Operating Instructions

Similar documents
Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

Operating Instructions

G a

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

RVL47. Heating Controller. Installations Instructions. Installation

RVL470. Heating Controller. Use. Functions. Series B

RVL480. Heating Controller

RVP310. Heating Controller. Building Technologies HVAC Products

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

RVL481. Heating Controller. including d.h.w. heating

Heating and D.h.w. Controller RVL482 Basic Documentation

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

RVL479. Heating Controller. for use with a partner unit

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

REA22 Room Temperature Controller

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

Landis & Gyr RAV 91 Operating Instructions

Use. Functions. Key function. Other functions

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

Self-learning Room Temperature Controller

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

MAKING MODERN LIVING POSSIBLE. TP7001 Range Electronic 7 Day Programmable Room Thermostat. User Guide. Danfoss Heating

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

INSTRUCTION FOR THE USER THC V E OIL BLU

QAW70. Room Unit. Building Technologies. for use with heating controllers

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

Room Unit. Building Technologies SYNERGYR

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

Operating Instructions Model : HC HC-N

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

ProCon Boiler Controller Commissioning Quick Reference Guide

PRELIMINARY EDITION

MAKING MODERN LIVING POSSIBLE. CP715Si. Electronic 2-Channel Common Timebase Programmer for Heating and Hot Water. User Guide.

AUTO CM CM USER GUIDE

Operating instruction. Remote control station WCM-FS /

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

Operating Instructions

Control solutions Biofloor

Self-learning Room Temperature Controller

Drayton Digistat +3RF

Type UCG/UDG. English...1 Français...7 Español Up button. OK button. Down button

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

ECO AND DATE /06 ARTWORK DESCRIPTION. 22 page A6 : Saddle stitch (2-wire) 6 page : 4 colour : 170gsm Silk 18 page : 1 colour : 100gsm Silk

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

R. Boiler Energy Management System FW 200. Operating Instructions for the User (2010/05)

Local Process Bus LPB

Operating Instructions Model: PRT-RP Version 3. 05/11 Revision 2 Ref: PRTRP

Synco 900 Operating instructions

COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual

R. Room temperature controller with solar control FR 120. Operating instructions for the user (2012/02)

3 Channel Multi-Purpose Programmer User Instructions

VR 90 Remote control unit

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

User s Manual

CM707. Programmable Room Thermostat with Optimum Start, Optimum Stop and Delayed Start. User Guide

Operating instructions

CM921 - User Guide 1 day Wireless Programmable Room Thermostat with LoT technology

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Heating Controller SDC Remote Heating Controller DHC

RF ELECTRONIC PROGRAMMABLE ROOM THERMOSTAT, 7 DAY

User Instructions For TopTronic RS-30

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating

Room thermostat with 24-hour time switch and large LCD

Synco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products

ECL Comfort 210 / 296 / 310

RF Programmable Room Thermostat User Instructions

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

- Data Brochure Universal Reset Module 422

Boiler controller Lambdatronic S 3200

Model: RT510RF. Installation Manual

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

Installation and User Guide eco Intelligent Radiator Thermostat

Operating Instructions

DAY/TIME Button: Selects hour, minute and day setting.

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual:

danfoss Heating Solutions 5

District heating controller

Model: PRT2-TS / PRT2-NTS EU. Model: Touch Duo

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

District heating controller

- Data Brochure Universal Reset Module 423

USERS GUIDE. Electronic Timer, 7 day. LOGIC+ Combi, LOGIC Combi & LOGIC Combi E 24, 30, 35

4 in 1 Digital Thermostat Control

DAY/TIME Button: Selects hour, minute and day setting.

Heating is great when you control it. USER MANUAL. Wireless Programmable Room Thermostat. Model No.: LS Scan for App

DIGISTAT OPTIMISER PROGRAMMABLE 7 DAY ROOM THERMOSTAT SYSTEM. Radio frequency controlled programmable room thermostat

Digital Thermostat Models: VS30W and VS30B

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

Transcription:

Operating Instructions Heating Controller Landis & Staefa RVL469 Overview... 2, 3 Symbols used... 4 Info button... 5 Operating modes... 6 Switching the heating on... 7 Room temperature is not correct... 8 Departing from the heating program... 10 Displaying and readjusting setting values... 11 Adjusting the room temperature setpoints... 12 Changing the heating program... 13 Entering the holidays... 16 Setting the clock... 17 Savings tips... 18 Tips if something seems wrong... 19 Faults and manual operation... 20 Siemens Building Technologies AG 74 319 0008 0 a 1/24

2/24 74 319 0008 0 a Siemens Building Technologies AG 2522Z01

Overview what is where? 1 Operating mode buttons; button of the current operating mode is lit 2 Info button 3 Display 4 Buttons for selecting and readjusting values 5 Heating curve adjustment 6 Knob for readjustment of room temperature 7 Buttons for manual operation: A = manual operation ON (LED lit) B = valve OPENS C = valve CLOSES 8 LED for valve OPENS 9 LED for valve CLOSES 10 LED for pump ON Siemens Building Technologies AG 74 319 0008 0 a 3/24

Meaning of symbols in the display ECO ERROR BUS NORMAL heating REDUCED heating No heating required (according to prevailing outside temperature) Holidays mode Heating OFF (frost protection ensured) Fault in the plant One of the maximum limitations is active One of the minimum limitations is active Controller is connected to data bus 4/24 74 319 0008 0 a Siemens Building Technologies AG

You want to obtain information Press button several times for the display of: Time of day Outside temperature Room temperature (only if a sensor is used) Flow temperature The arrow points at the displayed variable. The info selected last will be continuously displayed. Siemens Building Technologies AG 74 319 0008 0 a 5/24

The individual operating modes Heating OFF Automatic heating up and setback according to the heating program Heating automatically OFF during the holiday period entered Heating automatically OFF if permitted by the prevailing outside temperature (ECO function) Continuously REDUCED heating Continuously NORMAL heating Frost protection ensured in all operating modes. Remote operation with a room unit only possible in AUTO mode. If the button flashes, the room unit overrides the controller's heating program. In AUTO mode, the RVL469 is a fully automatic controller throughout the year. 6/24 74 319 0008 0 a Siemens Building Technologies AG

You want to switch the heating ON Is heating plant ready to operate? Check position of main switch Press button several times until the weekday and the time of day appear in the display Check time of day and date. Correct if necessary (refer to section «You want to set the clock» on page 17) Press button for AUTO mode. Correction of entries: for procedure, refer to pages 12 and 17. During commissioning, practice-oriented and proven values were entered! Siemens Building Technologies AG 74 319 0008 0 a 7/24

The room temperature is not correct If the room temperature is never correct, that is, neither in mild nor in cold weather, make a readjustment with the setting knob: Room temperature too low: Turn setting knob towards + Room temperature too high: Turn setting knob towards The knob's scale gives the room temperature readjustment in C. If the room temperature is not correct in mild weather only or in cold weather only, make the readjustment with the heating curve. For this purpose, there are three setting choices available, depending on the entries made by your heating engineer. To make a readjustment, proceed as follows: 8/24 74 319 0008 0 a Siemens Building Technologies AG

Setting choice Room temperature is not correct in mild weather Analog Use slider on the left and readjust by about 5 C Room temperature is not correct in cold weather Use slider on the right and readjust by about 5 C Digital Readjust line by Readjust line by about 5 C about 5 C Via data bus Contact plant operator Contact plant operator Ï (_ mark with a cross whichever applies) After a readjustment, wait two days the control system requires a certain time to adapt! Siemens Building Technologies AG 74 319 0008 0 a 9/24

You don't want to heat according to the heating program No REDUCED heating: Press the button to select the NORMAL mode Maintaining REDUCED heating: Press the button to select the REDUCED mode Don't forget to return to the normal heating program! The controller operates according to the heating program only when in AUTO mode. 10/24 74 319 0008 0 a Siemens Building Technologies AG

How to display or readjust the setting values Press or to access the setting level. The settings are assigned to 20 lines: Select next line below Select next line above Readjustment of values: Reduce Increase Values are adopted by selecting the next line or when leaving the setting level Leaving the setting level: press button of the required operating mode, or the button, or automatically after 30 minutes For list of lines, refer to the last page of these instructions. To «practise», reset the time of day refer to section «You want to set the clock» on page 17. Siemens Building Technologies AG 74 319 0008 0 a 11/24

You want to select other room temperature setpoints Selecting lines: press or Readjusting values: press or On line, change the setpoint of NORMAL heating (display ). Standard setting is 20 C On line, change the setpoint of REDUCED heating (display ). Standard setting is 14 C On line, change the setpoint of frost protection and holidays mode (display ). Standard setting is 10 C Leaving setting level: select required operating mode Don't forget temperature-sensitive objects like plants! 12/24 74 319 0008 0 a Siemens Building Technologies AG

You want to change the heating program Selecting lines: press Readjusting values: press or For the daily heating up and setback, the controller is supplied with a standard heating program: Daily from 06:00 to 22:00: NORMAL heating Daily from 22:00 to 06:00: REDUCED heating or You can enter a maximum of three heating periods per day. For each heating period, the following times must be entered: Start of NORMAL heating End of NORMAL heating Siemens Building Technologies AG 74 319 0008 0 a 13/24

Proceed as follows: 1. On line, select the weekday whose times shall be changed: 1 = Monday, 2 = Tuesday, etc. 1-7 = valid for all weekdays 2. On line, set the time for the start of NORMAL heating 3. On line, set the time for the end of NORMAL heating If additional daily heating periods are required: 4. On lines and, enter the times required for the start and the end of the 2nd heating period 5. On lines and, enter the times required for the start and the end of the 3rd heating period To cancel a heating period, change line, or until --:-- appears. Leaving setting level: select required operating mode 14/24 74 319 0008 0 a Siemens Building Technologies AG

Example of a 24-hour program with three heating periods: NORMAL heating from 07:00 to 12:00, from 14:00 to 18:00, and from 19:00 to 23:00 If the entries for the weekend shall differ, first enter the times for the entire week (1-7), then change days 6 and 7 individually. Siemens Building Technologies AG 74 319 0008 0 a 15/24

You want to enter your holidays Selecting lines: press or Readjusting values: press or Proceed as follows to enter the data for one period: 1. On line, enter the number of the holiday period 2. On line, enter the date of the first day of holiday 3. On line, enter the date of the last day of holiday (possible only when an entry was made on line!) To deactivate an entry, change line until --.-- appears. At the end of a holiday period, its data will be cancelled Leaving setting level: select required operating mode Before making entries, prepare a holiday plan on a piece of paper. 16/24 74 319 0008 0 a Siemens Building Technologies AG

You want to set the clock Selecting lines: press Readjusting values: press or 1. Select (time of day) and set the time 2. Use same procedure for weekday, date and year: The weekday on line (1 = Monday, 2 = Tuesday, etc.) The date (day and month) on line The year on line Leaving setting level: select required operating mode or The change from wintertime to summertime, and vice versa, is made automatically. Siemens Building Technologies AG 74 319 0008 0 a 17/24

Savings tips without sacrificing comfort During the day, make certain that a room temperature of 21 C will not be exceeded. Every degree above that level increases heating costs by 6 to 7 % Renew air in the house quickly, but open windows fully In unoccupied rooms, set the thermostatic radiator valves to their frost protection position Radiators should not be covered by curtains, furniture, etc., as this reduces heat emission Closed window shutters, blinds, etc., reduce heat losses Check heating energy consumption at regular intervals 18/24 74 319 0008 0 a Siemens Building Technologies AG

Tips to follow if something seems wrong The heating system does not work: Check the display: if ECO (Economy) is shown, the heating is shut down by the ECO function! The heating system always maintains the same room temperature: Check the operating mode (only AUTO mode reduces and heats up again!) The control has a room unit, but it cannot be operated: Check controller's operating mode. To enable the controller to be operated from the room unit, it must be in AUTO mode The desired room temperature is reached either too early or too late: Change the heating program If the building is well insulated, you can expect long cooling down times Siemens Building Technologies AG 74 319 0008 0 a 19/24

Faults and manual operation If you are uncertain: Is the plant switched on? Are all fuses of the plant in order? Is there sufficient fuel in the tank? Has the controller been readjusted by unauthorized persons (time of day, setpoints, etc.)? Check the display: if ERROR is shown, line displays an error code. The error codes have the following meaning: 10 = fault outside sensor 30 = fault flow temperature sensor 40 = fault return temperature sensor 60 = fault room temperature sensor 61 = fault room unit 81 = short-circuit on LPB bus 82 = same bus address assigned several times 100 = two clock time masters on LPB 20/24 74 319 0008 0 a Siemens Building Technologies AG

120 = flow alarm 140 = wrong controller address (LPB) 142 = no partner unit on data bus These error codes are helpful for service staff. If the controller uses a room temperature sensor: Is the room temperature sensor affected by draughts, solar radiation, etc.? Is the sensor affected by heat gains, such as people, machines, lighting, etc.? Is the room temperature sensor covered by furniture, curtains, or similar? Are all thermostatic radiator valves in the "sensor's room" in their fully open position? Siemens Building Technologies AG 74 319 0008 0 a 21/24

The control does not work: If heat producer and circulating pump still operate: press button A to select manual operation. The valve can be manually operated by pressing button B (opening) or C (closing) Switch manual operation off again: press button A or select the required operating mode. The heat producer no longer works: The burner has gone to lockout. Press the reset button! The circulating pump and/or the boiler pump do not operate. Check the fuses! The coupling mechanism between actuator and valve is disengaged. Engage it! If you cannot correct the cause of the trouble, call in your heating engineer! 22/24 74 319 0008 0 a Siemens Building Technologies AG

Address and phone no. of your heating engineer: Notes:............... Siemens Building Technologies AG 74 319 0008 0 a 23/24

Setpoint of NORMAL heating Setpoint of REDUCED heating Setpoint of holidays and frost protection mode Weekday, for entering the heating program (1 to 7) 1st heating period, start of NORMAL heating 1st heating period, end of NORMAL heating to 2nd and 3rd heating period Number of holiday period (1 to 8) First day of holiday period (day.month) Last day of holiday period (day.month) Heating curve, flow temperature at +15 C Heating curve, flow temperature at 5 C Time of day (hour:minute) Weekday (1 to 7) Date (day.month) Year Display of faults 24/24 74 319 0008 0 a Siemens Building Technologies AG