Chilled Ceiling Condensation Control Experience In A Movable Sash Building

Similar documents
NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Direct Digital Temperature, Humidity, and Condensate Control for a Dedicated Outdoor Air-Ceiling Radiant Cooling Panel System

Do All DOAS Configurations Provide the Same Benefits?

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Achieving Dry Outside Air in an Energy-Efficient Manner

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

7. MECHANICAL SYSTEM DESIGN

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

Displacement Ventilation in Classrooms

Two essential attributes of mechanical systems intended to

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

Chilled Ceilings / Beams Working Principles & Applications

Designing Energy Efficient Outdoor Air Systems

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation

A study of radiant cooling for a room with daytime application in tropical climate

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

ASHRAE JOURNAL ON REHEAT

The School District of Philadelphia Administration Headquarters

A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer

CHAPTER 4. HVAC DELIVERY SYSTEMS

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Optimisation of cooling coil performance during operation stage for improved humidity control

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Chilled Ceilings in Parallel with Dedicated Outdoor Air Systems: Addressing the Concerns of Condensation, Capacity, and Cost

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Benefits Offered by Passive Dehumidification Wheel Speed Control

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

HVAC DISTRIBUTION and DELIVERY SYSTEMS

Comfort and health-indoor air quality

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

HVAC 101. H V A C S y s t e m s

Radiant Heating & Cooling for Commercial Buildings

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

DIGI-VAV APPLICATIONS

National Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Chilled Beams. Getting a Warmer Reception

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Indoor Pool Design Considerations Colorado Springs, Colorado

Zehnder Rittling Corporate Headquarters and Manufacturing Facility

HVAC Controls Upgrades: Requirement Details ( )

Reviewing HVAC Designs for Compliance with ACCA Manual S

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Dehumidifying with Dedicated Outdoor Air

NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort

Modular Active. Chilled. Beams

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

KE2 EvaporatorEfficiency Theory of Operation

Air Conditioning Clinic

APPLICATION GUIDE BEAMS

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

The School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

chilled beams Redefine your comfort zone.

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

DADANCO Technical Paper

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

4-Pipe VAV vs. Active Chilled Beams for Labs

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

HVAC Controls Upgrades: Requirement Details ( )

Ultra Low Cost Solar Water Heater. Concept Generation and Selection Document

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

COMMISSIONING CASE STUDY OF A COOLING CEILING SYSTEM. Campus du Sart Tilman- Bât: B49 - P33. B-4000 Liège Belgium 3

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

Des Places Residence Hall

Selection of air conditioning systems

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

Dehumidification at Part Load

Summary Comparison of Simulation Program Features

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

ENGINEERING. Edition No. 13 October 2002

IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Hello, my name is Sarah Hilden and I am a Marketing Engineer in the C.D.S. group at Trane.

Select DOAS, Ceiling Radiant Cooling Panel- Chilled Beam Projects. Updated 9/23/2008

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

ASHRAE Headquarters Building: GSHP vs. VRF systems

Underfloor Air Distribution:

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Bring the fresh in. D E D I C A T E D O U T S I D E A I R S Y S T E M

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Transcription:

Chilled Ceiling Condensation Control Experience In A Movable Sash Building Introduction: A dedicated outdoor air system (DOAS) with a parallel sensible cooling chilled ceiling, or ceiling radiant cooling panel (CRCP) system (Jong, Mumma, Bahnfleth) has been in operation on campus for over a year. The design intent was to use the DOAS to meet the ventilation requirements and remove the entire space latent load (Shank, Mumma) and meet the space sensible loads with the CRCP without condensation concerns (Mumma, 2001a). In spite of the design intent, and subsequent condensation free operation to date, the university physical facilities personnel have remained skeptical of the systems ability to avoid condensation problems, a common concern expressed almost universally. Their primary skepticism seems to be based upon the fact that the CRCP is in an old building with a large area of movable sash, and is occupied by undergraduate students on an around the clock basis. Their concern is that condensation will form and drop onto valuable objects below. In addition, while not an explicit concern expressed by the personnel, condensation on a continual basis would lead to mold growth and potential IAQ problems. The intent of this column is to help alleviate the concerns and skepticism on the part of engineers, contractors, operational personnel (including the university facility personnel), investors/owners, and building occupants. Controls For CRCP Capacity And Condensation Control Capacity control can be achieved in two ways, much as capacity control can be achieved in an all air system. Using either a constant temperature variable flow (Mumma 2001b), or a constant flow variable temperature inlet water conditions (Conroy, Mumma) the CRCP capacity can be modulated. In either case, the CRCP inlet water temperature must not drop below the space DPT typically 55 to 60F when the sash and doors are closed. For small or single zone applications where a constant flow and variable temperature control is used, to avoid condensation, the zone dew point temperature (DPT) is monitored and the CRCP water inlet temperature is controlled by mixing CRCP return water with low temperature chilled water. As a backup, a passive fail safe condensation sensor is employed. Under muggy summer conditions, if a window or door is opened, the space DPT

will rise and the CRCP inlet water temperature will be controlled at or above the space DPT. CRCP cooling capacity may decrease below that required, but condensation will be avoided. In the worst-case limit, all of the windows and exterior doors are opened. This column will present data for such an occurrence with this control approach. For large multi-zone applications, a variable flow and constant temperature control would result in the lowest first cost installation. In this case, the controls would attempt to maintain the desired space DPT with the DOAS, and modulate the CRCP water flow to meet the required sensible load under a closed windows condition. In the event that a window or exterior door is opened longer than momentarily as detected by proximity switches (rather than individual space DPT to limit the project first cost), the CRCP flow control valve may need to close to prevent condensation. A decision on closure would be based upon a comparison of the design space DPT and the current outside DPT. If the outside DPT exceeds the design space DPT (a worst case scenario), the CRCP control valve serving the zone (may be a row of perimeter offices for example or a single space) must close to avoid condensation. Should all of the doors and windows return to their closed positions, the CRCP control valve may be permitted to modulate again following a suitable time delay that would allow the DOAS system to restore the space DPT to design. Field Experience With CRCP Condensation Control In A Movable Sash Building. The Architecture (not Engineering) students in the DOAS-CRCP space were briefly instructed the first week of fall semester a year ago concerning the system operation. Regarding window operation, they were informed that they were free to open the windows, as they desired, but that space temperature and comfort would be compromised. At no time did the students choose to open the windows. It is speculated that they behaved in this fashion since the DOAS, providing 100% fresh OA, maintained the space RH relatively uniform at around 50% while the CRCP maintained the space dry bulb temperature at set point. Apparently, because the controlled indoor environment was always to be favored over the outdoor conditions, there was no incentive to open the windows. Since the students did not create a situation to test the facilities personnel s open window concerns, such a test was conducted by the author. All of the

windows were opened, Figure 1, and the two exterior doors were opened at a time when the space DPT was 57.5F and the outside air DPT was 66F. A trend plot of the data is presented in Figure 2. The space DPT (DPT st4 on Figure 2) rose exponentially and approached a quasi-steady value of 65F, just 1F below the outdoor air DPT. And it rose rapidly, exhibiting a time constant of 5 minutes. The rapidly rising space DPT caused the control to close the CRCP control valve, denoted V2 pos on Figure 3, since the CRCP inlet fluid temperature was well below that of the space DPT. The valve response was delayed no more than one minute, and was completely closed within 4 minutes of the window and door opening. The delayed valve response caused a delay in the response of the CRCP inlet water temperature, denoted T3 (CHWS) on Figure 2. The closed CRCP control valve caused the inlet water temperature to rise quickly, a time constant of 12 minutes following a 3 minute delay, as heat from the space was added to the CRCP while the CRCP pump continued to run. Twenty-two minutes after the windows and doors were opened, the CRCP inlet water temperature and the space DPT curves crossed again, and the danger of condensation no longer existed. During the 22 minutes, the difference between the space DPT and the CRCP inlet water temperature was 5F or less. In prior research (Mumma, 2002), it was shown that the visible condensation is small, when a surface is held 5F below the space DPT for 8.5 hours. There was absolutely no condensation visible on the CRCP surface, Figure 4, and essentially none on the uninsulated chilled water supply piping Figure 5 (on a shiny copper surface, condensation is noticed when the reflection becomes even slightly diffuse). Any condensation on the supply pipe quickly dissipated after the CRCP inlet fluid temperature reached the space DPT. As expected, 23 minutes after the CRCP fluid temperature reached the space DPT, the control valve began to modulate. So sensible cooling was not completely lost even with the doors and windows fully open to the outside. However both sensible and latent comfort control was not adequately maintained with the doors and windows open. Conclusion: Condensation prevention control, in a historic building with large movable sash, was easily achieved even when the inside DPT was suddenly elevated

by opening all of the doors and windows. The test was repeated many times, with similar results and never a condensation problem. A future IAQ column will address another concern of the university facilities personnel: Can the passive fail safe condensate sensor prevent damaging condensation should the automatic temperature and humidity control system fail to cause the CRCP control valve to respond when the doors and windows are opened? References: Jeong, Jae-Weon, S. A. Mumma, W. P. Bahnfleth, Energy Conservation Benefits of a Dedicated Outdoor Air System with Parallel Sensible Cooling by Ceiling Radiant Panels, ASHRAE Transactions, Kansas City Meeting 2003 Shank, Kurt, S. A. Mumma Selecting The Supply Air Conditions For A Dedicated Outdoor Air System Working In Parallel With Distributed Sensible Cooling Terminal Equipment, ASHRAE Transactions, V107(1), pp. 562-570, 2001 Mumma, Stanley A., Ceiling Panel Cooling Systems ASHRAE Journal 43(11): 28-32, 2001a Mumma, Stanley A., Dedicated Outdoor Air in Parallel With Chilled Ceiling Systems Engineered Systems 18(11) 56-66, 2001b Conroy, Chris, Mumma, S. A., Ceiling Radiant Cooling Panels As A Viable Distributed Parallel Sensible Cooling Technology Integrated With Dedicated Outdoor-Air Systems, ASHRAE Transactions, V107(1), pp. 571-579, 2001 Mumma, Stanley A., Chilled Ceilings in Parallel with Dedicated Outdoor Air Systems: Addressing the Concerns of Condensation, Capacity, and cost ASHRAE Transactions, H-1749 V108(2), pp. 220-231, 2002

Figure 1, Picture of the exterior wall with the windows open

Time windows opened Figure 2, Trend plot of the important temperatures

Control valve % open Figure 3, Trend plot with control valve position

Figure 4, CRCP after opening windows, no condensation

Figure 5, Chilled water pipe with slight condensation visible after opening windows.