Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Similar documents
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Enhancement of COP in Vapour Compression Refrigeration System

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance investigation of Air-conditioning system using ejector as expansion device

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Performance of an Improved Household Refrigerator/Freezer

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Modified Air Cooler with Split Cooling Unit

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Design and Development of Water Cooled Condenser for Domestic Refrigerator

STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING DOUBLE PIPE HEAT EXCHANGER

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Numerical Simulation of Window Air Conditioner

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

II. OBJECTIVE OF RESEARCH

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Performance Study of Triple Concentric Pipe Heat Exchanger

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Development of Energy Efficient R-134a Automotive Air Conditioning System Using Internal Heat Exchanger

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

(Refer Slide Time: 00:00:40 min)

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Chapter 10. Refrigeration and Heat Pump Systems

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures

International Journal of Informative & Futuristic Research ISSN (Online):

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Performance Enhancement of Mini Refrigerator with Phase Change Materials

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

Global Journal of Engineering Science and Research Management

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

[Mali*, 4.(12): December, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Performance Assessment of Water Cooled Condenser Refrigeration System

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Adsorption refrigeration system using waste heat

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

A Comparison Between Refrigerants Used In Air Conditioning

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Optimization of the Evaporative Condenser Design

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

HVAC Fundamentals & Refrigeration Cycle

EFFECT OF INLET TEMPERATURE ON REYNOLDS NUMBER AND NUSSELT NUMBER WITH MIXED REFRIGERANTS FOR INDUSTRIAL APPLICATIONS

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Design & Fabrication of Hybrid Cooler


Waghmare Tushar Ramrao, D.S.Nakate

Transcription:

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical Engineering Govt. College of Engineering Amravati, Maharashtra India Refrigeration system works on the second law of thermodynamics specifically on the Clausius statement which summarizes that the refrigerator is nothing but a reversed heat engine which consumes energy in the form of work to transfer heat from Low temperature body to high temperature body. Refrigeration system mainly works on Vapour Compression Refrigeration cycle (VCR), in simple VCR cycle the refrigerant after condensation enters into the region of interest after throttling i.e. from where the heat is to be removed. Greater the extent of condensation that ensures the low temperature vapour in cooling region. To enhance the performance means to enhance the cooling capacity but with adjustment of the consequences of doing so. The heat exchanger is installed between the suction line and the discharge line which transfer the heat from low temp low pressure suction line to the high temperature high pressure discharge line also known as Liquid Suction Heat Exchanger. The liquid in the discharge line gets sub cooled and the vapour gets superheated due to which the compressor works increases due to increase in specific volume. In this experimentation various parameters change. This paper identifies the ways of installing the heat exchanger and to find the best suitable way and to analyze the impacts of experimentation on various operating parameters. Key Words: Clausius statement, VCR, Cooling capacity, Subcooling. 1. INTRODUCTION Refrigeration system takes energy in the form of work and transfer heat from low temperature to high temperature to get the desired cooling therefore it consumes a large amount of electrical energy to do so, as a result many methods have been developed by researchers to improve the system performance [2].The commercial refrigeration systems (freezer and air conditioner) consume approximately 50-60% of energy total. Installed heat exchanger (HX) uses an internal heat exchanging technique to subcool the discharge liquid, which transfers heat from the condenser outlet to the compressor suction, may lead to an increase in the cooling capacity produced by the 1

Shoeb J. Inamdar et al., Performance Enhancement of Refrigeration Cycle by Employing a Heat evaporator. This method is called subcooling using liquid suction heat exchanger (LSHX). The most important effect of the use of LSHX is the increase in cooling capacity because of the lower quality of refrigerant entering the evaporator, consequently the evaporator absorb more heat from the ambient. On the other hand due to the liquid suction heat exchanger (LSHX) the vapour to the suction of compressor get superheated. The positive effect of this superheating is that if the degree of superheating eliminates liquid refrigerant entering to the compressor, because wet intake can cause damage to the compressor [1]. The negative effect if the degree of superheating is too high, as a result an increase in the compressor discharge temperature (K). The increase in the compressor discharge temperature results in an increase in the power consumption. Consequently, the subcooling using LSHX does not always increase the COP. Figure1.1: LSHX Subcooler Schematics and P-h Plot In employment of the LSHX to enhance the performance the factors which dominate mainly are the proper selection of the refrigerant and the operating ambient temperature. Some of the famous refrigerant which suit to this design are R22, R290, R134a etc. because R22 has a high global warming potential (GWP), the near future this refrigerant shall be phased out and R290 (propane) is recommended as a substitute refrigerant for R22. The R290 is a natural refrigerant, abundant and relatively cheaper than that of R22. Many studies reported that replacement of R22 with R290 in freezer resulted in COP improvement. The discharge temperature of R290 at an ambient temperature greater than 40 0 C is above 110 0 C hence this puts limitation to the use of this refrigerant [5]. 1.2 Important Definitions In this section a few important terms commonly used in heat transfer and refrigeration are defined. 1) Coefficient of Performance (COP) It is defined as the ratio of the desired cooling effect to the work input given to the system. = www.ijerat.sretechjournal.org 2

2) Log Mean Temperature Difference (LMTD) This term takes into account the varying temperature difference along the length of the heat exchanger and is defined as the temperature difference which if remains constant would give the same heat transfer as given by the varying temperature difference. 3) Nusselt Number (Nu) The Nusselt number is a measure of the convective heat transfer occurring at the surface and is defined as hd/k, where h (W.m -2.k -1 ) is the convective heat transfer coefficient, d is the Diameter of the tube and k (W.m -1.k -1 ) is the thermal conductivity. As can be seen from the Pressure (bar)-enthalpy (kj/kg) (P-h) plot Fig.1.1 that In the simple VCR cycle without LSHX: Refrigerating effect = h 1 -h 4 (kj/kg) Compressor work = h 2 -h 1 (kj/kg) Hence, COP = R.E C.W = (h 1 -h 4 )/ (h 2 -h 1 ) In the simple VCR cycle with LSHX: Refrigerating effect = h 1 -h 4, (kj/kg) Compressor work = h 2 -h 1, (kj/kg) The refrigerating effect is increased and the compressor work also increases but to certain extent hence the overall COP Increases. COP = R.E C.W = (h 1 -h 4, )/ (h 2 -h 1, ) 1.3 Effect of LSHX on Operating Parameters Above introductory part explains that the employment of the heat exchanger for subcooling affects various operating parameters. The table shows that the use of heat exchanger subcooler is always followed by increasing cooling capacity but also the compressor work and superheating. As the COP is the ratio of the cooling capacity to compressor power, as a result the increase in the COP depends on the extent of subcooling and results are relative. 3

Shoeb J. Inamdar et al., Performance Enhancement of Refrigeration Cycle by Employing a Heat Most of the refrigerant gives COP improvement on the system when the LSHX is installed, and only few refrigerants don t because their specific volume increases to greater extent comparatively [6]. Table1.1. Effect of LSHX on operating parameters Quantity Effect Mass flow rate Vary* Subcooling Increases Superheating Increases Condensation pressure Constant * Compressor work Increases COP Increases * *Depending upon the Refrigerant used and degree of subcooling. 2. REVIEW OF THE BACKGROUND All over the world researchers have been performing research and experimentation on LSHX since 1980s. Stoecker and Walukas (1981) [3] focused on the influence of liquid-suction heat exchangers systems utilizing refrigerant mixtures. Their analysis indicated that liquid-suction heat exchangers yielded greater performance improvements when Refrigerant is chosen carefully. McLinden (1990) [10] used the principle of corresponding states to evaluate the anticipated effects of new refrigerants. He showed that the performance of a system using a liquidsuction heat exchanger increases with the specific heat of the refrigerant. Domanski and Didion [9] (1993) evaluated the performance of nine alternatives to R22 including the impact of liquid-suction heat exchangers. The analysis was extended by Domanski et al. [9] (1994) by evaluating the influence of liquid-suction heat exchangers installed in vapour compression refrigeration systems considering 29 different refrigerants in a theoretical analysis. Bivens et al. (1994) their analysis indicated a 6-7% improvement for the alternative refrigerant system when system modifications included a liquid-suction heat exchanger and counter flow system heat exchangers (evaporator and condenser). Bittle et al. (1995a) conducted an experimental evaluation of a Liquid-suction heat exchanger applied in a domestic refrigerator using R152a. The authors compared the system performance with that of a traditional R12-based system. This paper analyzes the liquid-suction heat exchanger to quantify its impact on system capacity and performance (expressed in terms of a system coefficient of performance, COP). The influence of liquid-suction heat exchanger size over a range of operating conditions (evaporating and condensing) is illustrated and quantified using a number of alternative refrigerants. Refrigerants included in the present analysis are R22, R290, and R134a. This paper extends the results presented in previous studies in that it considers new refrigerants, it specifically considers the effects of the pressure drops, and it presents general relations for estimating the effect of liquid-suction heat exchangers for any refrigerant. 3. DIFFERENT WAYS OF INSTALLING LSHX AND THEIR PROS. AND CONS. Following are the main ways of installing the LSHX in the VCR cycle. 1) Shell and tube type 4 www.ijerat.sretechjournal.org

2) Tube in tube Annulus type (Parallel and Counter flow) 3.1 Shell and Tube Type LSHX Shell and Tube Heat Exchangers are one of the most popular types of exchanger due to the flexibility the designer has to allow for a wide range of pressures and temperatures. A shell and tube exchanger consists of a number of tubes mounted inside a cylindrical shell. Fig.3.1 illustrates a typical unit of shell and tube type LSHX. Two fluids can exchange heat, one fluid flows over the outside of the tubes while the second fluid flows through the tubes. The fluids can be single or two phase and can flow in a parallel or a cross/counter flow arrangement. Figure 3.1: Shell and Tubes Heat Exchanger In shell and tube heat exchanger the vapour flows outside the tubes in a shell and the discharge liquid flows in the tubes due to that sudden expansion the sp. Volume of the vapour increases and the superheating adds to that and hence the work of compression increases and the inlet and outlet of the section faces energy losses and due to that the compressor works roughly and heat exchanger also incur jerks and vibrations, Hence that puts limitation to the use of this type. 3.2 Tube in Tube Annulus type (Parallel and Counter flow) Tube-in-tube heat exchangers consist of two tubes, an inner and an outer coiled together. This unique, compact design prevents thermal fatigue, increases efficiency and reduces the overall size. It is ideal for high temperature, high pressure and low flow applications. 5

Shoeb J. Inamdar et al., Performance Enhancement of Refrigeration Cycle by Employing a Heat Figure 3.2: Tube in Tube Heat Exchanger As shown in Fig. 3.2 in tube in tube HX two concentric tubes are used with not large difference in diameter hence when the vapour in the outer tube opens up they don t expands to the considerable extent and therefore the Sp. Volume of the gas don t increase to considerable extent and the work of compression don t rise considerably compared to earlier. 3.2.1 Operational Procedure The tube in tube type counter flow heat exchanger is most suitable type for the proposed design hence, to design that the following operational procedure is to be considered first. When the refrigerant leaves evaporator at that time refrigerant have low temperature. Condenser is used for the purpose of removing heat from refrigerant to the atmosphere, to reduce temperature of refrigerant and make phase change of refrigerant. Super heating is done at the inlet of compressor and subcooling is done at exit of condenser. Both evaporator and condenser heat to make subcooling and superheating are being used at the same time and in same device. Heat exchanger is used to make this heat exchange between hot and cold refrigerant. From the outer tube evaporator outlet refrigerant (low temp refrigerant) flowing and from inner tube condenser outlet refrigerant (High Temp refrigerant) flowing. Heat exchange between both refrigerant produces the superheating at entry of compressor and subcooling at exit of condenser. Hence refrigeration effect considerably increased with same amount of work supplied and Hence overall COP of system increases 3.2.2 Proposed Numerical Analysis for Design As it can be seen from the above procedure that at the exit of the LSHX we get the saturated vapour converted into the superheated state and due to that the specific volume of the vapour get increased and due to that the compressor work gets increased that may reduce the COP. Hence the design should be made such that the optimum value of superheating should be there so associated with the subcooling and that can be done by the proper choice of the refrigerant and the proper HE design. www.ijerat.sretechjournal.org 6

Figure 3.2.1: Simple VCR cycle with P-h Plot As can be seen from above figure, In the experimental setup we can get the following data. Suction and discharge pressure - P 1 and P 2 (bar) From the temp. Sensors We can get, Temp. At entry to compressor T 1 (K) Temp. At exit to compressor T 2 (K) Temp. At exit to condenser Temp. After expansion T 3 (K) T 4 (K) From Energy meter We get work of compression in the form of power for time t (sec), P = m (h 2 -h 1 ) kilowatt (KW). Where m- mass flow rate (kg/sec) is found from above Now, 7

Shoeb J. Inamdar et al., Performance Enhancement of Refrigeration Cycle by Employing a Heat From P-h chart R.E is found and finally COP R.E = m (h 1 -h 4 ) KW. COP = (R.E)/ (P) The Design of HX Figure 3.2.2: Schematics of tube in tube HX From Forced convection Analysis; For tube in tube counter flow heat exchanger. For defined degree of subcooling we can find degree of superheating. Then finding varied mass flow rate by maintaining the superheating condition. Apply analysis Nu = 0.023 (Re) 0.8 (Pr) n n = 0.4 for heating of fluid = 0.3 for cooling of fluid. We have Nu=hD/k We get h i and h o heat transfer co-efficient for inner and outer flow respectively. Then finding overall heat transfer coefficient U. Then calculating the desired dimensions of HX from heat transfer equation for HX. 4. CONCLUSION Superheating causes variation in the mass flow rate of the gas, if we neglect that variation as it varies to very small extent and can further be minimized by the proper selection of the refrigerant. We can conclude that liquidsuction heat exchangers lead to performance improvements for any refrigerant. The compressor power is only slightly affected by the change in state of the refrigerant entering the compressor, which causes the reduction in refrigerant mass flow rate because liquid-suction heat exchangers increase the temperature and reduce the pressure of the refrigerant entering the compressor causing a decrease in the refrigerant density and compressor volumetric efficiency. 8 www.ijerat.sretechjournal.org

REFERENCES [1]. B.A. Qureshi, S.M. Zubair. 2012. The effect of refrigerant combination of performance of a vapour compression refrigeration system with dedicated mechanical sub-cooling. International Journal of Refrigeration. 35: 47-57. [2]. S.S. Klein, D.T. Reindl, K. Brownell. 2000. Refrigeration system performance using liquid suction heatexchanger. International Journal of Refrigeration. 23: 588-596. [3]. G. Lorentzen. 1995. The use of natural refrigerants: a complete solution to the CFC/HCFC predicament. [4]. K. Sumeru, H. Nasution, F.N. Ani. 2013. Numerical study on ejector as an expansion device in a split-type air conditioner for energy savings. Journal of Engineering Technological Sciences. 45: 101-111 [5]. K. Sumeru, S. Sulaimon, H. Nasution, F.N. Ani. 2014. Numerical and experimental study on an ejector as an expansion device in a split-type air conditioner for energy savings. Energy and Buildings. 79: 98-105. [6]. G. Pottker, P. Hrnjak P. 2015. Experimental investigation of the effect condenser subcooling in R134a and R1234yf air-conditioning systems with and without internal heat exchanger. International Journal of Refrigeration. 50: 104-113. [7]. Conditioning Engineers, ISBN 1-883413-54-0, Chapter 2, (1998). [8]. Tube-Liquid-suction Heat Exchanger Performance with R152a", ASHRAE Transactions, Vol. 101, No. 1, pp. 124-135, (1995a). [9] Domanski, P. A., Didion, D. A., and Doyle, J. P., "Evaluation of Suction-Line/Liquid-Line Heat Exchange in the Refrigeration Cycle", Rev. Int. Froid, Vol. 17, No. 7, pp. 487-493, (1994). [10]. Stoecker, W. F., Industrial Refrigeration, Business News Publishing Corporation, Troy, MI. 9