A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Similar documents
FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

Global Journal of Engineering Science and Research Management

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Heat transfer property of refrigerant-oil mixture in a flooded evaporator: The role of bubble formation and oil retention

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Energy and Buildings

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

A New Dedicated Outdoor Air System with Exhaust Air heat recovery

Heat pump and energy recovery systems

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger

Numerical analysis of flow characteristics of fire extinguishing agents in aircraft fire extinguishing systems

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Study on the Effects of Learning by Changing the Color- Temperature LED Lamp

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water Vapor for Industrial Furnace

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Recent Advances in Energy, Environment and Economic Development

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Oxyvap Evaporative Cooling Applications

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Purdue e-pubs. Purdue University

Effect of magnetic field on the performance of new refrigerant mixtures

2. HEAT EXCHANGERS MESA

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Enhancement of Heat Exchanger Performance by the Extended Surfaces-Fins

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

ENSC 388: Engineering Thermodynamics and Heat Transfer

Compression of Fins pipe and simple Heat pipe Using CFD

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Chilled Ceilings / Beams Working Principles & Applications

EXPERIMENTAL PERFORMANCE INVESTIGATION OF SWIRLING FLOW ENHANCEMENT ON FLUIDIZED BED DRYER

A REVIEW ON HEAT EXCHANGER

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Process Simulation and Optimization of Cryogenic Operations Using Multi-Stream Brazed Aluminum Exchangers

Thermal Performance of a Loop Thermosyphon

THE COOLING CAPACITY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Transcription:

Journal of Mechanical Science and Technology 23 (2009) 528~535 Journal of Mechanical Science and Technology www.springerlink.com/content/738-494x DOI 0.007/s2206-009-0426-0 A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface Kyungmin Kwak and Cheolho Bai * School of Mechanical Engineering, Yeungnam University, Kyungsan, 72-749, Korea (Manuscript Received March 4, 2009; Revised March 6, 2009; Accepted March 8, 2009) -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- Abstract Three types of flow passage structure of a total heat exchanger (perforated type, slit type, and embossed and perforated type ) are studied to enhance the heat exchange performance of a heat recovery ventilation system (total heat exchanger). The perforated type has four punched rows of 6mm holes in the flow passage channel, and the slit type has six processed rows of 40mm length. The embossed and perforated type has holes of about mm diameter and protrusions of about 0.2mm height on all surfaces. The heat exchange efficiency of the modified total heat exchanger was compared to that of a general total heat exchanger with a smooth surface. The Korean Standard (KS) heat recovery ventilator test condition was applied for tests. In the case of cooling operation based on a typical Reynolds number of 40 (typical air flow rate of 00 m 3 /hr), the perforated type, slit type, and embossed and perforated type showed temperature efficiency improvement of.2%, 2.5%, and 5.0%; latent efficiency improvement of 8.0%, 32.3%, and 24.5%; and enthalpy efficiency improvement of 7.9%,.5%, and.2%, respectively. The corresponding improvements of heating operation were 3.0%, 3.4%, and 4.0%; 5.0%, 6.6%, and 8.7%; 3.2%, 4.3%, and 7.7%, respectively. On the other hand, the air pressure drop throughout the modified flow passage of the total heat exchanger increased by up to.7% at the typical Reynolds number of 40, from the air pressure drop of the regular total heat exchanger. Keywords: Heat recovery ventilation system (total heat exchanger); Enhancement of heat and moisture transfer; Temperature efficiency; Latent efficiency; Enthalpy efficiency --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------. Introduction This paper was recommended for publication in revised form by Associate Editor Dae Hee Lee * Corresponding author. Tel.: +82 53 80 2575, Fax.: +82 53 80 4627 E-mail address: chbai@yu.ac.kr KSME & Springer 2009 As the demand for refreshing indoor atmosphere and healthier environment increases, there have been many studies related to ventilation systems. To maintain a comfortable indoor atmosphere, it must be ventilated with the outside air, and this ventilation causes the energy loss of cooled or heated indoor air. One of the methods which can reduce such energy loss and, at the same time, improve indoor air quality (IAQ) using the ventilator is to apply the heat recovery ventilation system [-5]. Among the heat recovery ventilation systems, especially in high temperature and high humidity regions, a ventilation system which simultaneously processes both sensible heat and latent heat is needed; currently, membrane filter type total heat exchangers (a total heat exchanger or enthalpy exchanger with hydrophilic membrane cores) are used. A total heat exchanger uses a thin membrane material film which allows heat transfer and partial moisture transpiration between two fluids. Total heat exchangers found in the current market, like the one shown in Fig., generally have direct cross flows without a mixture of hot and cold air, and each flow passage is a corrugated type (front view in Fig. ). The surface of the corrugated shape is a smooth flow passage due to the production simplicity and the special characteristics of paper. (Top view in Fig. ) Zhang and Jiang [6] evaluated the performance of a

529 K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 Outdoor chamber Indoor chamber Total heat exchanger Blower EA RA Supply air SA Return air OA AHU Blower AHU Measuring point for dry/wet bulb temperature Flow passage Front view Top view Fig.. Schematic view and flow passage for general total heat exchanger. membrane type total heat exchanger by introducing a mathematical model of heat and moisture transfer. Zhang and Niu [7] proposed a formula related to the calculation of the effectiveness of a total heat exchanger from the NTU (number of transfer unit) for heat and mass transfer. Zhang [8], using the real boundary condition between the surface and flow of a total heat exchanger, indicated the characteristics of heat transfer and mass transfer as a Nusselt number and a Sherwood number, respectively. Bai et al. [9] experimentally evaluated the heat transfer characteristics of a total heat exchanger at various operating conditions. Since most studies evaluated existing total heat exchangers, a detailed study on the performance increase of a total heat exchanger is necessary. In the case of a metal heat exchanger, the corrugated shape of the flow passage distributes the flow evenly and acts as a fin, which increases the heat transfer area and improves the overall heat transfer. However, in the case of the total heat exchanger, the corrugated shape of the flow passage does not act as a fin due to the low thermal conductivity of the paper material. The heat transfer enhancement method of common compact heat exchangers can be applied to the total heat exchanger. The well known method of breaking the boundary layer and creating turbulent intensity through the flow passage gives good heat transfer even in a total heat exchanger. Since the air flow rate through the total heat exchanger is relatively low, the effect of heat transfer enhancement in this range is expected to be greater in the total heat exchanger. Compact type heat exchangers use a variety of meth- Fig. 2. Schematic view for facility of 2-chamber type. ods to improve heat transfer performance, one of these methods being the application of flow passage structures such as the louvered fin type, perforated fin type, slit fin type, wavy fin type and offset strip fin type [0]. Louvered type or offset strip type is difficult to apply because of their complicated shapes to total heat exchanger made of paper material. Rather, a simple flow passage structure shall be selected. The above well known method of heat transfer enhancement for a compact heat exchanger is applied for a relatively high Reynolds number. When the heat transfer enhancement technology for metal materials is applied to the total heat exchanger, the degree of heat transfer enhancement in the range of small Reynolds numbers of a typical operation range of a total heat exchanger must be confirmed. This study focuses on this confirmation. The result from this study contributes to the heat transfer enhancement of a total heat exchanger with both sensible heat transfer and latent heat transfer. 2. Test apparatus 2. Apparatus and method of the test To evaluate the performance of a total heat exchanger, the present study used a standard calorimeter. The performance tests were conducted in according to the Korean Standard KS B 6879 []. The calorimeter has two rooms. One simulates the indoor air conditions and the other the outdoor air conditions, required. Fig. 2 indicates the block diagram of the 2room method, and the size of each chamber was 3.5 (W) x 3.0 (D) x 3.2 (H) m. The AHU is an airconditioning unit that controls the temperature and humidity conditions in the chambers. The total heat exchanger was installed between indoor and outdoor chambers, and other spaces were isolated by using a polyurethane insulating panel of 0.m in thickness.

530 K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 The total heat exchanger was connected to blowers and wind tunnels, which were installed in the indoor chamber (SA side) and outdoor chamber (EA side). When flow is generated between these chambers with different temperature conditions, outside air (OA) will flow indoor through the total heat exchanger, and simultaneously, the room air (RA) for ventilation will be exhausted outdoor (EA) through the total heat exchanger. Meanwhile, the outside air and the room air process heat and moisture transfer through the total heat exchanger. Air-sampling sensors were placed at three different spots to measure the dry bulb and wet bulb temperatures of air. The air flow rate through the total heat exchanger was measured by a differential pressure meter installed at the nozzle on the wind tunnel. When both the indoor and outdoor chambers stabilized (it usually took two more hours), data such as dry bulb temperature, wet bulb temperature, air flow rate, etc., were measured for ten minutes. This procedure was repeated three times. Once the test results fell within an acceptable degree of less than % of each other, the average of the measured data was used as the performance result of the total heat exchanger. Fig. 3. Schematic view and flow passage for modified total heat exchangers. 2.2 The test elements and conditions This study designated three types of modification in the flow passage structure of a total heat exchanger: first, the perforated type structure with holes processed on the surface flow passage of corrugated shapes; second, the slit type structure with slits processed; and third, the embossed and perforated type structure with both embossing works and holes processed. Fig. 3(a) shows the perforated type with four rows of 6mm diameter holes processed parallel to the direction of flow. Fig. 3(b) shows the slit type with six rows of slits of 40mm in length. Fig. 3(c) shows the embossed and perforated type with approx..0mm diameter holes and approx. 0.2mm height protrusions all over the field of flow passage. The Fig. 3(d) shows an element of the total heat exchanger made by stacking each type of flow passage on layers. The total heat exchangers have direct cross flows without the mixture of hot and cold air. Although these heat transfer enhancement methods using structural modifications are used in general compact heat exchangers, they have never been used or evaluated in total heat exchangers made of paper material. An existing total heat exchanger shown in Fig. as well as each type of Fig. 4. Schematic view an element installed in acrylic chamber. the modified total heat exchangers was installed in the acryl cases, as shown in Fig. 4, to evaluate the heat exchange performance. The size of the heat exchanger was 220 (W) 220 (D) 245 (H)mm, and the typical air flow rate was 00CMH (m 3 /hr) (corresponding Reynolds number of about 40). All other specifications such as size of total heat exchanger, pitch and height of the corrugated shape, etc., except the surface structure, were the same, and Table shows specifications of each type of the modified total heat exchangers. The test condition of KS B6879 [] was selected for the evaluation of ventilation performance. In the case of cooling operation, the dry bulb temperature and wet bulb temperature were at 27 and 9.5 for indoor (corresponds to absolute humidity: 0.06 kg/kg dry air ), and 35 and 24 (corre-

K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 53 Table. Specifications of each type of total heat exchanger. Spec. General type Perforated type Slit type Embossed and perforated type Width length height 220 220 245 [mm] Corrugated number, pitch/one plate 52ea, 4mm Number of plate (one side flow) [ea] 65 Flow passage Corrugated structure Surface condition Smooth Four rows of 6mm diameter holes Six row of slit of 40mm in length Approx..0mm diameter holes and approx. 0.2mm height protrusions sponds to absolute humidity:0.0438 kg/kg dry air ) for outdoor, respectively. In the case of heating, the dry bulb temperature and wet bulb temperature were at 20 and 5 for indoor (corresponds to absolute humidity:0.008620 kg/kg dry air ), and 7 and 6 (corresponds to absolute humidity:0.005409 kg/kg dry air ) for outdoor, respectively. Since the incoming air to the total heat exchanger in the cooling operation has much more water vapor than that in heating operation, moisture transfer enhancement will greatly affect the efficiency of the total heat exchanger in cooling operation. 2.3 Data reduction The heat exchange efficiencies indicating the performance of the total heat exchangers are the temperature efficiency from the measured dry bulb temperature, latent efficiency from the absolute humidity, and enthalpy efficiency from enthalpy. Eq. () defines these efficiencies. x = x OA SA ε () xoa xra where, ε indicates temperature, latent and enthalpy efficiencies, and the corresponding measured values of x are dry bulb temperature, absolute humidity, and enthalpy of the air. The subscripts SA, OA, and RA in formula () indicate supplied air, outside air, and ventilation air, respectively. The effective ventilation volumes of the total heat exchangers were measured according to KS B 6879 [], and the leak rate was measured by using the CO 2 measurement method. The CO 2 concentration was analyzed by gas chromatography. Eq. (2) indicates the leak rate R, and formula (3) indicates the effective ventilation volume Q E considering the leak rate. R Q B B SA OA = (2) BRA BOA E = Q ( R) (3) S The leak rates of the modified total heat exchanger and the general total heat exchanger with a smooth surface were about 0%. The calorimeter that was used satisfied the KS B 6879 [] with respect to the accuracies of measurement devices. An uncertainty analysis was carried out by the method of Kline and McClintock [2]. For the typical Reynolds number of 40, the uncertainties of the temperature efficiency, latent efficiency and enthalpy efficiency were %, 2.5% and 3.4% for the cooling operation, and %, % and.4% for the heating operation, respectively. The error of the Reynolds number was estimated to be %. 3. Discussion Fig. 5 shows the temperature efficiency of the modified total heat exchangers and the general total heat exchanger with respect to a Reynolds number, under KS cooling operation. The Reynolds number varied from 05 to 280 (corresponding to 75-200CMH based on air flow rate). Temperature efficiency decreases as the Reynolds number increases, showing a tendency similar to the general air-to air heat exchanger. The temperature efficiency of the modified total heat exchanger is slightly higher than that of the general total heat exchanger with a smooth surface in the entire range of Reynolds numbers. For a typical Reynolds number of 40, which corresponds to the typical air flow rate of the total heat exchanger tested, the temperature efficiencies of the perforated type, slit type, and embossed and perforated type increase by.2%, 2.5% and 5.0% respectively, from that of the general heat exchanger. Fig. 6 shows the result of latent efficiency under KS cooling operation. The latent efficiency of the modified total heat exchanger is much higher than that of

532 K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 general heat exchangers with a smooth surface in the entire range of Reynolds numbers. For a typical Reynolds number of 40, the latent efficiencies of the perforated type, slit type, and embossed and perforated type increase by 8.0%, 32.2% and 24.5% respectively, from that of the general heat exchanger. Since moisture transfer enhancement greatly affects the performance of a total heat exchanger in cooling operation (humid condition), these significant increases of latent efficiency accelerate the energy performance in a total heat exchanger. The slit type heat exchanger shows the largest latent efficiency. Although we were able to obtain a large increment in latent efficiency, additional study would be necessary to propose the optimum flow passage structure considering the arrangement and size of the slit. The modified flow passage structure gave a larger increase in latent efficiency than in temperature efficiency, compared to the general heat exchanger. Since the temperature efficiency even in the general total heat exchanger is high (about 95%) already, there is not much room for further increase of efficiency. However, the typical latent efficiency in cooling operation for the total heat exchanger is quite low. In view of this, the modified total heat exchanger has a larger probability for increase of moisture transfer than for increase of temperature transfer. Fig. 7 shows the result of the enthalpy efficiency considering the temperature and latent efficiencies together under KS cooling operation. For the typical Reynolds number of 40, the enthalpy efficiencies of the perforated type, slit type, and embossed and perforated type increase by 7.9%,.5% and.2%, respectively, from the that of the general total heat exchanger. The large increase in latent efficiency results in a large increase in enthalpy efficiency. Figs. 8, 9 and 0 show the temperature efficiency, latent efficiency, and enthalpy efficiency with respect to Reynolds numbers under KS heating operation. As in the cooling operation, the efficiencies of the modified total heat exchangers are higher than those of the general total heat exchanger in the whole range of Reynolds numbers. For a typical Reynolds number of 40, the perforated type, slit type, and embossed and perforated type show increases in temperature efficiency of 3.0%, 3.4% and 4.0%, increases in latent efficiency of 5.0%, 6.6%, and 8.7%, and increases in enthalpy efficiency of 3.2%, 4.3%, and 7.7%, respetively, from that of the general total heat exchanger. Though the efficiencies of the modified total heat ex- Temperature efficiency Fig. 5. Temperature efficiency for the modified total heat exchangers and the general total heat exchanger with respect to Reynolds number (cooling operation). Latent efficiency Fig. 6. Latent efficiency for the modified total heat exchangers and the general total heat exchanger with respect to Reynolds number (cooling operation). Enthalpy efficiency Fig. 7. Enthalpy efficiency for the modified total heat exchangers and the general total heat exchanger with respect to Reynolds number (cooling operation).

K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 533 changers in heating operation are still high compared to that of the general total heat exchanger, the increases of the efficiencies are slightly less than those in cooling operation. Since the flow resistance in a modified flow passage may increase, it is necessary to evaluate the pressure drop of air through the total heat exchanger. Fig. and Fig 2 show the pressure drop of the total heat exchanger for the variation of Reynolds number under KS cooling and heating operations. The pressure drop is defined as the pressure difference of the air through the tested total heat exchanger. The pressure drop of the modified total heat exchanger is similar to that of the general total heat exchanger in the entire range of Reynolds numbers, in case of cooling operation. In the case of heating operation, the pressure drop of the modified total heat exchanger slightly increases as the Reynolds number increases. The increase of pressure drop is about.7% in the typical operation range (Reynolds number of 40), which is much less than the increment of efficiency of the modified total heat exchanger. Fig. 3 and Fig. 4 show the result of enthalpy efficiency for the variation of pressure drop of the total heat exchanger under KS cooling and heating operations. Here, the increase of pressure drop for a total heat exchanger represents the increase of the Reynolds number (air flow increase) for each total heat exchanger. Since the pressure drop of the modified total heat exchanger is not much different from that of the general total heat exchanger, the increase of enthalpy efficiency shows the same tendency, as shown in Fig. 7 and Fig. 0. In the case of cooling operation, the tested total heat exchangers of the modified flow passage show an increase of enthalpy efficiency from the general total heat exchanger. The slit type and the embossed and perforated type show the largest enthalpy efficiency. In the case of heating operation, the enthalpy efficiency of embossed and perforated type is the largest, and the slit type and perforated types show nearly the same efficiency. The above results show that the modified total heat exchanger increases the exchange efficiency at a modest expense of an additional pressure drop. In the modified flow passage structures applied in the study, the exchange efficiency increased in the following order: the perforated type, slit type, and embossed and perforated type. It is believed the modified total heat exchanger is effective for improving the performance of the total heat exchangers currently in use. Temperature efficiency Fig. 8. Temperature efficiency for the modified total heat exchangers and the general total heat exchanger with respect to Reynolds number (heating operation). Latent efficiency Fig. 9. Latent efficiency for the modified total heat exchangers and the general total heat exchanger with respect to Reynolds number (heating operation). Enthalpy efficiency Fig. 0. Enthalpy efficiency for the modified total heat exchangers and the general total heat exchanger with respect to Reynolds number (heating operation).

534 K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 0 Purssure drop [Pa] -20-40 -60-80 -00-20 -40-60 Enthalpy efficiency -60-40 -20-00 -80-60 -40-20 Pressure drop [Pa] Fig.. Pressure drop of total heat exchanger for the variation of Reynolds number (cooling operation). Fig. 4. Enthalpy efficiency for the variation of pressure drop (heating operation). 4. Conclusions Purssure drop [Pa] 0-20 -40-60 -80-00 -20-40 -60 Fig. 2. Pressure drop of total heat exchanger for the variation of Reynolds number (heating operation). Enthalpy efficiency -60-40 -20-00 -80-60 -40-20 Pressure drop [Pa] Fig. 3. Enthalpy efficiency for the variation of pressure drop (cooling operation). An experimental study was performed to increase the exchange efficiency of total heat exchangers. The present study utilized heat transfer enhancement technology, which was applied in a compact type heat exchanger, and evaluated the degree of enhancement of heat and moisture transfers in the range of low Reynolds numbers. The exchange efficiencies of the modified total heat exchangers were compared with that of the general total heat exchanger having smooth surface. The conclusions are as follows: () The heat exchange efficiencies of the perforated type, slit type, and embossed and perforated type total heat exchangers were greater than that of the general total heat exchanger with a smooth surface. Especially, for a typical Reynolds number of 40 (air flow rate of 00CMH) under KS cooling operation, it was shown that the increases in the temperature efficiency were.2%, 2.5%, and 5.0%; the increases in latent efficiency were 8.0%, 32.0% and 24.5%; and the increases in enthalpy efficiency were 7.9%,.5%, and.2%, respectively. The corresponding enhancement of heating operation were 3.0%, 3.4%, and 4.0%; 5.0%, 6.6%, and 8.7%; 3.2%, 4.3%, and 7.7%, respectively. (2) The modified total heat exchangers showed a slight increase of pressure drop compared to the pressure drop of a general total heat exchanger. (3) The modified flow passage structure applied in this study was reviewed from a manufacturing point of view, and it is judged to be applicable to the existing general total heat exchanger.

K. Kwak and C. Bai / Journal of Mechanical Science and Technology 23 (2009) 528~535 535 Acknowledgements This research was supported by the Yeungnam University research grants in 2007. References [] J. Dieckmann, K. W. Roth and J. Brodrick, Air-to- Air Energy Recovery Heat Exchangers, ASHRAE Journal, 45 (8) (2003) 57-58. [2] M. Fehrm, W. Reiners and M. Ungemach, Exhaust Air Heat Recovery in Building, International Journal of Refrigeration, 25 (4) (2002) 439-449. [3] E. Juodis, Extracted Ventilation Air Heat Recovery Efficiency as a Function of a Building's Thermal Properties, Energy and Buildings, 38 (6) (2006) 568-573. [4] R. M. Lazzarin and A. Gasparella, Technical and Economical Analysis of Heat Recovery in Building Ventilation System, Applied Thermal Engineering, 8 (-2) (998) 47-67. [5] S. M. Kim, B. Y. Park and J. Y. Sohn, Evaluation of the Performance and the Energy Consumption Characteristics of Heat Recovery Ventilation in Apartments, Korean Journal of Air-conditioning and Refrigeration Engineering, 7 (5) (2005) 496-504. [6] L. Z. Zhang and Y. Jiang, Heat and Mass Transfer in a Membrane-Based Energy Recovery Ventilator, Journal of Membrane Science, 63 (999) 29-38. [7] L. Z. Zhang and J. L. Niu, Effectiveness Correlations for Heat and Moisture Transfer Processes in an Enthalpy Exchanger with Membrane Cores, ASME J. Heat transfer, 22 (5) (2002) 922-929. [8] L. Z. Zhang, Heat and Mass Transfer in a Cross- Flow Membrane-Based Enthalpy Exchanger under Naturally Formed Boundary Conditions, International Journal of Heat and Mass Transfer, 50 (2007) 5-62. [9] C. H. Bai, Y. H. Lim, D. Gulnora, J. Y. Park, K. M. Kwak, E. S. Chu, Y. S. Kim and J. Y. Kim, A Study on the Characteristic of Total Heat Exchanger under Various Conditions, Korean Journal of Air-Conditioning and Refrigeration Engineering, 7 (0) (2005) 89-897. [0] R. L. Webb, Principles of Enhanced Heat Transfer, Wiley, New York, (994) 87-24. [] KS B 6879, Heat Recovery Ventilators, (2003). [2] S. J. Kline and F.A. McClintock, Describing Uncertainties in Single Sample Experiments, Mechanical Engineering, 75 (953) 3-8. Kyungmin Kwak received his B.S., M.S. and Ph.D. degrees in Mechanical Engineering from Yeungnam University, Korea, in 993, 995 and 999, respectively. Dr. Kwak is currently a Researcher at the Automotive RIC at Kyungil University, Korea. His research interests include heat transfer, refrigeration and air control. Cheolho Bai received his B.S. and M.S. degrees in Mechanical Engineering from Seoul Na-tional University, Korea, in 984 and 986, respectively. He then received his Ph.D. from UCLA, USA, in 992. Dr. Bai is currently a Professor at the School of Mechanical Engineering at Yeungnam University in Kyungsan, Korea. His research interests include heat transfer, refrigeration and air control.