Jetflush 4 Instruction Manual

Similar documents
JetFlush C40 & C90 Power flushing unit

USER MANUAL PLEASE READ THROUGH ALL INSTRUCTIONS BEFORE USE ANY FURTHER QUESTIONS PLEASE CALL OUR TECHNICAL HELP LINE:

Please take time to carefully read through these guidelines before using your Kamco pump.

Please take time to carefully read through these guidelines before using your Kamco pump.

Please take time to carefully read through these guidelines before using your Kamco pump.

n/a ROTARY JET ETCH/DEVELOPER TANK (RE)

Rota- Spray Instructions (Mega Part & )

SEALED THERMAL STORE

ROTA-SPRAY PROCESSOR MODEL 1210 (ROTARY-JET) INSTRUCTIONS MEGA PART NO: &

DEVIL CERAMIC SPACE HEATERS

1300W Pressure Washer RACHP133A

Built-in Gas Hob CZ55554 CZ55571

50L/D DEHUMIDIFIER. Model Number: IG9805 INSTRUCTIONS FOR USE

CLEAN WATER PUMP. MODEL No: Hippo4A OPERATION & MAINTENANCE INSTRUCTIONS. Part No:

Trouble Shooting and Help Guide TT / TTB 1840

Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw

SUBMERSIBLE WATER PUMPS

Assessment Schedule - TS.6

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PUDDLE PUMP PUDDLE PUMP. MODEL No: PSP125 OPERATION & MAINTENANCE INSTRUCTIONS. Part No:

Kinetic. Logic. Astin. THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions. Please retain for future reference

Pedestal Range. Installation and user manual. Kiosk. Trafalgar. Tube. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

Eliminator TotalGuard Installation Manual

Autofill wall mounted water. boiler. Getting the best from your water. boiler. Please read and keep these instructions

DUST MANAGER USER INSTRUCTIONS GENERATION FUTURE indd 1 28/11/ :27:15

Alpha CombiMax 350 and 600

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

FRANKE MINERVA 3-IN-1 HOT WATER TAP HEATING TANK INSTALLATION GUIDE

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

INSTALLATION & TECHNICAL MANUAL

Common central heating problems

Optimax Refrigerated Retail Merchandisers

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

ELECTRIC COMBINATION BOILER. (European Patent No: Design Right Protected.) TH12-450U MRK 2

USERS MANUAL. Desiccant Dehumidifier. Model: ECO DD322FW CLASSIC

BOILING UNIT REDITAP. Installation and User Guide. IMPORTANT: This booklet should be left with the user after installation and demonstration

POWER SHOWERS Models 4500M 5002M 4500T 5002T

CPE RANGE PUMPS CPE RANGE PUMPS. MODEL Nos: CPE15A1 15A3 20A1 20A3 30A1 30A3 PART Nos:

Flo~mate Mains Boost Pump Installation & Maintenance Instructions

3000W Pressure Washer RAC - HP006

The Professional s Choice

Aquamixa. Thermo. Thermostatic shower valve with manual bath fill

Saturn Booster PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USE AND KEEP THEM FOR FUTURE REFERENCE

IMPORTANT SAFETY INSTRUCTIONS

iheat 25c iheat 30c iheat 35c

ELECTRIC ASHCAN MODEL NO: ASHVAC1200 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: ORIGINAL INSTRUCTIONS

Varsity Concealed Shower System

Vote for your Installer of the year at HEATSLAVE

DUST MANAGER USER INSTRUCTIONS GENERATION FUTURE indd 1 28/11/ :43:21

COLD WATER WASHER OPERATING & MAINTENANCE INSTRUCTIONS. Model Nos. ELS140, 140R & ELS150. Part Nos , &

Hozelock Ltd. Midpoint Park, Birmingham B76 1AB. England Tel: +44 (0)

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

USER GUIDE VOGUE MAX SYSTEM

Optimax Refrigerated Retail Merchandisers

Inspect bath carefully and report any damage or faults before installation. No claims can be entered in to after installation.

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

EASYCLEAR 3000 YEAR GUARANTEE

INSTRUCTION MANUAL Model: SU3022

HW3 Handwash Installation and Operating Instructions

INSTALLATION AND QUICK COMMISSIONING INSTRUCTIONS EWC WARM WATER TIME CLOCK WATER SOFTENERS

ADVANCE ECB ELECTRIC COMBINATION BOILER

INSTALLATION & TECHNICAL MANUAL

Autofill counter top water boiler

Greenstar System Filter

User's Instructions. Alpha CB50

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Operating Instructions

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

Alpha FlowSmart 25 and 50

USERS MANUAL. Desiccant Dehumidifier. Model: ECO DD322FW SIMPLE. Read This Manual

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Installation, Operating and Servicing Instructions

Installation and Servicing Instructions. Alpha FlowSmart

Rota- Station and Plus Instructions (Mega Part & )

instructions FAN HEATER HVF3533 Please retain these instructions for future reference

Statesman 45/50L, 50/70L, 70/90L, 90/110L, Utility 50/70L, 70/90L, 90/110L, 110/130L, 130/150L

CONCEALED THERMOSTATIC SHOWER MIXER VALVE installation & aftercare instruction

CPC-150-ABIAB. Important Installation Notes.

CERAMIC HEATER MODEL NO: DEVIL 350B 230V/110V OPERATING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS GC ISS 1

Installation and servicing instructions

WC2 & WC3 Installation & Maintenance Instructions

SINGLE LEVER CERAMIC DISC MANUAL SHOWER VALVE

Installation and User Instructions HS10U, HS15U.

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

Installation Instructions and User Guide

Inta City Concealed Shower Mixing Valve CT80010CP

BASIN MIXERS INSTALLATION & AFTERCARE INSTRUCTIONS

Unvented Electric Water Heater 10/15 litre Undersink

Space Saver. Installation and user manual SS3 SS5 SS7 SS9. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

ME SERIES ELECTRICALLY OPERATED BOILERS INSTALLATION - OPERATION - MAINTENANCE MODELS

NON-SUBMERSIBLE WATER PUMP

Intatherm Safe Touch Basin Tap IT1008CP

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

User and Installation Instructions. Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461

DUST MANAGER USER INSTRUCTIONS

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

SMART SHOWERS ELITE SP P0985 READ ME THIS IS A HIGH PERFORMANCE HIGH SPECIFICATION PUMP AND HAS PRECISE INSTALLATION REQUIREMENTS

Transcription:

The Sentinel range of water treatment products for domestic central heating systems. GE Water & Process Technologies Jetflush 4 Instruction Manual Foundry Lane, Widnes, Cheshire WA8 8UD. Tel: 0151 420 9595. www.gewater.com/sentinel

INTRODUCTION These instructions cover the Sentinel Jetflush 4 domestic central heating system flushing unit. It is recommended that these instructions are read throughout before commencing any work with the unit, even if you have previous experience of using a high flow flushing system. You should also be familiar with the Code of Practice for treatment of water in domestic hot water central heating systems BS7593:1992, the Model Water Bylaws, The Health & Safety at Work Act and COSHH regulations and requirements. GETTING STARTED Your Jetflush 4 pack comprises; The Jetflush 4 unit 25 metres of 19mm (3/4 inch) flexible yellow tubing 15 metres of 12.5mm (1/2 inch) braided green tubing The Sentinel Jetflush 4 unit utilises a mechanical method of combining high flow and low pressure together with suitable chemical cleansers in order to clean and restore efficiency to dirty, problematic wet central heating systems. The Sentinel Jetflush 4 unit, has been ergonomically designed for ease of use. gives at a glance temperature indication. includes an automatic mains water cut off device to avoid over filling. allows direct dumping to drain for improved speed of flushing. provides instant flow reversal during operation. creates additional turbulence, which will further enhance cleaning. An accessory pack including: Hozelock 12.5mm outside tap connector 3 off 20mm and 1 off 15mm Geka quick fit valve connectors 2 off circulator service valve adapters with black plastic 20mm elbow connectors Selection of jubilee clips Instruction Manual 3

The low pressure, high flow, fully submersible Grundfos pump provides the mechanical power for your Jetflush 4 unit allowing: optimum flushing of domestic central heating systems efficient and thorough cleaning when combined with the recommended chemical cleaner an average size system to be completed typically in half a day. Attach the 15mm Geka fitting to one end of the green tubing and the Hozelock outside tap adapter (or other suitable mains water connecter) to the other end. Cut two lengths, typically 3 metres, from the yellow coloured tubing and connect a 20mm Geka valve and a circulator service valve adaptor to each length. The last Geka valve should be connected to the remaining yellow tubing. Secure all connections with jubilee clips. UNDERSTANDING JETFLUSH 4 CONTROLS The splash proof mains on/off switch is located on the hand grip immediately behind the Jetflush logo. A standard plug, attached to 5metres of mains cable, allows connection into a domestic outlet socket. The four Geka quick connection valves, pictured in the open position, are for: BLUE: Mains water inlet (Note, an automatic level device on the mains feed allows this valve to be left open unless an operation specifically calls for closure) YELLOW: System water dump to drain GREEN AND RED: Connection to the central heating system The valve functions are moulded as symbols into the Jetflush 4 body, beneath each Geka valve, as a visual reminder as to their purpose. Record your serial number in this Instruction Manual (page 16) to aid requests for technical support. It is located near to the power supply cable inlet on the top plate The temperature gauge on the top plate indicates what the temperature of the recirculating water is relative to the pump tolerance of 40ºC. 4 5

The orange and purple control valves on the top plate determine: the direction of water being pumped through the central heating system whether water is to be dumped to drain. Note: The pointers on the control valves must align with the appropriate tail of the arrow on the symbols. The orange control valve has three operating positions: 1. YELLOW WASTE PIPE: dump water to drain. 2. RED RADIATOR: flow through the system is instantly and safely reversed. 3. GREEN RADIATOR: allows water to be circulated around the system. USING JETFLUSH 4 TO CLEAN CENTRAL HEATING SYSTEMS Determine if the central heating system to be cleaned is open or closed (sealed) i.e. pressurised. If appropriate, open the three port valve if the system is of a Y configuration or both motorised valves if it is an S type. Set the room thermostat so that the boiler remains constantly on. Adjust the boiler thermostat so that the water temperature is below 40ºC and switch it on. Note that this temperature must not be exceeded otherwise the pump will automatically trip out and time will be needed before normal operation can be resumed. The purple control valve has only two positions: 1. YELLOW WASTE PIPE: dump water to drain. 2. WHITE JETFLUSH 4 UNIT: water is circulated around the system via Jetflush 4. Conduct a survey of the system. Record the temperatures reached by all the radiators and identify those with substantial cold spots. Note the settings of any TRV s and then make sure all the radiator valves are opened to their maximum. Take a sample of the system water and keep to one side for reference purposes. 6 7

Open or Fully Pumped System - Y Plan Red Geka Seal here Seal here Rads Green Geka For open systems the circulator should be isolated and removed so that Jetflush 4 can be connected in its place. Removal is preferred for any system whenever this is possible. Boiler Yellow Geka Seal the system at the F and E tank at the two positions shown using suitable bungs available from plumber s merchants. Use the alternate location shown if the system is closed (sealed). Connect Jetflush 4 to the system using the above diagrams as a guide For closed systems ensure the unit is connected as shown, i.e. in series with the circulator the circulator is electrically isolated so that it cannot pump Blue Geka Mains Connected to a sealed system via flow or return pipes Red Geka Blue Geka Bolier Main flow & return pipes System fill Seal here Mains Note: As a last resort, Jetflush 4 may be connected across radiator tails; however, this method does not allow full control over the rate or direction of flow since it is now connected in parallel across the system and not in series. Consequently cleaning efficiency will be impaired. Drain Drain Rads Rads Yellow Geka Rads Green Geka Rads With the circular clear plastic splash guard in place and all Geka valves closed: Fill the unit with water by turning on the mains supply tap and opening the blue Geka valve. Open the red and green Geka valves and switch on the pump. Let the water circulate for two or three minutes. Note 1: The water level will drop below the top level of the pump and will be restored automatically. However, if the level continues dropping switch off the pump, close all the Geka valves and investigate the water loss immediately. Note 2: An optional bund is available for Jetflush 4 to contain any accidental spillages. Add the recommended cleaning chemical to the unit, replacing the splash guard. Continue circulating the solution until fifteen minutes has elapsed from the time the water was first circulated, (it is not critical if this time is exceeded). 8 9

Reversing the flow every five minutes or so by turning the orange control valve between the red and green radiators will improve this initial cleaning process. The pump can be left running during this operation. Note: Whilst the chemical is being circulated, it is important to ensure that all radiator lock shield valves, wheelheads or TRV s are in the fully open position and that the boiler is maintaining the water at a temperature of about 40ºC. After the fifteen-minute period, the hot water circuit and all but one of the radiators should be isolated. Continue circulation through the radiator that has been left open. If during the primary checks, any radiators were identified as having cold spots, it is best to start with these. Periodically reverse the flow with the orange control valve. Banging the radiator with a rubber mallet or the flat of a hand will help to dislodge stubborn debris. Once the entire surface of the radiator has warmed up, the radiator should be isolated and the next radiator tackled. After all radiators, and the hot water circuit, have been flushed the secondary flush can proceed. Switch off the boiler. Close the red and green Geka valves. With the pump still running close the blue Geka valve and open the yellow one. Turn both the orange and purple control valves to the yellow waste pipe and let the contaminated water reduce to below the pump level in the tank. Turn off the pump and open the blue Geka valve. When the unit has refilled open the red and green Geka valves and turn the orange control valve to the green radiator. Start the secondary flush by turning on the pump and when water flowing to drain approximately matches the clarity of the water in the Jetflush 4 unit isolate the radiator and open the next so it too may be flushed clear. Note 1: The pump will dump water to drain faster than the Jetflush 4 unit can fill, so switch off the pump as neccessary to allow the level of the water in the unit to be restored. Alternatively the yellow Geka valve may be partly closed so as to balance the water being pumped to drain with the water filling the unit. Note 2: Badly fouled radiators may benefit by reverse flushing to speed up the time taken for the dump water to clear, to achieve this: Turn the orange control valve to the red radiator. Reverse the flow periodically by turning the orange control valve periodically back and forth between the green and red radiators. When all the radiators and the heating circuit have been flushed open all radiator valves. Flush the entire system until the water being dumped to drain, which may now be a faint straw colour, is clear. 10 11

Sample this water using a Turbidity Tube test procedure. Keep flushing until a reading of less than 100ppm is achieved. Alternatively a conductivity reading can be made, flushing being continued until the reading is within 10% of the value for the mains water supply to the property. Turn off the blue Geka valve and allow the pump to run until the water level in the Jetflush 4 unit is just above the bottom of the pump. Close the yellow Geka valve. Turn the purple control valve to the white Jeflush 4 unit. Add Sentinel X100 scale and corrosion inhibitor to the Jetflush 4 unit. Allow to re-circulate for 10 minutes. Take a sample of the system water and test the level of Sentinel X100. If necessary add more inhibitor chemical, re-circulate and test again. Stop the pump, close the red and green Geka valves and open the yellow Geka valve. Turn the orange and purple control valves to the yellow waste pipes. Restart the pump When the water in the Jetflush 4 unit has been pumped out close the yellow Geka valve and switch off the pump. Turn off the mains water supply and open the blue Geka valve. Disconnect the hoses from the mains water and the central heating system, allowing any water to drain back into Jetflush 4. Disconnect the hoses from Jetflush 4 and close any open Geka valves. REINSTATE THE SYSTEM Replace the circulator pump and remove the seals from the F and E tank if the system is an open one. Pipework, which has been altered to allow for isolation, must be made good to ensure safety during normal operation. For pressurised systems remove the seal from the mains supply fill point and re-pressurise. Return TRV s to their original positions. Switch on the boiler and allow the system to come up to temperature, without resetting the thermostat. Re-examine the radiators, bleed as necessary and then record your observations after they have reached their maximum temperatures. Compare with the original readings, using a suitable report form. Adjust the boiler thermostat to its normal operating value and re-set the room thermostat to its original level. Make a final check that all is satisfactory. Complete any final details of the report form and leave a copy with the customer. 12 13

SUMMARY OF JETFLUSH 4 OPERATIONS FAULT FINDING AND RECTIFICATION GEKA VALVES CONTROL VALVE POSITION STEP OPERATION RADIATORS BLUE RED YELLOW GREEN ORANGE PURPLE PUMP 1 Fill Jetflush 4 With Mains Water ALL OPEN CLOSED CLOSED CLOSED Green RADIATOR White JF4 OFF 2 Circulate System ALL OPEN OPEN CLOSED OPEN Green RADIATOR White JF4 ON 3 Add Cleaning Chemical ALL 4 Circulate System ALL OPEN OPEN CLOSED OPEN Green RADIATOR White Jetflush4 ON 5 Circulate System - Reverse Flow ALL OPEN OPEN CLOSED OPEN Red RADIATOR White Jetflush4 ON 6 Individual Clean 1 OPEN OPEN CLOSED OPEN Red RADIATOR White Jetflush4 ON 7 Individual Clean - Reverse Flow 1 OPEN OPEN CLOSED OPEN Green RADIATOR White Jetflush4 ON 8 Repeat 6 to 7 For Remaining Rads 9 Reduce Tank Level 1 CLOSED CLOSED OPEN CLOSED Yellow Waste Yellow Waste ON 10 Fill Jetflush 4 With Mains Water 1 OPEN OPEN OPEN OPEN Green RADIATOR Yellow Waste OFF 11 Secondary Flush - Dump, by balancing yellow Geka valve, until clarity matches tank water. Reverse flow if necessary. 1 OPEN OPEN OPEN OPEN Green RADIATOR Yellow Waste ON 12 Repeat 11 For Remaining Rads 13 Final Flush To Drain, Open all Rads ALL OPEN OPEN OPEN OPEN Green RADIATOR Yellow Waste ON 14 Reduce Tank Level ALL CLOSED OPEN OPEN OPEN Green RADIATOR Yellow Waste ON 15 Add Sentinel X100, Test Level ALL CLOSED OPEN CLOSED OPEN Green RADIATOR White Jetflush4 ON 16 Empty Tank ALL CLOSED CLOSED OPEN CLOSED Yellow Waste Yellow Waste ON 17 Isolate Mains, Disconnect Hoses (from system first) ALL OPEN OPEN OPEN OPEN Green RADIATOR White Jetflush4 OFF NO FLOW ON FILL LINE Check mains pressure is above 1.0 bar. Check inlet and fill valves are open. PUMP DOES NOT RUN Check that unit is plugged in. Check the fuse in the plug. Check the socket outlet is live. Check for breaks in the mains cable. Check that the thermometer gauge is not in the red zone. If the pump still does not run and the light is on at the switch, then there is an internal fault in the pump. PUMP RUNS BUT THERE IS NO FLOW IN TO THE TANK Check that the red and green Geka valves are open. Check that the circulator service valves are open. Check that all radiator valves are open. Check that closed system circulator is pumping. PUMP RUNS BUT WATER WILL ONLY CIRCULATE IN ONE DIRECTION Non return valve fitted in heating circuit. Another valve in circuit acting as a check valve. WATER LEVEL IN TANK CHANGES WHEN BLUE AND YELLOW GEKA VALVES ARE CLOSED Header tank not satisfactorily isolated. Leak on heating circuit. 14 15

WARRANTY AND SERVICE PLEASE NOTE FOR EFFICIENCY AND HEALTH AND SAFETY REASONS, THE SENTINEL JET FLUSH UNIT IS DESIGNED TO WORK AT TEMPERATURES NO GREATER THAN 40ºC The pump will cut out if this temperature is exceeded and will only reset when cool. The Sentinel Jetflush 4 unit must not be subjected to freezing conditions even when empty. Failure to adhere to this notice may result in permanent damage to the unit and will invalidate any warranty claim. Record your Serial Number here AFTER SALE WARRANTY Your Sentinel Jetflush 4 unit is covered by a parts warranty for a period of one year from date of purchase. Please complete and return the enclosed card in order to validate your warranty. Should you have any problems with your unit, please contact the Sentinel Helpline on 01942 26 36 26 for more assistance. The following items are NOT covered by the warranty: Physical damage to the unit occurring after purchase Component failure due to the system having been run with water exceeding 40ºC. Damage caused by freezing. MAINTENANCE The Sentinel Jetflush 4 unit has been designed to give a long service life with minimal maintenance. However, a few simple tasks need to be undertaken after every clean or periodically to ensure that the unit remains in top condition and continues to deliver outstanding performance. Post use After each time the Sentinel Jetflush 4 unit is used it should be thoroughly cleaned to remove deposits flushed out from the heating circuit that have accumulated in the bottom of the tank. Routine The connection hoses and mains power cable should be periodically examined for signs of abrasion or wear and replaced if necessary. SPECIFICATION DATA Product Name: Height Diameter Weight Empty Weight Working Sentinel JETFLUSH 4 Flushing Unit 900mm 450mm 35.5 kg 75 kg Power supply 240v 50 Hz Single Phase Full load current 4.4 Amps Locked rotor current 16.5 Amps Input power watts 940 Fuse rating 13 Amps Pump ref AP 12.40.06.1 Cable length 5 metres Power connection 13 Amp plug Motor insulation IP68 Class F Inlet connection Drain connection Recirculation connections Max inlet pressure Max drain pressure Max recirculation pressure Working recirculation pressure Max inlet flow at 5 bar Max drain flow Max recirculation flow Typical working recirculation flow 15mm Geka connector with flexible hose 20mm Geka connector with flexible hose 20mm Geka connector with flexible hose 75 psi (5 bar) 20 psi (1.3 bar) 20 psi (1.3 bar) 15 psi (1.0 bar) 30 lpm 35 lpm 50 lpm 40 lpm Max temperature re-circulating liquid 40ºC Optional bund diameter Optional bund height 680 mm 285 mm 16 17

FURTHER INFORMATION For more information on Sentinel Jetflush 4 and Sentinel s comprehensive range of water treatment products visit www.gewater.com/sentinel or call 0151 420 9595. Accessory Kit Jetflush 4 Accessory kits will be available from your Jetflush stockist comprising: Survey Sheets Infra-red thermometer Conductivity Meter Turbidity Tube X100 Test Kit 18