A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Similar documents
Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

PANELBOARDS & BUILDING DISTRIBUTION

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

PART GENERAL 1.01 SECTION INCLUDES

SECTION ENCLOSED CONTROLLERS

SECTION AUTOMATIC TRANSFER SWITCHES

A. This Section includes transfer switches rated 600 V and less, including the following:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION LIGHTING CONTROL DEVICES

A. This Section includes the following lighting control devices:

CONTENTS AUTOMATIC TRANSFER SWITCHES

A. This Section includes the following lighting control devices:

Emery County Senior Center Green River 06/07

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

Molded Case Circuit Breakers, Bulletin 140G

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

performed by City of Virginia Beach Public Utilities

SECTION ISOLATED POWER SYSTEMS

IN2 Lighting Control Devices

SECTION AUTOMATIC TRANSFER SWITCHES

TECHNICAL STANDARDS SECTION

LIGHTING CONTROL DEVICES

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

Element D Services Electrical

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

DIVISION 16 ELECTRICAL

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

PowerWave 2 Busway System

Coalition for the Homeless Men s Service Center Orlando, Florida PDGI Project Number: 965

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Allegany College of Maryland ACM Welcome Center M&D Project No

SECTION AUTOMATIC TRANSFER SWITCH

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

SECTION ELECTRICAL GENERAL PROVISIONS

UFGS (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

SECTION (16140) - WIRING DEVICES

SECTION FAN COIL UNITS

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

SECTION (15767) - UNIT HEATERS

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

SECTION BASIC ELECTRICAL MATERIALS AND METHODS. A. This Section includes basic electrical materials and methods including:

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

CADDY CORPORATION. Utility Distribution Systems

SECTION LIGHTING CONTROLS

SECTION CENTRIFUGAL WATER CHILLERS

Engineered Solutions SYSTEMS CUSTOM ENGINEERED TO YOUR SPECIFICATIONS. Fused Coordination Panelboards...ES 2. Fusible Shunt Trip Switch..

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features:

Schneider Electric ibusway for Data Center: Schneider Electric Powerbus Plug-In Busway

SECTION EXTERIOR LIGHTING

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

3. Provide revised typed circuit directory in panelboards that have circuits removed.

Powerohm Resistors Digital HRG System

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

National Electrical Code

B. Section Transfer Switches: Automatic transfer switch.

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

Guide Specification Model CTG Automatic Transfer Switch

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION GENERATOR PARALLELING CONTROLS

NECA 169. Standard for Installing and Maintaining Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs)

SECTION ELECTRIC WATER HEATERS

FIRE ALARM: BY OTHERS, IF REQUIRED.

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION DOMESTIC WATER HEATERS

FIRE ALARM: BY OTHERS, IF REQUIRED.

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

PART 4 ELECTRICAL STANDARDS

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

SECTION FIRE ALARM SYSTEMS

Division 26 ELECTRICAL TABLE OF CONTENTS

INVITATION TO TENDER ITT NO. PS KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

XP Series Non-Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

H Replace Emergency Generator Delmina Woods Youth Center Gentry Residential Treatment Center

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

GROUND FAULT PROTECTION PANELs. the power to protect GPD/GPFJ TYPES GPD, GPFJ, GPAD AND GPAFJ

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

Transcription:

SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance: Panelboards shall withstand the effects of earthquake motions. 1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to seismic forces. SUBMITTALS B. Product Data: For each type of product indicated. C. Shop Drawings: For each panelboard and related equipment. 1. Include dimensioned plans, elevations, sections, and details. Show tabulations of installed devices, equipment features, and ratings. 2. Detail enclosure types and details for types other than NEMA 250, Type 1. 3. Detail bus configuration, current, and voltage ratings. 4. Short-circuit current rating of panelboards and overcurrent protective devices. 5. Include evidence of NRTL listing for series rating of installed devices. 6. Detail features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components. 7. Include wiring diagrams for power, signal, and control wiring. 8. Include time-current coordination curves for each type and rating of overcurrent protective device included in panelboards. D. Seismic Qualification Certificates: Submit certification that panelboards, overcurrent protective devices, accessories, and components will withstand seismic forces defined in Division 26 Section "Vibration and Seismic Controls for Electrical Systems." E. Field quality-control reports. F. Panelboard schedules for installation in panelboards. G. Operation and maintenance data. DMR Project #3578 262416-1 Panelboards

1.3 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. Comply with NEMA PB 1. C. Comply with NFPA 70. 1.4 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace transient voltage suppression devices that fail in materials or workmanship within specified warranty period. 1. Warranty Period: Five years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 GENERAL REQUIREMENTS FOR PANELBOARDS A. Fabricate and test panelboards according to IEEE 344 to withstand seismic forces defined in Division 26 Section "Vibration and Seismic Controls for Electrical Systems." B. Enclosures: Flush- and surface mounted cabinets. 1. Rated for environmental conditions at installed location. a. Indoor Dry and Clean Locations: NEMA 250, Type 1. b. Outdoor Locations: NEMA 250, Type 3R. c. Kitchen and Wash-Down Areas: NEMA 250, Type 4X, stainless steel. d. Other Wet or Damp Indoor Locations: NEMA 250, Type 4. 2. Front: Secured to box with concealed trim clamps. For surface-mounted fronts, match box dimensions; for flush-mounted fronts, overlap box. 3. Hinged Front Cover: (Door-in-door) Entire front trim hinged to box and with standard door within hinged trim cover. 4. Directory Card: provide metal frame for panel schedule. C. Incoming Mains Location: Top and bottom. D. Phase, Neutral, and Ground Buses: Hard-drawn copper, 98 percent conductivity. E. Conductor Connectors: Suitable for use with conductor material and sizes. 1. Material: Hard-drawn copper, 98 percent conductivity. 2. Main and Neutral Lugs: Compression type. 3. Ground Lugs and Bus Configured Terminators: Compression type. DMR Project #3578 262416-2 Panelboards

4. Feed-Through Lugs: Compression type, suitable for use with conductor material. Locate at opposite end of bus from incoming lugs or main device. 5. Subfeed (Double) Lugs: Compression type suitable for use with conductor material. Locate at same end of bus as incoming lugs or main device. F. Service Equipment Label: NRTL labeled for use as service equipment for panelboards with one or more main service disconnecting and overcurrent protective devices. G. Future Devices: Mounting brackets, bus connections, filler plates, and necessary appurtenances required for future installation of devices. H. Panelboard Short-Circuit Current Rating: Rated for series-connected system with integral or remote upstream overcurrent protective devices and labeled by an NRTL. Include size and type of allowable upstream and branch devices, and listed and labeled for series-connected shortcircuit rating by an NRTL. I. Panelboard Short-Circuit Current Rating: Fully rated to interrupt symmetrical short-circuit current available at terminals. 2.2 DISTRIBUTION PANELBOARDS A. Manufacturers: Subject to compliance with requirements, provide the following or approved equal: 1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric. B. Panelboards: NEMA PB 1, power and feeder distribution type. C. Doors: Secured with vault-type latch with tumbler lock; keyed alike. D. Mains: Circuit breaker or Lugs only, as indicated. E. Branch Overcurrent Protective Devices: For Circuit-Breaker Frame Sizes 125 A and Smaller: Plug-in circuit breakers. F. Branch Overcurrent Protective Devices: For Circuit-Breaker Frame Sizes Larger Than 125 A: Bolt-on circuit breakers; plug-in circuit breakers where individual positive-locking device requires mechanical release for removal. G. Branch Overcurrent Protective Devices: Fused switches. 2.3 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS A. Manufacturers: Subject to compliance with requirements, provide the following or approved equal: DMR Project #3578 262416-3 Panelboards

1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric. B. Panelboards: NEMA PB 1, lighting and appliance branch-circuit type. C. Mains: Circuit breaker or lugs only, as indicated. D. Branch Overcurrent Protective Devices: Plug-in circuit breakers, replaceable without disturbing adjacent units. E. Contactors in Main Bus: NEMA ICS 2, Class A, electrically held, general-purpose controller, with same short-circuit interrupting rating as panelboard. 1. External Control-Power Source: 120-V branch circuit. F. Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike. G. Column-Type Panelboards: Narrow gutter extension, with cover, to overhead junction box equipped with ground and neutral terminal buses. 2.4 DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES A. Manufacturers: Subject to compliance with requirements, provide the following or approved equal: 1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric. B. Molded-Case Circuit Breaker (MCCB): Comply with UL 489, with interrupting capacity to meet available fault currents. 1. Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads, and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 250 A and larger. 2. Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with frontmounted, field-adjustable trip setting. 3. Electronic trip circuit breakers with rms sensing; field-replaceable rating plug or fieldreplicable electronic trip; and the following field-adjustable settings: a. Instantaneous trip. b. Long- and short-time pickup levels. c. Long- and short-time time adjustments. d. Ground-fault pickup level, time delay, and I2t response. 4. Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller; let-through ratings less than NEMA FU 1, RK-5. DMR Project #3578 262416-4 Panelboards

5. GFCI Circuit Breakers: Single- and two-pole configurations with Class A ground-fault protection (6-mA trip). 6. Ground-Fault Equipment Protection (GFEP) Circuit Breakers: Class B ground-fault protection (30-mA trip). 7. Arc-Fault Circuit Interrupter (AFCI) Circuit Breakers: Comply with UL 1699; 120/240- V, single-pole configuration. 8. Molded-Case Circuit-Breaker (MCCB) Features and Accessories: a. Standard frame sizes, trip ratings, and number of poles. b. Lugs: Compression style, suitable for number, size, trip ratings, and conductor materials. c. Application Listing: Appropriate for application; Type SWD for switching fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity discharge (HID) lighting circuits. d. Ground-Fault Protection: Integrally mounted relay and trip unit with adjustable pickup and time-delay settings, push-to-test feature, and ground-fault indicator. e. Communication Capability: Circuit-breaker-mounted communication module with functions and features compatible with power monitoring and control systems f. Shunt Trip: 120V trip coil energized from separate circuit, set to trip at 75 percent of rated voltage. g. Handle Padlocking Device: Fixed attachment, for locking circuit-breaker handle in on or off position. h. Handle Clamp: Loose attachment, for holding circuit-breaker handle in on position. C. Fused Switch: NEMA KS 1, Type HD; clips to accommodate specified fuses; lockable handle. 1. Fuses, and Spare-Fuse Cabinet: Comply with requirements specified in Division 26 Section "Fuses." 2.5 ACCESSORY COMPONENTS AND FEATURES A. Portable Test Set: For testing functions of solid-state trip devices without removing from panelboard. Include relay and meter test plugs suitable for testing panelboard meters and switchboard class relays. PART 3 - EXECUTION 3.1 INSTALLATION A. Receive, inspect, handle, store and install panelboards and accessories according to NECA 407 B. Mount top of trim 90 inches (2286 mm) above finished floor unless otherwise indicated. C. Mount panelboard cabinet plumb and rigid without distortion of box. Mount recessed panelboards with fronts uniformly flush with wall finish and mating with back box. D. Install overcurrent protective devices and controllers not already factory installed. DMR Project #3578 262416-5 Panelboards

1. Set field-adjustable, circuit-breaker trip ranges. E. Install filler plates in unused spaces. F. Stub four 1-inch (27-GRC) empty conduits from panelboard into accessible ceiling space or space designated to be ceiling space in the future. Stub four 1-inch (27-GRC) empty conduits into raised floor space or below slab not on grade. G. Arrange conductors in gutters into groups and bundle and wrap with wire ties. H. Comply with NECA 1. 3.2 IDENTIFICATION A. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs complying with Division 26 Section "Identification for Electrical Systems." B. Create a directory to indicate installed circuit loads and incorporating Owner's final room designations. Obtain approval before installing. Use a computer or typewriter to create directory; handwritten directories are not acceptable. C. Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." D. Device Nameplates: Label each branch circuit device in distribution panelboards with a nameplate complying with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." 3.3 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Acceptance Testing Preparation: 1. Test insulation resistance for each panelboard bus, component, connecting supply, feeder, and control circuit. 2. Test continuity of each circuit. C. Tests and Inspections: 1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters. 2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest. D. Panelboards will be considered defective if they do not pass tests and inspections. DMR Project #3578 262416-6 Panelboards

E. Prepare test and inspection reports, including a certified report that identifies panelboards included and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action. END OF SECTION 262416 DMR Project #3578 262416-7 Panelboards