Secretary of State determination under article 36 of the Fire Safety Order

Similar documents
NOTTINGHAM CITY HOMES

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

Personal Protection Systems (PPS)

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

Fire Safety Policy (Communal Areas)

Waking Watch / Common Fire Alarm. Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats

West Yorkshire Fire & Rescue Authority. Fire Protection Policy

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

Crown Premises Fire Inspection Group

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014

Fire Safety Logbook. FOLLOW the regulations. MANAGE fire risks. RECORD relevant checks

FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS

FP-PGN-14 Part of NTW(O)41 Fire Policy

Dan Gray, Property Director. Date: November 2017 Review Due Date: November 2020

BS 5839: Part THE CHANGES

Consultation on Fire and Smoke Alarms in Scottish Homes: Analysis of Responses PEOPLE, COMMUNITIES AND PLACES. social. research

AMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats

Design of Fire safety in Multi Occupancy Residential Accommodation

Proposed Social Housing (Automatic Fire Suppression Systems) (Scotland) Bill Shelter Scotland consultation response

Fire Enforcement Report

THE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

Do you have paying guests?

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

Protocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire safety

Fire Safety Policy. Contents. This policy was approved by the Trustees on 6 September 2018 and will be reviewed not later than every 5 years.

GDST Fire Safety Strategy March 2016

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

Dangerous Assumptions

CFOA Protocol for the Reduction of False Alarms & Unwanted Fire Signals

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Personal Emergency Evacuation Plan (PEEP) Guidance and Plan

NHS Tayside. Fire Safety Policy

Fire Safety Policy Date: 0

Shared Services Partnership

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES

SELF PRESERVATION SOCIETY By Jim Creak

In addition, Fire Protection and Business Support Information are included in the report.

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection

Technical reference Reference & design

BEST VALUE PERFORMANCE INDICATORS CONSULTATION: INSURERS VIEWS ON ITS IMPLICATIONS A RESPONSE BY THE ASSOCIATION OF BRITISH INSURERS

Fire safety policy. Contents. This policy was approved by the Trustees on 3 September 2015 and will be reviewed not later than every 3 years.

PERIODIC ELECTRICAL TESTING POLICY

NOT PROTECTIVELY MARKED. Fire Legislation

Cladding Screening Test Result

PREMISES FIRE SAFETY LOGBOOK

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY. To be read in conjunction with the H&S Policy and individual building fire evacuation arrangements

BUILDING CODE COMMISSION

Guidance for writing a Personal Emergency Evacuation Plan (PEEP)

BS 5839 Part 1 : 2013 Changes. By Don Scott

Thank you for your letter of 26 June regarding the Committee s scrutiny of building regulations in Scotland.

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fire Safety Management Audit Specification August 2017

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1

BEFORE THE ENVIRONMENT COURT I MUA I TE KOOTI TAIAO O AOTEAROA ENV-2018-AKL IN THE MATTER. of the Resource Management Act 1991 (RMA) AND

Fire alarm provisions for alerting the Fire Service

Glenmere Primary School Fire Safety Policy FIRE SAFETY POLICY. Revised on April Sam Conlon. Created by S.Conlon 1

To seek Cabinet approval of the Council s Fire Safety Policy. It is proposed that Cabinet approves the Fire Safety Policy.

Periodic Electrical Testing Policy

FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS

5 Sadly, recent tragic events in South Yorkshire saw a two year old girl, Libby- Jayne Hornsby lose her life in a house fire in Conisbrough.

FIRE SAFETY POLICY June 2014

DIVISION C ADMINISTRATIVE PROVISIONS

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE PROCEDURES 1. APPOINTMENTS

ISLE OF WIGHT FIRE & RESCUE SERVICE

Fire precautions in dwellings

FIRE SAFETY POLICY Revised March 2013

BYLAW NO (CONSOLIDATED)

Regulatory Reform (Fire Safety) Order A short guide to making your premises safe from fire

Policy for Safe Evacuation of Persons with Disabilities

BUILDING CODE COMMISSION

FIRE SAFETY EXPECTATIONS IN PRISONS

Annemount School Fire Safety Policy This Policy is for the whole school including the EYFS

Fire Risk Assessment

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007)

Fire Policy and Procedures. Cañada Blanch Spanish School

FIRE POLICY ST.GEORGES AND OUR LADY QUEEN OF PEACE PARISHES OF WORCESTER INTRODUCTION. Fire is one of the most common workplace hazards.

fire risk assessment For use by landlords of small premises Premises Address

Management Standard: Fire Safety

FIRE RISK ASSESSMENT

FIRE SAFETY POLICY April 2011

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

The Association for Specialist Fire Protection

Fire Sprinklers Working Group Final Report

Fire Safety Policy 2018/19

BUILDING CODE COMMISSION

(Fire) Emergency Evacuation Plan

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

Fire prevention and protection

Fire Risk Assessment 2017

COMMUNITY DEVELOPMENT. Automatic Fire Alarm Actuation Protocol

GREAT DENHAM PRIMARY SCHOOL FIRE SAFETY POLICY September 2017

Guided Learning Hours (GLH) 16 Invigilated Assessment Hours (IA) 2 Total Qualification Time (TQT) 18

Transcription:

Fire and Rescue Service Circular Circular number 48/2009 Date issued 13 August 2009 This circular is For information and consideration Status This circular covers the outcome of a referral to the Secretary of State of a question for determination under article 36 of the Regulatory Reform (Fire Safety) Order 2005. Secretary of State determination under article 36 of the Fire Safety Order Issued by: Rhian Blackman Fire and Rescue Service Development Division Addressed to: The Chair of the Fire and Rescue Authority The Chief Executive of the County Council The Clerk to the Fire and Rescue Authority The Clerk to the Combined Fire and Rescue Authority The Commissioner of the London Fire and Emergency Planning Authority The Chief Fire Officer Please forward to: Technical or statutory fire safety officers Summary This circular publishes the outcome of a request to the Secretary of State to determine a fire safety issue under article 36 of the Regulatory Reform (Fire Safety) Order 2005. For further information, contact: Rhian Blackman Fire Safety Policy Team Communities and Local Government Ashdown House 123 Victoria Street London SW1E 6DE Direct line 020 7944 6152 Fax 020 7944 8319 E-mail rhian.blackman@communities.gsi.gov.uk Website www.communities.gov.uk 48/2009 Fire and Rescue Service Circular 1

Secretary of State determination under article 36 of the Fire Safety Order 1.0 Introduction 1.1 This Fire and Rescue Service circular sets out the outcome of a determination request that the Secretary of State has received under article 36 of the Regulatory Reform (Fire Safety) Order 2005 ( the FSO ). It concerns the adequacy of fire detection in the bedrooms of a hotel. 1.2 Where the responsible person and the enforcing authority agree that there has been a failure to comply with the FSO in a premises, but do not agree on the technical solution to remedy that failure, they may agree, if appropriate, to refer the issue to the Secretary of State for determination under article 36 of the FSO. 2.0 Outcome 2.1 The Secretary of State has considered the facts of this request and determined that, in this case, the use of heat detectors provides a suitable technical solution to demonstrate compliance with the FSO. 2.2 This conclusion has been reached on the basis that the rooms will continue to be used for sleeping accommodation by people who do not have mobility or other relevant special needs. 2.3 This determination is based entirely on the circumstances of the specific premises and the decisions have been taken after careful consideration of the particular circumstances relating to this case. 2.4 The analysis underpinning this Determination by the Secretary of State can be found at http://www.communities.gov.uk/fire/firesafety/firesafetylaw. Rhian Blackman Fire and Rescue Service Development Division 48/2009 Fire and Rescue Service Circular 2

Determination in respect of the fire safety adequacy of fire detection in a hotel (Ref 004/006/003). Following advice from the Chief Fire and Rescue Adviser, the Secretary of State has determined, under article 36 of the Regulatory Reform (Fire Safety) Order 2005 ( the FSO ), that, in this case, the use of heat detectors provides a suitable technical solution to demonstrate compliance with the FSO. This conclusion has been reached on the basis that the rooms will continue to be used for sleeping accommodation be people who do not have mobility of other relevant special needs. This Determination is based entirely on the circumstances of the hotel in question and the decisions have been taken after careful consideration of the particular circumstances relating to this case. A copy of the advice of the Chief Fire and Rescue Adviser to the Secretary of State underpinning this determination is set out below.

Chief Fire and Rescue Adviser s advice on a request for Determination under article 36 of the Regulatory Reform (Fire Safety) Order 2005. Introduction 1. In accordance with article 36 of the Regulatory Reform (Fire Safety) Order 2005 (FSO) the enforcing Fire and Rescue Authority and the responsible person for the premises jointly applied to the Secretary of State for the determination of the disputed matters related to technical fire safety. The parties were not in agreement over the appropriate technical solution to satisfy the requirements of the FSO. 2. The Secretary of State has requested me to provide technical advice to the Secretary of State, in my role as Chief Fire and Rescue Adviser on receipt of a valid request for a Determination. 3. This determination relates to the requirement under article 13(1) (a) of The Regulatory Reform (Fire Safety) Order 2005 (fire-fighting and fire detection) which places a requirement upon the responsible person to provide: where necessary (whether due to the features of the premises, the activity carried on there, any hazard present or any other relevant circumstances) in order to safeguard the safety of relevant persons, the responsible person must ensure that (a) the premises are, to the extent that it is appropriate, equipped with appropriate fire-fighting equipment and with fire detectors and alarms. 4. In essence, the determination centres on the technical suitability of heat detectors heat or smoke detectors in hotel bedrooms. Technical Description 5. The premises are being put to use as a hotel. Built in the 1960s, the premises have two main buildings including 170 bedrooms and associated accommodation over ground and two upper floors. The bedrooms are provided with heat detectors, except for those used by disabled people where smoke detectors are installed. 6. The disagreement between the responsible person and the Fire and Rescue Authority is over the suitability of the type of fire detection

devices fitted in hotel bedrooms in the premises. The Fire and Rescue Authority is of the opinion that the heat detectors provided are not suitable and sufficient and do not satisfy the requirement given in Article 13 (1) (a) of the FSO. The responsible person maintains that heat detectors are in themselves suitable and sufficient. 7. No other features in the premises relating to risks from fire in this case have been considered in this advice. The Responsible Persons case 8. The responsible person rests on the case that the fire alarm is designed, installed and maintained in accordance with British Standard 5839-1 Fire detection and alarm systems for buildings-part 1. The premises has heat detectors in the majority of bedrooms and smoke detectors in those where people with disabilities may be accommodated. Smoke detectors are also located within the corridors, and would be described as being to an L2 category as defined within the British Standard. 9. The British Standard accepts that within this category and for this use of premises, heat detectors are regarded as appropriate for use in bedrooms. 10. The responsible person cites the Fire Safety Risk Assessment guidance for sleeping accommodation, issued by HM Government in support of the FSO, as an appropriate method of providing automatic fire detection within hotel bedrooms by referencing BB5839 as an appropriate standard. 11. The responsible person believes that this is a suitable and sufficient risk mitigation measure in relation to the risks posed in the bedrooms. The fire risk assessment does not show that these rooms pose any greater risk that any other hotel bedroom. Risk reduction measures, such as the banning of smoking also point to no particular increase in risk. 12. The responsible person is of the opinion that the test of what is acceptable is based on achieving risk reduction to a point which is as low a reasonably practicable by compliance with the appropriate British Standard. 13. This is underscored by the responsible person s assessment of the risk. The risk is regarded as being no greater than any typical hotel bedroom and so protection provided in the form of heat detectors is sufficient. The responsible person sites official statistics gathered and academic studies into the risks associated with hotel bedroom fires which they claim demonstrate that the protection offered by automatic fire alarm systems designed to BS5839 have reduced the risk of death and injury in hotel fires to a very low level.

14. The responsible person is also of the opinion that the choice of detector will have a significant effect on unwanted fire signals (false alarms). It is argued that using heat detectors will reduce the level of unwanted fire signals which will have a beneficial effect on safety by reducing the complacency that high levels of unwanted fire signals can produce. While accepting that other methods of reducing unwanted fire signals are possible, such as the use of staff alarms, these require a level of management response that is not available in this hotel. As such, the use of heat detectors is a suitable method of reducing the risk that complacency can cause in responding to unwanted fire signals. The Fire and Rescue Authority s case 15. The view of the Fire and Rescue Authority rests on the requirement of the FSO to adequately protect all relevant persons. Occupants using the hotel bedrooms are clearly relevant persons. 16. The Fire and Rescue Authority is of the view that the provision of heat detectors in the bedrooms does not provide adequate protection to the relevant persons. The Fire and Rescue Authority makes the case that smoke detectors would provide a quicker response to any fire in the room, particularly in the case of smouldering fires, and so provide better protection. This case is supported by reference to various factors. The Fire and Rescue Authority cite the concept used in fire engineering to understand how escape times in case of fire can be assessed which is explained in the British Standard document PD 7974-6:2004, The application of fire safety engineering principles to fire safety design of buildings. Human factors. Life safety strategies. Occupant evacuation, behaviour and condition (Sub-system 6). 17. This document analyses the processes and factors that are important in enabling people to evacuate safely from a building a fire situation. This analysis explains that the time it takes for people to become aware of a fire is of significant importance in determining whether people will have enough time to escape from a fire. The Fire and Rescue Authority claim that heat detectors will not give enough warning for occupants of a bedroom to escape a fire and that the likely type of fire within a bedroom is likely to be a smouldering fire with minimal heat release, unlikely to activate a heat detector. 18. The Fire and Rescue Authority use evidence from the CLG Fire Kills campaign to make the case that the provision of smoke detectors is appropriate, making the link between the success of the domestic smoke detectors campaigns arguing that as smoke detectors are appropriate in domestic settings, they are also appropriate for providing protection in the hotel bedrooms. The Fire and Rescue Authority also cites BS 5839-1:2002 which notes that heat detectors will not give early warning to smouldering fires.

19. The Fire and Rescue Authority also discuss the status of the British Standard 5839-1 and the Fire Safety Risk Assessment guidance for sleeping accommodation, issued by HM Government. They argue that by following these guidance documents alone does not in itself guarantee compliance with the requirements of the FSO. 20. The issue of cost is addressed by the Fire and Rescue Authority. They do not directly address the cost statements made by the responsible person. However, they make the case that domestic fire detectors could be installed as an interim measure in bedrooms to reduce the risk. 21. The Fire and Rescue Authority addresses the potential problem of unwanted fire alarm signals. Their case is that unwanted fire signals in similar hotels are not a significant problem and so to use smoke detection in hotel bedrooms should not a problem. The Fire and Rescue Authority also argue that the management of unwanted fire signals can be successfully performed where smoke detectors are fitted as it is a management issue, and not a technical problem solved by detector choice. The Chief Fire and Rescue Adviser s View 22. The central issue to be determined is how the choice of appropriate detector type is established, and how this decision is made. It is my view that to comply with the FSO the technical solutions will have to reduce the risk to a level which safeguards the safety of relevant persons so far as is reasonably practicable. In deciding whether the risk is reduced to a level which is as far as is reasonably practicable involves a comparison between the control measures that the responsible person is proposing and the measures that would normally be found in such circumstances appropriate to that hazard i.e. relevant good practice. 23. Neither the responsible person or the Fire and Rescue Authority have offered any technical or evidential based analysis to compare the differing levels of risk reduction that smoke detectors may achieve when compared with heat detectors, for example an evaluation of the differing times to activation of both types of detector in the hotel rooms in question. 24. The responsible person has relied on a risk assessment of the premises, carried out to satisfy the requirements of the FSO. As such, the risk assessment is based on an understanding of the risks from fire in the hotel rooms and establishing the control measures guided by appropriate standards. My view is that this has been carried out appropriately. 25. BS 5839-1 does allow for the provision of heat detectors in bedrooms. In discussing the choice of detectors, BS 5839-1 explains that a

balance has to be achieved between the effectiveness of the detector and potential problems given by unwanted fire signals. The responsible person is of the view that this balance has been struck by the use of heat detectors in this case. 26. BS 5839-1 does note that the use of heat detectors in bedrooms is not to provide the earliest warning of fire to the occupants but to provide an adequate means of fire detection when combined with smoke detectors in the escape route. The responsible person s assessment is that heat detectors will give warning and that the escape distance within the bedroom is relatively small. This is supported by statistical analysis of fires in hotel bedrooms that demonstrate that in terms of risk, the technical standards contained within BS 5839-1 is adequate. 27. The Fire and Rescue Authority have based their case on a general argument about the relative performance of smoke detectors compared to heat detectors. In making their case they have used a very general approach. The reference to PD 7974-6:2004 is by way of illustration and make no reference to the particular hotel in question or make any attempt to quantify the perceived difference in detector would make, as would be expected by the use of a fire engineering case. 28. The Fire and Rescue Authority uses examples of some hotel fires to point to the risks posed in such premises. The case made by the Fire and Rescue Authority does not illustrate how these examples advance the discussion over the choice of detectors. 29. The Fire and Rescue Authority cites the CLG Fire Kills campaign as evidence that smoke detectors should be used in this hotel. It is recognised that this campaign has been successful. However, it relates to the risk presented in a domestic setting. There is no evidence offered as to how this relates to the particular hotel in question, other than in the most general terms. It is also worth noting that the guidance on placing smoke detectors in this campaign is within escape routes, and not bedrooms. As such their success has been achieved by offering the same type of detector in escape routes as BS5839-1 requires. 30. It is therefore my view that the choice of heat detector over smoke detectors in this particular case has been carried out in accordance with avaliable guidance related to the particular hotel. In conforming to the British Standard, the responsible person has evaluated the risk in the hotel and concluded that the provision of heat detectors is as low as reasonably practical and that the risk presented in the hotel are those envisaged in these documents. 31. The Fire and Rescue Authority based their assessment on general arguments about risk without demonstrating why this particular hotel presents a higher risk than those anticipated within the British Standard. They have failed to show in this particular case that the

Conclusion relevant persons in the hotel bedrooms would be put at a higher risk which would be unacceptable. The reliance on a general approach does not carry sufficient weight to question the reliance on the British Standard. The determination is not intended to be a commentary on the technical standards in themselves. However, in this case, compliance with the British Standard does show that the risk has been appropriately assessed and therefore that the technical decision to use heat detectors within the hotel bedrooms is the appropriate technical solution in this case. 32. Article 13(1) (a) of the Regulatory Reform (Fire Safety) Order 2005 requires that where necessary, in order to safeguard the safety of relevant persons, the responsible person must ensure that the premises are, to the extent that it is appropriate, equipped with appropriate fire detectors and alarms. 33. I have given careful consideration to the particular circumstances of this case and the arguments of both parties. I have concluded that in this case, the use of heat detectors in the hotel bedroom provides a suitable technical solution to demonstrate compliance with the FSO, and I am advising the Secretary of State accordingly.