General RATIONALE services. dedicated. utility. that do not. sized. The. over the selection of the. equipment. Voltage.

Similar documents
General RATIONALE services. dedicated. utility. that do not. sized. The. over the selection of the. equipment. Voltage.

Electrical Design Guidelines Table of Contents

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

Page 1 of General

GARCIA GALUSKA DESOUSA Consulting Engineers

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Related Sections: TBD. Effective Date: January 1, 2016

WINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

SECTION ELECTRICAL IDENTIFICATION

MEDIUM, LOW AND CONTROL VOLTAGE CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

ELECTRICAL POWER SYSTEMS

Technical Report 2: Electrical Systems Criteria and Existing Conditions

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

Element D Services Electrical

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

Chapter 1 General... 5

2009 ELECTRICAL CODE REQUIREMENTS

FIRE ALARM: BY OTHERS, IF REQUIRED.

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

Electrical Program. Electrical Laws & Rules. Electrical RCW WAC B. Permits Inspections Access Description Directions Comments.

Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson

FIRE ALARM: BY OTHERS, IF REQUIRED.

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS

Construction Management at Risk Services. New North East Branch Library Project. August 3, 2018

3. Provide revised typed circuit directory in panelboards that have circuits removed.

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

SECTION (16140) - WIRING DEVICES

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

SUBJECT: Effective Date: Procedure Number:

DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and

Building Electrical System Overview

TOM BURNS, PLANNING DIRECTOR

Applications. Standard Materials

Element D Services Electrical ODG010107

SECTION LIGHTING

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

Electrical Inspection Lighting & Power

SECTION EMERGENCY POWER SYSTEMS

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

Division 26 ELECTRICAL TABLE OF CONTENTS

Explosion Proof Exit Sign - Class I, Division I - IP65-120V/277VAC - Emergency Battery Back-Up

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

TABLE OF CONTENTS. Part I Administrative... 1

SECTION AUTOMATIC TRANSFER SWITCHES

Air Flow Diagram. Orange County Sanitation District SP-194 Section 05 Conceptual Design

13. ELECTRICAL - TECHNICAL

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

ELECTRICAL CURRICULA OUTLINE CORE CURRICULUM 2015

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2

Product Specifications Dialog Room Controller* (*patent pending)

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

INSTALLATION INSTRUCTIONS - POWER SENTRY CONTROL POWER SENTRY CONTROL UNIT PSBCEB2 INSTALLATION INSTRUCTIONS

Project Description Clinical Research Building (CRB) Animal Area Renovation

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

5.0 Installation Instructions

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004

Explosion Proof Light Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1

The following is a University standard specification and shall be reviewed and edited by the Design Professional to be project specific.

SECTION ISOLATED POWER SYSTEMS

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required.

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST

Catalog Number. Notes. Type. FST Snap on frosted, diffuse L/LENS No diffuser

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Bdl60u Fluorescent Emergency Ballast

Assessing Your Airfield Electrical Distribution System

STYLISH SOLUTIONS FOR OUTDOOR AND INDOOR SPACES

THAILAND REGULATORY BODY LEGISLATIVE FRAMEWORK RATIONALE FOR REGULATION. Consumer Protection.

PLATTEVILLE MIDDLE SCHOOL

UNC Chapel Hill Design Requirements for Level 3 Biological Safety Laboratories & Animals

SECTION INTRUSION DETECTION SYSTEM

DIVISION 16 - ELECTRICAL

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:

Executive Summary. CNBC Global Headquarters Christine Cajilig

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3

Residential Energy Efficiency Measures

Renovate MCRC Facilities Great Lakes, IL

Explosion Proof LED Light - Equivalent to Watt Metal Halide - Class 1 Division 2

Port of Portland Conveying Equipment Guidelines

Electrical Safety Program

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

POINT ROLLOVER LIGHTS PRL LED HELIDECK SEMIFLUSH LIGHT

SECTION ELECTRICAL GENERAL PROVISIONS

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

DIVISION 16 - ELECTRICAL. A. This division contains the following elements:

NYC Department of Education

2011 and 2014 National Electrical Code Changes Residential Only

DOMESTIC WATER PACKAGED BOOSTER PUMPS

THAILAND REGULATORY BODY LEGISLATIVE FRAMEWORK RATIONALE FOR REGULATION. Consumer Protection.

Electrical Safety Requirements

Transcription:

Section 10 9 6 14 12 1 2 3 4 5 6 8 9 0 11 14 15 16 17 18 19 10 11 12 23 24 25 26 25 20 21 22 23 24 31 37 38 39 340 341 342 38 347 348 49 40 41 42 43 44 45 48 49 40 Section 10.9 General 10.9.0. This section describes additional requirements for BSL33 and ABSL3 facilities. These additional requirements provide greater level of safety and reliability of operation. BSL3 Laboratory Power 10.9.1. a) Electrical Servicee (1) Buildings other than NIH Bethesda campus shall have minimum two dedicated utility services, physicallyy separated in different duct banks and different manholes. Thesee dedicatedd services shall be fed by different primary substations or by one double endedd utility substation, which is fed by two dedicated utility service lines that do not servee any other facility. Each required electric service to the facility shall be sized to handle 100% of the design load (i.e. 2N redundancy). The customer rather than the utility company should own the onsite mediumm voltage distribution including Medium Voltage (MV) / Low Voltage (LV) transformers. When customer owned distribution system installation is not possible, coordinate with the local utility company to ensure that they provide electrical distribution system that meets the facility s requirements. (2) For non-nih Bethesda, Maryland campus BSL3/ABSL3 projects with low voltage double ended switchgear, an automatic main-tie-main breakerr configuration is acceptable. The switchgear shall be metal clad compartmentalized type with each breaker capable of being racked out and replaced with the switchgear energized. BSL3 & ABSL3 Biocontainment 55 56 57 58 64 65 61 62 63 64 65 66 67 68 69 70 71 72 83 84 85 76 77 78 104 105 106 107 108 109 85 106 107 108 109 110 91 92 93 94 95 96 97 This is to increase reliability of electrical services. This provides the owner greater control over the selection of the equipment and aids maintenance of the equipment. Electrical demand of the facility may considerably exceed the utility s own engineering and construction standards. As a result, coordination with utility company is critical in providing reliable electrical service. This is to increase reliability of electrical services as tie breakerr closes to allow transfer of electric power to other available electrical service when one of the main circuit breakers opens. 1

93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 (3) The preferred method of installation for the electric utility services is underground; overhead lines may be used only within the secure perimeter of the facility. (4) Locate distribution equipment, such as MV switches and transformers, in a secure location. (5) Reliability: The A/E shall evaluate and minimize single points of failure for all projects. (6) Downstream electrical distribution from switchgear to critical areas, such as mechanical support rooms with redundant motors in each set, shall comprise pairs of distribution switchboards/panelboards, each fed from a separate side of the switchgear, to supply approximately half of each set of motors. Where possible, provide separate feeders to packaged units with multiple motors, i.e. a separate feeder for each motor. 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 This is to protect electrical service feeders from vandalism and natural disasters such as high winds, thunderstorms and falling tree branches. This is to ensure electrical service equipment is protected from physical damage, vandalism or compromise. This is to preclude outage due to a single point of failure. This is to ensure that critical equipment remains operational when one of the service feeders fail. b) Standby Power Requirements (1) In addition to the loads listed in Section 10.3 - Emergency Power, connect the following loads to the standby electrical systems: i) Critical support fan coil units. ii) Receptacles serving selected equipment. iii) Environmental rooms. iv) General lighting. v) Laboratory air compressors. vi) Sterilizers. vii) Supplemental heating/cooling. viii) Water heaters. (2) As determined per program basis, recommend connecting the following loads to the standby electrical system: i) Freezers/Refrigerators/Environmental rooms, other than high value specimen units. ii) Distilled water systems. iii) General laboratory receptacles. iv) Heat-reclaim systems. v) Imaging equipment. vi) Task lighting. vii) Vacuum pumps. 2

170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 194 196 197 197 198 192 193 204 205 203 204 204 205 206 207 208 209 210 211 212 213 215 216 217 218 219 210 (3) Consider providing 100% generator back-up for facilities where the loads mandated to be connected to a generator comprise the majority of load of the facility. (4) Provide a local generator dedicated to the facilityy to provide emergency/standby power; however, a remote generatorr farm (with redundant feeders) may also be acceptable. (5) Provide a load bank (including a connection point suitable for use for a portable generator) for all BSL3 facilities for periodic testing of generator. c) Uninterruptible Power Supply (UPS) (1) A central UPS system or a number of local UPSs may be required to back-up all building wide low voltage systems that are essential for containmen operation and for critical BSL3/ABSL3 specific loads. Perform an economic analysis to select the appropriate UPS system. (2) A central UPS shall be of the double-conversion on-line type; wet cell type batteries are recommended. (3) Recommend connecting the following systems to thee UPS: i) Building automation systems (BAS). ii) Select light fixtures in lieu of emergency battery packs. iii) Communications and PA systems. iv) Fire alarm systems. v) Lab equipment monitoring systems. vi) Mechanical controls. vii) Security, CCTV and access control systems. 10.9.2. BSL3 Laboratory Conductors, Cables, and Boxes a) Power Wiring Insulationn shall be compatible with sealing compound (sealing compound non- deleterious to insulation), using THW, THWN, THHN/THWN N, or XHHW. b) Other System Wiring Voice/Data, fire alarm, control, and security system wiring shall follow the same sealing requirements as that of the power wiring. Cable types shall be determinedd by NIH IT and manufacturer s recommendations for voice/data wiring and by respective system manufacturer for other systems. The A/E shall coordinate exact requirements for security wiring with Division of Physical Security Management (DPSM). 225 226 227 228 229 235 236 232 233 234 235 241 242 238 239 240 241 242 243 244 245 246 247 248 249 250 Thiss is to protect insulationn of the electrical wiree from damage from sealing compound. Thiss is to protect the low voltage cable from damage from sealing compound. 3

247 248 249 240 251 252 253 254 255 256 257 258 259 250 261 262 266 267 268 269 267 261 262 263 274 272 273 279 270 271 272 273 274 270 281 282 283 317 318 322 323 324 325 326 327 328 c) Sealing Requirements (1) Provide silicon based caulk in all areas. See Chapter 4, Exhibit X4-2-A for additional information. Provide a 25 mmm (1 in.) barrier of silicone caulk around the wire within a devicee box hub. Provide a continuous bead of caulk between the device box and the adjacent surface. Provide a continuous bead of caulk around the device cover plate and the adjacent surface. d) Boxes for All Systems (1) Provide cast boxes with external mounting provisions, external hub, and gasketed devicee cover plates. Provide sealing as mentioned paragraph (c). (2) All boxes shall be double gang type; the box depth shall be at least the next size larger than the minimum size required per code. e) Conduits for Alll Systems Use RGS conduit with threaded fittings in all BSL3 areas. Provide seal-off fittings when conduits exit defined BSL3/ABSL3 perimeter. Use of surface metal raceway systems is NOT allowed in BSL3/ABSL3 areas. 10.9.3. 288 289 290 316 317 318 297 298 299 300 301 302 303 322 308 312 313 349 350 351 352 353 354 355 356 BSL3 Area Lighting Requirements Thiss is to require use of approved sealing compounds, specify required sealing and provide a gas-tight electrical distribution system to facilitate decontamination, and prevent vermin harborage and transmission through the electrical raceway system. Thiss is to provide for a gas-tight electrical installation for decontamination, and to prevent vermin harborage and transmission through the electrical raceway system. Thiss is to provide added device box volume for wiring and required sealing within device boxes. Thiss is to provide a gas-tight electrical distribution system to facilitate decontamination, and prevent vermin harborage and transmission throughh the electrical raceway system. Surface metal raceway is not available with manufactured approved gasketing to eliminate vermin harborage and transmission. a) Lighting Control Laboratories shall utilize line voltage toggle switches. Occupancy sensors may be used in lab support and other areas. In addition, specialized lightingg controls (such as dimming systemss and DC lighting controls) shall be provided per specific program requirements. b) Containment The lighting systemss shall be designed to ensure that biohazards are contained within the BSL3 lab area. Lighting fixtures shall allow full decontamination with ease of effort, and permit easy re-lamping and access to ballasts. 4

329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 c) BSL3 Laboratory Lighting Fixtures Lighting fixtures in BSL3 area shall comply with the following requirements: (1) Provide fixtures with stainless steel housings, glass or heavy duty acrylic prismatic lens and stainless steel door with tool-less fasteners. (2) Fixtures shall be UL listed for damp location and provided with a continuous bead of sealant around its perimeter to seal housing to ceiling. (3) Use surface mounted, fully sealed, enclosed and gasketed fluorescent fixture. Lighting fixtures may be pendant mounted only in an open ceiling. Pendant mounted lighting fixtures shall be fully sealed and gasketed with same features as those of surface mounted fixtures. (4) Install fixtures in continuous rows and aligned with edge of laboratory bench in laboratories and lab support areas. Install lighting fixtures in a symmetrical pattern. (5) Imaging Laboratory: Provide surface mounted lighting fixtures. In specific imaging modalities, such as MRI, fixtures shall be made of non-ferrous materials; use DC rated incandescent lamps and use dimming controls. All special requirements shall be coordinated with the manufacturer of each modality. d) Emergency Lighting (1) Connect 50% of light fixtures in the BSL3 laboratories to the emergency power source. (2) Provide at least one lighting fixture per room in BSL3 laboratory areas with selftesting emergency battery ballast. Connect the lighting fixtures with emergency ballasts to un-switched local emergency generator circuits. 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 This is to allow cleaning of lighting fixture and decontamination by gaseous means. This is required for strict moisture and vermin control required within the space. This is required for strict moisture and vermin control required within the space. This is to provide uniform level of lighting at work surfaces. This to specify unique requirements of the imaging laboratories. This allows for continuation of laboratory function in case of loss of normal power. This allows continuous illumination in case of loss of power and during transfer from once source to other. 5

429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 10.9.4. ABSL3 Animal Research Facility a) Animal Research Facility Standby Power Requirements (1) In addition to the equipment required to be connected to the standby power in BSL3 laboratory, connect the following equipment to the local generator: i) Animal Watering Systems. ii) Animal Cagingg and Ventilation Systems. (2) The following load is recommended to be connected to the local generator per specific program requirements. i) Cage Wash equipment. b) Animal Research Facility Lighting (1) Lighting Fixtures: Lighting fixtures for ABSL3 animal research facilities shall meet all the requirements of lighting fixtures of BSL3 researchh laboratories. In addition, the following requirement applies: i) Self-testing emergency battery ballastss in ABSL3 areas shall have visual indication only. 6