unit can be used in any application where on/off signals are to be supervised. The annunciator unit provides immediate fault recognition, fault identification and visual and audible alarm in an abnormal process situation. The annunciator unit also provides a means for subsequent fault analyses, Issued: pril 1999 Status: Revised Version: /07.10.2003 Data subject to change without notice Extensive communication with superior systems via the serial interface and the SP bus High immunity to electrical and electromagnetic interference Sophisticated hardware and software selfsupervision system for maximum operational reliability even under severe environmental conditions Powerful software support for parameterization of the annunciator units via the serial interface Member of the SPOM product family and s substation utomation system E marking according to the E directive for EM which means that corrective measures can be carried out without delay and full control of the process can be maintained. The annunciator units can be used as independent stand-alone units, or several units can be interconnected and connected to printers, terminals, etc. to form complete supervision, event sequence reporting and data acquisition systems. The maximum annunciator system capacity is 560 channels in one system and the resolution of the time marking is 10 milliseconds. The annunciator unit is a member of SP- OM, the ultimate integrated secondary equipment system for power systems. 1

Design 2 The annunciator unit is composed of ten modules, i.e. four alarm annunciator modules, four input/output modules, a connection module and a power module, housed in a rugged 19 inch subrack, height 3U (~133 mm). The annunciator units are normally mounted in 19 inch cabinets, but they can also be panelmounted. In the latter case the annunciator units can be provided with a raising frame, which reduces the depth behind the panel by 40 mm. Each alarm annunciator module includes alarm channels. The channels are activated by normally open or normally closed process contacts. The required 48 V dc contact circuit voltage is generated and supervised by the annunciator unit. Each channel can separately be assigned a start delay from 5 ms to 0 s. On activation of a channel the visual indicator of the channels starts blinking. One of five standardized blinking systems according to IS and DIN can be selected by the operator at commissioning. When several annunciator units are interconnected the total system works as a whole, which means that blinkings are synchronized, alarm signals from different subracks can be routed to the same group alarm output relay, etc. Each annunciator module is provided with an event register, which stores the last nine events of the module in chronological order. The event register can be read via the serial interface. The standard annunciator unit is provided with output relays, of which 14 normally are used as group alarm output relays, one is used for the control of a buzzer and one as alarm output relay for the selfsupervision system. If more output relays are needed an additional relay subrack type SO 128R4 can be used. The maximum capacity of the relay subrack is 128 relays. If additional grouping possibilities are needed the alarm signals from the can be wired via a grouping unit type SO 645. When the total annunciator system includes several units and the units are interconnected using wires type SWIR one of the units can be provided with a reset/test push-button module SWDM 31 the other being provided with a blank front plate. Data communication The annunciator unit is provided with a serial interface on the rear panel. y means of a bus connection module type SP-Z 17/S or SP-Z 21/S the unit can be connected to the fibre-optic SP bus. The bus connection module type SP-Z 21/S is powered from the host unit, whereas the bus connection module SP-Z 17/S is provided with a built-in power unit, which can be fed from an external secured power source. The unit communicates with higher-level data acquisition and control systems over the SP bus. Self-supervision The annunciator incorporates a sophisticated self-supervision system which increases the availability of the device and the reliability of the system. The self-supervision system continuously monitors the hardware and the software of the unit. The system also supervises the operation of the auxiliary supply module and the level of the electronics voltages generated by the module. If a permanent fault is detected, the fault indicator on the front panel of the faulty module is lit, the output relay of the self-supervision system operates and the outputs are blocked. uxiliary supply voltage The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module types are available: type SWSM 22048 with two inputs, 19 70 V dc and 80 265 V and type SWSM 220220, also with two inputs, 80 265 V dc and 80 265 V ac/dc. The power supply module forms the internal voltages required by the annunciator.

Technical data Table 1: larm channels larm channels per annunciator unit, max. 64 channels Type of contact types or signal types (default) reak contact Make or break contact without recognition of contact return Field contact voltage 48 V dc ±20% Loop current of closed field contact circuit 4 m ±20% hannel input and reset delay time, field-selectable 5 ms, 20 ms (default), 100 ms, 1 s, 5 s, 20 s, 60 s values or 0 s Table 2: External control input udible device reset larm acknowledge hannel reset Remote testing Local control Remote control The control voltage provided by the annunciator unit 48 V dc ±20% Table 3: Output relays outputs contacts Parallel lamp control outputs 64 contacts (with SO 128R4) udible device output 1 contact Self-supervision output 1 contact Output contact type make (by soldering a jumper also break) ontact ratings 3 /250 V, 50 Hz ontact breaking capacity of circuit L/R 40 ms and 1 /0.25 /0.15 48/110/220 V dc Table 4: Data communication Transmission mode oding Data transfer, selectable Electrical/optical bus connection module, powered from the host unit Electrical/optical bus connection module, powered from the host unit or from an external power source for plastic core cables for glass fibre cables for plastic core cables for glass fibre cables Table 5: uxiliary supply modules Fibre-optic serial bus SII 4800 or 9600 d SP-Z 21/S SP-Z 21MM/S SP-Z 17/S SP-Z 17MM/S Type of module SWSM 22048 Supply 1 19 70 V dc Supply 2 80 265 V ac/dc SWSM 220220 Supply 1 80 265 V dc Supply 2 80 265 V ac/dc Power consumption ~20 W 3

lock diagram Supply 1: 19...70V D or 80...265V D 4 Field contact supply, 48 V D Supply 2: 80-265V or D Supply Table 6: Tests and standards Test voltages - alarm and acknowledge/reset inputs to frame - output relay contacts to frame - auxiliary supply circuits to frame - inputs, outputs and supply circuits between themselves Dielectric test voltage (IE 60255-5) 2 kv, 50 Hz, 1 min Impulse test voltage (IE 60255-5) 5 kv, 1.2/50 µs, 0.5 J Disturbance tests HF test voltage (IE 60255-6) 2.5 kv, 1 MHz Environmental conditions mbient service temperature range -10 +55 mbient transport and storage -40 +70 temperature range Long term damp heat withstand <95%, +40, 56 d/a (IE 60068-2-3) Degree of protection by enclosure when IP 40 panel-mounted Weight ~8.1 kg hannel inputs 1... Remote silence and acknowledge inputs SP-bus connection Fig. 1 outputs, 1...4 lock diagram hannel inputs 17...32 Remote channel reset and test inputs outputs, 5...8 SP-bus, supervising bus and blocking bus = Field contact follower output = Lamp follower output = reflash output hannel inputs 33...48 hannel inputs 49...64 (Local/remote inputs) outputs, 9...12 outputs, 13... udible output Self-supervision output

Mounting and dimensions Ordering 19 subrack 7,5 Fig. 2 Dimensions (in mm) and panel cut-out for flush mounting Panel mounting 482,6 (19") 465 57,1 4 x ø8 The annunciator can also be flush mounted in doors and panels. The relevant panel cut-out and drilling pattern for the fixing screws are illustrated above. When ordering, please specify: 132,5 266 450 ±1 465 ±0,5 Ordering information Ordering example 1. Type designation and quantity, 5 pieces 2. Order number RS 811 644-3. uxiliary voltage U aux1 = 110 V dc, U aux2 = 220 V ac 4. ccessories Reset/test push-button unit SWDM 31, RS 962 031-, 5 pieces 5. Special requirements - Order numbers 57,1±0,5 133±1 case19 s without reset/test push-button unit SWDM 31-0, no channels RS 811 640-, - -1, incl. channels RS 811 641-, - -2, incl. 32 channels RS 811 642-, - -3, incl. 48 channels RS 811 643-, -, incl. 64 channels RS 811 644-, - Reset/test push-button unit SWDM 31 RS 962 031- Programming unit SO PM RS 891 071- The last two letters of the order number indicate the auxiliary voltage U aux of the annunciator unit as follows: -: input 1 = 80 265 V dc, input 2 = 80 265 V ac/dc (module SWSM220220) -: input 1 = 19 70 V dc, input 2 = 80 265 V ac/dc (module SWSM22048) 5

References Oy Substation utomation P.O. ox 699 FIN-65101 Vaasa, Finland Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation dditional information User s manual User s manual SO D1 User s manual SO 64D3 1MRS 752014-MUM 1MRS 750944-MUM 1MRS 751354-MUM