Performance Analysis of a Domestic Refrigerator in Malaysia using Experimental Method

Similar documents
Performance of an Improved Household Refrigerator/Freezer

Performance Assessment of Water Cooled Condenser Refrigeration System

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Design and Analysis of Water Cooled Condenser

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Experimental Study on the Performance of Twisted Capillary Tube

Effect of magnetic field on the performance of new refrigerant mixtures

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

AN EXPERIMENTAL INVESTIGATION INTO THE EFFECT OF THERMOSTAT SETTINGS ON THE ENERGY CONSUMPTION OF HOUSEHOLD REFRIGERATORS

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

BUTANE, ISOBUTANE AND THEIR MIXTURES AS AN ALTERANTIVES TO R-134a IN DOMESTIC REFRIGERATOR

Performance Investigation of Domestic Refrigerator Using Pure Hydrocarbons and Blends of Hydrocarbons as Refrigerants

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Enhancement of COP in Vapour Compression Refrigeration System

Numerical Simulation of Window Air Conditioner

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

DEEPAK PALIWAL, S.P.S.RAJPUT

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Performance Enhancement of Mini Refrigerator with Phase Change Materials

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

SBS5311 HVACR II Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

A study of Transient Performance of A Cascade Heat Pump System

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Department of MCE, Islamic University of Technology 2. Abstract

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

JJMIE Jordan Journal of Mechanical and Industrial Engineering

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Experimental Mapping of the Thermodynamic Losses in Vapor Compression Refrigeration Systems

EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

A Review of Household Compressor Energy Performance

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Experimental Performance Analysis of an Automotive Air Conditioning and Heat Pump System using R134a with and without Internal Heat Exchanger

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Refrigerant Mass and Oil Migration During Start-up Transient

International Journal of Informative & Futuristic Research ISSN (Online):

Refrigeration Cycle Demonstration Unit R634

Low GWP Refrigerants for Air Conditioning Applications

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Methods of Testing Capacity of Refrigerant Solenoid Valves

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Air & Water Heat Pump R832

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Mechanical Heat Pump R515

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

HFO-1234yf Performance in a Beverage Cooler

Performance Study on A Window Type Air Conditioner Condenser Using Alternative Refrigerant R407C

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

Study of Behavior of Refrigerant Mixtures in Domestic Refrigerator- Practical Research

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Sarthak Thakar, 2 R.P.Prajapati 1

Pure Butane as Refrigerant in Domestic Refrigerator Freezer

1.1. SCOPE OF THE WORK:

Santanu Prasad Datta (Student) P. K. Das & S. Mukhopadhyay

Transcription:

erformance Analysis of a Domestic Refrigerator in Malaysia using Experimental Method M.Y. aib 1, M. S. M. Sani 2, M. M. Noor 3, K. Kadirgama 4 Faculty of Mech. Engineering Universiti Malaysia ahang un Razak Highway, 26300 Kuantan, ahang myusof@ump.edu.my 1, mshahrir@ump.edu.my 2, muhamad@ump.edu.my 3, kumaran@ump.edu.my 4 Abstract Refrigerator is one of the home appliance utilizing mechanical vapour compression cycle in it process. erformance of the system becomes main issue and many researches are still ongoing to evaluate and improve efficiency of the system. herefore, this paper presents the development process of refrigerator test rig and performance evaluation of a domestic refrigerator that has been used in Malaysia. he experiment platform which called test rig was developed from refrigerator model NRB33A National brand. he main objective in this study was to obtain performance of the refrigeration system in term of Coefficient of erformance (CO) by determining three important parameters during in operating mode which are temperature, pressure and refrigerant flowrate. In the test rig, all temperature probes were connected to thermocouple scanner to measure temperature at particular points on the refrigeration system. ressure gauges were used to measure pressure and a magnetic flowmeter was used to measure refrigerant flowrate. In order to avoid effects of a changing the measured data, the environmental of testing was controlled according to Association of Home Appliance Manufacturers (AHAM) standard. here are five sets of experiment data were collected in order to evaluate the CO of the refrigerator. Each data was collected for a cycle of operation in about 2 hours. he result shows that the average CO of the refrigeration system using the refrigerator test rig was about 2.7. Keyword: Refrigerator est Rig, Refrigeration Cycle, CO 1. INRODUCION Refrigerator is a cooling appliance comprising a thermally insulated compartment and a refrigeration system to produce cooling effect to the insulated compartment. Meanwhile, refrigeration is define as a process of removing heat from a space or substance and transfers that heat to another space or substance. Nowadays, refrigerators are extensively used to store foods which deteriorate at ambient temperatures; spoilage from bacterial growth and other processes is much slower at low temperatures. In refrigeration process, the working fluid called refrigerant employed as the heat absorber or cooling agent. he refrigerant absorbs heat by evaporating at low temperature and pressure and remove heat by condensing at a higher temperature and pressure. As the heat is removed from the refrigerated space, the area appears to become cooler. he process of refrigeration occurs in a system which comprises of a compressor, a condenser, a capillary and an evaporator arranged as depicted schematically in Figure 1(a).

Capillary tube (a) Figure 1. (a) Schematic diagram of refrigeration system (b) p-h diagram of vapour compression cycle (b) Compressor is a mechanical device to compress and pump the refrigerant vapour from a lowpressure region to a high-pressure region. he condenser is a device for removing heat from the refrigeration system. hen the capillary tube controls the refrigerant flow from the condenser to the evaporator and separates the system to high-pressure and low-pressure sides. he evaporator is a device for absorbing heat from the refrigerated space into the refrigeration system by evaporating the refrigerant (Jordan and riester, 1985). o accomplish the heat removing process from the refrigerated space, a system called refrigeration plant is created and the plant works in a thermodynamic cycle which obeys Second Law of hermodynamic and based on vapour compression cycle as shown in Figure 1(b). here are two main parameters that were considered in this study; refrigeration capacity and coefficient of performance. he refrigeration capacity, Q in is defined as the amount of heat absorbed by a unit mass of refrigerant in the evaporator. he refrigeration capacity can be obtained using equation below. Q in = m h 1 h 4 Watt (1) he coefficient of performance (CO) is a measure of efficiency of the refrigerator. he CO of a domestic refrigerator is the ratio of the refrigeration capacity, Q in to the energy supplied to the compressor,. It can be expressed by equation below (Dincer, 2003). CO = Q in = m h 1 h 4 m h 2 h 1 (2) he values of enthalpy h are determined by using NIS Refrigerant roperties Database based on relationship between temperature and pressure data from experiment.

Currently, refrigerator is used widely around the world and this appliance become necessity for household. he performance of the refrigerator is very efficient but the researches still ongoing to optimize the system. hus, the performance study of the refrigeration system in Malaysia is one of the efforts to discover performance of the refrigerator. 2. MEHODOLOGY Methodology of this work is concentrated on two important things that need to be developed in order to investigate the performance of the domestic refrigerator which is location of measurement points and it devices, and experiment set-up. 2.1 Development of Location of Measurement oints Refrigerator test rig was developed in order to investigate the performance of the system. Figure 3 shows the photograph of the refrigerator model that was used in the study. In developing the reliable refrigerator test rig, consideration should be highly addressed especially the development method, measurement locations of pressure and temperature. hese are very important to ensure that the test rig can produce reliable data. o accomplish this, the author referred to the several technical papers related to the study. reviously, (annock et al., 1994: hilipp et al., 1996: Mc keller & ree, 1988: Melo & ereira, 1988) discussed the development of refrigerator test rig. hey discussed the locations of temperature and pressure measurement points, measurement devices and measurement methods. As a result, a refrigerator test rig was developed as shown in figure 4. here are eight points of temperature measurement, four points of pressure measurement and one point of flow rate measurement. From the eight points of temperature measurement, six points have been placed inside the refrigeration circuit to measure refrigerant temperature and another two points have been placed in refrigerator compartments. he same number of points and locations were adopted by (annock et al., 1994: hilipp et al., 1996: Mc keller & ree, 1988: Melo & ereira, 1988) who followed several standards such as ANSI/AHAM HRF-1-2008 (AHAM, 2008) and European standard for measuring the energy consumption of electric mains operated on household refrigerators (DIN EN 153) (hilipp et al., 1996). he thermocouple wire (ASHRAE, 1986) was used to measure the temperature of refrigerant in the tube. he technique to measure the temperature is the same as (hilipp et al., 1996), whereas the thermocouple wire was put inside the refrigerant tube so that the measurement made was exactly the temperature of the refrigerant. Figure 2(a) shows the method to construct the temperature measurement point in the refrigerant tube. By applying this method, a suitable length of ¼ copper tube with flared end as shown in Figure 2(a-i) was used to hold a thermocouple wire which was inserted into the tube and effectively sealed, as shown in Figure 2(a-ii). he flared tube is fitted securely on to a copper - junction which was then joined mechanically to the tube to reconnect every two consecutive components (Langley, 1982). he temperature of the refrigerant which now flowed through each -junction was measured by the hot thermocouple junction or head, as shown in Figure 2(a-iii).

(a-i) (a-ii) (a-iii) Figure 2. a) Construction method of temperature measurement point and b) Construction method of pressure measurement using Bourdon type pressure gauge (b-i) (b-ii) (b-iii) Besides that, four points of pressure were tapped respectively made on pipes connecting all main components. Experimental works of (annock et al., 1994: hilipp et al., 1996: Melo & ereira, 1988) only measured suction and discharge pressures of compressor while the present works allowed pressure drops across each component and along connecting pipes to be known as well as (Jones, 2001: ASHRAE, 2001). Bourdon ube pressure gauges (ASHRAE, 1989: ARI, 1998) were used for each pressure measurement in this test rig. A tube with diameter 2.1 mm was used to connect the refrigerant tube to each pressure gauge as what was done by (hilipp et al., 1996). Figure 2(b) shows the detail construction of the pressure measurement points. In this work also, a metal tube flowmeter with magnetic coupled indicator was used. his flow meter was manufactured and calibrated by Brooks Instruments. he flowmeter was assembled between condenser and capillary tube to measure the refrigerant flowrate in liquid form. 2.2 Experiment Set-up he experiment was conducted conventionally by taking all of data manually. he all eight points of thermocouple wire were connected to -type mini plugs and these plugs were connected to the thermocouple scanner. hermocouple scanner is a device to read the measured temperature. he time interval between consecutive scans was five minutes and printing was done immediately. Besides that, the pressure gauges were fitted on a panel. he data was collected manually every five minutes and at the same time when the temperature of each point was recorded by the printer. he flowmeter which was connected to the pipe between condenser and filter dryer was fixed to the panel next to the pressure gauges. he data was read manually through visualization and recorded every five minutes. Figure 3 shows the illustration of above discussion. here are five set of data were recorded from five experiments in order to investigate the performance of the refrigerator.

Side condenser Evaporator Back condenser Brand: National Model: NR-B33A Capacity: 262 liters Charging: R134a (160 g) Amp. Load: 0.56 amp. Heat exchanger 3 Main condenser hermocouple Scaner rinter 4 Suction line Filter dryer Capillary tube Wooden anel ressure Gauges Flowmeter Legend: (3) Flow meter (4) Sight glass () ressure Gauge () hermocouple Charging port Compressor Discharge line Figure 3. Schematic diagram of test rig and experiment set-up 3. RESUL AND DISCUSSION here are three important parameters that were recorded which are temperature, pressure and refrigerant flowrate. he data were analyzed according to the theory of refrigeration system and the result is tabulated in Figure 4 and Figure 5. 3.1 Refrigeration Capacity Refrigeration capacity is determined using equation 1. Figure 4 shows graph of the refrigeration capacity versus time for the all data. he graph shows a general trend at the first 5 to 10 minutes operation. In the period of time the refrigeration capacity is significantly high and then decreases towards almost constant value. Experiment 5 (Exp. 5) is more stable than others that was around 208 W to 263 W. his was caused by the setting of temperature level in the freezer compartment which influenced the values of the refrigeration capacity.

CO Ref. Capacity (W) Refrigeration Capacity vs ime 450 400 350 300 250 200 150 100 50 0 0 20 40 60 80 100 120 Exp. 1 Exp. 2 Exp. 3 Exp. 4 Exp. 5 ime ested (min) Figure 4. Graph refrigeration capacity versus time 3.2 Coefficient of erformance Coefficient of performance (CO) was calculated using equation 2 and Figure 5 shows the graph of CO versus time. Referring to the figure, the CO values are higher at the beginning of each test run, and then it was achieved the steady state condition after 10 minutes of running. he variance between each dataset was due to the condition of test such as quantity of refrigerant charged or initial pressure, initial cooling load, ambient temperature and humidity all of which could not be set constant. However, the differences became smaller at the end of each test run. CO vs ime 4.00 3.50 3.00 2.50 2.00 1.50 1.00 0.50 0.00 0 20 40 60 80 100 120 Exp. 1 Exp. 2 Exp. 3 Exp. 4 Exp. 5 ime ested (min) Figure 5. Graph CO versus time

4. CONCLUSION erformance of the domestic refrigerator was investigated with indicator of CO was about 2.75 and refrigeration capacity was ranging from 150 watt to 205 watt. Besides that, test rig development method that has been presented in this work was plays important role in order to investigate the performance of the refrigerator. he correct data from experiment can be produced from a reliable test rig as such presented and the method must be parallel with high skill of work and reliable measurement devices. 5. REFERENCES Jordan, R. C. and riester, G. B. (1985). Refrigeration and Air Conditioning System. 2 nd edition. rentice-hall of India rivate Limited, New Delhi. Dincer, I. (2003). Refrigeration System and Application. John Wiley & Sons Ltd, England. annock, J., Liu, Z., Radermacher, R. and Yu, K. (1994). Evaluation of R-134a And R-152a as Working Fluids in a Domestic Refrigerator / Freezer. ASHRAE ransaction: Symposia, Volume 100, art 1. ASHRAE Inc. 1344 1350. hilipp, J., Kraus, E. and Meyer, A. (1996). resentation of a est Rig o Record Mass Flow Rate, ressures and emperatures of a Household Refriherator During On/Off Cycling Mode. roc. of the 1996 International Refrigeration Conference at urdue. West Lafayette, Indiana: IIR, 1996. 477 482. McKellar, M. G. and ree, D. R. (1988). Steady State Characteristics of Failures of a Household Refrigerator. reprints of the 1988 urdue International Refrigeration (IIR) Conference. West Lafayette, Indiana: IIR, 1988. 257 265. Melo, C. and ereira R. H. (1988). Steady State Characteristics of Failures of a Household Refrigerator. reprints of the 1988 urdue - International Refrigeration (IIR) Conference. West Lafayette, Indiana: IIR, 1988. 98 106. ANSI / ASHRAE Standard (1986). Standard Method for emperature Measurement. Atlanta: (ANSI / ASHRAE 41.1-1986 (RA 2001). Langley, B. C. (1982). Refrigeration and Air Conditioning. 2 nd Company, Reston Virginia. edition. rentice-hall American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). 2001 ASHRAE Handbook CD. 1.12. ANSI/ASHRAE Standard (1989). Standard Method for ressure Measurement. Atlanta: (ANSI / ASHRAE 41.1-1986 (RA 2001).