Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

Similar documents
MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

WSA120: New Energy Codes and Lighting Controls

TITLE 24 ICONOGRAPHY. Iconography System

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

ASHRAE October 18, 2013

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

INSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

Here we see the list of auto shutoff controls we will cover in the next few slides

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

MANDATORY MEASURES. There are two major steps for exterior spaces to comply with Title 24:

ANSI/ASHRAE/IES

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

ANSI/ASHRAE/IES

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Lighting Control Strategies. to meet code requirements save energy and improve building performance

California Title Design Guide for Smart Lighting Control and Energy Solutions

Are LED s ready for Prime Time?

Code Review TITLE PRESENTED BY POURIA NIKNAM

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

Codes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012

Wireless Lighting Control Made Easy

Energy Codes. Connected Lighting simplified by Eaton. design and application guide

Note: A summary of the applicable code sections is shown in the CEC _Table100A.

Decoding 2016 Title 24, Part 6

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

MANDATORY MEASURES DAYLIGHTING. (Reference: Sub-Chapter 4, Section 130)

Code Compliance Commercial Application Guide

2015 IECC. Design Guide for Smart Lighting Control and Energy Solutions

A Guide for Applicants and Lighting Designers

What s New in the 2013 Energy Code? Changes to mandatory Title 24 lighting requirements

PRESCRIPTIVE APPROACH

visual environment technologies etcconnect.com

Hospitality Title Solutions

2017 Michigan Energy Code Changes Electrical Provisions-Commercial Michigan Energy Code Training and Implementation Program

Office Title Solutions

Lighting Summary - Interior

Dimming Ballast + Controls and CALCTP Bonus. New Product Overview

Reduce lighting energy costs with controls

Lighting Application Guide for K-12 Classrooms

2005 Title 24 Outdoor Lighting Regulations Overview. 77 slides

Education Title Solutions

High Performance Lighting. Terry Egnor Senior Consultant NBI

C A L I F O R N I A E N E R G Y C O M M I S S I O N

Healthcare Title Solutions

9. LIGHTING. 9.1 General Scope. This section shall apply to the following: Exceptions:

2018 IECC Electrical & Lighting Systems

Integrated LED Lighting Solution

Advanced Lighting Control for High Building Performance

Oregon Non-Residential Building Energy Code

Lighting Controls An Introduction and Review

WELCOME TITLE 24 REQUIREMENTS & THE MAXLITE PRODUCT LINE. 9/5/14 Webinar Presented by: Greg Murphy

Advanced Lighting For Office

Applied Lighting Controls

Aesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS

Lighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1

Thesis Proposal. Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA

visual environment technologies etcconnect.com

Nonresidential Outdoor Lighting Controls

COMcheck Software Version Interior Lighting Compliance Certificate

LIGHTING CONTROLS

Advances in Non-Residential Lighting Technologies

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

Table of Contents. Fast Fact. Sensor Models 2 Advantages of Sensors 3 FAQs 4-5

Restaurants ASHRAE Solutions

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

Daylighting Control Design and Application Guide

Hubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

Lighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03

Indoor Controls. SpaceWise SWZG2. Wireless technology

Best practices in lighting design to comply with California s Title 24 energy code

Related Sections: TBD. Effective Date: January 1, 2016

Lighting Controls: The Next Big Thing in Lighting. June 18th, 2014

Lindsey Beane. Executive Summary

Best practices in lighting design to comply with California s Title 24 energy code

Surface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile

Restaurants IECC 2015 Solutions

Mini Product Guide.

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

SENSORS. Vacancy Sensors. Occupancy Sensors A4-A7 A-1

Lighting is typically one of the

Design and Commissioning of Lighting Control Systems. Rick Miller, PE, LC, LEED AP RNM Engineering, Inc. October 18, 2012

Advances in Lighting Controls and the Impact of ASHRAE Requirements. Rich Rattray, LC OSRAM SYLVANIA

What You Need to Know About California Compliance T20, T24 and JA8 Chris Primous VP OEM National Accts and Industry Relations April 18, 2018

Pacific Gas and Electric Company Energy Efficiency Rebates for Your Business. Lighting Rebate Catalog Saving energy for a brighter future

New LED Product Offerings

CA TITLE 24 QUICK SOLUTIONS GUIDE FOR

IECC. nlight Applications Guide.

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

A Guide to the Commercial Building Tax Deduction. Effective: January 1, 2006 to December 31, 2008 HL /07

SECTION LIGHTING CONTROLS

Hubbell Controls Application Guide to CA Title 24 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

Application Guide to CA Title 24

miniz Quick Start Guide

Lobby Lighting Design

Transcription:

Guides for California Title 24 & ASHRAE Code Compliance Lightcloud Makes Compliance Easy What are California Title 24 & ASHRAE? Links to Energy Codes Interior Lighting Controls Exterior Lighting Controls Other Energy Savings Application Solutions Lightcloud

Lightcloud Makes Compliance Easy This compliance solution guide recommends Lightcloud Devices to get your site in compliance with California Title 24 Part 6 and ASHRAE. Once the devices are installed, RAB will handle commissioning and compliance. For additional compliance solutions, give us a call at 1 (844) - LIGHTCLOUD What are California Title 24 and ASHRAE? is the state energy code for all buildings. New buildings as well as renovations/alterations must adhere to the requirements in Title 24-2016. ANSI/ASHRAE/IES 90.1-2016 is a standard. The 90.1 standard is the reference that serves as the basis for state energy codes. Links to Energy Codes 1 energy.ca.gov/title24/2016standards/index.html energy.ca.gov/2015publications/cec-400-2015-037/cec-400-2015-037-cmf.pdf 2 energycodes.gov/resource-center/training-courses/ansiashraeies-standard-901-2016 1. is California state law (the state energy code ). Therefore, the code text as well as all other associated guides and forms are available to download on-line, free of charge. 2. ANSI/ASHRAE/IES 90.1-2016 is a standard. States are supposed to adopt energy codes at least as stringent as ASHRAE 90.1-2013 or equivalent. Currently, different states have energy codes based on different versions of 90.1, or on some version of IECC (International Energy Conservation Code), while some states have no energy code at all. This is a link to a comprehensive presentation on the 2016 version. Code Compliance Guides for California Title 24 Part 6 & ASHRAE 2

Interior Lighting Controls Area Controls: Manual On/Off Interior spaces must have local switches to allow occupants to turn lights ON and OFF, overriding other controls if necessary. 130.1 (a) 1 All luminaires shall be functionally controlled with manual ON and OFF lighting controls. Each area enclosed by ceiling-height partitions shall be independently controlled. Up to 0.2 watts per square foot of lighting in any area within a building may be continuously illuminated to allow for means of egress illumination. 9.4.1.1 (a) At least one control that controls all the lighting in the space; in spaces 10,000 ft2, each control serves 2,500 ft2 maximum and in spaces > 10,000 ft2, serves 10,000 ft2 maximum. Refer to code text for spaces that allow remote location of manual control(s). OR + OR Occupancy Sensor Dimmer Touch Multi-Level Controls: Dimming Almost all light sources must be either dimmable in a full range (i.e. 10-100%) or in steps. For example, in California Title 24, any LED lamp or fixture must be dimmable from 10-100%. 130.1 (b) 1 The general lighting of any enclosed area 100 ft2 or larger, with a connected lighting load that exceeds 0.5 watts per ft2, shall provide multi-level lighting control. All LED fixtures and lamps must be dimmable in a range of 10-100%. Linear fluorescent lamps must be able to reduce output to intermediate ranges as defined in Table 130.1A. Must meet requirements for control steps and uniformity as shown on Table 130.1A. Various exemptions apply. (The downloadable code document contains this table as well as other graphics describing specific code requirements.) 9.4.1.1 (d) General lighting to provide at least one intermediate step in lighting power between 30-70% or continuous dimming in addition to full ON and full OFF. OR Occupancy Sensor Code Compliance Guides for California Title 24 Part 6 & ASHRAE 3

Interior Lighting Controls Automatic Daylighting Controls: Photo Sensor In interior spaces, all light fixtures near windows and under skylights must be automatically controlled by photosensors. 130.1 (d) 1 Luminaires providing general lighting that are in or partially in the Skylit Daylit Zones or the Primary Sidelit Daylit Zones (as well as Secondary Sidelit Daylit Zones) shall be controlled independently by fully functional automatic daylighting controls. Must comply with multi-level requirements as shown on Table 130.1A. Other specific requirements and exemptions apply. 9.4.1.1 (e) or 9.4.1.1 (f ) If primary sidelighted areas is 150W; or primary and secondary sidelighted areas is 300W; control system must have: separate control of general lighting in primary and secondary sidelighted as well as toplighted areas, photocontrol to reduce electric lighting in response to available daylight using: continuous dimming, or at least one control point between 50% and 70% of design light power and second control point either 1.) between 20% and 40% of design light power or 2.) lowest dimming level technology allows and third control point that turns off all controlled lighting. OR + Calibration does not require anyone to touch the actual photosensors (must be capable of being calibrated remotely). Other specific requirements and exemptions apply. Occupancy Sensor Daylight Harvester Toplighting: Width of Primary Daylight Zones The Primary Daylight Zone creates a perimeter around the skylight that extends 70% of the average ceiling height in the space. For example, a room with 10' ceilings would have a Primary Daylight Zone extending 7' from the perimeter of the skylight..7 Y Y Average Ceiling Height.7 Y Skylight Primary Daylight Zone Code Compliance Guides for California Title 24 Part 6 & ASHRAE 4

Sidelighting: Width of Primary and Secondary Daylight Zones The Primary Daylight Zone has the same width as the window head height (distance from top of the window to the floor), and should extend half the window head height to either side of the window. For example, a room with an 8' window head height would have a Primary Daylight Zone of 8' and a Secondary Daylight Zone of 8'. Both the Primary and Secondary Daylight Zones would extend 4' to the left and right of the window. Primary Daylight Zone Secondary Daylight Zone Non-Daylight Zone Width: Remainder of space Fixtures in Non-daylight zones can still be dimmed based on photosensor input, even though that isn t required by code Window Head Height.5.5 Primary Daylight Zone Secondary Daylight Zone Code Compliance Guides for California Title 24 Part 6 & ASHRAE 5

Interior Lighting Controls Automatic Shut-off Controls: Schedules & Sensors Interior spaces require some method of automatically shutting off most/all light fixtures. This is typically achieved by occupancy sensors, scheduling, or both. 130.1 (c) 1 a. Shall be controlled with an occupant sensing control, automatic time-switch control, or other control capable of automatically shutting OFF all of the lighting when the space is typically unoccupied; and b. Separate controls for the lighting on each floor, other than lighting in stairwells; and c. Separate controls for a space enclosed by ceiling height partitions not exceeding 5,000 ft2; and d. Separate controls for general, display, ornamental, and display case lighting. In the following function areas the area controlled may not exceed 20,000 ft2: malls, auditoriums, single tenant retail, industrial, convention centers, and arenas. 9.4.1.1 (h) or 9.4.1.1 (i) h. All lighting automatically shut off within 20 minutes of all occupants leaving the space and control device to control <5,000 ft2. i. Control lights on a scheduled basis (automatic time switch) based on input from a time-of-day controller or signal from another control or alarm OR Either (h) or (i) meets the requirement for automatic shutoff. Certain spaces may use a Partial ON or Partial OFF strategy to meet code requirements. Occupancy Sensor Demand Response: Automatic Dimming In spaces larger than 10,000 ft2, controls must be able to automatically dim lights by at least 15% when a signal is received from an Automated Demand Response (ADR) server. 130.1 (e) 1 Buildings larger than 10,000 ft2 shall be capable of automatically reducing lighting power in response to a Demand Response Signal; so that the total lighting power of non-excluded spaces can be lowered by a minimum of 15% below the total installed lighting power. Lighting shall be reduced in a manner consistent with uniform level of illumination requirements in Table 130.1-A. Exception Note Spaces with a lighting power density of 0.5 watts per ft2 or less. OR Occupancy Sensor Code Compliance Guides for California Title 24 Part 6 & ASHRAE 6

Exterior Lighting Controls Parking Garage Shutoff Controls: Occupancy Sensor Garages and certain other applications require the use of occupancy sensors to dim light fixtures. Fixtures must be dimmed by at least 30% (ASHRAE 90.1) or by 50-80% (Title 24). Certain exemptions apply, e.g. transition zones, such as the entry into a garage from the outside. 130.1 (c) 7.B. In parking garages, parking areas and loading and unloading areas, general lighting shall be controlled by occupant sensing controls having at least one control step between 20 percent and 50 percent of design lighting power. Occupancy sensors automatically switch lights in appropriate zones to full ON from all designated paths of egress. Zones 500 watts; uniformity based on Table 130.1-A see page 6. 9.4.1.2 Automatic lighting shutoff per 9.4.1.1(i) <scheduled shutoff>; must reduce lighting power by minimum of 30% when no activity is detected for 20 minutes within a lighting zone 3,600 ft2. Lighting for 24/7 operation; areas where auto shutoff causes safety or security concerns; lighting load 0.02 W/ft2 Occupancy Sensor Parking Garage Automatic Daylighting Controls: Photo Sensor In garages with glazing or wall openings, all light fixtures near windows must be automatically dimmed by photosensors. 130.1 (d) 3 In a parking garage area with a combined total of 36 ft2 or more of glazing or opening, luminaires providing general lighting that are in the combined primary and secondary sidelit daylit zones shall be controlled independently from other lighting in the parking garage by automatic daylighting controls. Exception 1 Luminaires in the daylight transition zone, and luminaires strictly for use with dedicated ramps; Exception 2 The total combined general lighting power in the primary sidelit daylight zones is less than 60 watts. 9.4.1.2 Automatically reduce power at least 50% in response to daylight for luminaires within 20 ft. of any perimeter wall that has a net opening to wall ratio of 40% and no exterior obstructions within 20 ft. OR + Exception 1 Luminaires in the daylight transition zone, and luminaires strictly for use with dedicated ramps; Exception 2 Daylight transition zones and ramps without parking are exempt from 30% reduction and daylight control. Occupancy Sensor Daylight Harvester Code Compliance Guides for California Title 24 Part 6 & ASHRAE 7

Exterior Lighting Controls Outdoor Lighting Controls: Schedules & Sensors All fixtures must turn OFF based on scheduling, for example by a time clock or lighting control system, or by input from a photosensor. All fixtures (including pole and wall-mounted) 24 ft. high must dim based on input from motion sensors (occupancy sensors) by > 50% (ASHRAE 90.1) or by 40-90% (Title 24). Various exemptions apply to controls requirements for many exterior lighting applications, especially where there are concerns about life safety, security, 24/7 operation, etc. 130.2 (c) Automatic shutoff based on an astronomical timeclock or photosensor. Fixtures mounted 24 ft. above the ground shall be controlled by motion sensors that reduce the output by 40-90%. For certain exempted exterior lighting, part-night controls are required (i.e. controls that turn off fixtures at a specified time). All incandescent luminaires 100 watts shall be controlled by motion sensor. Outdoor lighting not permitted by a health or life safety statute, ordinance, or regulation to be turned OFF; tunnel lighting; outdoor sales frontage; building facades; ornamental hardscape; outdoor dining; pole-mounted fixtures 75 watts; non-pole-mounted fixtures 30 watts 9.4.1.4 Lighting must be OFF when there is sufficient daylight. Building façade and landscape lighting must be OFF between midnight or business closing (whichever is later) until 6am or business opening (whichever comes first)... OR... times established by the authority having jurisdiction. Power for other lighting and signage lighting shall be automatically reduced by 50% from midnight or within 1 hour of end of business operations (whichever is later) until 6am or business opening (whichever is earlier)... OR... during any period when no activity has been detected for a time 15 minutes. Luminaires for outdoor parking areas > 78W (Watts) and with a mounting height of 24 ft above ground must automatically reduce power by > 50% when no activity is detected in the area for 15 minutes. + Calibration does not require anyone to touch the actual photosensors (must be capable of being calibrated remotely). Other specific requirements and exemptions apply. Stealth Code Compliance Guides for California Title 24 Part 6 & ASHRAE 8

Other Lighting Power Density (LPD) Limits For interior as well as exterior spaces, both Title 24 and ASHRAE 90.1 limit the amount of installed lighting power. Interior lighting power allowances may be determined based on the Building Method, Space-by-Space Method, or Tailored Method (depending on applicable code). Exterior lighting power allowances are determined based on the type of lighting zone in which the building is located. Some codes (i.e. Title 24) have more complex calculations to determine power allowance for exterior lighting. Both codes have provisions to modify the power allowances based on unusual room geometries (i.e. atriums, high ceilings, etc.). In general, LPD limits are lower than in previous code versions based on the availability of higher-efficacy and more effective LED lamps and fixtures. Exterior Lighting Title 24 Part 6 and ASHRAE 90.1 both have specific requirements for mandatory controls for exterior lighting as summarized on Page 8. These requirements apply to building-mounted exterior lighting, other area and roadway lighting as well as parking garages. Plug-Load Control Both Title 24 Part 6 and ASHRAE 90.1 require that at least half of all 120-volt receptacles can be automatically turned OFF either during periods of vacancy or after hours (requiring the use of either occupancy sensors or time-of-day devices i.e. a time-clock or advanced lighting control system with scheduling). Specific requirements, limitations and exemptions apply. Documentation & Commissioning Title 24 as well as ASHRAE 90.1 have specific requirements for documenting the proposed lighting and controls equipment and operation, as well as for the commissioning process for installed lighting control devices and systems. Title 24 Acceptance Testing In addition to specific requirements to verify installation of mandatory or other lighting controls, Title 24 also has extensive requirements for acceptance testing by someone trained as a CLCATT (California Licensed Controls Acceptance Test Technician). Alterations Many of the mandatory controls requirements as well as LPD limits are also applicable to alterations in existing buildings. These are triggered when > 20% (in ASHRAE 90.1) or 10% (in Title 24) of the total connected lighting load is affected by the alteration. Certain types of 1-for-1 retrofits or routine maintenance of existing fixtures either have minimal compliance requirements or don t actually trigger the need to comply with any code measures. Energy Reporting, Disaggregation of Load Types, Sub-Metering These are some of the additional code requirements in Title 24 and/or ASHRAE 90.1. Refer to code text for more information about all applicable requirements and limitations. Code Compliance Guides for California Title 24 Part 6 & ASHRAE 9

Energy Savings Savings Method Potential Savings* Occupancy / Vacancy Sensing Adjust lights based on the presence or absense of individuals in a space 43% Scheduling Zones and scenes adjust based on time of day or astronomical sunrise/sunset 24% Daylighting Dim Zones or scenes to account for sunlight or other light sources in a space 60% Task Tuning Set a maximum light level and dim lights for specific tasks 36% Demand Response Set energy saving scenes when notified by energy utility 50% at peak Plug Load Control Eliminate power draw after hours or when a room is unoccupied 43% of load Lightcloud Lightcloud can combine some or all of these methods for greater energy savings. 68% Lightcloud-Enabled RAB LED Fixtures Combine the power of Lightcloud with RAB's high-efficiency LED fixtures 88% * Energy savings are a conservative upper-limit estimate but may be exceeded for some applications. Savings refer to energy used for lighting with the exception of the plug load control. Code Compliance Guides for California Title 24 Part 6 & ASHRAE 10

Application Solutions Space Occupancy / Vacancy Sensing Scheduling Daylighting Task Tuning Demand Response Plug Load Control Auditorium Break Room Conference Room Gymnasium Hallway Industrial Indoor Lobby Medical Office Restroom Stairwell Storage Restaurant Retail Outdoor Landscaping and Walkway Parking Lot These solutions are recommended, but each application is unique. If you need help determining the ideal solution for your site, give us a call at 1(844)LIGHTCLOUD. Code Compliance Guides for California Title 24 Part 6 & ASHRAE 11

Interested? lightcloud.com 1 (844) LIGHTCLOUD 2018 RAB Lighting, Inc. RAB is continually improving our products. Specifications may change without notice. The designs of RAB fixtures are protected under U.S. and international intellectual property laws.