Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Similar documents
Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

LMA LINE MONITOR ALERT USER S MANUAL

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Protocol Station Remote Alarm

Expanded Backup Control Installation & Operator s Instruction Manual

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

ion Genesis Pump Controller

Single Station Remote Alarm

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Non-Programmable Digital Thermostat

Operating Instructions Model 4400/VC-115V Portable Powder Filler (115VAC. Model)

MaxLite LED Vapor Tight Linear Fixture

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

HotPoly Tote Tank / IBC Heaters (TTH Series)

Installation Manual. THM-0100 Setpoint Thermostat Version THM HBX Control Systems Inc.

Instruction Manual Model L2 RF Switch

OPERATION, SERVICE & PARTS MANUAL

2-Port alarmcharge Hub - Manual

RAM3 Remote Alarm Module

(HSTAT Series) Instruction Manual

INSTALLATION & OPERATION MANUAL

OWNER'S MANUAL T0140. Contents Page #

Controllers. Instruction Manual WARNING

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Instruction Manual WARNING

CT2 Retro Box Installation Instruction Manual

User's Manual H-VC5. Chore-Logic. H-VC5 User manual. Version HPS 11/11/2006 User manual 1.02 ST50737MA 3/07. Page 1

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

OWNERS MANUAL For IN ROOM BREWING SYSTEM MODEL REFILLABLE CAPSULES K901. Includes: Installation Use & Care Servicing Instructions

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS!

ELECTRIC FIREPLACE HEATER WITH SINGLE GLASS DOOR

Air Pump Up to 800 gallons

Model 20201/20201-A/20201-B Wind Sensor Heater. User's Manual. All Weather Inc National Drive Sacramento, CA USA

Spa Control System OWNER S MANUAL

PSW112 Owners Manual. Platinum Series Subwoofer. Models. PSW112 Powered Subwoofer

5+2 DAY. Digital Thermostat. residential. & 1-cool. up to 2-heat PROGRAMMABLE THERMOSTAT. Venstar Inc. 05/08

SONANCE GARDEN SERIES SGS SYSTEM INSTRUCTION MANUAL

IN-GROUND SUBWOOFER INSTRUCTION MANUAL LS12T SUB LS15T SUB

Owner & Operator s Manual. Table of Contents

LiqTec, V GRUNDFOS INSTRUCTIONS

STATUS ALARM HISTORY ALARM RESET

IMPORTANT SAFETY INFORMATION:

FW-RA-LED Remote Multiplex Annunciator Panels

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Owner s Manual Use with most Heat Pump systems: 1-Heat, 1-Cool 2-Heat, 1-Cool

SAFETY INFORMATION AND WARNINGS

BLT-999W-2 Item # 60757

36 IN. ELECTIC FIREPLACE FMI MODEL # LEF36 Mounting Base Feet and Wall Mounting Bracket Included

RATIO:GUARD Model E-1S EC Monitor

1022 R/T Remote Monitor

ELECTRIC FIREPLACE OWNER S MANUAL

MaxLite LED MICRO-T PANEL

MaxLite LED VAPOR TIGHT LINEAR FIXTURES

ASG EZ-9000GR Tape Dispenser User Manual ASG #66136

Operations Manual. Motion Detector Module Model ZS10

Remote Relay Module (RRM)

MaxLite 4, 6, 8 & 9 LED Architectural & Commercial Downlights

SPILLSTOP ULTRA Alarm Controller with Hose Protection Overfill Prevention System

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

Bench Top Ionizer Installation, Operation and Maintenance

Multiple Boilers Electro TS Series Application EB-C-STG5

Owner s Manual. Digital. Heat Pump. 5+2 Day Programmable. Model S1-THEH21P5S HVAC SERVICE PARTS TM

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

OWNERS MANUAL MODEL EXTERMINATOR VS900 C/R BLACK VAPOR CLEANING SYSTEM SAFETY INSTRUCTIONS OPERATIONS CARE AND MAINTENANCE TROUBLESHOOTING WARRANTY

DataPoint Continuous Relay Controller LC52 Series Manual

Installation, Operation & Service Manual

SEALING FIBER SEALING COMPOUND

5+2 DAY. OWNER S MANUAL Venstar Inc. 05/08

Figure 1. These Installation Instructions -1- K4866 4/00 OmniProx Reader Model Series OP-10/20/30/40

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

OPERATION, SERVICE & PARTS MANUAL

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

OPERATING INSTRUCTIONS

OWNER S MANUAL PLEASE READ AND SAVE THESE INSTRUCTIONS WHOLE ROOM RADIATOR HEATER. Model: HO-0221 THERMOSTAT

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

Securitron. Switching Power Supplies

IMPORTANT SAFETY INFORMATION:

Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series)

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

7-Day. Digital Thermostat. residential. & 2-cool

Model 4001 Series Single Channel Controller

No Touch Door Release Exit Sensor ACA-NTEB

3800 North Mill Road Vineland, NJ USA Tel: Fax: Web: Rev. A

VX SERIES Wireless Thermostat with Occupancy Sensor

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

PLL Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

MAN AUTO IMPORTANT INSTRUCTIONS PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE

CD6102 / CD6102 OC / CD6102-2

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

SYSTEM CONTROL KIT Model: CK-41P

Transcription:

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com

TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3 FILL CONTROLLER 3. INSTALLATION... 4 3.1 GENERAL SETUP NOTES 3.2 SETTINGS FOR HIGH AND LOW ALARM SERVICE 3.3 SETTINGS FOR PUMP DOWN SERVICE 3.4 SETTINGS FOR FILL OPERATION SERVICE 3.5 INSTALLATION OF THE CONTROLLER 3.6 TEST THE OPERATION 4. OPERATION AND TROUBLESHOOTING... 11 5. SPECIFICATIONS... 13 6. WARRANTY... 14 Printed in Canada Rev Nov 2015 Page 2

1. SAFETY PRECAUTIONS The potential for electrical shock exists whenever water is present near conductive electrical equipment. Check for sources of electricity from other nearby devices before working on this equipment. There is no possibility of serious shock from the energy levels used by this Controller. The low voltage direct current and transformer isolation provide safety when handling or opening the enclosures or the probe. Best practice, however, is to disconnect power when working on this equipment. 2. APPLICATION The probes continuously monitor water levels, one rising (HIGH) level and one falling (LOW) level. The probe status is displayed with the tri colored LED and, if required, an audio alarm. Audio can be silenced and will auto reset when the alarm condition is corrected. The Controller also continuously monitors that all parts are operating correctly and displays any problems. Green heartbeat power on and monitoring Red flashing alarm condition Yellow / red flashing probe not connected Red solid probe wire short or reverse polarity See section 4 for further details. The relay LEDs are on red when the relay is energized. The Controller can be configured in one of three modes. 2.1 HIGH AND LOW LEVEL ALARM Monitor a HIGH level and a LOW level probe in one tank or in separate tanks. The relays provide switching for remote alarms, security system, remote lights, auto dialers or control systems. 2.2 PUMP DOWN CONTROLLER Control a pump down operation by suspending the HIGH probe at the turn on level and the LOW probe at the turn off level. The HIGH level relay is used to perform the switching to control the pump. The high relay LED indicates when the relay is energized. Page 3

2.3 FILL CONTROLLER Control a fill valve operation by suspending the LOW probe at the turn on level and the HIGH probe at the turn off level. The low level relay controls the fill valve or pump. The low level relay LED indicates when the relay is energized. 3. INSTALLATION 3.1 GENERAL SETUP NOTES The factory pre-set is for HIGH and LOW alarm mode with the audio on. The relays are 5 Amps, designed for low voltage AC or DC service. Relays are set for Normally Open operation. The jumper setting instructions are located inside the rear cover of the enclosure. See FIG 1 Page 4

FIG 1 Jumper Settings Page 5

3.2 SETTINGS FOR HIGH AND LOW ALARM SERVICE In normal operation the probe LEDs indicate a green heartbeat when the HIGH probe is out of the water and the LOW probe is submerged. The relay LEDS are off. When one of the probes change state the corresponding LED will flash red, the audio pulses and the relay is energized as indicated by the relay LED. The relay operation is set for Normally Open or Normally Closed operation. The factory settings of the jumpers inside the Controller are shown in FIG 2 NORMALLY OPEN * HIGH ALARM HIGH RELAY NORMALLY OPEN * LOW ALARM LOW RELAY AUDIO ACTIVE FIG 2 Jumper Settings for High and Low Alarm Service The jumpers are set on both pins (shorting) for the HIGH RELAY and the LOW RELAY. The relay operation is set for Normally Open. The audio jumper is set off on one pin (non-shorting) to set the audio in service. 3.3 SETTINGS FOR PUMP DOWN SERVICE Page 6 The Controller energizes the HIGH RELAY when the water rises to the HIGH. When the level falls to the LOW the relay is de-energized. During operation the HIGH and LOW LEDs have a green heartbeat to indicate that power is on and the probes are monitoring both the water level and the correct operation of the Controller.

When the level is above the HIGH probe or below the LOW probe the LEDs indicate an alarm condition, flashing red. Pump Down Service settings are shown in FIG 3 NO CONTACTS PUMP DOWN HIGH RELAY NO CONTACTS LOW ALARM LOW RELAY AUDIO OFF FIG 3 Jumper Settings for Pump Down Controller Service The pump down jumper is set off one pin (non-shorting). Normally the audio is set to off (shorting) for Controller service. 3.4 SETTINGS FOR FILL OPERATION SERVICE The Controller energizes the LOW RELAY until the water rises to the HIGH, de-energizing the LOW RELAY. The relay is re-energized when the level falls below the LOW. During operation the HIGH and LOW LEDs have a green heartbeat to indicate that power is on and the probes are monitoring both the water level and the correct operation of the Controller. When the level is above the HIGH probe or below the LOW probe the LEDs indicate an alarm condition, flashing red. Fill Operation Service settings are shown in FIG 4 Page 7

NORMALLY OPEN * HIGH ALARM HIGH RELAY NORMALLY OPEN * FILL LOW RELAY AUDIO SILENCED FIG 4 Jumper Settings for Fill Controller Service The fill jumper is set off one pin (non-shorting). Normally the audio is set to off (shorting) for Controller service. 3.5 INSTALLATION OF THE CONTROLLER The indoor Controller is either wall mounted or mounted in an appropriate enclosure, depending upon the service and location. The 120VAC receptacle powering the AC adapter should be supplied from a circuit separate from any pump or equipment that is being monitored or operated by this Controller. To wall mount, install two supplied screws, 3 apart vertically and projecting ¼ from the wall. The probes are installed into the screw terminal plug on the bottom of the Controller. See FIG 5 and 6. The HIGH RELAY and THE LOW RELAY are connected as required for the service. 18 gauge stranded conductors are recommended for low voltage AC or DC control circuits. Page 8

FIG 5 Terminal Block Page 9

LOW WHITE & BLACK HIGH WHITE & BLACK LOW ALARM or FILL RELAY HIGH ALARM or PUMP DOWN RELAY L W B H W B L RELAY H RELAY FIG 6 FIG 6 Terminal Block Labelling 3.6 TEST THE OPERATION Test the operation of each probe, out of water and immersed in water, to prove the operation of the Controller. Page 10

4. OPERATION AND TROUBLESHOOTING Sentry Liquid Level Alarm FIG 7 Operating Instructions Page 11

The LEDs display the water level state and the testing that the Controller is operating correctly. The RELAY LEDs display whether the relay is energized. When audio is selected, it will pulse upon a HIGH or LOW probe condition. Audio sounds continuously if the probes are disconnected or there is a short. The audio will automatically reset after the unwanted condition is corrected. LED AUDIO HIGH LEVEL LOW LEVEL CORRECTIVE ACTION OFF OFF No Power Check breaker Check Transformer Check Controller plug GREEN HEARTBEAT OFF DRY WET OK RED FLASHING PULSING WET DRY OK RED FLASHING SILENCED WET DRY OK RED STEADY CONTINUOUS SHORT Probe conductor polarity reversed Short in the probe wiring Replace probe RED / YELLOW FLASHING CONTINUOUS DISCONNECTED Connect probe wires Check probe wire for damage; make a waterproof repair GREEN / YELLOW FLASHING CONTINUOUS ERROR Replace probe Page 12

5. SPECIFICATIONS POWER SUPPLY ENCLOSURE BUZZER RELAY 120VAC~60 Hz input, 12VDC 5W output, UL listed, CSA certified, indoor unit flame retardant ABS Solid state, 85db min @ 10 cm digital RF proximity probe, stainless steel, type 304 or 316, 25.4mm diameter x 100mm long, cable - 2 conductor, 18 Ga, CSA CMG, PVC jacket, 15m (50 feet) or 30m (100 feet) 5 Amp at 30Volts, dry contacts, Normally Open or Normally Closed configurable Page 13

6. WARRANTY Aquatic Sentry Controls Inc. warrants that this product is free from defects in materials and workmanship under normal use and service for a period of three years from the date of purchase by the initial owner. Aquatic Sentry shall be responsible only for actual loss or damage suffered and then only to the extent of Aquatic Sentry s invoiced price. Within the warranty period we shall repair, refurbish or replace, at our option, such products or components, which are returned to us with shipping charges prepaid, and which are determined by us to be defective. This warranty will not apply to any product or part thereof which has been subject to misuse, negligence, or accident; or misapplied; or modified; or repaired by unauthorized persons; or improperly installed. The provisions of the above warranty are our sole obligation and exclude all other remedies or warranties, expressed or implied, including warranties of merchantability and fitness for a particular purpose, whether or not purposes or specifications are described herein. We further disclaim any responsibility whatsoever to the customer, or to any person, for injury to person, damage to, or loss of property or value caused by any product, regardless of whether the defect is warrantable or whether the product has been subjected to misuse, negligence, accident; or modified or repaired by unauthorized persons; or improperly installed. Under no circumstances shall the company be liable for any incidental, consequential or special damages, loss or expenses arising from the use of this product, or in connection with the use of, or inability to use, our product for any other purpose whatsoever. Aquatic Sentry products or parts thereof assumed to be defective by the purchaser within the stipulated warranty period should be returned to the seller or local distributor for evaluation and service. If deemed necessary, the seller or distributor shall contact Aquatic Sentry Controls Inc. for a Returned Materials Authorization and then return the item for direct factory evaluation, service or replacement. No material may be returned to Aquatic Sentry Controls Inc. without proper factory authorization. Page 14

NOTES Page 15